12-354-005Miami-Dade Fire Rescue Fire Alarm Pre-Submittal Checklist Based On NFPA 72 2002 edition & NFPA 1 and 1012006 edition MIAMMM DE I Designed by: I(folvip, kpifj vaYS Phone #: - ftl$"0-54� Signature: Created by: MDFR 11 / 2009 THIS IS A REQ ON ALL FIRE ALARM PLAN SUBMITTALS YES NO N/A LOCATION I COMMENTS This system Is an "Existing Remote Supervising Station Fire Alarm System" and is stated as such on the plant, (24 hours of secondary powir) AHJ may require documentation of prior approval of systerin as i Remote Supervising StaUdh Fire Alarm System In the form ofthe original FIrb DepL approved job copy set of plans is or certified microfilm copy of same. A complete detailed statement of the scope of work Is stated on the plan._ Please note that the complete tenant space, In Its entirety, will be hispeicted for compliance 19 with NFPA. 72 (2002) and NFPA, 101 (2006), or prior editions of thise-iodes It applicable. Ex Is the building "New" or" istin 9%_ and Is indicated as such on the A 20 plans. A descripUon of the building Is provided, including fire sprinkler systems, fire 21 suppression systems, number of storles,'sqivam footage per. floor, and elevation of the last occupied floor It over 5 stories. A location key Is provided showing the area-of proposed work within the building, 22 Also -a site key for projects with multiple bulldlnRs showing locations of all X buildinas with addresses. All Interconnected fire alarm control panels are arranged to function as a single 23 -,-system and monitored for Integrity as per NFPA 72. The class and/or style are shown Wall initiating device circuits, signal line circuits 24 and notification appliance circuits. The maximum number of each device type Is provided for each JDC based on 25 device load or each SLC, based on class and style, per NFPA 72 and the manufacturer's specifications. A specific sequence of operation Including all alarm, supervisory, trouble and-, control functions such as fire sprinkler, door release, smoke control, elevator 26 recall, suppression systems, and transmission of signals offsite, etc-, are specified on the plan. The type of monitoring station, (i.e. listed central station, remote supervising station, listed proprietary supervising station), whom alarm, trouble, and 27 supervisory signals are transmitted to, is clearly and consistently stated In the sequence of operations. 28 The method of communication to the monitoring station Is included on the riser. 29 Elevator recall Is connected to the fire alarms stem. If this building contains elevators, but elevators are not capable of recall. written ,30 documentation on elevator manufacturer's letterhead advising that elevators are not capable of recall function, is provided. If this building does not contain afire alarm system, and fire alarm panel Is exclusively for elevator recall, plans clearly designate same as "Elevator Recall 31 Control and Supervisory Panel". Manufacturer and model number for each device, module, power supply and 32 component Is specified In the !Mbol le end. Each device, module, appliance and component Is identified with Its own unique 33 number and Indicated on the floor plan and riser. Also label each module and relay function on riser. Floor plans are drawn to 1/8' s;a-10 or, If using another scale, all device coverage is 34 diagrammed on the plan and all room dimensions are-included. All roams & spares are labeled Indicating-their use, and the occupant load has-- 35 been provided for all assembly use rooms with an occupant load of 60 or greater. All new, existing, replaced or relocated devices are Indicated on the floor plan and a 36 complete riser diagram showing all new'and existing devices of the entire fire alarm system Is provided. 37 Coiling condition and height Is provided for all ceiling mounted devices. All devices In areas in which the voltage, temperature, and humidity variations exceed those conditions stated 1r NFPA 72, are listed for conditions and all such 38 areas are Identified. The FACP and NAC Panels are located In a mechanically ventilated room or conditioned space. A note Is provided on the plans stating "Room containing FRCP and/for Booster - Power Supply panel(s) Is mechanically ventilated", If applicable. 39 Designed by: I(folvip, kpifj vaYS Phone #: - ftl$"0-54� Signature: Created by: MDFR 11 / 2009 THIS IS A REQ ON ALL FIRE ALARM PLAN SUBMITTALS