12-354-005Miami-Dade Fire Rescue
Fire Alarm Pre-Submittal Checklist
Based On NFPA 72 2002 edition & NFPA 1 and 1012006 edition
MIAMMM
DE
I
Designed by: I(folvip, kpifj vaYS Phone #: - ftl$"0-54�
Signature: Created by: MDFR 11 / 2009
THIS IS A REQ ON ALL FIRE ALARM PLAN SUBMITTALS
YES
NO
N/A
LOCATION I COMMENTS
This system Is an "Existing Remote Supervising Station Fire Alarm System" and is
stated as such on the plant, (24 hours of secondary powir) AHJ may require
documentation of prior approval of systerin as i Remote Supervising StaUdh Fire
Alarm System In the form ofthe original FIrb DepL approved job copy set of plans
is
or certified microfilm copy of same.
A complete detailed statement of the scope of work Is stated on the plan._ Please
note that the complete tenant space, In Its entirety, will be hispeicted for compliance
19
with NFPA. 72 (2002) and NFPA, 101 (2006), or prior editions of thise-iodes It
applicable.
Ex
Is the building "New" or" istin 9%_ and Is indicated as such on the
A
20
plans.
A descripUon of the building Is provided, including fire sprinkler systems, fire
21
suppression systems, number of storles,'sqivam footage per. floor, and elevation of
the last occupied floor It over 5 stories.
A location key Is provided showing the area-of proposed work within the building,
22
Also -a site key for projects with multiple bulldlnRs showing locations of all
X
buildinas with addresses.
All Interconnected fire alarm control panels are arranged to function as a single
23
-,-system and monitored for Integrity as per NFPA 72.
The class and/or style are shown Wall initiating device circuits, signal line circuits
24
and notification appliance circuits.
The maximum number of each device type Is provided for each JDC based on
25
device load or each SLC, based on class and style, per NFPA 72 and the
manufacturer's specifications.
A specific sequence of operation Including all alarm, supervisory, trouble and-,
control functions such as fire sprinkler, door release, smoke control, elevator
26
recall, suppression systems, and transmission of signals offsite, etc-, are specified
on the plan.
The type of monitoring station, (i.e. listed central station, remote supervising
station, listed proprietary supervising station), whom alarm, trouble, and
27
supervisory signals are transmitted to, is clearly and consistently stated In the
sequence of operations.
28
The method of communication to the monitoring station Is included on the riser.
29
Elevator recall Is connected to the fire alarms stem.
If this building contains elevators, but elevators are not capable of recall. written
,30
documentation on elevator manufacturer's letterhead advising that elevators are
not capable of recall function, is provided.
If this building does not contain afire alarm system, and fire alarm panel Is
exclusively for elevator recall, plans clearly designate same as "Elevator Recall
31
Control and Supervisory Panel".
Manufacturer and model number for each device, module, power supply and
32
component Is specified In the !Mbol le end.
Each device, module, appliance and component Is identified with Its own unique
33
number and Indicated on the floor plan and riser. Also label each module and relay
function on riser.
Floor plans are drawn to 1/8' s;a-10 or, If using another scale, all device coverage is
34
diagrammed on the plan and all room dimensions are-included.
All roams & spares are labeled Indicating-their use, and the occupant load has--
35
been provided for all assembly use rooms with an occupant load of 60 or greater.
All new, existing, replaced or relocated devices are Indicated on the floor plan and a
36
complete riser diagram showing all new'and existing devices of the entire fire alarm
system Is provided.
37
Coiling condition and height Is provided for all ceiling mounted devices.
All devices In areas in which the voltage, temperature, and humidity variations
exceed those conditions stated 1r NFPA 72, are listed for conditions and all such
38
areas are Identified. The FACP and NAC Panels are located In a mechanically
ventilated room or conditioned space.
A note Is provided on the plans stating "Room containing FRCP and/for Booster
-
Power Supply panel(s) Is mechanically ventilated", If applicable.
39
Designed by: I(folvip, kpifj vaYS Phone #: - ftl$"0-54�
Signature: Created by: MDFR 11 / 2009
THIS IS A REQ ON ALL FIRE ALARM PLAN SUBMITTALS