Loading...
12-1366-002NOTES: 1. FIRE ALARM SYSTEM SHALL BE POWER LIMITED UTILIZING POWER LIMITED WIRING., 2. WIRING SHALL BE #12 THHN, #14 THHN OR 18/2 TWISTED SHIELDED PAIR FPL TYPE CABLE, 3. INSTALLATION SHALL COMPLY WITH NFPA 1, 2009, APPLICABLE CHAPTERS. 4. INSTALLATION SHALL COMPLY WITH NFPA 72, 2007, APPLICABLE CHAPTERS. 5. INSTALLATION SHALL COMPLY WITH NFPA 101, 2009, APPLICABLE CHAPTERS. 6. INSTALLATION SHALL COMPLY WITH NEC 2008. 7. CONDUIT, AS APPLICABLE SHALL BE 1/2" MINIMUM WITH A MAXIMUM FILL OF 40 %. COMPLY WITH NEC. 8. SYSTEM SHALL BE GROUNDED PER MANUFACTURERS SPECIFICATIONS. 9. ALL DEVICES SHALL BE COMPATIBLE & SHALL BE UL LISTED FOR FIRE SERVICE USE. 10, ALL SPACES SHALL MEET THE AUDIBLE CHARACTRISTICS OF NFPA 72 AND NFPA 101. 11. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 3' OF A/C DIFFUSERS, KITCHEN OR BATHROOM DOORS. 12. CEILING MOUNTED DEVICES SHALL BE LOCATED AT A HEIGHT OF 10' +/ ON SMOOTH FLAT CEILINGS UNLESS OTHERWISE NOTED. 13. SIGNALLING LINE CIRCUITS SHALL HAVE A MAXIMUM OF 127 POINTS PER CHANNEL. SEE FLOOR PLANS FOR QUANTITIES & TYPES OF DEVICES. 14. FIRE ALARM PANEL & ANY ASSOCIATED FIRE ALARM TRANSPONDERS SHALL BE FED BY A 120VAC, SINGLE PHASE, 20 AMP, DEDICATED BREAKER. 15. ALL INTERCONNECTED FIRE ALARM PANELS SHALL BE ARRANGED TO FUNCTION AS A SINGLE SYSTEM AND SHALL BE MONITORED FOR INTEGRITY PER NFPA 72. 16. RACKS, SHELVES AND EQUIPMENT ARE ALL LOWER THAN 80" ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED. 17. THE DESIGN INSTALLATION COMPLIES WITH FLORIDA BUILDING CODE - 2010 FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION. 18. THIS FACILITY IS FULLY SPRINKLED.' 19, THIS IS A SEVEN STORY BUILDING. 20. ROOM CONTAINING FRCP AND /OR BOOSTER POWER SUPPLY PANEL(S) IS MECHANICALLY VENTILATED. 21. MAXIMUM MOUNTING HEIGHT FOR ALL PANELS SHALL BE SIX FEET TO THE TOP OF THE ENCLOSURE. 22. MIMIMUM CLEAR WORKING SPACE OF THREE FEET IN FRONT OF ALL FIRE ALARM PANELS SHALL BE PROVIDED. SCOPE OF WORK: 1. PROVIDE & INSTALL FIRE ALARM SYSTEM AS SHOWN ON DRAWINGS. 2. SIGNALING LiNE CIRCUIT WIRING SHALL BE STYLE 4. 3. NOTIFICATION APPLIANCE CIRCUIT WIRING SHALL BE STYLE Y. 4. THiS SYSTEM IS MONITORED BY AN EXISTING REMOTE SUPERVISORY STATION PER NFPA - 72.8.5. 5. ADD 2 SMOKES AND REUSE 1 EXISTING. 6. ADD 2 SPEAKERiSTROBES AND RELOCATE 1 EXISTING. 7. ADD 1 STROBE. FIRE ALARM SYSTEM SEQUENCE OF OPERATION TYPICAL: UPON ACTIVATION OF A MANUAL PULL STATION, ANY AUTOMATIC INITIATION DEVICE (i.e. Smoke or Heat detector). OR A FIRE SPRINKLER FLOW SWITCH THE FOLLOWING SEQUENCE OF EVENTS SHALL OCCUR: ALL AUDIO /VISUAL APPLIANCES, SPEAKERS AND STROBES WITHIN THE FLOOR WHERE THE ALARM INITIATED SHALL BE ACTIVATED. IN ADDITION, ALL AUDIOVISUAL APPLIANCES, SPEAKERS AND STROBES LOCATED ON THE FLOOR IMMEDIATELY ABOVE AND ON THE FLOOR IMMEDIATELY BELOW, SHALL ALSO BE ACTIVATED. ALL STROBES ACTIVATED UPON ALARM, WITHIN EACH SMOKE COMPARTMENT, SHALL BE SYNCHRONIZED. ALL MAGNETIC DOOR HOLDERS ASSOCIATED WITH THE DOORS LEADING INTO AND OUT OF THE SMOKE COMPARTMENT IN ALARM SHALL BE ACTIVATED TO RELEASE DOORS TO ISOLATE THE SMOKE COMPARTMENT WHERE THE ALARM INITIATED FROM. ALL AIR HANDLING UNITS AND FANS SERVING THE SMOKE COMPARTMENT, FROM WHICH THE ALARM ORIGINATED FROM, SHALL BE SHUT DOWN PER NFPA 90 -A. ALL SMOKE DAMPERS ASSOCIATED WiTH THE AIR CONDITIONING DUCTS PENETRATING THE RATED PARTITIONS ASSOCIATED WITH THE SMOKE COMPARTMENT WHERE THE ALARM IS ORIGINATED FROM, SHALL BE CLOSED. UPON ACTIVATION OF THE ELEVATOR LOBBY SMOKE DETECTORS (WITH THE EXCEPTION OF THE ELEVATOR LOBBY DETECTOR AT THE PRIMARY LEVEL OF EGRESS), THE FOLLOWING SHALL OCCUR IN ADDITION TO ABOVE: 1. ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL OF EGRESS. 2. WARNING SiGN SHALL ILLUMINATE. UPON ACTIVATION OF THE ELEVATOR LOBBY SMOKE DETECTOR AT THE PRIMARY LEVEL OF EGRESS, THE FOLLOWING SHALL OCCUR, IN ADDITION TO ABOVE: 1. ELEVATORS SHALL RECALL TO THE ALTERNATE LEVEL OF EGRESS. 2. WARNING SIGN SHALL ILLUMINATE. UPON ACTIVATION OF THE ELEVATOR MACHINE ROOM SMOKE DETECTOR, THE FOLLOWING SHALL OCCUR, IN ADDITION TO THE ABOVE: 1. ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL OF EGRESS. 2. WARNING SIGN SHALL BLINK. UPON ACTIVATION OF THE ELEVATOR TOP OF SHAFT SMOKE DETECTOR, THE FOLLOWING SHALL OCCUR: 1. ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL OF EGRESS. 2. WARNING SIGN SHALL BLINK. UPON ACTIVATION OF A TAMPER SWITCH, THE FOLLOWING SHALL OCCUR. 1, A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT. UPON ACTIVATION OF A DUCT SMOKE DETECTOR, THE FOLLOWING SHALL OCCUR. 1. A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT. 3. THE AIR HANDLER UNIT ASSOCIATED WiTH THAT DUCT DETECTOR SHALL SHUT DOWN. UPON ACTIVATION OF A ELEVATOR HEAT DETECTOR LOCATED IN THE SHAFT OR MACHINE ROOM THE FOLLOWING SHALL OCCUR. 1. A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT. 3. THE SIGNAL WILL BE SENT TO THE SHUNT SWITCH FOR POWER SHUTDOWN. SMOKE CONTROL SEQUENCE OF OPERATION THE AREAS COVERED UNDER THIS PROJECT ARE DESIGNED FOR A PASSIVE SMOKE CONTROL OPERATION. THE BUILDING IS DIVIDED INTO MULTIPLE SMOKE COMPARTMENTS SEPARATED BY FiRE/SMOKE BARRIERS THAT CONTAIN THE SMOKE WITH THE ZONE OF FIRE ORIGIN (ZOFO), UPON ACTIVATION OF ANY FIRE ALARM DEVICE THE FOLLOWING SEQUENCE OF OPERATION SHALL OCCUR: 1. ALL EXHAUST FANS SERVING THE ZOFO SHALL BE DE- ENERGIZED. 2. ALL AIR HANDLING UNITS SERVING ONE ZOFO SHALL BE DE- ENERGIZED. 3. ALL COMBINATION FIREISMOKE DAMPERS LOCATED ON PERIMETER WALL OF ZOFO SHALL MODULATE TO THE CLOSE POSITION. NOTE: THE FOLLOWING EQUIPMENT SHALL BE PART OF THE SEQUENCE OF OPERATION DESCRIBED ABOVE: 1. TOILET EXHAUST FANS DEDICATED TO INDIVIDUAL TOILET ROOMS. 2. FAN COIL UNITS DEDICATED TO SERVE INDIVIDUAL ROOMS. WIRE LEGEND A= INITIATING DEVICE CIRCUIT- IDC 2 #14 AWG THHN MINIMUM we- °°�6 POWER41MITED AND NON4'WVER{IMnED WIRING `�® MUST ENTER THROUGH SEPARATE CONCUITISERVICE ENTRANCES. AC POWER ENTRANCE INTO BACK BOX IS �TMa 00000 REODIREOATDESIGN ATEDLOCATIONOFTHEBACK L= NOTIFICATION APPLIANCE CIRCUIT - NAC/VISUAL O, psSfFfFQ BOX FARUREIMITED PJNGF FROM t R. 2 #14 AWG THHN MINIMUM NON POWER {lWRIN WIRING FROM E UL LISTING F awn LOW VOLTAGE WIRING, WILL VOID THE tit LISTING FOR THE BEJN AND WILL PREVENTART INSTALLATION C = AUXILIARY CONTROL CIRCUIT - ACC FROM BEING CERTIFIED. (SEE CHART INSTALLATION ��, OS 4009 INSTRUCTION 2 #14 AWG THHN MINIMUM FILL. VOID OA CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS , _ 4a 1 O D = VOICE COMMUNICATION CIRCUIT - VCC LABORATOPoES, ING.:A FOR USE IN System No,W -L -1228 18/2 TWISTED SHIELDED PAIR - NPLF w�awn THROUGH-PENETRATION YT S (XH Sun d 2 r (S e F = FIRE FIGHTERS TELEPHONE CIRCUIT - FTC FIRESroP SYSTEMS (XHEZ). F Raking - i and 2 Hr (See Item 1) a�„�xnw sEECURRENT DIRECTORY T Rating - o, 1/2 and 1 Hr (see Item 3) a.r 18/2 TWISTED SHIELDED PAIR - NPLF RESISTANCE DIRECTORY L Rating At Ambient - Less Than 1 CFM /sq ft 5�g" WO L Rating t 400 F - 2 CFM /sq ft 400lHg201 WIRING ENTRIES Irmo BACK Box g 4010 FACP WRING ENTRIES IWO BACK BOX MN = MULTI - ADDRESSABLE PERIPHERAL NETWORK - MAPNET 18/2 TWISTED /SHIELDED PAIR - NPLF MP= MAPNET POWER CIRCUIT - APC -�n - 00000 00000 t.� 2 #14 AWG THHN MINIMUM A III � 4O UL us FILL VOID OR CAVITY MATERIALS CLASSFIED BY UNDERWRITERS LAWRATORIES, INC.0 FOR USE IN THROUGH-PENETRAT)ON FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FIRE RESISTANCE DIRECTORY EMS, POGO V \uu LW v.l. w -LW..1 u wNaww \awn cocoa rnOriuv. timv,i n oim)\JNn a 4m aoo 11 mcrui\-um - ra-Im - Ivem NrleAA/{611JW: nuvatmw "4u e4 - Mnaar sawraanu: rgrSlWa a, 4u11 -1. .7AraL: iRrwl4w a, 4.14 SECTION A -A 1. Walt Assembly The i or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and In the manner described In the individual 0400 or V400 series Wail and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs- Wall framing shall consist of min 3 -5/8 in. (92 mm) wide steel channel studs spaced max 24 In. (610 mm) OC. B. Gypsum Board* Thickness, type, number of layers and fasteners shall be as specified in the Individual U400 or V400 series Wail and Partition Design in the UL Fire Resistance Directory. Max area of opening is 67 -1/2 sq. in. (435 sq cm) with max dimension of 22 -1/2 In. (572 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly In which it Is installed. 2. Through Penetrant One or more nom 2 In. (51 mm) diam (or smaller) rigid steel conduit or electrical metallic tubing (EMT) installed either concentrically or eccentrically within the firestop system. The annular space between conduits or tubing and periphery of opening shall be min 0 In. (0 mm, point contact) to max 1 -1/4 in. (32 mm). The space between conduits or tubing shall be min 1/4 in.(6 mm) to max 1 in. (25mm). Conduit or tubing to be rigidly supported on both sides of wall assembly. 3. Fili,Vold or Cavity Material* - Caulk or SealMA 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. Min 1/2 in, (13 mm) diam bead of caulk applied to the penetrant/gypsum board interface at the point contact location on both sides of wail The hourly T Rating of the firestop system is 0 Hr when used in 1 Hr rated assemblies. The T Rating for 2 Hr rated assemblies Is 1/2 and 1 Hr for FlreDam 150+ and IC 15WB and Is 1 Hr for CP- 25WB+ and FB -300 WT. 3M COMPANY - CP 25WB +, FireDam 150 +, IC 15WB+ caulk or FB -3000 WT sealant. *Bearing the UL Classification Mark * NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2011 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. System No. C -Al -1044 March 15, 2007 F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr L Rating At Ambient - 2 CFM /sq ft L Rating At 400 F - less than 1 CFM /sq ft W Rating - Class I (See Item 4) SECTION A -A 1. Floor or Wall Assembly- Lightweight or normal weight (100-150 pd or 1600-2400 kg/m3) concrete. Except as noted In cable under Item 4, min thickness of sold concrete floor or wall assembly la 4.1/2 In. (114 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UIL Classified hollow wrtracast Concrete tmksWhen floor is constructed d hollow core precast concrete units, packing material (Item 3) and mulk fill material (Item 4) to be installed symmetrically on both sides of floor, flush with floor surface. Wail assenbly may also be constructed of any UL ClasM86dmTtne Bbcks!Max diem of opening Is In sped lightweight or normal weight concrete. Floor is 32 lee. (813 mm). Max diem of opening In floor constructed of hollow-core precast concrete merits Is 7 In. (178 mm). See Concrete Wocks(CAZT) anrPremst Concrete Ur"CFfV) categories In the are Resistance Directory for names of manufacturers. IA. Steel Sie"t(Optional, nor shown) - Max 15 Im (381 mm) ID (or smaller) Schedule 10 (or heavier) steel sleet cast or grouted Into flan or wall assembly. Sleeve may extend a max of 2 In. (51 mm) above top of floor or beyond either surface of wall. Max 16 ore. (406 mm) ID (or smaller) min 0.028 (0.71 mm) wall thickness (or heavier) galvamted steel sleeve cast or grouted Into floor or wall assembly, Sleeve may extend a max of 12 in. (13 mm) beyond either surface of floor or wall. 2. Through PenetrantsOee metallic pipe, conduit or tubing to be Installed either concentrically or eccentrically within the firestop system. Max ar ndar space between pipe, conduit or tubing and edge a through opening or sleeve Is dependent on the parameters shown In )ten 4. Min anmdar space between pipe or conduit and edge of through opening Is O In. (0 mm) (point contact). Pipe conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and Sizes of metallic pipes, conduits or tubing may be used: A. Steel pipe- Nan 30 In. (762 mm) them (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe- Nan 30 In. (762 mm) diam (or smarter) cast or ductile Iron pipe. C. Conduit- Nan 6 in. (152 mm) diam (or smaller) rigid steel conduit D. CondWt- Nan 4 In. (102 mm) diam (or Smaller) steel electrical metallic tubing. E. Copper- Tubing Nan 6 lee. (152 mm) diam (or smaller) Type L (or heavier) copper tube. F. Copper Pipe - Nan 6 in. (152 mm) dram (or snalrer) Regular (or heavier) copper pipe. 3. Paddlg Material Polyethylene backer rod or nom I In. (25 mm) thlckMss M tightty -packed mineral woof batt or glass fiber Insulation firmly packed Into opening as a permanent form. Packing material to be recessed from top surface of floor or from bah surfaces of wall as required to accommodate the required thickness of caulk fig material (Item 4). 4. FlII,Vod or Cavity Matedel* - Caulk or Seatapplied to fill the annular space Rush with top surface of floor. In wall assemblies, required caulk thickness to be Installed symmetrically on both sides of wall, Bush with wall srf ace. At point contact location between penetrant and sleeve or between penetrant and concrete, a min 14 In. (6 mm) dram bead of caulk shall be applied at top surface of floor and et both surfaces of wall. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown in the following table: Min nor or Wall Nom Pipe Tube or Max Annular Mln Caulk F Rating Thins tn. (mm) duR [Nam in. (mm) Space In. (mm) (a)MIn 21n. (51 mm) thickness of mineral wool beet Insulation required In annular space. (b)Mln I In. (25 mm) thickness a mineral wool batt insulation required In annular space on both sdes d Roor or wall assembly. Min 1 In. (25 mm) thickness a caulk to be Installed flush with each surface of floor or wall assembly. 3M COMPANY - CP 25WB+ caulk or FB-3000 Wr sealant. (tote: W Raring applies only when FB -3000 WT sealant is used.) -Bearing the UL Classification Markin} - NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2011 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. 4006/4008 axrrw-vw 400614008 FACP WIRING ENTRIES INTO BACK BOX 41001.1 FACP WIRING ENTRIES INTO BACK BOX - CEILING MOUNTED SMOKE/HEAT DETECTOR DEVICE MOUNTING HEIGHTS A/C SUPPLY DIFFUSER 3' (MIN) + lens In. (mm Hr 2-1/2(64) 1/2 -12 (13 -305) 1-3/8(35) U2 (13) 2 2.1/2 (64) 1/2 -12 (13 -305) 3414 (83) 1 (25) 2 4-12 (114) 1 /2-6 (13 -152) 1.3/8(35) 1/4(6)(3) 2 4.12 (114) 1/2 -12 (13 -305) 1.14 (32) 1/2 (13) 3 4 -12 (114) 1/2 -20 (13 -508) 2 (51) . 1 (25) 3 4 -12 (114) 1(2.20 (13 -508) 2 (51) 1 (25) 3 4 -12 (Illj I(2 -12 (13 -305) 3 -14 (83) d (25} 3 4 -12 (dl4j 22 -30 (558 -762} 2 (SAy 2 (51} 3 5 -12 (140) 1/2-6 (13 -152) 1 -3/8 (35) i (25} (b) 4 (a)MIn 21n. (51 mm) thickness of mineral wool beet Insulation required In annular space. (b)Mln I In. (25 mm) thickness a mineral wool batt insulation required In annular space on both sdes d Roor or wall assembly. Min 1 In. (25 mm) thickness a caulk to be Installed flush with each surface of floor or wall assembly. 3M COMPANY - CP 25WB+ caulk or FB-3000 Wr sealant. (tote: W Raring applies only when FB -3000 WT sealant is used.) -Bearing the UL Classification Markin} - NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2011 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. 4006/4008 axrrw-vw 400614008 FACP WIRING ENTRIES INTO BACK BOX 41001.1 FACP WIRING ENTRIES INTO BACK BOX - �4FSSrF/ o UL us FILL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS LABORATORIES, GV)C.0 Tt POUGH- P£NETF FIRESTOP SYSTEMS SEE CURRENT UL RESISTANCE DIRE( SOLO. 0000 NOTES 48' MAX (ADA 42' MIN /48' MAX (NFPA) NFPA 72 2DO7 EDITION (SECTION 5,13.4) System No.W -L -3001 September 07, 2004 (Formerly System No. 149) F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 3/4, 1, 1 -1/2 and 2 Hr (See Item 2) L Rating At Ambient - 15 CFM /sq ft (See Item 3) L Rating At 400 F - less than 1 CFM /sq ft (See Item 3) MOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST OF THE DETECTOR SIDE WALL 1. Wall Assembly -The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shalt be constructed of the materials and in the manner described In the individual 0300 or 0400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall Include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 In. lumber spaced 16 In. OC with Tom 2 by 4 In. lumber end plates and crass braces. Steel studs to be min 3 -5/8 In. wide by 1 -3/8 in. deep channels spaced max 24 In OC. B. Gypsum Board• - Nom 1/2 or 5/8 In. thick, 4 it wile with square or tapered edges. The gypsum wallboard type, thickness, number of layers and sheet orientation shall be as specified In the Individual Wail or Partition Design. Dlam of circular through opening to be 3/8 In. to 5/8 In. larger than outside diam of cable or cable bundle. C. Fasteners - When wood stud framing Is employed gypsum wallboard layers attached to studs With cement coated nails as specified In the Individual Wall or Partition Design. When steel channel stud framing is employed, gypsum wallboard attached to studs with Type S self - drilling, self- tapping bugle -head steel screws as specified In the individual Wall or Partition Design. The hourly F Rating of the firestop system Is equal to the hourly fire rating of the wail assembly in which R Is Installed. 2. Cables - Individual cable or max 3 in. diam table bundle Installed In through opening with an annular space of min 0 in. (point contact) to max 3/4 In. Cable to be rigidly supported on both sides of wall assembly. The following types and sizes of cables may be used: A. Max 15D pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride (PVC Insulation and jacket materials. When max 25 pair telephone cable Is used, • Rating Is 2 hr.When 50 to 150 pair telephone Cable Is used in 1 hr fire rated wall, • Rating la 3/4 hr.When 50 to 150 pair telephone cable Is used In 2 hr fire rated wall, T Rating Is 1 hr. B. Max No. 10 AWG multiple copper conductor Type NM ('Romex' ) nonmetallic sheathed cable with PVC Insulation and jacket materials. When Type NM cable Is used, max T Rating Is 1 -1/2 hr. C. Multiple fiber optical communication cable jacketed with PVC and having a max outside dlam of ! 5 /8 In. ®R When fiber optic cable Is used max T Rating r P 4is2h. D. Max 12 AWG multi Conductor (max seven conductors) power /control cable with cross- linked - polyethylene (XLPE) Insulation and XLPE or PVC jacket materials. When multi conductor power /control cable Is used, max T Rating Is 2 hr. E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER Cables with polyvinyl 4 chloride Insulation and jacket materials. 3. FID,Vod or Cavity Materials* - Caulk, Sealant or Putty - Caulk or putty fill material installed to completely fig annular space between cable and gypsum wallboard on both sides of wall and with a min 1/4 In. diam bead of caulk or putty applied to perimeter of cable(s) at Its egress from each side of the wall. 3M COMPANY - MP+ stlx putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap putty (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant Is used.) SYSTEM - Bearing the UL Classification Mark INSTALLED IN ACCORDANCE x NOTE a 70;11 - THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2011 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. rpm MMM-DADE LIE BLDG. PERMIT FIRE ALARM FIRE SUPPRESSION WATERMAINEXt DATE: .-' / 0 SYMBOL LEGEND DEVICES CEILING MOUNTED SMOKE/HEAT DETECTOR DEVICE MOUNTING HEIGHTS A/C SUPPLY DIFFUSER 3' (MIN) + 4•- 6' BELOW CEILING 4100 -9111 NETWORK FIRE ALARM PANEL WITH VOiCE & PHONES 24' MIN HANDICAP 4100 -9600 NETWORK FiRE ALARM PANEL BASIC PANEL BEDROOM STROBE AUDIO/VISUAL ACCEPTED HERE (- F VISUAL -ONLY DEVICES ❑F Z 4099- 9001 2099 -9813 PULL STATION ADDRESSABLE PULL STATION FLUSH TRIM HERE SD 4098 -9792 4098 -9714 IMPORTANT NOTE SD E 4098 -9792 4098 -9714 SSD SENSOR BASE SSD PHOTO SENSOR FOR ELEVATOR CAPTURE VERIFY EXACT MOUNTING Fz-11 Mi LL 4090 -9001 REQUIREMENTS WITH MANUFACTURERS DATA SHEETS 2190 -9161 5' Z3 4090 -9002 RELAY IAM OH E WALL MOUNTED HEAT DETECTOR 135' FIXED ELEVATOR SHUNT TRIP OPERATION MORE THAN TWO VISIBLE 4098 -9792 4098 -9733 SMOKE/HEA SD APPLIANCES ARE NOT SSD DUCTSENSOR HOUSING SAMPLING TUBE 49" DETECTOR 2098 -9806 PERMITTED IN ANY FIELD DOOR WIDTH 4098- 9i343 RELAY FORM C SPDT PAM -SD OF VIEW UNLESS THEIR LESS 3' RELAY SPDT W /LED MR -801(r FLASHES AS SYNCHRONIZED. FLOW DETECTOR SWITCH FURNISHED BY DIVISION 15 NFPA 72 2007 EDITION o 0 TS ) : (SECTION 7.5.4.3.2) TAMPER (GATE VALVE) SWITCH FURNISHED BY DIVISION 15 a. 11 -\Mr- `� 6 SM 4905 -9938 80' MIN FIRE AANUAL 4903 -9357 SPEAKER/STROBE75CD SYNC WALL MOUNT 96" MAX PHONE PULL SPEAKER WALL MOUNT 75CD NFPA 72 2OD7 DUCT JACK TATION F 2084 -9001 EDITION MA DO EL -1 -SS ELEVATOR WARNING SIGN (SECTION 7.5.4.1} .4.1) RDKII TEST ' HOLDER DOOR HOLDER = D ® 0 FINISHED/ WALL �4FSSrF/ o UL us FILL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS LABORATORIES, GV)C.0 Tt POUGH- P£NETF FIRESTOP SYSTEMS SEE CURRENT UL RESISTANCE DIRE( SOLO. 0000 NOTES 48' MAX (ADA 42' MIN /48' MAX (NFPA) NFPA 72 2DO7 EDITION (SECTION 5,13.4) System No.W -L -3001 September 07, 2004 (Formerly System No. 149) F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 3/4, 1, 1 -1/2 and 2 Hr (See Item 2) L Rating At Ambient - 15 CFM /sq ft (See Item 3) L Rating At 400 F - less than 1 CFM /sq ft (See Item 3) MOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST OF THE DETECTOR SIDE WALL 1. Wall Assembly -The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shalt be constructed of the materials and in the manner described In the individual 0300 or 0400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall Include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 In. lumber spaced 16 In. OC with Tom 2 by 4 In. lumber end plates and crass braces. Steel studs to be min 3 -5/8 In. wide by 1 -3/8 in. deep channels spaced max 24 In OC. B. Gypsum Board• - Nom 1/2 or 5/8 In. thick, 4 it wile with square or tapered edges. The gypsum wallboard type, thickness, number of layers and sheet orientation shall be as specified In the Individual Wail or Partition Design. Dlam of circular through opening to be 3/8 In. to 5/8 In. larger than outside diam of cable or cable bundle. C. Fasteners - When wood stud framing Is employed gypsum wallboard layers attached to studs With cement coated nails as specified In the Individual Wall or Partition Design. When steel channel stud framing is employed, gypsum wallboard attached to studs with Type S self - drilling, self- tapping bugle -head steel screws as specified In the individual Wall or Partition Design. The hourly F Rating of the firestop system Is equal to the hourly fire rating of the wail assembly in which R Is Installed. 2. Cables - Individual cable or max 3 in. diam table bundle Installed In through opening with an annular space of min 0 in. (point contact) to max 3/4 In. Cable to be rigidly supported on both sides of wall assembly. The following types and sizes of cables may be used: A. Max 15D pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride (PVC Insulation and jacket materials. When max 25 pair telephone cable Is used, • Rating Is 2 hr.When 50 to 150 pair telephone Cable Is used in 1 hr fire rated wall, • Rating la 3/4 hr.When 50 to 150 pair telephone cable Is used In 2 hr fire rated wall, T Rating Is 1 hr. B. Max No. 10 AWG multiple copper conductor Type NM ('Romex' ) nonmetallic sheathed cable with PVC Insulation and jacket materials. When Type NM cable Is used, max T Rating Is 1 -1/2 hr. C. Multiple fiber optical communication cable jacketed with PVC and having a max outside dlam of ! 5 /8 In. ®R When fiber optic cable Is used max T Rating r P 4is2h. D. Max 12 AWG multi Conductor (max seven conductors) power /control cable with cross- linked - polyethylene (XLPE) Insulation and XLPE or PVC jacket materials. When multi conductor power /control cable Is used, max T Rating Is 2 hr. E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER Cables with polyvinyl 4 chloride Insulation and jacket materials. 3. FID,Vod or Cavity Materials* - Caulk, Sealant or Putty - Caulk or putty fill material installed to completely fig annular space between cable and gypsum wallboard on both sides of wall and with a min 1/4 In. diam bead of caulk or putty applied to perimeter of cable(s) at Its egress from each side of the wall. 3M COMPANY - MP+ stlx putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap putty (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant Is used.) SYSTEM - Bearing the UL Classification Mark INSTALLED IN ACCORDANCE x NOTE a 70;11 - THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2011 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. rpm MMM-DADE LIE BLDG. PERMIT FIRE ALARM FIRE SUPPRESSION WATERMAINEXt DATE: .-' / 0 SYMBOL LEGEND DEVICES SYMBOL SIMPLEX MODEL # DESCRIPTION NODE 7 FACP 4100 -9111 NETWORK FIRE ALARM PANEL WITH VOiCE & PHONES M[NIPLEX 4100 -9600 NETWORK FiRE ALARM PANEL BASIC PANEL FATC FIRE ALARM TERMINAL CABINET FURNISHED BY ELECTRICAL CONTRACTOR .. ❑F Z 4099- 9001 2099 -9813 PULL STATION ADDRESSABLE PULL STATION FLUSH TRIM SD 4098 -9792 4098 -9714 SSD SENSOR BASE SSD PHOTO SENSOR SD E 4098 -9792 4098 -9714 SSD SENSOR BASE SSD PHOTO SENSOR FOR ELEVATOR CAPTURE Fz-11 Mi LL 4090 -9001 INDIVIDUAL ADDRESS MODULE CONNECT TO N/O CONTACTS ONLY 2190 -9161 NOTIFICATION APPLIANCE ZAM Z3 4090 -9002 RELAY IAM OH E CC -623 HEAT DETECTOR 135' FIXED ELEVATOR SHUNT TRIP OPERATION �� JJ 4098 -9792 4098 -9733 SSD SENSOR BASE SSD HEAT SENSOR SD 4098 -9756 2098 -9797 SSD DUCTSENSOR HOUSING SAMPLING TUBE 49" O 2098 -9806 REMOTE TEST STATION RED LED KEY SWITCH ® 4098- 9i343 RELAY FORM C SPDT PAM -SD ® M 2088 -9032 RELAY SPDT W /LED MR -801(r FS FLOW DETECTOR SWITCH FURNISHED BY DIVISION 15 01 a�� o 0 TS ) : CL a TAMPER (GATE VALVE) SWITCH FURNISHED BY DIVISION 15 a. 11 -\Mr- END OF LINE RESISTOR SM 4905 -9938 SMARTSYNC CONTROL MODULE 75CD LJj 4903 -9357 SPEAKER/STROBE75CD SYNC WALL MOUNT a 4902 -9703 SPEAKER WALL MOUNT 75CD 4904 -9333 STROBE 75CD SYNC WALL MOUNT F 2084 -9001 FIREMAN'S PHONE JACK EWS EL -1 -SS ELEVATOR WARNING SIGN ® 2088 -9608 DOOR HOLDER = CONNECTION TO AN APPROVED, DEDICATED EARTHGROUND, NFPA 70. COMPLY WITH NEC. 120VAC SOURCE DEDICATED BREAKER COMPLY WITH NFPA 70. fn E Q MOTOR CONTROL CENTER BY OTHERS Par PIV (GATE VALVE) SWITCH FURNISHED BY DIVISION 15 SD R 4098 -9756 2098 -9799 SSD DUCTSENSOR HOUSING, RETURN, SAMPLING TUBE 97" SD 4098 -9756 2098 -9799 SSD DUCTSENSOR HOUSING, SUPPLY, SAMPLING TUBE 97" SD H 4098 -9756 2098 -9799 SSD DUCTSENSOR HOUSING, SUPPLY, SAMPLING TUBE 97" E EXISTING F FIELD LOCATED N NEW R RELOCATED W o WATTS �-� win CD L"N 4906 -9151 0.186 AMPS SPEAKER/STROBE MULTICANDELLA WALL RED 75CD 4906 -9101 STROBE MULTICANDELLA WALL RED 0.186 AMPS WP I ° 1I ET70 -WP SPEAKER /STROBE WEATHERPROOF, WALL, WHEELOCK 0.138 AMPS WP O 2099 -9138 2975 -9211 WEATHERPROOF PULL STATION 1 N/O SINGLE ACTION," WEATHERPROOF RED BACK BOX © MB- GIO -24 -R MB MOTOR BELL INDOORS /OUTDOORS OA Q� PS : 4 LO reef rk ••a � {{a44 aa'e•�a - � Lu wU) U) .. Z w Mi LL CD `L C'4 dN [W- Z N a- �C) �(0 L11 J e= t1) L(i � LL M (r) �clI �� Co 01 a�� o 0 -� ) : CL a C a. 11 a V Uj _j .4 ;,- CO z ern a wW � Z> Z W _ W OW 4 I- C.) ,� �S2 fn E Q NJ O Q 8 z 0 CL z0 o Cr z 0 F' z Tn W O W 0 C0 LL 0 F- J W CO to 4 CO cc 0 L) U 0 W N N O z `- 0 Z IOU. r Q N W ow z co O FI u°n aUJI a Q W 2 d Q o L, o j cc n go, Q J Q BI 0' o 11J o .j U Qm0 J !L H N M ��ea U �J W 1--i F- � I-�( E .. U) uj U 2 ry > W < o Q Q ULI Z w � W U. r/) w LU LL LL cli d O co 0 z .ti M ►--H � c E 't15 CL E- � z Ta) i IY4 Q J U O U � UJ z U U � UL4i C0 � tL _= `( F-- v_ L) K O Z z W 0 W W d w F- Q± a- � ui °w c� OL n W 0 4 ? 0 0= (n Q Q; X o O F- z0 Fri O U z F- O a H W .j Z j J O T C) �../ W (0 Z Z zW Z z o J � l/ 1 W O z O Q G) o=) IX 0 E-1 w W z o w E to Uj Q_ 11. �{! C13 U) U_ cc 0 it .a )-I-( � � w � wrl �yr 1-4 C� SZS I O SOW Z O ccZ ai/�fsl m �aa o DRAWN BY: DATE: CCRJR 9/18/12 DESIGNED BY: DATE: CCRJR 9118/12 APPROVED BY: DATE: PROJECT NUMBER: 263- 4100341966250317 SHEET TITLE/ PATH: \\Sgmiamil \DRAFTI NG\00- 2003\SOUTH MIAMI HOSPITAL (MASTER SITE)\SMH ET CVVI 966250317 REV00 SHEET NUMBER: NOTES SIZED (24-X36`}