12-1353-042Oj INSTALL NEW PANEL 1 MNHI AND RE -FEED LOADS OF EXISTING
PANELS D5, D6 & D8 AS WELL AS DUCT HEATER EDH -I.
REFER TO RISER ON SHEET 3.02 FOR FURTHER DETAILS.
FCU -M -2
O
REPLACE EXISTING LIGHTS IN ROOM
WITH NEW. REFER TO SHEET EO.01
FOR LIGHT FIXTURES SPECIFICATIONS.
LA -29
MAIN BUILDING FIRST FLOOR
ELECTRIC ROOM PLAN - PHASE 2E
N
f'I'I'r'I I
0' 2' 4' 8' 16' 24'
KEYED NOTES
O COORDINATE EXACT PLACEMENT OF FAN COIL UNIT IN FIELD
TO ENSURE ALL CLEARANCES TO EXISTING PANELBOADS AND
ATS's ARE MAINTAINED.
MED GAS
STORAGE
REMOVE EXISTING EXHAUST
FAN AND BRANCH CIRCUITING
BACK TO SOURCE.
ATS -2 T
i
N
1—
Q
ROOM
1
o.
t
1 X LD
Qw
e m
i 4 i
Uj
J -BOX O
NORMAL
—� EXISTING I
I I SWBD I–
MSBH3 — JI
rO
w
L �I
I ( .
ROOM 10
f j
EXISTING
300kVA
IF XFMR
MSBL3
If
MAIN BUILDING FIRST FLOOR
ELECTRIC ROOM PLAN - PHASE 2B
N
I'I'I'I'I I
0' 1' 2' 4' 8' 12'
KEYED NOTES
O ONCE ALL LOADS HAVE BEEN RE -FED, REMOVE EXISTING
SWITCHBOARD MSBH3 AND ALL ASSOCIATED WIRING. DEMOLISH
EXISTING CONDUITS NOT BEING REUSED TO THE FURTHEST
EXTENT POSSIBLE. CUT AND CAP EXISTING UNDERGROUND
CONDUITS FLUSH WITH THE FLOOR SLAB.
O2 REMOVE EXISTING JUNCTION BOX ASSOCIATED WITH SPLICES FOR
MSBH3. REMOVE ALL WIRING BACK TO SOURCE AND ALL CONDUITS
TO THE FURTHEST EXTEND POSSIBLE. TURN OFF ASSOCIATED
BREAKER IN MSN2 AND PROVIDE NEW LABEL TO INDICATE 'SPARE'.
SEAL ALL UNUSED OPENINGS.
O3 REMOVE EXISTING PANEL D8.
O4 REMOVE ABANDONED ANNUNCIATOR PANEL AND ANY ALL OTHER
ABANDONED EQUIPMENT, CABINETS, CONDUITS, EQUIPMENT, ETC
WITHIN ROOM.
O REMOVE ABANDONED EQUIPMENT, CONDUIT AND WIRING IN ROOM.
CUT BACK ALL CONDUITS TO FURTHEST EXTENT POSSIBLE.
UP TO B8 /E8
WIREWAY
MED A
STORAGE
MAIN BUILDING FIRST FLOOR
ELECTRIC ROOM ;PLAN - PHASE 2C N
f i'T
0' 1' 2' 4' 8' 12'
KEYED NOTES
O1 INSTALL NEW XFMR IMCLDI, PANEL IMCLDI AND ASSOCIATED
FEEDERS FROM 300A ENCLOSED BREAKER INSTALLED DURING
PHASE 1.
O INSTALL NEW FEEDER TO XFMR 1MCLDi TO 300A ENCLOSED
BREAKER INSTALLED DURING PHASE 1.
O INSTALL NEW CONDUIT ! AND FEEDERS TO EXISTING PANELS
FED BY MSBL3 TO THE FURTHEST EXTENT POSSIBLE.
COORDINATE A SHUTDOWN WITH THE HOSPITAL TO REMOVE
EXISTING FEEDER AT EACH OF THESE EXISTING PANELS /LOADS
AND CONNECT NEW FEEDER FROM IMCLDI. REFER TO RISER
ON SHEET E3.02 FOR PANELS TO BE RE -FED.
i XuoJ �
I O
` m �.I
a00 i
REMOVE EXISTING EXHAUST
FAN AND BRANCH CIRCUITING
BACK TO SOURCE.
MAIN BUILDING FIRST FLOOR
ELECTRIC ROOM PLAN - PHASE 2' D
N
I'I'I'I'I I
0' it 2' 4' 8' 12'
KEYED NOTES
0 ONCE ALL LOADS FROM MSBL3 HAVE BEEN RE -FED TO IMCLDI,
REMOVE EXISTING SWITCHBOARD MSBL3, XFMR MSBL3 & DISCONECT
SWITCH AND ALL ASSOCIATED FEEDER WIRING BACK TO SOURCE
AND LOADS. REMOVE ALL CONDUITS TO THE FURTHEST EXTENT
POSSIBLE.
O CONTRACTOR SHALL CLEAN AND PAINT ENTIRE ROOM. REFER TO
ARCHITECTURAL DOCUMENTS FOR PAINTING SPECIFICATIONS.
CONSTRUCTION LEGEND
SYMBOL
DESCRIPTION
EXISTING TO REMAIN
- - --
EXISTING TO BE REMOVED
NEW CONSTRUCTION
Rte.,
R
R
Rte,.
s__ R Na ithl C • an
ld,inc.
600 ablest Hillsboro, Suite 300
Deerfield Reach, FL: 33441
(954) 421 -1260
ry AX: (904,- 421 -14ao
www.ssr- inc.com
Firm Certification - EB- 0000857
John E. Moulder PE - 33200
Michael A Steward PE - 65701
SSR JOB # 1232030.0
.J
Q W U)
(L 3: T
z CM
U3 O W w C
0 � I=
_ =W �;
"a o
tiL
Q O
—z� �Q
W C6
_ °� Cr o =
1—ZCn ��
O Q U)
U)
�,�`G�PE�• srE`yq
No
• F : �Z' G
%� .,CORIOP`.•��j ��
S/O N
rrrlil
DRAWN
CHECKED
DATE 11/12/12
REVISED
SHEET NO.
MAIN BLDG
ENLARGED ELEC RM
FLOOR PLANS
- PHASE 2
E2.03