12-1353-040r
MAIN BUILDING FIRST FLOOR
ELECTRIC ROOM PLAN — PHASE 1 A N
I'1'I'i'I I
0' 1' 2' 4' 8' 12'
KEYED NOTES
OI DEMOLISH ABANDONED ATS -I. REMOVE ALL CONDUIT AND WIRING
BACK TO SOURCE. TURN OFF ASSOCIATED BREAKERS IN MSHB4
AND EDP4 AND PROVIDE NEW LABEL TO INDICATE 'SPARE'.
REMOVE ANY NON-APPLICABLE LABELS.
O REMOVE ABANDONED ENCLOSED CIRCUIT BREAKER AND ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE /LOAD.
''(EPLACE EXISTING LIGHTS IN ROOM
WITH NEW. REFER TO SHEET EO.01
=0R LIGHT FIXTURES SPECIFICATIONS.
LA -27
MAIN BUILDING FIRST FLOOR
ELECTRIC ROOM PLAN — PHASE 1 E
N
0' 2' 4' 8' 16' 24'
KEYED NOTES
OI COORDINATE EXACT PLACEMENT OF FAN COIL UNIT IN FIELD
TO ENSURE ALL CLEARANCES TO EXISTING PANELBOADS AND
ATS's ARE MAINTAINED.
MAIN BUILDING FIRST FLOOR
ELECTRIC ROOM PLAN — PHASE 1 B
N
1'1'1'1')
0' 1' 2' 4' 8' 12'
KEYED NOTES
(D INSTALL NEW XFMR EM. ECB EM AND ASSOCIATED
FEEDERS FROM 2LSHD AND TO EXISTING PANEL EM.
O RE -FEED EXISTING PANEL EM FROM NEW TRANSFORMER & ECB
OAFTER WORK TO RE -FEED PANEL EM IS COMPLETE REMOVE
EXISTING XFMR EM. REMOVE CONDUIT AND WIRE BACK TO
SOURCE.
qO AFTER WORK TO RE -FEED PANEL EM IS COMPLETE REMOVE
ATS -4. REMOVE ALL CONDUIT AND WIRING BACK TO SOURCE.
TURN OFF ASSOCIATED BREAKERS IN MSHB3 AND EDP4 AND
PROVIDE NEW LABEL TO INDICATE 'SPARE'. REMOVE ANY
NON- APPLICABLE LABELS.
1
O2 UP TO 4TH FLR-
REFER TO SHEET
E1.03 FOR
CONTINUATION
0
SWBD MSHB4
ESSENTIAI_
=�
N
MAIN BUILDING FIRST FLOOR
ELECTRIC ROOM PLAN — PHASE 1 C N
0' 1' 2' 4' 8' 12'
KEYED NOTES
(D INSTALL NEW ATS -2 INSTALL NEW EMERGENCY AND NORMAL
FEEDERS UP TO THE.....,,.,. INTERCEPTION POINT. REFER TO
KEYED NOTE 3.
O INSTALL NEW LOAD FEEDERS FROM NEW ATS -2 UP TO EXISTING
TAP BOX FOR PANELS DP & DPA ON 4TH FLOOR. COORDINATE
CONNECTION OF NEW! FEEDERS WITH SHUTDOWN OF EXISTING ATS -2.
ANY EXPOSED CONDUITS SHALL BE PAINTED TO MATCH THE COLOR
OF THE ADJACENT SURFACE.
O3 PROVIDE NEW JUNCTION BOXES AND INTERCEPT EXISTING ATS -2
EMERGENCY AND NORMAL SOURCE FEEDERS AND SPLICE TO NEW
ATS -2 FEEDERS. COORDINATE DOWNTIME WITH HOSPITAL.
i
qO AFTER WORK TO SPLICE ATS -2 FEEDERS TO NEW ATS -2 IS
COMPLETE. REMOVE EXISTING ATS -2 AND ASSOCIATED CONDUIT
AND WIRING NO LONGER IN USE.
O PROVIDE 12'X12' JUNCTION BOX FOR ATS ENGINE START WIRING.
PROVIDE 1' CONDUIT TO EMERGENCY PARALLELING SWITCHGEAR
ESPS. PROVIDE 3/4' CONDUIT TO EACH ATS. REFER TO KEYED
NOTE 1 ON SHEET E3.01.
O PROVIDE 120X12' JUNCTION BOX FOR ATS COMMUNICATIONS WIRING.
PROVIDE In CONDUIT TO EMERGENCY PARALLELING SWITCHGEAR
ESPS. PROVIDE 3/4' CONDUIT TO EACH ATS. REFER TO KEYED
NOTE 2 ON SHEET E3.01.
REFER TO SHEET E1.01
DESCRIPTION
FOR CONTINUATION
1
— — — -
EXISTING TO BE REMOVED
ATS =2 C
5
6 IT
n n
;4
0
F
I�
a
- -�,N
r
N
H
t 3
L
L E C T.
EDP4
MED GAS
} EDP4 ODM
STORAGE
C°x
MSBH4 4
MSBH4
)W
M
1
1
U'
In
H
r
a
U
XZ
Ow
m�
W nnv
O2 UP TO 4TH FLR-
REFER TO SHEET
E1.03 FOR
CONTINUATION
0
SWBD MSHB4
ESSENTIAI_
=�
N
MAIN BUILDING FIRST FLOOR
ELECTRIC ROOM PLAN — PHASE 1 C N
0' 1' 2' 4' 8' 12'
KEYED NOTES
(D INSTALL NEW ATS -2 INSTALL NEW EMERGENCY AND NORMAL
FEEDERS UP TO THE.....,,.,. INTERCEPTION POINT. REFER TO
KEYED NOTE 3.
O INSTALL NEW LOAD FEEDERS FROM NEW ATS -2 UP TO EXISTING
TAP BOX FOR PANELS DP & DPA ON 4TH FLOOR. COORDINATE
CONNECTION OF NEW! FEEDERS WITH SHUTDOWN OF EXISTING ATS -2.
ANY EXPOSED CONDUITS SHALL BE PAINTED TO MATCH THE COLOR
OF THE ADJACENT SURFACE.
O3 PROVIDE NEW JUNCTION BOXES AND INTERCEPT EXISTING ATS -2
EMERGENCY AND NORMAL SOURCE FEEDERS AND SPLICE TO NEW
ATS -2 FEEDERS. COORDINATE DOWNTIME WITH HOSPITAL.
i
qO AFTER WORK TO SPLICE ATS -2 FEEDERS TO NEW ATS -2 IS
COMPLETE. REMOVE EXISTING ATS -2 AND ASSOCIATED CONDUIT
AND WIRING NO LONGER IN USE.
O PROVIDE 12'X12' JUNCTION BOX FOR ATS ENGINE START WIRING.
PROVIDE 1' CONDUIT TO EMERGENCY PARALLELING SWITCHGEAR
ESPS. PROVIDE 3/4' CONDUIT TO EACH ATS. REFER TO KEYED
NOTE 1 ON SHEET E3.01.
O PROVIDE 120X12' JUNCTION BOX FOR ATS COMMUNICATIONS WIRING.
PROVIDE In CONDUIT TO EMERGENCY PARALLELING SWITCHGEAR
ESPS. PROVIDE 3/4' CONDUIT TO EACH ATS. REFER TO KEYED
NOTE 2 ON SHEET E3.01.
14 1_-
MAIN BUILDING FIRST FLOOR
ELECTRIC ROOM PLAN — PHASE 1 D N
1111111
0' 1' 2' 4' 8' 12'
KEYED NOTES
O INSTALL NEW ATS -3. INSTALL NEW EMERGENCY AND NORMAL
FEEDERS UP TO THE INTERCEPTION POINT. REFER TO
KEYED NOTE 4.
O INSTALL NEW LOAD FEEDERS FROM NEW ATS -3 TO EXISTING
ATS -3 LOAD SIDE DISCONNECT. COORDINATE CONNECTION OF
NEW FEEDERS WITH SHUTDOWN OF EXISTING ATS -3
O3 INSTALL NEW 3P.300A ENCLOSED CIRCUIT BREAKER AND
FEEDER FROM NEW ATS -2 LUGS AND LEAVE BREAKER OFF
FOR FUTURE CONNECTION UNDER PHASE 2.
4O PROVIDE NEW JUNCTION BOXES AND INTERCEPT EXISTING ATS -3
EMERGENCY AND NORMAL SOURCE FEEDERS AND SPLICE TO NEW
ATS -3 FEEDERS. COORDINATE DOWNTIME WITH HOSPITAL.
O AFTER WORK TO SPLICE ATS -3 FEEDERS TO NEW ATS -3 IS
COMPLETE. REMOVE EXISTING ATS -3 AND ASSOCIATED CONDUIT
AND WIRING NO LONGER IN USE.
OCONTRACTOR SHALL CLEAN AND PAINT ENTIRE ROOM.REFER TO
ARCHITECTURAL DOCUMENTS FOR PAINTING SPECIFICATIONS.
CONSTRUCTION LEGEND
SYMBOL
DESCRIPTION
EXISTING TO REMAIN
— — — -
EXISTING TO BE REMOVED
NEW CONSTRUCTION
F
I�
a
r
xxz
EDP4
-
C°x
MSBH4 4
E
)W
1
U'
J -BOX
NORMAL
EXISTING
SWBD
MSBH3
�IW
M
ROOM
co
V)
_j
�
fr/
d
EXISTING
300kVA
XFMR
MSBL3
14 1_-
MAIN BUILDING FIRST FLOOR
ELECTRIC ROOM PLAN — PHASE 1 D N
1111111
0' 1' 2' 4' 8' 12'
KEYED NOTES
O INSTALL NEW ATS -3. INSTALL NEW EMERGENCY AND NORMAL
FEEDERS UP TO THE INTERCEPTION POINT. REFER TO
KEYED NOTE 4.
O INSTALL NEW LOAD FEEDERS FROM NEW ATS -3 TO EXISTING
ATS -3 LOAD SIDE DISCONNECT. COORDINATE CONNECTION OF
NEW FEEDERS WITH SHUTDOWN OF EXISTING ATS -3
O3 INSTALL NEW 3P.300A ENCLOSED CIRCUIT BREAKER AND
FEEDER FROM NEW ATS -2 LUGS AND LEAVE BREAKER OFF
FOR FUTURE CONNECTION UNDER PHASE 2.
4O PROVIDE NEW JUNCTION BOXES AND INTERCEPT EXISTING ATS -3
EMERGENCY AND NORMAL SOURCE FEEDERS AND SPLICE TO NEW
ATS -3 FEEDERS. COORDINATE DOWNTIME WITH HOSPITAL.
O AFTER WORK TO SPLICE ATS -3 FEEDERS TO NEW ATS -3 IS
COMPLETE. REMOVE EXISTING ATS -3 AND ASSOCIATED CONDUIT
AND WIRING NO LONGER IN USE.
OCONTRACTOR SHALL CLEAN AND PAINT ENTIRE ROOM.REFER TO
ARCHITECTURAL DOCUMENTS FOR PAINTING SPECIFICATIONS.
CONSTRUCTION LEGEND
SYMBOL
DESCRIPTION
EXISTING TO REMAIN
— — — -
EXISTING TO BE REMOVED
NEW CONSTRUCTION
.. M1 n. 1 1 1
I-ml ht p Inc.
600 `Nest Hillsborc, Suite 300
Deerf>,eld @each, 'FL, 33441
a (954) 421 -1260
FAX: (954) 421 -1466
www.ssr- inc.com
Firm Certification - EB- 0000857
John E' Moulder PE -33200
Michael A Steward PE - 65701
SSR JOB # 1232030.0
J
�W�
F— �
C3:z r
U) O W w M
0E-� �o
_ =W F-
—� �o
O
M LL
—zlimmAmms �Q
W u)
_OZ5cr cc::))
1— z U) � �
Q I-- �
O Q
C/)�
\\ OWN \ \` \\\``wlk 1 11111 I /M.I.
1 =.
OC1—
DRAWN
CHECKED
DATE 11/12/12
REVISED
SHEET N0.
MAIN BLDG
ENLARGED ELEC RM
FLOOR PLANS
- PHASE 1
E2.01