12-1353-035RATED PENETRATION DETAILS ULlcUL SYSTEM NO. C -AJ -1421 METAL PIPE THROUGH A SLEEVE IN CONCRETE FLOOR/WALL OR BLOCK WALL F- RATING = 2 -HR. AND 3 -HR. T- RATING = 0 -HR. TOP VIEW "T ` I 1 A SECTION A -A 1. CONCRETE FLOOR OR WALL ASSEMBLY (2 -HR. OR 3 -HR. FIRE - RATING) : A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MINIMUM 4 -112" THICK). B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL. 2.OPTIONAL: MAXIMUM 6" DIAMETER STEEL PIPE SLEEVE (SCHEDULE 40 OR HEAVIER). 3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING: A. MAXIMUM 4" DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER). B. MAXIMUM 4" DIAMETER CAST IRON PIPE. C. MAXIMUM 4" NOMINAL DIAMETER COPPER PIPE. D. MAXIMUM 4" NOMINAL DIAMETER STEEL CONDUIT. E. MAXIMUM 4" NOMINAL DIAMETER EMT. 4. MINIMUM 4" THICKNESS MINERAL WOOL (MINIMUM 4 PCF DENSITY) TIGHTLY PACKED. 5. MINIMUM 1/4" DEPTH CP 604 SELF - LEVELING FIRESTOP SEALANT OR HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT. 6. MINIMUM 1/4" BEAD HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT AT POINT OF CONTACT. IWNT 0CnI I10 En lA1UChi U I I TI nn dnA 0 C1 C 1 C\/C1 IAI P! CICCQTAC CCAI ALIT IQ 110CM ITC 1111 \IA G\ NOTES: 1. MAXIMUM DIAMETER OF OPENING = 6 ". 2. ANNULAR SPACE = MINIMUM 0 ", MAXIMUM 5- 318 ". 3. MINIMUM 114" DEPTH HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT IS REQUIIRED ON EACH SIDE OF A WALL ASSEMBLY. 4. F- RATING IS 3 -HR. WHEN HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT IS USED, AND 2 -HR. WHEN HILTI CP 604 SELF - LEVELING FIRESTOP STOP SEALANT IS USED. C4 M O N Q U Sheet 1 of 1 Drawing No. HILTI, Inc. Scale 7132« =1" CAJ FIRESTOP SYSTEMS Tulsa, Oklahoma USA (918) 252 -6000 Date March 22, 2004 1421 e Saving Lives through Innovation and Educat /on UL1cUL SYSTEM NO. W -L -1054 METAL PIPE THROUGH 1 -HR. OR 2 -HR. GYPSUM WALL ASSEMBLY F- RATING =1 -HR. OR 2 -HR. T- RATING = 0 -HR. L- RATING AT AMBIENT = LESS THAN 1 CFM /SQ. FT. L- RATING AT 400 "F = 4 CFM /SQ. FT. FRONT VIEW A A 1. GYPSUM WALL ASSEMBLY (UL1ULC CLASSIFIED U300 OR 0400 SERIES) (1 -HR. OR 2 -HR. FIRE- RATING) (2 -HR. SHOWN). 2. (NOT SHOWN). WOOD STUDS TO CONSIST OF NOMINAL 2" x 4" LUMBER. STEEL STUDS TO BE MINIMUM 2 -112" WIDE. 3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING: A. MAXIMUM 30" DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER). B. MAXIMUM 30" DIAMETER CAST IRON PIPE. C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE. D. MAXIMUM 6" NOMINAL DIAMETER STEEL CONDUIT. E. MAXIMUM 4" NOMINAL DIAMETER EMT. 4. MINIMUM 5/8" DEPTH HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT. 5. MINIMUM 112" BEAD HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT AT POINT OF CONTACT. NOTES: 1. MAXIMUM DIAMETER OF OPENING: A. 32 -114" FOR STEEL STUD WALLS. B.14 -112" FOR WOOD STUD WALLS. 2. ANNULAR SPACE = MINIMUM 0 ", MAXIMUM 2- 114 ". 3. PIPE MAY BE INSTALLED WITH CONTINUOUS POINT OF CONTACT. 4. PIPE MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45° FROM PERPENDICULAR. N O 0 0 Sheet 1 of 1 Drawing No. �D HILTI, Inc Scale 7/32"= V WL FIRESTOP SYSTEMS Tulsa, Oklahoma USA (918) 252 -6000 Date Nov. 6, 2002 1054q Saving Lives through Innovation and Education ABBREVIATIONS SYMBOL DESCRIPTION ABC ABOVE COUNTER ACLG ABOVE FINISHED CEILING AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE ATS AUTOMATIC TRANSFER SWITCH BKR BREAKER CB CIRCUIT BREAKER cd CANDELA CKT CIRCUIT CL CENTER LINE CLG CEILING MOUNTED DEVICE DISC DISCONNECT DIV DIVISION ECB ENCLOSED CIRCUIT BREAKER EX EXISTING F FRAME F/A FIRE ALARM FBO FURNISHED BY OTHERS FLA FULL LOAD AMPS FU FUSE G GROUND HP HORSE POWER K KILO MCB MAIN CIRCUIT BREAKER MLO MAIN LUGS ONLY NEC NATIONAL ELECTRIC CODE NIC NOT IN CONTRACT OC OVER CURRENT OCP OVER CURRENT PROTECTION P POLE PH PHASE SMH SPECIAL MOUNTING HEIGHT TV TELEVISION TYP TYPICAL UH UNIT HEATER UG UNDER GROUND ELECTRICAL LION UNLESS OTHERWISE NOTED V VOLT(S) VA VOLT - AMPS) W WATT(S). WIRE, WALL TELEPHONE OUTLET WP WEATHERPROOF DEVICE. NEMA 3R XFMR TRANSFORMER GENERAL NOTES IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REMOVE EXISTING EQUIPMENT AS REQUIRED TO ACCOMPLISH THE NEW WORK AS SHOWN OR REASONABLY IMPLIED. THE CONTRACTOR SHALL REFER TO ALL OTHER DOCUMENTS INCLUDING ARCHI TECTURAL. PLUMBING. FIRE PROTECTION. MECHANI CAL AND ELECTRICAL WORK SHOWN ON THE OTHER DRAWINGS OF THIS SET TO DETERMINE THE EXTENT OF DEMOLI TI ON REOUI RED. WHEN REMOVING ELECTRICAL EQUIPMENT AND SYSTEMS. ALL PRECAUTIONS SHALL BE TAKEN TO PREVENT STRUCTURAL DAMAGE TO THE BUILDING. THE CONTRACTOR SHALL COORDINATE INSTALLATION OF ANY STRUCTURAL SUPPORTS REQUIRED. TEMPORARY OR PERMANENT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL DEMOLITION AND CONSTRUCTION DEBRIS GENERATED FROM WORK ON ALL FLOORS. TAKING CARE TO PREVENT EXCESSIVE LOADING OF FLOOR ASSEMBLIES. THE CONTRACTOR SHALL MAINTAIN CONTINUITY OF CIRCUITS WHERE EXISTING EQUIPMENT IS TO BE REMOVED AND DOWN STREAM DEVICES MAY BE EFFECTED. THE CONTRACTOR SHALL COORDINATE ALL POWER INTERRUPTIONS WITH OWNER. SEE SPECI FI CATI DNS. WHEN EXISTING ELEMENTS OF ELECTRICAL EQUIPMENT AND SYSTEMS ARE REMOVED. ALL REMAINING OPENINGS IN THE SLAB AND WALLS SHALL BE FILLED IN BY THE CONTRACTOR. THE FIRE RATING OF THE EXISTING STRUCTURE SHALL BE MAI NTAI NED. REMOVE ALL MISCELLANEOUS FIXTURES AND EQUIPMENT RETAINING ITEMS TO BE IDENTIFIED FOR SALVAGE AND STORAGE AT THE DIRECTION OF THE OWNER. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO MAINTAIN THE INTEGRITY AND OPERATION OF EXISTING LIFE SAFETY & EMERGENCY EGRESS EQUIPMENT. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO MAINTAIN ACCESS TO ALL MEANS OF EGRESS CORRIDORS. DOORWAYS AND STAIRS. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO PERMIT EFFECTED AREAS TO CONTINUE TO FUNCTION TO THE GREATEST EXTENT POSSIBLE. THIS EFFORT SHALL INCLUDE SCHEDULED COORDINATION WITH OWNER OF ELECTRICAL SHUTDOWNS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL FLUORESCENT AND HID TYPE LAMPS AND PROPER DISPOSAL OF SAID LAMPS AND SHALL PROVI DE VERI FI CATI ON OF LAMP DI SPOSAL TO THE OWNER UPON REQUEST. ALL CONDUIT, JUNCTION BOXES AND WIRING DEVICES THAT ARE NOT INTENDED TO RE -USED MUST BE DEMOLISHED BACK TO THE SOURCE. PROVIDE PANEL SCHEDULES. TO THE ENGINEER, INDICATING THE CIRCUITS MADE SPARE BY DEMOLITION AND THE EXISTING CIRCUITS THAT REMAIN ACTIVE. IT SHALL BE THE RESPONSIBILITY OF THE CONSTRUCTION MANAGER (CM) . GENERAL CONTRACTOR (GC). AND THE SUB - CONTRACTORS (SC) TO STUDY ALL THE DRAWINGS AND DETAILS SO THAT THE INSTALLATION OF ALL NEW WORK CAN BE FULLY COORDINATED. THE CM. GC, AND SC SHALL VISIT THE SITE, INCLUDING DOI NG AN ABOVE CEILING INSPECTION. DURING BIDDING TO SATISFY HIM /HER SELF THAT ALL PROVISIONS HAVE BEEN MADE FOR ALL ASPECTS OF THIS PROJECT. IF DISCREPANCIES EXIST BETWEEN DRAWINGS AND /OR SITE CONDITIONS. THE CONTRACTOR SHALL NOTIFY THE GENERAL CONTRACTOR IN WRITING PRIOR TO BID DUE DATE. FAILURE TO DO SO WILL NOT BE ALLOWED ON A BASIS FOR ADDITIONAL COMPENSATION TO CORRECT A DIFFICULTY OR DIFFERENCE FROM CONDITIONS INFERRED OR INDICATED ON THE DRAWINGS. DRAWINGS ARE DIAGRAMMATIC AND DO NOT INDICATE ALL DEVICES TO BE DEMOLISHED. CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID TO FIELD CONFIRM ALL REQUIREMENTS. CONTRACTOR SHALL SUPPORT ALL EXISTING CONDUITS AND LOW VOLTAGE WIRING PASSING THRU OR SERVING THE AREA THAT ARE TO REMAIN WHICH ARE NOT PROPERLY SUPPORTED AS REQUIRED BY THE SPECIFICATIONS. INFECTION CONTROL MEASURES: A. CONTRACTOR SHALL OBTAIN FROM THE OWNER A COPY OF THE INFECTION CONTROL RISK ASSESSMENT (ICRA) PREPARED FOR THIS PROJECT. CONTRACTOR SHALL REVIEW THE REQUIREMENTS IN THE REPORT AND PERFORM ALL WORK IN ACCORDANCE WITH THOSE REQUIREMENTS. CONTRACTOR SHALL STRICTLY ADHERE TO THE LIMITS OF THE CONSTRUCTION AREA, AND WHERE PHASING APPLIES SHALL ADHERE TO THE PHASING PLAN. ANY WORK OUTSIDE THE CONSTRUCTION AREA SHALL BE COORDINATED WITH THE OWNER AND PERFORMED IN ACCORDANCE WITH THE ICRA REPORT, UNDER THE SUPERVISION OF THE OWNER'S REPRESENTATIVE OR OTHER DESIGNATED ICRA COMMITTEE OFFICER. B- TO THE EXTENT THAT IT IS REQUIRED BY THE ICRA, THE CONTRACTOR SHALL ENDEAVOR TO MAINTAIN EXISTING LEVELS OF INDOOR AIR QUALITY IN AREAS SURROUNDING AND ADJACENT TO THE CONSTRUCTION WORK ZONE, AND ELSEWHERE IN THE FACILITY. IT SHOULD BE ANTICIPATED THAT THE ICRA REPORT WILL REQUIRE MEASURES TO THIS EFFECT INCLUDING ERECTION OF CONSTRUCTION ZONE BARRIERS AND PROVISION OF NEGATIVE AIR PRESSURE IN THE CONSTRUCTION ZONE RELATIVE TO OTHER AREAS OF THE FACILITY. C. REFER TO MECHANICAL DRAWINGS FOR CONTAINMENT VESTIBULE DETAILS FOR WORK DONE IN PUBLIC AND PATIENT CORRIDORS AND SPACES. LIGHTING FIXTURE SCHEDULE ® BEGHELLI BS100T5- 4- SA- 228W -FP -CH 2 -28WT5 NON- FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES) 48W SUSPENDED CHAIN HUNG VAPOR TIGHT FLUORESCENT TYPE MANUF. CATALOG NO. LAMPS VOLTS WATTAGE MOUNTING REMARKS ® BEGHELLI BS100T5- 4- SA- 228W -FP -CH 2 -28WT5 NON- FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES) 48W SUSPENDED CHAIN HUNG VAPOR TIGHT FLUORESCENT qEj COMBINATION MOTOR STARTER ® FACTORY WIRED CONTROLLER OR EQUIPMENT WITH INTEGRAL BATTERY PACK GENERAL LIGHTING FIXTURE NOTES: COORDINATE VOLTAGE WITH CIRCUIT FOR LIGHT 1. CONTRACTOR MUST QUOTE SPECIFIED LIGHTING FIXTURES AS BASE BID. ANY ALTERNATE LIGHTING PRODUCTS MUST BE SHOWN AS AN EXCEPTION TO BASE BID, AND MUST BE ACCOMPANIED BY UNIT PRICES AND TOTAL DOLLAR DEDUCT FROM THE BASE BID. 2. ANY PROPOSED ALTERNATES SHALL MATCH SPECIFIED LIGHTING FIXTURE CHARACTERISTICS AS FOLLOWS: a. ALL RATINGS INCLUDING, BUT NOT LIMITED TO, WATTAGE, FIRE RATINGS, AND SPECIAL LOCATION RATINGS SUCH AS DAMP OR WET LABELS, HAZARDOUS LOCATION, CLEAN ROOM, TAMPER PROOF, ETC. b. PHYSICAL SIZE AND DIMENSION c. CONSTRUCTION d. MATERIAL e. LAMP AND BALLAST TYPE f. LENS AND REFLECTOR TYPE g. PAINT APPLICATION PROCESS h. PHOTOMETRIC CHARACTERISTICS 3. PROVIDE IN -LINE FUSING FOR ALL FLUORESCENT FIXTURES ON THE LIFE SAFETY AND CRITICAL BRANCHES. LEGEND SYMBOL DESCRIPTION MOUNTING HEIGHT ® CRITICAL BRANCH SUSPENDED FLUORESCENT FIXTURE q= NON- FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES) FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES) qEj COMBINATION MOTOR STARTER ® FACTORY WIRED CONTROLLER OR EQUIPMENT MOTOR CONNECTION O JUNCTION BOX s PANELBOARD - FLUSH MOUNTED PANELBOARD - SURFACE MOUNTED S 120V MOTOR RATED SWITCH WITH THERMAL OVERLOAD T - MOUNT NEXT TO EQUIPMENT BEING CONTROLLED. $3 THREE WAY SWITCH - RED TOGGLE PACP PRE - ACTION CONTROL PANEL CONCEALED CONDUIT CONDUIT CONCEALED IN FLOOR OR BELOW GRADE HOMERUN TO PANELBOARD - NUMBER OF PHASE CONDUCTORS IN MINIMUM 3/4 CONDUIT UNLESS NOTED OTHERWISE NOTES: 1. ONE NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR, ALTHOUGH NOT INDICATED. SHALL BE INCLUDED IN EACH RACEWAY UNLESS OTHERWISE NOTED. 2. ONE INSULATED GREEN GROUNDING CONDUCTOR, ALTHOUGH NOT INDICATED, SHALL BE INCLUDED IN EACH RACEWAY UNLESS OTHERWISE NOTED. 3. HOMERUNS TO PANELBOARDS SHALL HAVE A MAXIMUM OF THREE (3) PHASE CONDUCTORS (ONE PER PHASE) PLUS THREE (3) NEUTRAL CONDUCTORS AND ONE (1) GROUND CONDUCTOR IN EACH CONDUIT. 4. MULTI -WIRE BRANCH CIRCUITS THAT SHARE A COMMON NEUTRAL SHALL NOT BE PERMITTED FOR INDIVIDUAL LINE -TO- NEUTRAL LOADS. 5. EACH CIRCUIT (PHASE AND NEUTRAL CONDUCTORS) SHALL BE GROUPED TOGETHER USING CABLE TIES AT THE PANELBOARD AND ALL JUNCTION BOXES, PULL BOXES AND ALL OTHER LOCATIONS WHERE TERMINATIONS, CONNECTIONS OR SPLICES ARE MADE. 6. ALL CONDUCTORS SHALL BE n12 AWG UNLESS OTHERWISE NOTED. ALL WORK SHALL COMPLY WITH THE 2008 EDITION OF THE NEC. 0 TRANSFORMER (MAX. WT. = 500lbs.) SECURELY ANCHOR TRANSFORMER TO UNISTRUT 0 NINETY DEGREE FITTING. UNISTRUT #P1068 (TYPICAL OF 4) TYPICAL CHANNEL. UNISTRUT UP1000 ANGULAR FITTING. UNISTRUT "P1186 (TYPICAL ON THREE SIDES OF LOWER TRANSFORMER) UNISTRUT #P1068 WITH - v 1/2 DIA. HILT. KWIK BOLT INTO CONCRETE. ANGULAR FITTING. UNISTRUT #P1546 (TYPICAL ON THREE SIDES OF LOWER TRANSFORMER) 0 0 0 o to 0 r� STACKED TRANSFORMERS r� 0 0 0 0 • ' 4' CONCRETE PAD SECURELY ANCHOR TRANSFORMER TO CONCRETE PAD 6' MINN. J T -0' MAX. _mi h ger-ran eI Inc. 600 Wsst Hillsbpr0, Suite 300 - Deer*ield Beach, FL 33441 /pt; 4) h21-1260- FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification - EB- 0000857 John E. Moulder PE - 33200 Michael A. Steward PE - 65701 SSR JOB # 1232030.0 W vJ � �: T- cn O w W M 0�1� 11=o _ =LU ion -�0 -0 LL Q O -Z� �g LU Gr Z °� °o= E- Z U) � 11 � Q � O O Q Cn ��Ipillll��7� ��` t, E X, • Sr. �vq�; GENSF ' • Q �i� No 5 1 s rE OF 111111 DRAWN CHECKED DATE 11/12/12 REVISED SHEET N0. ELECTRICAL LEGEND, ABBREVIATIONS & DRAWING INDEX E0.01