MAIN BUILDING FIRST FLOOR PLAN
DEMOLITION - FIRE PROTECTION N
0' 1' 2' 4' 8' 12'
GENERAL NOTES:
I. CONTRACTOR SHALL PHASE WORK AS DIRECTED BY OWNER.
2. CONTRACTOR SHALL PATCH WALLS, FLOORS, AND CEILINGS TO MATCH EXISTING
FINISHES FOR DEMOLITION AND INSTALLATION OF FIRE PROTECTION SYSTEMS. COORDINATE
WITH ARCHITECTURAL DRAWINGS.
3. THE HOSPITAL IS OPEN 24 HOURS A DAY, 7 DAYS A WEEK. THE CONTRACTOR SHALL HAVE
TO PERFORM WORK WITHIN ACTIVE PATIENT CARE AREAS. CONTRACTOR SHALL:
A. COORDINATE SHUTDOWN OF EXISTING SYSTEMS WELL IN ADVANCE WITH OWNER.
B. PERFORM WORK AT SUCH TIMES AND UNDER SUCH CONDITIONS AS PRESCRIBED BY OWNER.
C. PERFORM WORK WITHIN THE GUIDELINES OF THE ICRA REPORT PREPARED FOR THIS PROJECT
BY THE OWNER.
D. SEQUENCE DEMOLITION AND NEW CONSTRUCTION TO MINIMIZE NUMBER & DURATION OF
SHUTDOWNS REQUIRED. WHERE FEASIBLE INSTALL NEW MAINS PRIOR TO DEMOLITION OF EXISTING.
4. CONTRACTOR SHALL COORDINATE WORK WITH EXISTING CONDITIONS (STRUCTURE, DUCTWORK,
PIPING, CONDUIT, ETC.). PROVIDE OFFSETS AS REQUIRED TO INSTALL NEW WORK.
5. PIPING SHOWN TO BE REMOVED IS NOT TO BE CAPPED AND ABANDONED.
6. CONTRACTOR SHALL COORDINATE TIMING, DURATION AND AREAS AFFECTED BY SHUTDOWNS WITH
HOSPITAL IN ORDER TO FACILITATE REQUIRED FIRE WATCH.
7. CONTRACTOR SHALL COORDINATE NEW SPRINKLER HEAD LOCATIONS WITH CEILING
MOUNTED DEVICES (LIGHTS, DIFFUSERS, SMOKE DETECTORS, ETC.) AND OBSTRUCTIONS TO SPRINKLER
THROW (SOFFITS, PRIVACY CURTAINS, ETC.) PER NFPA 13.
MAIN BUILDING FIRST FLOOR PLAN
NEW CONSTRUCTION - FIRE PROTECTION N
0' 1' 2' 4' 8' IT
KEYED NOTES:
O REMOVE EXISTING SPRINKLER HEAD AND EXTEND EXISTING
HEAD. SEE NEW CONSTRUCTION PLAN.
COORDINATE ALL WORK INCLUDING PHASING
AND SEQUENCING WITH DIV 26.
1' BRANCH PIPING TO NEW SPRINKLER
SPRINKLER SCHEDULE
2 SPRINKLER HEADS REMOVED.
3 SPRINKLERS HEADS ADDED.
ISPRINKLER HEAD ADDED
DEMOLITION LEGEND
SYMBOL
DESCRIPTION
ENEW
EXISTING TO REMAIN
EXISTING TO BE REMOVED
�--�
REMOVE EXISTING TO THIS POINT
CONSTRUCTIO N LEGEND
DESCRIPTION
ENEW
EXISTING TO REMAIN
NEW CONSTRUCTION
CONNECT TO EXIST. AT THIS POINT
AREA OF WORK
)F WORK
KEY IDLA N
SCALE N.T.S.
mi h
er- an
elT,Tnc.
60A W-est Hillsboro, Suite 300
D,'9errWId Beach, FL 33441
:954) 421 -1260
"FAX: (954) 421 -1466
www.ssr- inc.com
Firm certification - EB- 0000857
John E. Moulder PE - 33200
Michael A. Steward PE - 65701
SSR JOB # 1232030.0
WA
T
z HM
cn O W w M
O ~� 1=0
_ = W F- I=
—�U .moo
Cr) LJ_
Q O
—z� �Q
W Gf
=HOC o=
I— ZU) co�
—� O
QQ
O�
C/
E` M0
No. 3
'
,0I :tom.
AL
DRAWN
CHECKED
DATE 11/12/12
REVISED
SHEET NO.
MAIN BUILDING - FIRST
FLOOR PLAN - DEMO. AN
NEW CONSTRUCTION
FIRE PROTECTION
FP2.01