12-1353-024SPRINKLER NOTES
1. ALL FIRE PROTECTION SYSTEM SHALL BE IN COMPLIANCE WITH THE LOCAL FIRE
CODES AND ORDINANCES AND AS PER NFPA 13, 2007 EDITION REQUIREMENTS.
2. MAKE ALL OFFSETS REQUIRED AS PER JOB CONDITIONS.
3. CONTRACTOR TO PROVIDE AND TURN OVER TO THE OWNER AT LEAST (6)
SPARE SPRINKLERS OF SAME TYPE AND TEMPERATURE RATING BEING INSTALLED
INSIDE OF BOX. COORDINATE LOCATION WITH OWNER.
4. PROVIDE AND MAINTAIN A MINIMUM CLEARANCE OF 18" BETWEEN THE
BOTTOM OF THE SPRINKLER DEFLECTOR AND THE TOP OF STORAGE,
FILE, SHELVING, ETC.
5. CONTRACTOR SHALL FIELD VERIFY LOCATION AND QUANTITY OF ALL CEILING
MOUNTED DEVICES INCLUDING SMOKE DETECTORS TO BE REMOVED DURING
CONSTRUCTION TO INSTALL SPRINKLER PIPING. EXISTING EQUIPMENT AND FIXTURES
SHALL BE REPAIRED TO ORIGINAL OPERATION OR REPLACED SHOULD THEY BE
DAMAGED DURING CONSTRUCTION.
6. SCHEDULE 5 PIPING AND FLEXIBLE SPRINKLER HEAD DROPS ARE
NOT APPROVED OR ACCEPTED PRODUCTS.
7. CONTRACTOR SHALL COORDINATE WITH STRUCTURE AND OTHER TRADES
BEFORE INSTALLING SPRINKLER WORK.
8. SPRINKLER HEAD RATED @ 155 DEGREES F., %" ORIFICE WITH 5.6, "K" FACTOR,
STANDARD RESPONSE.
9. INSTALL PIPING TIGHT TO STRUCTURE WHERE POSSIBLE.
10. SPRINKLER SYSTEM TO BE INSTALLED BY A STATE CERTIFIED FIRE
PROTECTION CONTRACTOR.
11. FIRE PROTECTION SERVICES TO BE REMOVED SHALL BE CAPPED AND PLUGGED.
12. SYSTEM DESIGNED FOR ORDINARY HAZARD GROUP 1 OCCUPANCY.
13. CONTRACTOR SHALL REMOVE EXISTING SPRINKLER HEADS AS SHOWN AND
ADJUST PIPING TO NEW CEILING PATERN.
14. CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINES INVOLVED
SO AS TO AVOID ANY PIPE ROUTING PROBLEMS.
15. EXISTING SERVICES INDICATED ON THESE DRAWINGS WERE DERIVED
FROM EXISTING DRAWINGS AND LIMITED FIELD OBSERVATIONS. THESE
DRAWINGS MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE
PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES, LOCATION, TYPE
AND SIZE PRIOR TO ANY CONSTRUCTION. ANY DEVIATIONS IMPACTING WORK
SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ENGINEER
FOR COORDINATION PRIOR TO CONSTRUCTION.
16. CONTRACTOR IS RESPONSIBLE FOR RELOCATING ALL EXISTING FIRE MAINS AND
SPRINKLER PIPING TO FACILITATE THE INSTALLATION OF NEW ELECTRICAL,
MECHANICAL AND PLUMBING SYSTEMS. THIS INCLUDES ALL CEILING SPACES,
SHAFTS, WALLS, ETC.
17. PRESSURE TEST PIPING AT 200 PSIG FOR A MINIMUM
OF TWO HOURS. IF LEAKS ARE FOUND THEN CONTRACTOR SHALL
FIX LEAKS AND TEST AGAIN.
18. ANY SYSTEM OR PORTION OF THE FIRE SPRINKLER SYSTEM, THAT IS SHUTDOWN,
FOR 4 HOURS OR GREATER SHALL REQUIRE A FIRE WATCH AS REQUIRED PER THE
FLORIDA FIRE PREVENTION CODE 2010. A FIRE WATCH SHALL ALSO BE PROVIDED FOR
AREAS WHERE THE TEMPORARY ZIP WALLS OR TEMPORARY PARTITIONS ARE PROVIDED
IF ANY FIRE SPRINKLER COVERAGE IS BEING OBSTRUCTED.
COORDINATE WITH HOSPITAL REPRESENTATIVE BEFORE DEACTIVATING ANY SYSTEM.
19. CONTRACTOR SHALL PROVIDE INSTALLATION SHOP DRAWINGS TO THE
ENGINEER FOR APPROVAL PRIOR TO INSTALLATION.
20. SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS IN ACCORDANCE
WITH U.L. FIRE RESISTANCE INDEX FOR THROUGH PENETRATION FIRE STOP
SYSTEMS. COORDINATE REQUIREMENTS WITH ARCHITECTURAL PLANS AND
SPECIFICATIONS.
21. ALL PENETRATIONS OR OPENINGS FROM REMOVED
PIPES THROUGH EXISTING BUILDING
WALLS AND FLOORS SHALL BE SLEEVED AND /OR
PATCHED TO MATCH ORIGINAL. SEE ARCHITECTURAL
DRAWINGS FOR FINAL FINISHES.
22. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE
TO EXISTING PIPING OR EQUIPMENT DUE TO NEW
CONSTRUCTION AND HE SHALL RESTORE EXISTING
WORK TO ITS ORIGINAL CONDITION AT NO COST TO THE
OWNER.
23. PROVIDE HANGERS ON ALL ARMOVERS OF 12" OR MORE IN LENGTH AND PER
NFPA 13.
24. WARRANTY /GUARANTEE
A. THE CONTRACTOR SHALL WARRANTY /GUARANTEE AND MAINTAIN THE STABILITY
OF WORK AND MATERIALS AND KEEP SAME IN PERFECT REPAIR AND CONDITION
FOR THE PERIOD OF ONE YEAR.
B. DEFECTS OF ANY KIND DUE TO FAULTY WORK OR MATERIALS, APPEARING
DURING THE ABOVE MENTIONED PERIOD, MUST BE IMMEDIATELY REPAIRED BY
THE CONTRACTOR AT HIS OWN EXPENSE TO THE ENTIRE SATISFACTION OF THE
OWNER AND ENGINEER. SUCH RECONSTRUCTION AND REPAIRS SHALL INCLUDE
DAMAGE TO THE FINISH OR FURNISHING OF THE BUILDING RESULTING FROM THE
ORIGINAL DEFECT OR REPAIR THERETO.
25. SPRINKLER HEADS SHALL BE A MINIMUM OF 12" FROM ANY DIFFUSER PER NFPA 13.
26. PIPING SHALL NOT BE RUN OVER ANY ELECTRICAL AND PHONE PANELS.
27. THE FIRE PROTECTION CONTRACTOR SHALL KEEP A SET OF MARKED UP DRAWINGS
AS THE JOB PROGRESSES. NO MAJOR CHANGE SHALL BE MADE TO FIRE PROTECTION
DESIGN ENGINEERING UNLESS IT HAS BEEN COORDINATED, DRAWN AND SUBMITTED
FOR APPROVAL.
28. CONTINUITY OF SERVICE: INTERRUPTIONS OF EXISTING SERVICES
OR FACILITIES SHALL BE KEPT TO A MINIMUM AND THE
CONTRACTOR SHALL FURNISH ALL MATERIALS AND LABOR
REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE NECESSARY
TO MAINTAIN CONTINUITY OF SERVICE. INTERRUPTIONS OF THE
EXISTING SERVICES, THE INSTALLATION OF TEMPORARY FACILITIES,
AND THE WORK OF MAKING FINAL CONNECTIONS TO NEW WORK
SHALL BE DONE ONLY AT SUCH TIMES AS PERMITTED AND SCHEDULED
BY THE OWNER. ALL SUCH CONNECTIONS AND TIE -INS SHALL BE
COORDINATED THROUGH THE OWNERS PROJECT MANAGER.
1. THE DURATION OF EACH SHUTDOWN SHALL BE LIMITED TO NIGHTS AND /OR
WEEKENDS WITH THE TIME FRAME FOR SHUTDOWNS AS SPECIFIED BY THE
OWNER. THE CONTRACTOR SHALL NOTIFY THE OWNER IN WRITING FORTY -EIGHT
(48) HOURS IN ADVANCE OF EACH REQUIRED INTERRUPTION
OF EXISTING SERVICE.
2. THE CONTRACTOR SHALL INCLUDE IN BID PRICE ALL PREMIUM TIME CHARGES
(E.G. SHUTDOWNS OF EXISTING SYSTEMS FOR TIE -INS) FOR LABOR AND EQUIPMENT
REQUIRED FOR ALL NIGHT AND WEEKEND OVERTIME WORK, AS NECESSARY, TO
COMPLETE THE SCOPE OF THE CONTRACT.
29. CONTRACTOR SHALL PROVIDE AS BUILT DRAWINGS ALONG WITH ALL CLOSE OUT
DOCUMENTS PRIOR TO PROJECT COMPLETION.
30. CONTRACTOR SHALL OBTAIN FROM THE OWNER A COPY OF THE INFECTION CONTROL
RISK ASSESSMENT (ICRA) PREPARED FOR THIS PROJECT. CONTRACTOR SHALL REVIEW
THE REQUIREMENTS IN THE REPORT AND PERFORM ALL WORK IN ACCORDANCE WITH
THOSE REQUIREMENTS. SEE MECHANICAL DRAWINGS FOR COORDINATION OF VENTILATION
REQUIREMENTS REQUIRED BY ICRA.
" "" DIMENSION. MINIMUM DIA.
"B" (INCHES)
ADJUSTIBLE
CLEVIS MANGER
FOR PIPING 4' AND LARGER
ANVIL FIG #260
3
A
SIDE JOIST ATTACHMENT
OR
SIDE JOIST ADJUSTABLE
HANGER
NOTE:
HANGER ROD DIAMETER IS THE MINIMUM
SIZE PER NFPA. HANGER ROD DIAMETER
SHALL BE THE DIAMETER APPROVED FOR
USE WITH THE HANGER ASSEMBLY.
PIPE HANGER DETAIL
"'" DIMENSION.
[MUM DIA.
PHILLIPS CONCRETE
FASTENER I.T.T. ANVIL
(RED HEAD) TO BE USED ON
NEW CONSTRUCTION. PROVIDE
HILTIKWIK BOLT, ZINC PLATED,
METAL EXPANSION ANCHOR ON
EXISTING CONSTRUCTION
(SEE SPECIFICATIONS).
ADJUSTIBLE
SWIVEL RING HANGER
FOR PIPING 3" AND SMALLER
ANVIL FIG #69
CENTER I -BEAM CLAMP
HANGERS
"A" DIMENSION.
MINIMUN DIA.(INCHES)
THREADED ROD
SIZE. CUT TO ;
LENGTH - -- -
SELF DRILLING CONCRETE WEDGE ANCHOR
)1��
TOP BEAM CLAMP
DANGER SPACING
I. 1" AND 1 ?" DIA. STEEL PIPE: MAXIMUM 12 FT. SPACING.
2. 1" JHRU 3" DIA. THREADED LIGHTWALL PIPE: MAX. 12 FT. SPACING
3. 11/2 AND LARGER DIA. STEEL PIPE: MAXIMUM 15 FT. SPACING.
4. ALL PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH
NFPA -13. EACH SECTION OF PIPE SHALL HAVE NO LESS
THAN ONE HANGER. ARMOVERS EXCEEDING 1 FT. SHALL HAVE
A HANGER.
5. PROVIDE PIPE CLAMP AT EACH FLOOR FOR RISERS
PENETRATING FLOORS.
6. TRAPEZE HANGERS SHALL NOT BE USED.
7. ALL HANGERS SHALL BE U.L. LISTED.
8. ALL EXTERIOR HANGERS SHALL BE STAINLESS STEEL INCLUDING
CLAMPS.THREADED RODS. NUTS & BOLTS.
S. ALL INTERIOR HANGERS SHALL BE GALVANIZED INCLUDING
CLAMPS,THREADED RODS. NUTS & BOLTS.
PIPE
SIZE
A
NOTES:
PIPE
SIZE
A
1. IF ANY PIPES ARE TO BE INSULATED, DO NOT RUN INSULATION THROUGH A RATED FIRE
1
3/8
BARRIER OR RATED SMOKE BARRIER. AFTER SEALING PENETRATIONS AROUND PIPE THROUGH
_-Tv-
3/8
THE WALL WITH "THROUGH - PENETRATION FIRESTOP SYSTEM ", FLARE INSULATION ONTO FACE
1?
3/8
OF WALL AROUND PIPE ON BOTH SIDES OF WALL, AND SEAL TO FACE OF WALL WITH
6
172
INSULATION MASTIC.
1
3/8"_`F/8
2. COMBUSTIBLE CONDUIT AND /OR COMBUSTIBLE PIPE IS NOT ALLOWED.
8
3 5/8" (MINIMUM) SEAL PENETRATIONS WITH APPROVED TESTED
METAL STUDS AT "THROUGH - PENETRATION FIRESTOP SYSTEM" AS
16" O.C. (MAXIMUM) INDICATED BELOW
4 NON- COMBUSTIBLE PIPE OR CONDUIT
&_ /
B
METAL RUNNER
�� �� VERIFY REQUIRED NUMBER OF LAYERS AND TYPE
"X"
A SECTION OF 5/8" TYPE GYPSUM BOARD
2' -0" MAXIMUM FOR FULL - HEIGHT 2' -0" MAXIMUM FOR FULL - HEIGHT
20 GAGE (MINIMUM) METAL STUDS 20 GAGE (MINIMUM) METAL STUDS
1/4
V -4" MAXIMUM
fIA"
(TYPICAL)
METAL RUNNER BEHIND 2" MAXIMUM
GYPSUM BOARD (TYPICAL)
I
SECURELY ATTACHED
0 VERTICAL STUDS)
"A"
"A" 2" MAXIMUM
(TYPICAL) CD z
O.S. &Y. GATE OR BUTTERFLY VALVE
WITAMPER SWITCH.
NON- COMBUSTIBLE
CONDUIT OR PIPING
PACK TIGHTLY WITH "MINERAL FIBER SAFING INSULATION" FOR
V -4" MAXIMUM FULL DEPTH OF BARRIER, AND SEAL PENETRATIONS WITH
(TYPICAL) APPROVED TESTED "THROUGH - PENETRATION FIRESTOP SYSTEM"
PER REQUIREMENTS OF:
ELEVATION 2009 NFPA 101, LIFE SAFETY CODE SECTION 8.3.5
2010 FBC SECTION 712.3 AND
2010 FLORIDA EDITION OF NFPA 101, LIFE SAFETY CODE
SECTION 8.3.5.
TYPICAL MULTIPLE NON- COMBUSTIBLE
CONDUIT OR PIPE PENETRATIONS
DETAIL THROUGH RATED FIRE BARRIERS
NOT TO SCALE AND /OR RATED SMOKE BARRIERS
I HR PENETRATION DETAIL
FIRE STANDPIPE
SYSTEM
INDICATING TYPE FLOOR CONTROL
I VALVE W/ SUPERVISORY SWITCH 7' -0" AFF
FEED MAIN
TO SPRINKER HEADS
WATERFLOW SWITCH
X3.
SIGHT GLASS TEST VALVE
0
SECTIONAL DRAIN
VALVE
TO DRAIN
UNION W/ CORROSION RESISTANT ORIFICE
GIVING FLOW EQUAL TO SMALLEST
SPRINKLER ORIFICE IN SYSTEM.
EXISTING FIRE SPRINKLER FLOOR
CONTROL VALVE DETAIL
SPRINKLER HEAD
1' X 1/2' REDUCER ---�'
I' CLOSE NIPPLE
- BRANCH LINE
UPRIGHT SPRINKLER HEAD
DETAIL
" "" DIMENSION. MINIMUM DIA.
"B" (INCHES)
ADJUSTIBLE
CLEVIS MANGER
FOR PIPING 4' AND LARGER
ANVIL FIG #260
3
A
SIDE JOIST ATTACHMENT
OR
SIDE JOIST ADJUSTABLE
HANGER
NOTE:
HANGER ROD DIAMETER IS THE MINIMUM
SIZE PER NFPA. HANGER ROD DIAMETER
SHALL BE THE DIAMETER APPROVED FOR
USE WITH THE HANGER ASSEMBLY.
PIPE HANGER DETAIL
"'" DIMENSION.
[MUM DIA.
PHILLIPS CONCRETE
FASTENER I.T.T. ANVIL
(RED HEAD) TO BE USED ON
NEW CONSTRUCTION. PROVIDE
HILTIKWIK BOLT, ZINC PLATED,
METAL EXPANSION ANCHOR ON
EXISTING CONSTRUCTION
(SEE SPECIFICATIONS).
ADJUSTIBLE
SWIVEL RING HANGER
FOR PIPING 3" AND SMALLER
ANVIL FIG #69
CENTER I -BEAM CLAMP
HANGERS
"A" DIMENSION.
MINIMUN DIA.(INCHES)
THREADED ROD
SIZE. CUT TO ;
LENGTH - -- -
SELF DRILLING CONCRETE WEDGE ANCHOR
)1��
TOP BEAM CLAMP
DANGER SPACING
I. 1" AND 1 ?" DIA. STEEL PIPE: MAXIMUM 12 FT. SPACING.
2. 1" JHRU 3" DIA. THREADED LIGHTWALL PIPE: MAX. 12 FT. SPACING
3. 11/2 AND LARGER DIA. STEEL PIPE: MAXIMUM 15 FT. SPACING.
4. ALL PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH
NFPA -13. EACH SECTION OF PIPE SHALL HAVE NO LESS
THAN ONE HANGER. ARMOVERS EXCEEDING 1 FT. SHALL HAVE
A HANGER.
5. PROVIDE PIPE CLAMP AT EACH FLOOR FOR RISERS
PENETRATING FLOORS.
6. TRAPEZE HANGERS SHALL NOT BE USED.
7. ALL HANGERS SHALL BE U.L. LISTED.
8. ALL EXTERIOR HANGERS SHALL BE STAINLESS STEEL INCLUDING
CLAMPS.THREADED RODS. NUTS & BOLTS.
S. ALL INTERIOR HANGERS SHALL BE GALVANIZED INCLUDING
CLAMPS,THREADED RODS. NUTS & BOLTS.
PIPE
SIZE
A
B
PIPE
SIZE
A
B
1
3/8
178
_-Tv-
3/8
1/4
1?
3/8
1/8"'
6
172
174
1
3/8"_`F/8
ABOVE FINISHED FLOOR
8
1/2
1/4
2
8
1/41
10
5/8
1/4
2/
8
1/4
12
PIPING TO BE REMOVED
1/4
3
1/4
PROTECTION
REMOVE EXISTING HEAD AND PLUG FITTING
HANGER ROD SCHEDULE
N.T.S
FIRE PROTECTION ABBREVIATIONS
F.H.C.
FIRE HOSE CABINET
O.S. & Y.
OUTSIDE STEM AND YOKE
F.E.
FIRE EXTINGUISHER
S.C.V.
SECTIONAL CONTROL VALVE
A/S
AUTOMATIC SPRINKLER
F.H.
FIRE HYDRANT
F.SP.
FIRE STANDPIPE
R.P.B.P.
REDUCED PRESSURE BACKFLOW PREVENTER
RCV
RISER CONTROL VALVE
A.F.F.
ABOVE FINISHED FLOOR
T.S
TAMPER SWITCH
F.S
FLOW SWITCH
FIRE PROTECTION LEGEND
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
F
FIRE LINE OR MAIN
=
FIRE DEPARTMENT VALVE CABINET
A/S
AUTOMATIC SPRINKLER MAIN
FP -1, ETC
FIXTURE INDENTIFICATION
D
DRAIN LINE
PROTECTION SPECIFICATIONS
CONNECTION TO EXISTING
FPO.03
PIPE TURNED UP
•
FIRE EXTINGUISHER
ED
PIPE TURNED DOWN
BUILDING FIRST FLOOR PLAN
FLOW SWITCH
-6
BALL VALVE
PROTECTION
CAP ON LINE
FP2.02
CHECK VALVE
- DEMOLITION & NEW CONSTRUCTION
SPRINKLER HEAD BELOW DUCT WORK
oil
UNION IN PIPE
PIPING TO BE REMOVED
--►f-
SECTIONAL CONTROL VALVE
FIRE HYDRANT WITH VALVE
PROTECTION
REMOVE EXISTING HEAD AND PLUG FITTING
O.S. &Y. GATE OR BUTTERFLY VALVE
WITAMPER SWITCH.
REMOVE EXISTING HEAD & EXTEND 1" BRANCH LINE
TO NEW HEAD LOCATION
FIRE DEPARTMENT CONNECTION
CHECK VALVE
SPRINKLER HEAD LEGEND
TYPE
K -FACT
TEMP
LOCATION
1. UPRIGHT - STANDARD RESPONSE W /GUARD
5.6
1550
ALL SPACES UNLESS OTHERWISE NOTED
FIRE
PROTECTION NOTES, LEGENDS, DETAILS AND DRAWING INDEX
FPO.02
FIRE
! SEE SPECIFICATIONS FOR MODEL NUMBERS.
PLUG ALL UNUSED OUTLETS.
FIRE PROTECTION AS- BUILTS NOTE
FIRE PROTECTION CONTRACTOR IS REQUIRED TO SUBMIT FIRE PROTECTION AS BUILT
PLANS UPON COMPLETION OF THE PROJECT. COMPLETION IS DEFINED AS THE OWNER
RECEIVING A 'CO' AND FIRE PROTECTION INSPECTOR HAS FINALIZED AND APPROVED
THE INSTALLATION.
AS BUILTS SHALL BE SUBMITTED IN ELECTRONIC FASHION IN EITHER AUTOCAD
FORMAT OR SCANNED FILES IN PDF FORMAT.
AS BUILTS SHALL BE LEGIBLE AND NEAT. AS BUILTS WILL BE RETAINED BY
ARCHITECT AND ENGINEER FOR RECORDS OF CHANGES TO THE SYSTEM. AS BUILTS
WILL BE SUBMITTED TO OWNER THROUGH ARCHITECT AND ENGINEER.
Y
mi h
e� an
el�nc.
6001WBst Hillsboro, Suite 300
E�erfiMd Beach, FL 33441
X954) 421 -1260
FAX: -(954) 421 -1466
www.ssr- inc.com
Firm Certlflcation - EB- 0000857
John E. Moulder PE - 33200
Michael k Steward PE - 65701
SSR JOB # 1232030.0
r
r
i
I
le- LU VJ
z T
U) O w w CO CO
0 °C o
_ = Uj a
U 00
Ch LL i
Q0 ti
Gi
-z� Q;
W U)
06 Cr O
= o=
I-ZC/)
Fee, Oi
0 Q W,
VJ
i
No 2
S O �� v
.t� • Q..
R IV
DRAWN
CHECKED
DATE 11/12/12
REVISED {
`I
SHEET NO.
FIRE PROTECTION
NOTES, LEGENDS,
DETAILS AND
DRAWING INDEX
FP0001
DRAWING
INDEX
SHEET
NUMBER
SHEET
TITLE
FP0.01
FIRE
PROTECTION NOTES, LEGENDS, DETAILS AND DRAWING INDEX
FPO.02
FIRE
PROTECTION SPECIFICATIONS
FPO.03
FIRE
PROTECTION SPECIFICATIONS
FP2.01
MAIN
BUILDING FIRST FLOOR PLAN
- DEMOLITION & NEW CONSTRUCTION
FIRE
PROTECTION
FP2.02
NORTH TOWER FIRST FLOOR PLAN
- DEMOLITION & NEW CONSTRUCTION
FIRE
PROTECTION
FP2.03
MAIN
BUILDING SECOND FLOOR PLAN - DEMOLITION & NEW CONSTRUCTION
FIRE
PROTECTION
Y
mi h
e� an
el�nc.
6001WBst Hillsboro, Suite 300
E�erfiMd Beach, FL 33441
X954) 421 -1260
FAX: -(954) 421 -1466
www.ssr- inc.com
Firm Certlflcation - EB- 0000857
John E. Moulder PE - 33200
Michael k Steward PE - 65701
SSR JOB # 1232030.0
r
r
i
I
le- LU VJ
z T
U) O w w CO CO
0 °C o
_ = Uj a
U 00
Ch LL i
Q0 ti
Gi
-z� Q;
W U)
06 Cr O
= o=
I-ZC/)
Fee, Oi
0 Q W,
VJ
i
No 2
S O �� v
.t� • Q..
R IV
DRAWN
CHECKED
DATE 11/12/12
REVISED {
`I
SHEET NO.
FIRE PROTECTION
NOTES, LEGENDS,
DETAILS AND
DRAWING INDEX
FP0001