12-1353-024SPRINKLER NOTES 1. ALL FIRE PROTECTION SYSTEM SHALL BE IN COMPLIANCE WITH THE LOCAL FIRE CODES AND ORDINANCES AND AS PER NFPA 13, 2007 EDITION REQUIREMENTS. 2. MAKE ALL OFFSETS REQUIRED AS PER JOB CONDITIONS. 3. CONTRACTOR TO PROVIDE AND TURN OVER TO THE OWNER AT LEAST (6) SPARE SPRINKLERS OF SAME TYPE AND TEMPERATURE RATING BEING INSTALLED INSIDE OF BOX. COORDINATE LOCATION WITH OWNER. 4. PROVIDE AND MAINTAIN A MINIMUM CLEARANCE OF 18" BETWEEN THE BOTTOM OF THE SPRINKLER DEFLECTOR AND THE TOP OF STORAGE, FILE, SHELVING, ETC. 5. CONTRACTOR SHALL FIELD VERIFY LOCATION AND QUANTITY OF ALL CEILING MOUNTED DEVICES INCLUDING SMOKE DETECTORS TO BE REMOVED DURING CONSTRUCTION TO INSTALL SPRINKLER PIPING. EXISTING EQUIPMENT AND FIXTURES SHALL BE REPAIRED TO ORIGINAL OPERATION OR REPLACED SHOULD THEY BE DAMAGED DURING CONSTRUCTION. 6. SCHEDULE 5 PIPING AND FLEXIBLE SPRINKLER HEAD DROPS ARE NOT APPROVED OR ACCEPTED PRODUCTS. 7. CONTRACTOR SHALL COORDINATE WITH STRUCTURE AND OTHER TRADES BEFORE INSTALLING SPRINKLER WORK. 8. SPRINKLER HEAD RATED @ 155 DEGREES F., %" ORIFICE WITH 5.6, "K" FACTOR, STANDARD RESPONSE. 9. INSTALL PIPING TIGHT TO STRUCTURE WHERE POSSIBLE. 10. SPRINKLER SYSTEM TO BE INSTALLED BY A STATE CERTIFIED FIRE PROTECTION CONTRACTOR. 11. FIRE PROTECTION SERVICES TO BE REMOVED SHALL BE CAPPED AND PLUGGED. 12. SYSTEM DESIGNED FOR ORDINARY HAZARD GROUP 1 OCCUPANCY. 13. CONTRACTOR SHALL REMOVE EXISTING SPRINKLER HEADS AS SHOWN AND ADJUST PIPING TO NEW CEILING PATERN. 14. CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINES INVOLVED SO AS TO AVOID ANY PIPE ROUTING PROBLEMS. 15. EXISTING SERVICES INDICATED ON THESE DRAWINGS WERE DERIVED FROM EXISTING DRAWINGS AND LIMITED FIELD OBSERVATIONS. THESE DRAWINGS MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES, LOCATION, TYPE AND SIZE PRIOR TO ANY CONSTRUCTION. ANY DEVIATIONS IMPACTING WORK SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ENGINEER FOR COORDINATION PRIOR TO CONSTRUCTION. 16. CONTRACTOR IS RESPONSIBLE FOR RELOCATING ALL EXISTING FIRE MAINS AND SPRINKLER PIPING TO FACILITATE THE INSTALLATION OF NEW ELECTRICAL, MECHANICAL AND PLUMBING SYSTEMS. THIS INCLUDES ALL CEILING SPACES, SHAFTS, WALLS, ETC. 17. PRESSURE TEST PIPING AT 200 PSIG FOR A MINIMUM OF TWO HOURS. IF LEAKS ARE FOUND THEN CONTRACTOR SHALL FIX LEAKS AND TEST AGAIN. 18. ANY SYSTEM OR PORTION OF THE FIRE SPRINKLER SYSTEM, THAT IS SHUTDOWN, FOR 4 HOURS OR GREATER SHALL REQUIRE A FIRE WATCH AS REQUIRED PER THE FLORIDA FIRE PREVENTION CODE 2010. A FIRE WATCH SHALL ALSO BE PROVIDED FOR AREAS WHERE THE TEMPORARY ZIP WALLS OR TEMPORARY PARTITIONS ARE PROVIDED IF ANY FIRE SPRINKLER COVERAGE IS BEING OBSTRUCTED. COORDINATE WITH HOSPITAL REPRESENTATIVE BEFORE DEACTIVATING ANY SYSTEM. 19. CONTRACTOR SHALL PROVIDE INSTALLATION SHOP DRAWINGS TO THE ENGINEER FOR APPROVAL PRIOR TO INSTALLATION. 20. SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS IN ACCORDANCE WITH U.L. FIRE RESISTANCE INDEX FOR THROUGH PENETRATION FIRE STOP SYSTEMS. COORDINATE REQUIREMENTS WITH ARCHITECTURAL PLANS AND SPECIFICATIONS. 21. ALL PENETRATIONS OR OPENINGS FROM REMOVED PIPES THROUGH EXISTING BUILDING WALLS AND FLOORS SHALL BE SLEEVED AND /OR PATCHED TO MATCH ORIGINAL. SEE ARCHITECTURAL DRAWINGS FOR FINAL FINISHES. 22. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO EXISTING PIPING OR EQUIPMENT DUE TO NEW CONSTRUCTION AND HE SHALL RESTORE EXISTING WORK TO ITS ORIGINAL CONDITION AT NO COST TO THE OWNER. 23. PROVIDE HANGERS ON ALL ARMOVERS OF 12" OR MORE IN LENGTH AND PER NFPA 13. 24. WARRANTY /GUARANTEE A. THE CONTRACTOR SHALL WARRANTY /GUARANTEE AND MAINTAIN THE STABILITY OF WORK AND MATERIALS AND KEEP SAME IN PERFECT REPAIR AND CONDITION FOR THE PERIOD OF ONE YEAR. B. DEFECTS OF ANY KIND DUE TO FAULTY WORK OR MATERIALS, APPEARING DURING THE ABOVE MENTIONED PERIOD, MUST BE IMMEDIATELY REPAIRED BY THE CONTRACTOR AT HIS OWN EXPENSE TO THE ENTIRE SATISFACTION OF THE OWNER AND ENGINEER. SUCH RECONSTRUCTION AND REPAIRS SHALL INCLUDE DAMAGE TO THE FINISH OR FURNISHING OF THE BUILDING RESULTING FROM THE ORIGINAL DEFECT OR REPAIR THERETO. 25. SPRINKLER HEADS SHALL BE A MINIMUM OF 12" FROM ANY DIFFUSER PER NFPA 13. 26. PIPING SHALL NOT BE RUN OVER ANY ELECTRICAL AND PHONE PANELS. 27. THE FIRE PROTECTION CONTRACTOR SHALL KEEP A SET OF MARKED UP DRAWINGS AS THE JOB PROGRESSES. NO MAJOR CHANGE SHALL BE MADE TO FIRE PROTECTION DESIGN ENGINEERING UNLESS IT HAS BEEN COORDINATED, DRAWN AND SUBMITTED FOR APPROVAL. 28. CONTINUITY OF SERVICE: INTERRUPTIONS OF EXISTING SERVICES OR FACILITIES SHALL BE KEPT TO A MINIMUM AND THE CONTRACTOR SHALL FURNISH ALL MATERIALS AND LABOR REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE NECESSARY TO MAINTAIN CONTINUITY OF SERVICE. INTERRUPTIONS OF THE EXISTING SERVICES, THE INSTALLATION OF TEMPORARY FACILITIES, AND THE WORK OF MAKING FINAL CONNECTIONS TO NEW WORK SHALL BE DONE ONLY AT SUCH TIMES AS PERMITTED AND SCHEDULED BY THE OWNER. ALL SUCH CONNECTIONS AND TIE -INS SHALL BE COORDINATED THROUGH THE OWNERS PROJECT MANAGER. 1. THE DURATION OF EACH SHUTDOWN SHALL BE LIMITED TO NIGHTS AND /OR WEEKENDS WITH THE TIME FRAME FOR SHUTDOWNS AS SPECIFIED BY THE OWNER. THE CONTRACTOR SHALL NOTIFY THE OWNER IN WRITING FORTY -EIGHT (48) HOURS IN ADVANCE OF EACH REQUIRED INTERRUPTION OF EXISTING SERVICE. 2. THE CONTRACTOR SHALL INCLUDE IN BID PRICE ALL PREMIUM TIME CHARGES (E.G. SHUTDOWNS OF EXISTING SYSTEMS FOR TIE -INS) FOR LABOR AND EQUIPMENT REQUIRED FOR ALL NIGHT AND WEEKEND OVERTIME WORK, AS NECESSARY, TO COMPLETE THE SCOPE OF THE CONTRACT. 29. CONTRACTOR SHALL PROVIDE AS BUILT DRAWINGS ALONG WITH ALL CLOSE OUT DOCUMENTS PRIOR TO PROJECT COMPLETION. 30. CONTRACTOR SHALL OBTAIN FROM THE OWNER A COPY OF THE INFECTION CONTROL RISK ASSESSMENT (ICRA) PREPARED FOR THIS PROJECT. CONTRACTOR SHALL REVIEW THE REQUIREMENTS IN THE REPORT AND PERFORM ALL WORK IN ACCORDANCE WITH THOSE REQUIREMENTS. SEE MECHANICAL DRAWINGS FOR COORDINATION OF VENTILATION REQUIREMENTS REQUIRED BY ICRA. " "" DIMENSION. MINIMUM DIA. "B" (INCHES) ADJUSTIBLE CLEVIS MANGER FOR PIPING 4' AND LARGER ANVIL FIG #260 3 A SIDE JOIST ATTACHMENT OR SIDE JOIST ADJUSTABLE HANGER NOTE: HANGER ROD DIAMETER IS THE MINIMUM SIZE PER NFPA. HANGER ROD DIAMETER SHALL BE THE DIAMETER APPROVED FOR USE WITH THE HANGER ASSEMBLY. PIPE HANGER DETAIL "'" DIMENSION. [MUM DIA. PHILLIPS CONCRETE FASTENER I.T.T. ANVIL (RED HEAD) TO BE USED ON NEW CONSTRUCTION. PROVIDE HILTIKWIK BOLT, ZINC PLATED, METAL EXPANSION ANCHOR ON EXISTING CONSTRUCTION (SEE SPECIFICATIONS). ADJUSTIBLE SWIVEL RING HANGER FOR PIPING 3" AND SMALLER ANVIL FIG #69 CENTER I -BEAM CLAMP HANGERS "A" DIMENSION. MINIMUN DIA.(INCHES) THREADED ROD SIZE. CUT TO ; LENGTH - -- - SELF DRILLING CONCRETE WEDGE ANCHOR )1�� TOP BEAM CLAMP DANGER SPACING I. 1" AND 1 ?" DIA. STEEL PIPE: MAXIMUM 12 FT. SPACING. 2. 1" JHRU 3" DIA. THREADED LIGHTWALL PIPE: MAX. 12 FT. SPACING 3. 11/2 AND LARGER DIA. STEEL PIPE: MAXIMUM 15 FT. SPACING. 4. ALL PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH NFPA -13. EACH SECTION OF PIPE SHALL HAVE NO LESS THAN ONE HANGER. ARMOVERS EXCEEDING 1 FT. SHALL HAVE A HANGER. 5. PROVIDE PIPE CLAMP AT EACH FLOOR FOR RISERS PENETRATING FLOORS. 6. TRAPEZE HANGERS SHALL NOT BE USED. 7. ALL HANGERS SHALL BE U.L. LISTED. 8. ALL EXTERIOR HANGERS SHALL BE STAINLESS STEEL INCLUDING CLAMPS.THREADED RODS. NUTS & BOLTS. S. ALL INTERIOR HANGERS SHALL BE GALVANIZED INCLUDING CLAMPS,THREADED RODS. NUTS & BOLTS. PIPE SIZE A NOTES: PIPE SIZE A 1. IF ANY PIPES ARE TO BE INSULATED, DO NOT RUN INSULATION THROUGH A RATED FIRE 1 3/8 BARRIER OR RATED SMOKE BARRIER. AFTER SEALING PENETRATIONS AROUND PIPE THROUGH _-Tv- 3/8 THE WALL WITH "THROUGH - PENETRATION FIRESTOP SYSTEM ", FLARE INSULATION ONTO FACE 1? 3/8 OF WALL AROUND PIPE ON BOTH SIDES OF WALL, AND SEAL TO FACE OF WALL WITH 6 172 INSULATION MASTIC. 1 3/8"_`F/8 2. COMBUSTIBLE CONDUIT AND /OR COMBUSTIBLE PIPE IS NOT ALLOWED. 8 3 5/8" (MINIMUM) SEAL PENETRATIONS WITH APPROVED TESTED METAL STUDS AT "THROUGH - PENETRATION FIRESTOP SYSTEM" AS 16" O.C. (MAXIMUM) INDICATED BELOW 4 NON- COMBUSTIBLE PIPE OR CONDUIT &_ / B METAL RUNNER �� �� VERIFY REQUIRED NUMBER OF LAYERS AND TYPE "X" A SECTION OF 5/8" TYPE GYPSUM BOARD 2' -0" MAXIMUM FOR FULL - HEIGHT 2' -0" MAXIMUM FOR FULL - HEIGHT 20 GAGE (MINIMUM) METAL STUDS 20 GAGE (MINIMUM) METAL STUDS 1/4 V -4" MAXIMUM fIA" (TYPICAL) METAL RUNNER BEHIND 2" MAXIMUM GYPSUM BOARD (TYPICAL) I SECURELY ATTACHED 0 VERTICAL STUDS) "A" "A" 2" MAXIMUM (TYPICAL) CD z O.S. &Y. GATE OR BUTTERFLY VALVE WITAMPER SWITCH. NON- COMBUSTIBLE CONDUIT OR PIPING PACK TIGHTLY WITH "MINERAL FIBER SAFING INSULATION" FOR V -4" MAXIMUM FULL DEPTH OF BARRIER, AND SEAL PENETRATIONS WITH (TYPICAL) APPROVED TESTED "THROUGH - PENETRATION FIRESTOP SYSTEM" PER REQUIREMENTS OF: ELEVATION 2009 NFPA 101, LIFE SAFETY CODE SECTION 8.3.5 2010 FBC SECTION 712.3 AND 2010 FLORIDA EDITION OF NFPA 101, LIFE SAFETY CODE SECTION 8.3.5. TYPICAL MULTIPLE NON- COMBUSTIBLE CONDUIT OR PIPE PENETRATIONS DETAIL THROUGH RATED FIRE BARRIERS NOT TO SCALE AND /OR RATED SMOKE BARRIERS I HR PENETRATION DETAIL FIRE STANDPIPE SYSTEM INDICATING TYPE FLOOR CONTROL I VALVE W/ SUPERVISORY SWITCH 7' -0" AFF FEED MAIN TO SPRINKER HEADS WATERFLOW SWITCH X3. SIGHT GLASS TEST VALVE 0 SECTIONAL DRAIN VALVE TO DRAIN UNION W/ CORROSION RESISTANT ORIFICE GIVING FLOW EQUAL TO SMALLEST SPRINKLER ORIFICE IN SYSTEM. EXISTING FIRE SPRINKLER FLOOR CONTROL VALVE DETAIL SPRINKLER HEAD 1' X 1/2' REDUCER ---�' I' CLOSE NIPPLE - BRANCH LINE UPRIGHT SPRINKLER HEAD DETAIL " "" DIMENSION. MINIMUM DIA. "B" (INCHES) ADJUSTIBLE CLEVIS MANGER FOR PIPING 4' AND LARGER ANVIL FIG #260 3 A SIDE JOIST ATTACHMENT OR SIDE JOIST ADJUSTABLE HANGER NOTE: HANGER ROD DIAMETER IS THE MINIMUM SIZE PER NFPA. HANGER ROD DIAMETER SHALL BE THE DIAMETER APPROVED FOR USE WITH THE HANGER ASSEMBLY. PIPE HANGER DETAIL "'" DIMENSION. [MUM DIA. PHILLIPS CONCRETE FASTENER I.T.T. ANVIL (RED HEAD) TO BE USED ON NEW CONSTRUCTION. PROVIDE HILTIKWIK BOLT, ZINC PLATED, METAL EXPANSION ANCHOR ON EXISTING CONSTRUCTION (SEE SPECIFICATIONS). ADJUSTIBLE SWIVEL RING HANGER FOR PIPING 3" AND SMALLER ANVIL FIG #69 CENTER I -BEAM CLAMP HANGERS "A" DIMENSION. MINIMUN DIA.(INCHES) THREADED ROD SIZE. CUT TO ; LENGTH - -- - SELF DRILLING CONCRETE WEDGE ANCHOR )1�� TOP BEAM CLAMP DANGER SPACING I. 1" AND 1 ?" DIA. STEEL PIPE: MAXIMUM 12 FT. SPACING. 2. 1" JHRU 3" DIA. THREADED LIGHTWALL PIPE: MAX. 12 FT. SPACING 3. 11/2 AND LARGER DIA. STEEL PIPE: MAXIMUM 15 FT. SPACING. 4. ALL PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH NFPA -13. EACH SECTION OF PIPE SHALL HAVE NO LESS THAN ONE HANGER. ARMOVERS EXCEEDING 1 FT. SHALL HAVE A HANGER. 5. PROVIDE PIPE CLAMP AT EACH FLOOR FOR RISERS PENETRATING FLOORS. 6. TRAPEZE HANGERS SHALL NOT BE USED. 7. ALL HANGERS SHALL BE U.L. LISTED. 8. ALL EXTERIOR HANGERS SHALL BE STAINLESS STEEL INCLUDING CLAMPS.THREADED RODS. NUTS & BOLTS. S. ALL INTERIOR HANGERS SHALL BE GALVANIZED INCLUDING CLAMPS,THREADED RODS. NUTS & BOLTS. PIPE SIZE A B PIPE SIZE A B 1 3/8 178 _-Tv- 3/8 1/4 1? 3/8 1/8"' 6 172 174 1 3/8"_`F/8 ABOVE FINISHED FLOOR 8 1/2 1/4 2 8 1/41 10 5/8 1/4 2/ 8 1/4 12 PIPING TO BE REMOVED 1/4 3 1/4 PROTECTION REMOVE EXISTING HEAD AND PLUG FITTING HANGER ROD SCHEDULE N.T.S FIRE PROTECTION ABBREVIATIONS F.H.C. FIRE HOSE CABINET O.S. & Y. OUTSIDE STEM AND YOKE F.E. FIRE EXTINGUISHER S.C.V. SECTIONAL CONTROL VALVE A/S AUTOMATIC SPRINKLER F.H. FIRE HYDRANT F.SP. FIRE STANDPIPE R.P.B.P. REDUCED PRESSURE BACKFLOW PREVENTER RCV RISER CONTROL VALVE A.F.F. ABOVE FINISHED FLOOR T.S TAMPER SWITCH F.S FLOW SWITCH FIRE PROTECTION LEGEND SYMBOL DESCRIPTION SYMBOL DESCRIPTION F FIRE LINE OR MAIN = FIRE DEPARTMENT VALVE CABINET A/S AUTOMATIC SPRINKLER MAIN FP -1, ETC FIXTURE INDENTIFICATION D DRAIN LINE PROTECTION SPECIFICATIONS CONNECTION TO EXISTING FPO.03 PIPE TURNED UP • FIRE EXTINGUISHER ED PIPE TURNED DOWN BUILDING FIRST FLOOR PLAN FLOW SWITCH -6 BALL VALVE PROTECTION CAP ON LINE FP2.02 CHECK VALVE - DEMOLITION & NEW CONSTRUCTION SPRINKLER HEAD BELOW DUCT WORK oil UNION IN PIPE PIPING TO BE REMOVED --►f- SECTIONAL CONTROL VALVE FIRE HYDRANT WITH VALVE PROTECTION REMOVE EXISTING HEAD AND PLUG FITTING O.S. &Y. GATE OR BUTTERFLY VALVE WITAMPER SWITCH. REMOVE EXISTING HEAD & EXTEND 1" BRANCH LINE TO NEW HEAD LOCATION FIRE DEPARTMENT CONNECTION CHECK VALVE SPRINKLER HEAD LEGEND TYPE K -FACT TEMP LOCATION 1. UPRIGHT - STANDARD RESPONSE W /GUARD 5.6 1550 ALL SPACES UNLESS OTHERWISE NOTED FIRE PROTECTION NOTES, LEGENDS, DETAILS AND DRAWING INDEX FPO.02 FIRE ! SEE SPECIFICATIONS FOR MODEL NUMBERS. PLUG ALL UNUSED OUTLETS. FIRE PROTECTION AS- BUILTS NOTE FIRE PROTECTION CONTRACTOR IS REQUIRED TO SUBMIT FIRE PROTECTION AS BUILT PLANS UPON COMPLETION OF THE PROJECT. COMPLETION IS DEFINED AS THE OWNER RECEIVING A 'CO' AND FIRE PROTECTION INSPECTOR HAS FINALIZED AND APPROVED THE INSTALLATION. AS BUILTS SHALL BE SUBMITTED IN ELECTRONIC FASHION IN EITHER AUTOCAD FORMAT OR SCANNED FILES IN PDF FORMAT. AS BUILTS SHALL BE LEGIBLE AND NEAT. AS BUILTS WILL BE RETAINED BY ARCHITECT AND ENGINEER FOR RECORDS OF CHANGES TO THE SYSTEM. AS BUILTS WILL BE SUBMITTED TO OWNER THROUGH ARCHITECT AND ENGINEER. Y mi h e� an el�nc. 6001WBst Hillsboro, Suite 300 E�erfiMd Beach, FL 33441 X954) 421 -1260 FAX: -(954) 421 -1466 www.ssr- inc.com Firm Certlflcation - EB- 0000857 John E. Moulder PE - 33200 Michael k Steward PE - 65701 SSR JOB # 1232030.0 r r i I le- LU VJ z T U) O w w CO CO 0 °C o _ = Uj a U 00 Ch LL i Q0 ti Gi -z� Q; W U) 06 Cr O = o= I-ZC/) Fee, Oi 0 Q W, VJ i No 2 S O �� v .t� • Q.. R IV DRAWN CHECKED DATE 11/12/12 REVISED { `I SHEET NO. FIRE PROTECTION NOTES, LEGENDS, DETAILS AND DRAWING INDEX FP0001 DRAWING INDEX SHEET NUMBER SHEET TITLE FP0.01 FIRE PROTECTION NOTES, LEGENDS, DETAILS AND DRAWING INDEX FPO.02 FIRE PROTECTION SPECIFICATIONS FPO.03 FIRE PROTECTION SPECIFICATIONS FP2.01 MAIN BUILDING FIRST FLOOR PLAN - DEMOLITION & NEW CONSTRUCTION FIRE PROTECTION FP2.02 NORTH TOWER FIRST FLOOR PLAN - DEMOLITION & NEW CONSTRUCTION FIRE PROTECTION FP2.03 MAIN BUILDING SECOND FLOOR PLAN - DEMOLITION & NEW CONSTRUCTION FIRE PROTECTION Y mi h e� an el�nc. 6001WBst Hillsboro, Suite 300 E�erfiMd Beach, FL 33441 X954) 421 -1260 FAX: -(954) 421 -1466 www.ssr- inc.com Firm Certlflcation - EB- 0000857 John E. Moulder PE - 33200 Michael k Steward PE - 65701 SSR JOB # 1232030.0 r r i I le- LU VJ z T U) O w w CO CO 0 °C o _ = Uj a U 00 Ch LL i Q0 ti Gi -z� Q; W U) 06 Cr O = o= I-ZC/) Fee, Oi 0 Q W, VJ i No 2 S O �� v .t� • Q.. R IV DRAWN CHECKED DATE 11/12/12 REVISED { `I SHEET NO. FIRE PROTECTION NOTES, LEGENDS, DETAILS AND DRAWING INDEX FP0001