12-1337-002G%p SSIF /FQ OUL US FILL VOID OR CAVITY MATERIALS CLASSIFIED BY U14DEMVRITERS LABORATORIES, INC. ®FOR USE IN THROUGH- PENETRATION FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FIRE RESISTANCE DIRECTORY 50.6, Ow CC/`TIrIAI A A 1. Wall Assembly -The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and In Me manner described In the thdlvHual U400 or V400 series Wall and Partition Design In the UL Fin Resistance Directory and shall Include the folmng construction features. A. Studs -Wet Mming shag tourist of min 3316 In (92 mm) wide steel channel studs spaced max 24 b (a 10 mm) OC. B. Gypsum Boards - Thickness, type, number of layers and fasteners shag be as specified In the IrMMdual U400 series Wall and Partition Design in the UL Fire Resistance Directory Max am* of opening is 67 -12 sq N (435 sq cm) With max di nenYon of 22 -12 h (572 mm) The hourly F Rating of the Rrestop system Is equal to the hourly fire rating of the wall assembly In which It Is Installed. 2. Through Penetrant -One or more nom 2 in (51 mm) diam (or smeller) rigid steel conduit or ebctmal metallic tubing (EMT) Installed either concentrically or eccentrically within it* firestop system The annular .Paw between conduits or tubing and periphery of opening shat be min 0 M (point contact) to max 1.1/4 N (0 mm b max 32 mm). The space between conduls or tubing shall be min 1/4 N to max 1 in (6 mm to max 25 mm) Conduit or tubing to be rigidly supported on both sides of coal assembly 3. rill Vold or Cavity Materials - Caulk or Sealant - Min 5/6 In (16 mm) thickness of fin material applied whin the annulus. flush with both surfaces ofwal Min 12 In (13 mm) dlam bead of caulk applied to the penetrant/gypsum board Interface at the point contact location on both sides of wait The hourly T Rating of the firestep system Is 0 Hr when used In 1 Hr rated assemblies. The T Rating for 2 Hr rated assemblies Is 1/2 and 1 Hr for FlmDam 150+ and CP 25WB +, respectively. 3M COMPANY - IC 15WBq CP 25WB•, FireDan, 150+ caulk or F 13-3000 WT se•tant 'Bearing the UL Classification Mark s NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. System No. C -Al -1044 June 15, 2005 F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr L Rating At Ambient - 2 CFM /sq ft L Rating At 400 F - less than 1 CFM /sq ft W Rating - Class I (See Item 4) SECTION A -A 7 Fik- W l Awwrbly - Llyivwi2M W noriN wWpi (100 -150 pd a 1110D2400 kghr0) resew Except as nolyd in table under flown 4. min esrJnhess d sold aasaea sow a wall assembly b 4.121.(114 mm). Flow may also be con.nmad deny min 6 K (152 mm) tack UL Classified hollow core Precalt Cornea Ihsa• . Won floor la aorrbcad d hdbw care precaY commis uhXa paddng maternal (lien 3) and caulk all netarfd (lam 4) to be weaned symmeably on both aides d tor. huh wet /oor erfsce w1 aeawMly may also be constructed of any UL Cla-tied Caysa Bach- Max dam d opening a h sold Ipntweign air romW ssi014 corhaea Floor a 321. (613 mm) Msx dam d opting in tow co.alru,sed of hobwwn pewM wrwea,nb Is 7 h (178 mm). See Carves Bieck. (GAIT) and Prereat Concrete List. (CFTV) categories in to Fire Resstarcer Welly Be rein.e of nwxxaclumm 1A S" Sle- (optional, not Yam) - Ma 15 in (381 mm) ID (air sneer) Sded,le 10 (or havier)whir vi- wY or grouted lab Bon or wal aseurbly Sleeve my stand a max d2 In (11 -) b- M d Soar or beyond a it- .0-of -9 M.. 161. (408 mm) to (or salty) con 0 028 (0 71 mm)wsi thiclimme (air h-ler) geMNzod a" Wawa cant or pouted orb roar air wait assembly Saaiw may sriro a rte. d 12 h (13 mm) beyond ear .iaf.c. d flan arwal 2. Through h Perotrants - Oro metal. pp, oaskA w tubing b be MaMd titer concentrically eonrbkely within re hnbp ayebm Max annxer paw beNwsn pipe. w,dit or Lbkg and edge of trough opening or Wawa Is depwK%rt on M parameters at- In lam 4 Mrs ersube spew bshwen pp or condit and do. of hwgh opening la O in (0 mm) (point wnt c0 Pip conduit or l big b lea dg{dy s ppor ed on both sdm of Boor orwal wnby Tor. kaowirq bores end szr orm.rlke pp.., aanddb n adrg m.y M ued A SIsel Pip - Nan 30 h (782 mm) dwm (a sreMr) SdodJe 70 (a Imvi.O sing pip S. Iran Pip . Nom 301. (782 mm) dom(or - neser)ast nd tN km pip. C Condut - Nomeln (152mm)dem(oramaser)dgida"oxrdit D Conduit - Nom 4 h (1 02 mm) don (a staler) abN.Mdrlul meal. kb,ng E Copper .Tubing N- Sim (152mm)dWn(or-S.)Typ L(ahwW) copper bb F. Copper pip - Nom 61.(152 mm) loco(. reler) RpJ4(or h Wr)copper pipe 3 Padang MsanY - Poyst6iero beebr and or ram l h (25 mm) Ned- of agtey -p-Imd ..n" wed b.t or gar Bb.r k-A.U. army pecked leb opening as • pmrwrx brrR PwAd g m0"o le be moesssd tan by wxhce of floor or team both safamsof well as required b accorrerndale to required Ilklaess of oadk M meads (pen 4) 4 Fll.Vold re Cawxy Maahr -caulk or Sealant - Appiod to M to amiler pace Bush whh by surface or Ban la wet aa.snbbe, requed caulk Veld- b be installed .ymmYdwny m boM Oda. dwal, Bwh with wort mface At poky aorbd bsslan bdwess paroeant and reeve or between p.rebant and oavaa, a min 1/41.(11 mm) dam beed d caulk area be applied at by uace of Now and at boh whites of won. Th. howdy F Raerps and se required ceuik tidnera are dependant Won • number d pnmeam, Be a-- In 9. ,.-.V aba Min Floor or Wall Thkm In. (mm) Nom Pip Tube " Conduit Diam In. (mm Max Annular Space In. (mm) G�,pSSIFjFo F Rating Hr 2-112(64) 1/2 -12 (13 -305) 1-3/8(35) 0 UL US 2.1/2(64) twwav aAa AFI®1re:luor FILL VOID OR CAVITY MATERIALS 1 (25) 2 CLASSIFIED BY UNDERWRITERS 1126 (13452) rexRS aOe'nor �H° awc7 LABORATORIES, INC19 FOR USE IN System No.W -L -1228 2 a THROUGH- PENETRATION May 19, 2005 1. 1/4(32) -FORe, FIRESTOP SYSTEMS (XHEZ). F Rating - 1 and 2 Hr (See Item 1) 4-1/2(114) M 4009 SEE CURRENT FIRE T Rating - 0, 1/2 and 1 Hr (See Item 3) 1 (25) o nes,orA nw RESISTANCE DIRECTORY L Rating At Ambient - Less Than 1 CFM ft 112 -20 (13 -508) .Pon L1„Ir® scvxV 1"°rw" -n 6M6 Dow /sq 3 ream xx L Rating At 400 F - 2 CFM /sq ft�* 3 -1/4 (83) roa,arc-U p n01�4T1r�r ,lief ArfA,OR ta7v errRrl ear G%p SSIF /FQ OUL US FILL VOID OR CAVITY MATERIALS CLASSIFIED BY U14DEMVRITERS LABORATORIES, INC. ®FOR USE IN THROUGH- PENETRATION FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FIRE RESISTANCE DIRECTORY 50.6, Ow CC/`TIrIAI A A 1. Wall Assembly -The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and In Me manner described In the thdlvHual U400 or V400 series Wall and Partition Design In the UL Fin Resistance Directory and shall Include the folmng construction features. A. Studs -Wet Mming shag tourist of min 3316 In (92 mm) wide steel channel studs spaced max 24 b (a 10 mm) OC. B. Gypsum Boards - Thickness, type, number of layers and fasteners shag be as specified In the IrMMdual U400 series Wall and Partition Design in the UL Fire Resistance Directory Max am* of opening is 67 -12 sq N (435 sq cm) With max di nenYon of 22 -12 h (572 mm) The hourly F Rating of the Rrestop system Is equal to the hourly fire rating of the wall assembly In which It Is Installed. 2. Through Penetrant -One or more nom 2 in (51 mm) diam (or smeller) rigid steel conduit or ebctmal metallic tubing (EMT) Installed either concentrically or eccentrically within it* firestop system The annular .Paw between conduits or tubing and periphery of opening shat be min 0 M (point contact) to max 1.1/4 N (0 mm b max 32 mm). The space between conduls or tubing shall be min 1/4 N to max 1 in (6 mm to max 25 mm) Conduit or tubing to be rigidly supported on both sides of coal assembly 3. rill Vold or Cavity Materials - Caulk or Sealant - Min 5/6 In (16 mm) thickness of fin material applied whin the annulus. flush with both surfaces ofwal Min 12 In (13 mm) dlam bead of caulk applied to the penetrant/gypsum board Interface at the point contact location on both sides of wait The hourly T Rating of the firestep system Is 0 Hr when used In 1 Hr rated assemblies. The T Rating for 2 Hr rated assemblies Is 1/2 and 1 Hr for FlmDam 150+ and CP 25WB +, respectively. 3M COMPANY - IC 15WBq CP 25WB•, FireDan, 150+ caulk or F 13-3000 WT se•tant 'Bearing the UL Classification Mark s NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. System No. C -Al -1044 June 15, 2005 F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr L Rating At Ambient - 2 CFM /sq ft L Rating At 400 F - less than 1 CFM /sq ft W Rating - Class I (See Item 4) SECTION A -A 7 Fik- W l Awwrbly - Llyivwi2M W noriN wWpi (100 -150 pd a 1110D2400 kghr0) resew Except as nolyd in table under flown 4. min esrJnhess d sold aasaea sow a wall assembly b 4.121.(114 mm). Flow may also be con.nmad deny min 6 K (152 mm) tack UL Classified hollow core Precalt Cornea Ihsa• . Won floor la aorrbcad d hdbw care precaY commis uhXa paddng maternal (lien 3) and caulk all netarfd (lam 4) to be weaned symmeably on both aides d tor. huh wet /oor erfsce w1 aeawMly may also be constructed of any UL Cla-tied Caysa Bach- Max dam d opening a h sold Ipntweign air romW ssi014 corhaea Floor a 321. (613 mm) Msx dam d opting in tow co.alru,sed of hobwwn pewM wrwea,nb Is 7 h (178 mm). See Carves Bieck. (GAIT) and Prereat Concrete List. (CFTV) categories in to Fire Resstarcer Welly Be rein.e of nwxxaclumm 1A S" Sle- (optional, not Yam) - Ma 15 in (381 mm) ID (air sneer) Sded,le 10 (or havier)whir vi- wY or grouted lab Bon or wal aseurbly Sleeve my stand a max d2 In (11 -) b- M d Soar or beyond a it- .0-of -9 M.. 161. (408 mm) to (or salty) con 0 028 (0 71 mm)wsi thiclimme (air h-ler) geMNzod a" Wawa cant or pouted orb roar air wait assembly Saaiw may sriro a rte. d 12 h (13 mm) beyond ear .iaf.c. d flan arwal 2. Through h Perotrants - Oro metal. pp, oaskA w tubing b be MaMd titer concentrically eonrbkely within re hnbp ayebm Max annxer paw beNwsn pipe. w,dit or Lbkg and edge of trough opening or Wawa Is depwK%rt on M parameters at- In lam 4 Mrs ersube spew bshwen pp or condit and do. of hwgh opening la O in (0 mm) (point wnt c0 Pip conduit or l big b lea dg{dy s ppor ed on both sdm of Boor orwal wnby Tor. kaowirq bores end szr orm.rlke pp.., aanddb n adrg m.y M ued A SIsel Pip - Nan 30 h (782 mm) dwm (a sreMr) SdodJe 70 (a Imvi.O sing pip S. Iran Pip . Nom 301. (782 mm) dom(or - neser)ast nd tN km pip. C Condut - Nomeln (152mm)dem(oramaser)dgida"oxrdit D Conduit - Nom 4 h (1 02 mm) don (a staler) abN.Mdrlul meal. kb,ng E Copper .Tubing N- Sim (152mm)dWn(or-S.)Typ L(ahwW) copper bb F. Copper pip - Nom 61.(152 mm) loco(. reler) RpJ4(or h Wr)copper pipe 3 Padang MsanY - Poyst6iero beebr and or ram l h (25 mm) Ned- of agtey -p-Imd ..n" wed b.t or gar Bb.r k-A.U. army pecked leb opening as • pmrwrx brrR PwAd g m0"o le be moesssd tan by wxhce of floor or team both safamsof well as required b accorrerndale to required Ilklaess of oadk M meads (pen 4) 4 Fll.Vold re Cawxy Maahr -caulk or Sealant - Appiod to M to amiler pace Bush whh by surface or Ban la wet aa.snbbe, requed caulk Veld- b be installed .ymmYdwny m boM Oda. dwal, Bwh with wort mface At poky aorbd bsslan bdwess paroeant and reeve or between p.rebant and oavaa, a min 1/41.(11 mm) dam beed d caulk area be applied at by uace of Now and at boh whites of won. Th. howdy F Raerps and se required ceuik tidnera are dependant Won • number d pnmeam, Be a-- In 9. ,.-.V aba Min Floor or Wall Thkm In. (mm) Nom Pip Tube " Conduit Diam In. (mm Max Annular Space In. (mm) Min Caulk rhkm In. from F Rating Hr 2-112(64) 1/2 -12 (13 -305) 1-3/8(35) 1/2(13) 2 2.1/2(64) t/2 -12 (13 -305) 3-1/4(83) 1 (25) 2 4-1/2(114) 1126 (13452) 1-3/8(35) 1/4(6)(s) 2 4-1/2(114) 1/2- 12(13 -305) 1. 1/4(32) 1/2(13) 3 4-1/2(114) 1/2- 20(13 -508) 2 (51) 1 (25) 3 4-1/2(114) 112 -20 (13 -508) 2 (51) 1 (25) 3 (314) 11 2.12 (13 -305) 3 -1/4 (83) 1 (25) 3 4 -112 (114) 22.30 (558 -762) 2 (51) 2 (51) 3 5 -1/2 (140) 1/26 (13 -152) 1-3/8(35) 1 1 (25)(b) 4 (a Ban 2 H (51 mm) I ickoaa d mineral wool bat Muiaaon requ and b an xier apace (b) Mn 7 In (25 mm) Ictoss of mwrei wool bat Insulation regaed In annular pace on both alit» of floor or wail assembly Mn 1 h (25 mm) lidaess of caulk b be insisted Bush with each reface of floor or cowl esse rbly 3M COMPANY - CP 25WB. caulk or FB -3000 WT rWnt (Not, W Rating ppi.. only when 1`13J000 Wr ssalara la ued ) 'sewing ee u. cl waxsesah Marling s NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. \ \SCUA►11\ TP10\00- 2003\ALL W -2003 M DRAWNCS \SOM W9 HOSPIGL (MAM SRE\SMH DIALYSIS 967227004 \SMH DIALYSIS 967227CDOLMCIMAT'ED: November 13, 2012 DA776 PLOTTED: November 14, 2012 DA73 SAVED: November 14, 2012 4009 -9207 WIRING ENTRIES INTO BACK BOX rrvou.mraar tpkuhr.x- 1yPxALOPon laurion axe Powa,urer ®www rw.ara,ssr ®ws-o 00000 1 00000 4100 8201 roPVaw 41000 ,1£1110 AlEA wn,aw gray 1rPCVwtpxr kocxr.n nm PQr811nar ®wnw 00000 ropvtw 4010 usE eArsw roR,m/ arar 4010 FACP WIRING ENTRIES INTO BACK BOX CAUTION POWER {IMITED AND NON-POWERIIMITED WIRING MUST ENTER THROUGH SEPARATE CONOUIT/SERVICE ENTRANCES AC POWER ENTRANCE INTO BACK BOX IS REQUIRED AT DESIGNATED LOCATION OF THE BACK BOX FAILURE TO PROPERLY SEPARATE 120V NON- POWER LIMITED WIRING FROM POWER- LIMITED LOW VOLTAGE WIRING, WILL VOID THE UL LISTING FOR THE DEVICE AND WILL PREVENT THE INSTALLATION FROM BEING CERTIFIED (SEE CHART INSTALLATION INSTRUCTION SHEET) L=Txn tall unmwnro Ills craw r,oR n7v4yr uisr® RNERu"nM �mr 4006/4008 `. ' 1Mn9iB1r Power ro ews¢ss°n ear4i ,Teat rl� ,nw �nlrwr® uBE nnoAra=APOR,xN guar DEVICE MOUNTING HEIGHTS A/C SUPPLY DIFFUSER CEILING MOUNTED SMOKE/HEAT 3' (MIN) DETECTOR 1 NC 6" BELOW CEILING 24" MIN HANDICAP AUDIO SUAL ACCEPTED HER BEDROOM STROBE VISUAL-ONLY • L DEVICES � IMPORTANT NOTE VERIFY EXACT MOUNTING REQUIREMENTS WITH MANUFACTURERS DATA SHEETS MORE THAN TWO VISIBLE APPLIANCES ARE NOT PERMITTED IN ANY FIELD OF VIEW UNLESS THEIR FLASHES AS SYNCHRONIZED. NFPA 72 2007 EDITION (SECTION 7.5.4.3.2) 80" MIN 96" MAX NFPA 72 2007 EDITION (SECTION 7.5.4.1) G�%SSIFjF4 OUL US FILL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS LABORATORIES IMrrrthcnC1 IMcIt' THROUGH FIRESTOP S SEE CUR RESISTANI 50L MANUAL PULL STATION FIRE PHONES � JACK f o I 48' MAX (ADA 42" MIN /48- MAX (NFPA) NFPA 72 2007 EDITION (SECTION 5.13.4) HOLDER LESS 3" 1 System No.W -L -3001 September 07, 2004 (Formerly System No. 149) F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 3/4, 1, 1 -1/2 and 2 Hr (See Item 2) L Rating At Ambient - 15 CFM /sq ft (See Item 3) L Rating At 400 F - less than 1 CFM /sq R (See Item 3) • WALL MOUNTED WALL SECTION A -A 1. Wall Assembly - The 1 or 2 hr (Ire-rated gypsum wallboard /stud wall assembly shall be constructed of the materials and In the manner described In the Individual U300 or U400 Series Wall or Partition Designs In the UL Fire Resistance Directory and shall Include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 In. lumber spaced 16 In. OC with nom 2 by 4 In. lumber end plates and cross braces. Steel studs to be min 3 -5/8 In. wile by 1.3/8 In. deep channels spaced max 24 In OC. B. Gypsum Boards - Nom 1/2 or 5/8 In. thick, 4 It wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers and sheet orientation shall be as specified In the individual Wall or Partition Design. Diam of circular through opening to be 3/8 In. to 5/8 In. larger than outside diam of cable or cable bundle. C. Fasteners - When wood stud framing is employed gypsum wallboard layers attached to studs with cement coated nails as specified In the Individual Wall or Partition Design. When steel channel stud framing Is employed, gypsum wallboard attached to studs with Type s self - drilling, self - tapping bugle-head steel screws as specified In the individual Wall or Partition Design. The hourly F Rating of the flrestop system Is equal to the hourly fire rating of the wall assembly In which It Is Installed. 2. Cables - Individual cable or max 1 In. diam cable bundle Installed in through opening with an annular space of min 0 In. (point contact) to max 3/4 In. Cable to be rigidly supported on both sides of wall assembly. The following types and sizes of cables may be used: A. Max 150 pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride (PVC Insulation and Jacket materials, When max 25 pair telephone cable is used, • Rating is 2 hr.When 50 to 150 pair telephone cable Is used In 1 hr fire rated wall, • Rating Is 3/4 hr.When 50 to 150 pair telephone cable Is used in 2 hr fire rated wall, T Rating Is 1 hr. B. Max No. 10 AWG multiple copper conductor Type NM ( "Romex" ) nonmetallic sheathed cable with PVC Insulation and Jacket materials. When Type NM cable Is used, max T Rating is 1 -1/2 hr. C. Multiple fiber optical communication cable jacketed with PVC and having a max outside diam of 5/8 In. When fiber optic cable is used, max T Rating Is 2 hr. D. Max 12 AWG mufti conductor (max seven conductors) power /control cable with cross - linked polyethylene (XLPE) Insulation and XLPE or PVC jacket materials. When multi conductor power /control cable Is used, max T Rating Is 2 hr. E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER cables with polyvinyl chloride Insulation and Jacket materials. 3. FIII,Vold or Cavity Materials' - Caulk, Sealant or Putty - Caulk or putty fill material installed to completely fill annular space between cable and gypsum wallboard on both sides of wall and with a min 1/4 1n. diam bead of caulk or putty applied to perimeter of cable(s) at Its egress from each side of the wall. 3M COMPANY - MP+ Stlx putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap putty (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant Is used.) 'Bearing the UL Classification Mark NOTES NOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST OF THE DETECTOR. 12' SIDE WALL SYMBOLLEGEND SYMBOL SIMPLEX MODEL # DESCRIPTION NODE 6 4100 8201 NETWORK FIRE ALARM PANEL WITH VOICE & PHONES EXISTING IN 4TH FLOOR ELECTRIC ROOM 7C7�! - FIRE ALARM TERMINAL CABINET FURNISHED BY ELECTRICAL CONTRACTOR Zt 4090 -9001 INDIVIDUAL ADDRESS MODULE W CONNECT TO N/O CONTACTS ONLY ❑F 4099 -9001 PULL STATION ADDRESSABLE MI U- 2099 -9813 PULL STATION FLUSH TRIM O 4098 -9792 SSD SENSOR BASE 4098 -9733 SSD HEAT SENSOR 4098 -9792 SSD SENSOR BASE Q CL to 4098 -9714 SSD PHOTO SENSOR 1-_ 4098 -9756 SSD DUCTSENSOR HOUSING O 2098 -9797 SAMPLING TUBE 49" OR 2098 -9806 REMOTE TEST STATION RED LED KEY SVTCH FS P: 0) FLOW DETECTOR SWITCH fY FURNISHED BY DIVISION 15 7S TAMPER (GATE VALVE) SWITCH FURNISHED BY DIVISION 15 r 4. END OF LINE RESISTOR ® 4905 -9938 SMARTSYNC CONTROL MODULE U LU 0.038 AMPS 75W �C 4906-9151 SPEAKER /STROBE MC, RED, WALL. Z (A 0.186 AMPS 750d OL MC 4906 -9101 STROBE MC, RED, WALL. •3.e 0.186 AMPS 15Cd 01 4903 -9150 SPEAKER /STROBE 15CD, RED, WALL. 0.082 AMPS 300d EM 4903 -9148 SPEAKER /STROBE 30CD, RED, WALL. V 0.123 AMPS 1100d 4903 -9149 SPEAKER/STROBE 11OCD, RED, WALL. y Q 0.275 AMPS 15cd �L 4904 -9176 STROBE 15CD, RED, WALL. Z O 0.082 AMPS FJ 20849001 FIREMAN'S PHONE JACK ER 4098 -9843 RELAY, SPOT AT 10 AMP, PAM -SD W U U) 0 1 CONNECTION TO AN APPROVED, DEDICATED = C- EARTHGROUND, NFPA 70. COMPLY WITH NEC. _ 120VAC SOURCE DEDICATED BREAKER O Z COMPLY WITH NFPA 70. E EXISTING N O U NEW R RELOCATED W 0 WATTS NOTES - 1. FIRE ALARM SYSTEM SHALL BE POWER LIMITED. 2. WIRING SHALL BE #12 THHN, #14 THHN OR 18/2 TWISTED SHIELDED PAIR FPL TYPE CABLE. 3. INSTALLATION SHALL COMPLY WITH NFPA 1, 2009, APPLICABLE CHAPTERS. 4. INSTALLATION SHALL COMPLY WITH NFPA 72, 2007, APPLICABLE CHAPTERS. 5. INSTALLATION SHALL COMPLY WITH NFPA 101, 2009, APPLICABLE CHAPTERS. 6. INSTALLATION SHALL COMPLY WITH NEC 2008. 7. CONDUIT, AS APPLICABLE SHALL BE 1/7 MINIMUM WITH A MAXIMUM FILL OF 40 %. COMPLY WITH NEC. 8. SYSTEM SHALL BE GROUNDED PER MANUFACTURERS SPECIFICATIONS. 9. ALL DEVICES SHALL BE COMPATIBLE & SHALL BE UL LISTED FOR FIRE SERVICE USE. 10. ALL SPACES SHALL MEET THE AUDIBLE CHARACTRISTICS OF NFPA 72 AND NFPA 101. 11. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 3' OF A/C DIFFUSERS, KITCHEN OR BATHROOM DOORS. 12. CEILING MOUNTED DEVICES SHALL BE LOCATED AT A HEIGHT OF 10' +/- ON SMOOTH FLAT CEILING UNLESS OTHERWISE NOTED. 13. SIGNALLING LINE CIRCUITS SHALL HAVE A MAXIMUM OF 127 POINTS PER CHANNEL SEE FLOOR PLANS FOR QUANTITIES & TYPES OF DEVICES. 14. FIRE ALARM PANEL & ANY ASSOCIATED FIRE ALARM TRANSPONDERS SHALL BE FED BY A 120VAC, SINGLE PHASE, 20 AMP, DEDICATED BREAKER. 15. ALL INTERCONNECTED FIRE ALARM PANELS SHALL BE ARRANGED TO FUNCTION AS A SINGLE SYSTEM AND SHALL BE MONITORED FOR INTEGRITY PER NFPA 72. 16 RACKS, SHELVES AND EQUIPMENT ARE ALL LOWER THAN 80" ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED. 17. THE DESIGN INSTALLATION COMPLIES WITHFLORIDA BYULDING CODE -2012 FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION. 18. THE SYSTEM IS AN EXISTING REMOTE SUPERVISORY FIRE ALARM STATION PER NFPA- 72.8.5. 19. BUILDING HAS BACK UP GENERATOR 20 THIS IS A FULLY SPRINKLED FACILITY. 21. THIS IS A 7 STORY BUILDING. 22. ROOM CONTAINING FACP AND /OR BOOSTER POWER SUPPLY PANEL(S) IS MECHANICALLY VENTILATED. 23. MAXIMUM MOUNTING HEIGHT FOR ALL PANELS SHALL BE SIX FEET TO THE TOP OF THE ENCLOSURE. 24 MINIMUM CLEAR WORKING SPACE OF THREE FEET IN FRONT OF ALL FIRE ALARM PANELS SHALL BE PROVIDE. SCOPE OF WORK 1. PROVIDE & INSTALL FIRE ALARM SYSTEM AS SHOWN ON DRAWINGS. 2. SIGNALING LINE CIRCUIT WIRING SHALL BE STYLE 4. 3 NOTIFICATION APPLIANCE CIRCUIT WIRING SHALL BE STYLE Y. 4. THIS SYSTEM SHALL BE A EXISTING REMOTE STATION SIGNALING SYSTEM. 5. The scope of work shall consist of remodeling the 6th floor MRI Suite as show on prints. New devices will tie to existing panel or new NAC (Strobes only). Only the area boxed in shall be under contract. 11 SMOKES, 1 PULL, 1 DUCT, 11 STROBES, 3 SPEAKER/STROBES AND 1 NAC PANEL. EXISTING SEQUENCE OF OPERATION - UPON ACTIVATION OF ANY MANUAL STATION THE FOLLOWING SHALL OCCUR: 1. ALL AUDIBLES WILL SOUND UNTIL SYSTEM IS SILENCED. 2. ALL STROBES WILL FLASH UNTIL SYSTEM IS RESET. 3. AN ALARM SIGNAL SHALL BE SENT TO THE FACP & NPU'S. 4. A SIGNAL SHALL BE SENT TO THE OWNERS MONITORING STATION STATION VIA DACT. UPON ACTIVATION OF ANY SMOKE DETECTOR THE FOLLOWING SHALL OCCUR: 1. ALL AUDIBLES WILL SOUND UNTIL SYSTEM IS SILENCED. 2. ALL STROBES WILL FLASH UNTIL SYSTEM IS RESET. 3. ALL AIR HANDLERS SHALL SHUT DOWN PER THE DESIGNATED SEQUENCE. 4. AN ALARM SIGNAL SHALL BE SENT TO THE FACP & NPU'S. 5. A SIGNAL SHALL BE SENT TO THE OWNERS CENTRAL STATION VIA DACT. 6 MAGNETIC DOOR HOLDERS SHALL RELEASE ON THE FLOOR OF INCIDENT ONLY. 7. ALL FIRE SMOKE DAMPER SHALL ACTIVATE. UPON ACTIVATION OF ANY DUCT SMOKE DETECTOR THE FOLLOWING SHALL OCCUR: 1. A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & NPLPS. 2. ALL AIR HANDLERS SHALL SHUT DOWN PER THE DESIGNATED SEQUENCE. 3. A SIGNAL SHALL BE SENT TO THE OWNERS CENTRAL STATION VIA DACT. 4. MAGNETIC DOOR HOLDERS SHALL RELEASE ON THE FLOOR OF INCIDENT ONLY. 5. ALL FIRE SMOKE DAMPER SHALL ACTIVATE. NOTES: 1- REFER TO ENGINEER DRAWINGS FOR EXACT QUANTITY, LOCATION AND PLACEMENT OF DEVICES; 2- THE CONTRACTOR SHALL VERIFY THE SIZE REQUIREMENTS OF ALL BOXES, RACEWAYS AND Tr-RMINAL CABINETS AND ASSURE THEIR CONFORMANCE TO NEC. - 3. MAXIMUM ALLOWABLE LINE RUN, (FOR SLC DATA LINE) FROM F.A.C.P. TO FARTHEST DEVICE; T)OT TO EXCEED 2500 FEET. 4. MAXIMUM TOTAL WIRE (INCLUDING ALL T -TAPS) ON CIRCUIT, (FOR SLC DATA LINE) FROM F.A.C.P. NOT TO EXCEED 10,000 FEET OR .58uF. (CLASS B ONLY) - - - - 5- WIRE TYPES LISTED IN THE WIRE LEGEND ARE THE MANUFACTURER'S MINIMUM WIRING REQUIREMENTS. CONTRACTOR SHALL CHOOSE WIRE TYPES, COLOR AND RATING TO MEET THESE REQUIREMENTS AND ALL OF THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AND NFPA FOR THE APPLICATICNS ANA _ t LOCATIONS OF USE. ALSO AS PER LOCAL AND OWNERS WIRING CODES. - - - WIRE LEGEND A= INITIATING DEVICE CIRCUIT - IDC 2 #14 AWG THHN B = NOTIFICATION APPLIANCE CIRCUIT- NACNISUAL 2 #12 AWG THHN C = AUXILIARY CONTROL CIRCUIT -ACC 2 #14 AWG THHN D= VOICE COMMUNICATION CIRCUIT -VCC 18/2 TWISTED SHIELDED PAIR - NPLF F as FIRE FIGHTERS TELEPHONE CIRCUIT - FTC 18/2 TWISTED SHIELDED PAIR - NPLF MN= MULTI - ADDRESSABLE PERIPHERAL NETWORK- MAPNET 18/2 TWISTED /SHIELDED PAIR - NPLF MP= MAPNET POWER CIRCUIT- APC 2 #14 AWG THHN FrFX ALARM SYSTEM TO BE~ INSTALLED IN ACCORDANCE WrM NFPA 72; 70; 101• 'A�Q��® Ml"H -DADE COUNTY FIRE DEPARTMENT BLDG. PERMIT FIRE ALARM FIRE SUPPRESSION WATER MAIN EXT, DATE: ,Z ,<'' BY: J W W U) - Z Q W �U- W MI U- a O Q CL to N W 104 Z LU C1 O d W M (r) W J to r d U) LL M(v) P: 0) fY o = W 4. Co C C) ° � IL IL (A U LU .0 T' Q Z (A m a J •3.e W W > Z O�W C7 O Of U) V �O F- N_W y Q N J O J U 9 a Z O F- Z O W U U) 0 W 0 C- O Z (q O U G: 0 LL O w rq W m 0 U U N Q 0 O Z ++11111 /1► o CO c(*p Q14M• •e. J��'�i • �i � � � eau to 6 a - �yP 111 + + ++ W H N W U) U Z Cd g RI a W Z (--I W 07 O �W�JJ S r > LL N sd O J J Z w O Z .y.4 V) g DO -4-) T id sH I- U 0 U J z 0 d ace ° U) J [o� z a U, V w fed to z U R w CO .in r't .�-t v�l ° 3 !Y w Z W Q U L) Z ,LL U W fY O � a� W C7 J a a V i I- O Q U) CT IX Q r-1 U F- 0 F- Fg- LV S g Z S S-4 ZO O W (7 a O W I O Z Q J _ F5--( U Z Z c Z W O r 1 <4 N F- J J LL W � dr .r O Z (� W Z ^ ` W C0 O � ILD W .Y) � a W O �I ,�{ l�^-` I 'C1 N 0 FF- Z � LV W < • r1 l� O W Z o 0 Z L=,'x CO O 0 ZO Of a°"4U1U r- 0 aa °o DRAWN BY: DATE: CCRJR 11/13/12 DESIGNED BY: DATE: CCRJR 11113/12 APPROVED BY: DATE: PROJECT NUMBER: 263310304 / 967227004 SHEET TITLE/ PATH: LA00- 2003VUI 00 -2003 CAD DrawingsL.SOUTH MIAMI HOSPITAL (MASTER SITE)I.SMH DIALYSIS 967227004 SHEET NUMBER: NOTES SIZE D (24-X36-) J