12-1303R-009ELECTRICAL SPECIFICATIONS 16010 - BASIC ELECTRICAL REQUIREMENTS A. THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND INSTALLATION OF THE NECESSARY MATERIAL AND LABOR TO ACCOMPLISH THE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. ALL WORK BY CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL. STATE AND LOCAL. BUILDING CODES AND STANDARDS INCLUDING BUT NOT LIMITED TO.-REFER TO SHEET E0.00 B. CODES AND STANDARDS REFERRED TO ARE MINIMUM. WHERE THE REQUIREMENTS OF THE DRAWINGS OR SPECIFICATIONS EXCEED THOSE OF THE CODES AND REGULATIONS, THE DRAWINGS AND SPECIFICATIONS GOVERN. C. THE CONTRACTOR SHALL OBTAIN AND PAY FOR PERMITS, PLAN CHECKS, INSPECTIONS, AND APPROVALS APPLICABLE TO THE WORK AS REQUIRED BY THE REGULATORY AUTHORITIES. FEES AND COSTS OF ANY NATURE WHATSOEVER INCIDENTAL TO THESE PERMITS, INSPECTIONS AND APPROVALS SHALL BE ASSUMED AND PAID BY THE CONTRACTOR. THE PROM COSTS, IF ANY, FOR UTILITIES SERVING THIS PROPERTY WILL BE PAID FOR BY THE OWNER AND SHALL NOT BE INCLUDED AS PART OF THIS CONTRACT. D. SPACE ALLOCATIONS FOR MATERIALS, EQUIPMENT AND DEVICES HAVE BEEN MADE ON THE BASIS OF PRESENT AND KNOWN FUTURE REQUIREMENTS AND THE DIMENSIONS OF ITEMS OF EQUIPMENT OR DEVICES OF A PARTICULAR MANUFACTURER WHETHER INDICATED OR NOT. THE CONTRACTOR SHALL VERIFY THAT ALL MATERIALS, EQUIPMENT AND DEVICES PROPOSED FOR USE ON THIS PROJECT ARE WITHIN THE CONSTRAINTS OF THE ALLOCATED SPACE E ALL EXISTING SYSTEMS, EQUIPMENT OR MATERIAL CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING THE EXISTING CONDITIONS AT THE JOB SITE BEFORE SUBMITTING PROPOSALS. SUBMISSION OF PROPOSALS SHALL BE TAKEN AS EVIDENCE THAT SUCH INSPECTION HAS TAKEN PLACE. THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE COMPLETE SET OF CONSTRUCTION DOCUMENTS, AND THE LAIC OF SPECIFIC INFORMATION ON THE DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR OF ANY RESPONSIBILITY. F. EQUIPMENT SHALL BE NEW AND SHALL BEAR THE U.L. LABEL WHERE APPLICABLE, UNLESS NOTED OTHERWISE ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR AFTER COMPLETION AND ACCEPTANCE BY THE OWNER. G. CONTRACTOR SHALL INSTALL ELECTRICAL SYSTEMS WITHOUT INTERFERENCE AND IN STRICT COORDINATION WITH OTHER TRADES. H. MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE CONTRACT DOCUMENTS AND APPLICABLE CODES AND STANDARDS. IN CASE OF DIFFERENCE BETWEEN APPLICABLE CODES AND STANDARDS AND THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL PROMPTLY NOTIFY THE ARCHITECT/ENGINEER IN WRITING OF SUCH DIFFERENCE SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE REQUIREMENTS OF APPLICABLE CODES AND STANDARDS, HE /SHE SHALL BEAR ALL COSTS ARISING IN CORRECTING SUCH DEFECTS. APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL ORDINANCES, U11UTY COMPANY REGULATIONS, AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. SHOULD THE CONTRACTOR SUPPLY EQUIPMENT DIFFERING FROM THE SPECIFIED ITEMS IN THE CONTRACT DOCUMENTS WITHOUT NOTIFICATION TO THE ENGINEER, HE SHALL BEAR ALL COSTS TO UPGRADE DEFICIENCIES ARISING FROM SUCH. L WHERE ONLY ONE MANUFACTURER'S NAME IS LISTED IN THE EQUIPMENT SPECIFICATION, OTHER MANUFACTURERS OF SIMILAR CHARACTERISTICS AND OF EQUAL OR BETTER PERFORMANCE CAPACITIES MAY BE CONSIDERED FOR 'OR EQUAL' ACCEPTANCE BY THE ENGINEER. SUBSTITUTION REQUESTS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL WHERE MORE THAN ONE MANUFACTURER IS LISTED IN THE NOTES AND EQUIPMENT SPECIFICATIONS. ONLY THOSE NAMED MANUFACTURERS WILL BE CONSIDERED FOR ACCEPTANCE. SHOULD A SUBSTITUTION BE ACCEPTED, AND SHOULD THE SUBSTITUTE MATERIAL PROVE DEFECTIVE, OR OTHERWISE UNSATISFACTORY FOR THE SERVICE INTENDED WITHIN THE GUARANTEE PERIOD, THIS MATERIAL OR EQUIPMENT SHALL BE REPLACED WITH THE MATERIAL OR EQUIPMENT SPECIFIED AT NO COST TO THE OWNER. J. PROVIDE ACCESS, INCLUDING NECESSARY ACCESS DOORS, FOR NEW AND EXISTING EQUIPMENT REQUIRING OPERATION AND/OR MAINTENANCE. RELOCATE EXISTING AND LOCATE ALL NEW EQUIPMENT SUCH THAT OPERATION OR MAINTENANCE IS NOT RESTRICTED. K INSTALL EQUIPMENT WITH WORKING CLEARANCES COMPLYING WITH NEC 110 -26 AND 110 -34. L SHOP DRAWING SUBMITTALS 1. CONTRACTOR SHALL PREPAY AND SUBMIT SEVEN COPIES OF ALL SUBMITTALS FOR ALL PERTINENT ELECTRICAL EQUIPMENT AND DEVICES INDICATED IN THE SCOPE OF WORK 2. COMPLETE LIST OF MATERIALS TO BE FURNISHED UNDER EACH SPECIFIC SECTION. 3. MANUFACTURERS' SPECIFICATIONS AND OTHER DATA REQUIRED TO ASSURE SPECIFICATION COMPLIANCE 4. CATALOG SHEETS! CLEARLY MAR KO FOR IDENTIFICATION OF ITEMS TO BE PROVIDED, INCLUDING DISCONNECT SWITCHES. BREAKERS, FUSES, STARTERS, LIGHTING FIXTURES, TRANSFORMERS, OR OTHER MATERIAL NOT REQUIRING SPECIALLY PREPARED SHOP DRAWINGS. 56 ALL SHOP DRAWING CUT SHEETS SHALL CLEARLY IDENTIFY THE SPECIFIC PRODUCT TO BE REVIEWED AND APPROVED, INCLUDING MANUFACTURER. GENERIC CUT SHEETS. INCOMPLETE CUT SHEETS AND CUT SHEETS SUBMITTED "OUT IDENTIFYING THE SPECIFIC PRODUCT PROVIDED, WILL BE AUTOMATICALLY REJECTED. 6. AS PART OF EQUIPMENT SHOP DRAWINGS, PROVIDE DETAILED DIMENSIONED LAYOUT DRAWING FOR ALL LARGE ELECTRICAL EQUIPMENT AND ELECTRICAL ROOMS WHERE NEW EQUIPMENT IS BEING INSTALLED. M. EACH CONDUIT. REGARDLESS OF MATERIAL. WHICH PASSES THROUGH A CONCRETE SLAB, MASONRY WALL, OR ROOF OR PORTION OF THE BUILDING STRUCTURE SHALL BE FREE FROM THE STRUCTURE AND SHAT PASS THROUGH A SLEEVE ALL SI.EEVES SHALL BE CONSTRUCTED FROM ELECTRIC-METALLIC TUBING OR EQUIVALENT WEIGHT GALVANIZED STIIl. TUBING AND SHALL BE FLUSH ON 607H SIDES OF THE SURFACE PENETRATED. U.N.O. ALL REM PENETRATING THE ROOF AREAS SHALL EXTEND A MINIMUM 10 INCHES ABOVE THE ROOF WITH APPROVED WEATHERPROOF COUNTERFLASHING ATTACHED TO THE CONDUIT ABOVE THE ROOF. ALL SLEEVES PENETRATING FLOORS SHALL EXTEND A MINIMUM OF 6 INCHES A.F.F. THE SLEEVES SHALL BE SIZED TO ALLOW FREE PASSAGE OF THE CONDUIT TO BE INSERTED. SLEEVES PASSING THROUGH WALLS OR FLOORS ON OR BELOW GRADE OR IN MOIST AREAS SHALL BE CONSTRUCTS) OF GALVANIZED RIGID STEEL. AND SHAT BE DESIGNED WITH A SUITABLE FLANGE INT HE CENTER TO FORM A WATERPROOF PASSAGE AFTER THE CONDUIT HAS BEEN INSTALLED IN SLEEVES, THE VOID SPACE AROUND THE CONDUIT SHALL BE CAULKED AND FILLED WITH AN ASPHALT -BASE COMPOUND TO INSURE A WATERPROOF PENETRATION. JUTE TWINE CAULKING SHALL NOT BE USED. 16020 - ELECTRICAL WORK IN EXISTING FACILITIES A. THE CONTRACT DOCUMENTS DO NOT PROPOSE TO SHOW ALL EXISTING SYSTEMS MATERIAL OR EQUIPMENT. OBTAIN INFORMATION RELATED TO EXISTING FACILITIES FROM EXISTING DOCUMENTS. MEASUREMENTS, NOTATIONS, PHOTOGRAPHS, SURVEYS, AND OTHER OBSERVATIONS AT THE SITE B. SINCE THE BUILDING WILL CONTINUE IN USE THROUGHOUT THE CONSTRUCTION PERIOD. CARRY OUT THE WORK UNDER THIS DIVISION IN SUCH A MANNER AS TO MINIMIZE DISTURBANCE TO THE OCCUPANTS. C. REMOVE EXISTING WIRE, CONDUIT, EQUIPMENT, FIXTURES AND OTHER ITEMS TO PROVIDE ACCESS FOR WORK IN EXISTING FACILITIES. REINSTALL AND REFINISH ITEMS REMOVED, OR OTHERWISE DAMAGED, TO MATCH EXISTING ADJACENT SURFACED UPON COMPLETION OF THE WORK D. WHERE EXISTING FUNCTIONS TO REMAIN IN USE ARE DISRUPTED. THEY SHALL BE FULLY RESTORED AFTER DISRUPTION, IN FULL COMPLIANCE WITH THIS DIVISION OF THE SPECIFICATIONS FOR NEW WORK. E MODIFY, REMOVE OR RELOCATE MATERIALS AND ITEMS INDICATED ON THE DRAWINGS OR REQUIRED BY THE INSTALLATION OF NEW WORK. F. WORKING JOINTLY WITH THE ARCHITECT, ESTABLISH AND MARK SALVAGE AND DEMOLITION ITEMS BEFORE COMMENCING WORK; REPORT ITEMS SCHEDULE FOR RELOCATION, REINSTALLATION OR REUSE, WHICH ARE FOUND TO BE IN DAMAGED CONDITION; AWAIT FURTHER INSTRUCTIONS FROM THE ARCHITECT BEFORE COMMENCING WITH WORK. G. DEMOLITION EQUIPMENT, DEVICES AND MATERIAL SHALL BE REMOVED FROM THE SITE AND DISPOSED OF BY THE CONTRACTOR. SALVAGED EQUIPMENT AND DEVICES SHALL BE THE PROPERTY OF THE OWNER UNLESS NOTED OTHERWISE H. MAKE MINOR RELOCATIONS NECESSITATED BY THE CONDITIONS AT THE SITE OR AS DIRECTED BY THE ARCHITECT, WITHOUT ADDITIONAL COST TO THE OWNER. REPAIR AND RESTORE TO GOOD FUNCTIONAL CONDITION, EQUIPMENT, MATERIALS AND ITEMS SCHEDULED FOR RELOCATION, WHICH ARE DAMAGED DURING DISMANTLING OR REASSEMBLY OPERATIONS. NEW MATERIALS AND ITEMS OF SIMILAR DESIGN AND QUALITY MAY BE SUBSTITUTED FOR MATERIALS AND ITEMS INDICATED TO BE RELOCATED UPON APPROVAL OF SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. REMOVE CAREFULLY, IN REVERSE ORDER TO ORIGINAL ASSEMBLY OR PLACEMENT, ITEMS WHICH ARE TO BE RELOCATED. PROTECT ITEMS UNTIL RELOCATION IS COMPLETE. CLEAN AND REPAIR 11EMS TO BE RELOCATED, AND PROVIDE NEW MATERIALS, FITTINGS AND APPURTENANCES REQUIRED TO COMPLETE THE RELOCATIONS AND TO RESTORE TO GOOD OPERATING ORDER. PERFORM THE RELOCATION WORK IN ACCORDANCE WITH APPLICABLE PORTIONS OF THESE SPECIFICATIONS, UTILIZING SKILLED WORKERS. 1. RELOCATING DEVICES: REMOVE AND REINSTALL IN LOCATIONS DESIGNATED BY THE ARCHITECT TEMPERATURE CONTROL SYSTEM DEVICES, RELAYS, WIRE, CONDUIT, FIXTURES, EQUIPMENT AND OTHER DEVICES REQUIRED FOR THE OPERATION OF THE VARIOUS SYSTEMS THAT ARE INSTALLED IN EXISTING- TO-BE- REMOVED CONSTRUCTION. 16084 - THROUGH - PENETRATION FIR57OLPPING FOR ELECTRICAL SYSTEMS A. ONLY TESTED FIRESTOP SYSTEMS SHALL BE USED IN SIPEanc LoCAnoNs AS FOLLOWS: 1. PENETRATIONS FOR THE PASSAGE OF CONDUIT AND OTHER ELECTRICAL EQUIPMENT THROUGH FIRE -RATED VERTICAL BARRIERS (WALLS AND PARTITIONS), HORIZONTAL BARRIERS (FLOOR /CEILING ASSEMBLIES), AND VERTICAL SERVICE SHAFT WALLS AND PARTITIONS. 2. COMPLETION OF FIRESIOP INSTALLATIONS TO MAINTAIN THE RATING INTEGRITY OH= THE BARRIER PENETRATED. B. INSTALLER SHALL CONSULT THE STRUCTURAL ENGINEER PRIOR TO PENETRATING ANY LOAD BEARING ASSEMBLY. C. ACCEPTABLE MANUFACTURERS: HILT INC., TREMCO SEALANTS do COATINGS, 3M FIRE PROTECTION PRODUCTS, JOHN - MANVILLE FIRETEMP, OR OTHER MANUFACTURERS LISTED IN THE UL FIRE RESISTANCE DIRECTORY - VOLUME 2. D. CONTRACTOR IS RESPONSIBLE FOR PROVIDING FIRESTOPPING BARRIER AT ALL ELECTRICAL BOXES (EXISTING AND NEW) AND PENETRATIONS FOR ANY EXISTING FIRE WALLS IN THE SCOPE OF WORK AREA AND/OR FOR ANY NEW FIRE WALLS. FOR NEW FIRE WALLS IN WHICH ONE SIDE OF THE WALL FALLS OUTSIDE OF THE SCOPE OF WORK AREA AND OTHER DOES NOT, CONTRACTOR SHALL PROVIDE FIRSTOPPING BARRIER FOR ALL PENETRATIONS AND ELECTRICAL BOXES ON THE WALL SIDE NOT IN THE SCOPE OF WORK AREA. 16110 - SYSTEMS OF RACEWAYS A CONDUIT I. RIGID STEEL CONDUIT (CITE - GALVANIZED RIGID CONDU17j. CONSTRUCTED OF MILD STEEL PIPING, GALVANIZED INSIDE AND OUTSIDE, CONFORMING WITH FED. SPEC. WW- C -581E, ANSI CBO.1 AND UL 6. 2. INTERMEDIATE METAL CONDUIT I CONSTRUCTED OF ZINC COATED STEEL TUBING MANUFACTURED IN ACCORDANCE WITH FED. SPEC. WW- C- 5814, UL -1242 AND MEETING THE REQUIREMENTS OF THE NEC. 3• ELECTRIC METALLIC TUBING (EMT): CONSTRUCTED OF HIGH GRADE STEEL MANUFACTURED SPECIFICALLY TO STANDARDS ASSURING MAXIMUM WELDING CHARACTERISTICS AND DUCTILITY, AND SHALL CONFORM TO FED. SPEC. WW-C-563 -A, ANSI C80-3, AND UL 797. 4. LIQUIDTIGHT FLEXIBLE CONDUIT: FLEXIBLE METAL CONDUIT AS SPECIFIED HEREIN WITH A COPPER GROUNDING STRAND AND FACTORY - APPLIED NEOPRENE JACKET. LIQUID TIGHT FLEXIBLE CONDUIT SHALL BE UL LISTED, EQUIVALENT TO ANACONDA 'SEAL 711r. TYPE UA. 56 INSTALLATION OF BUILDING CONDUIT a ALL INTERIOR RACEWAYS SHALL BE BAT. RACEWAYS IN DAMP OR WET LOCATIONS, OR IN HAZARDOUS LOCATIONS, SHALL BE GRC OR IMC. b. CONDUITS SHALL BE OF SUCH SIZE AND SO INSTALLED THAT THE CONDUCTORS MAY BE DRAWN THROUGH WITHOUT INJURY OR EXCESSIVE STRAIN, SHALL BE SECURED AT CABINETS AND BOXES WITH GALVANIZED LOCKNNUIS, BOTH INSIDE AND OUTSIDE, AND SHALL HAVE APPROPRIATE BUSHING INSIDE BUSHING SHALL BE INSULATING TYPE WITH BOND GROUND CLAMPS. Q USE LENGTHS OF FLEXIBLE METAL CONDUIT NOT LESS THAN 12 INCHES LONG AT FINAL CONNECTIONS TO ALL MOTORS, TRANSFORMERS AND SIMILAR DEVICES SUBJECT TO MOVEMENT BECAUSE OF VIBRATION OR MECHANICAL ADJUSTMENT. USE FLEXIBLE METAL CONDUITS TO EFFECT FINAL CONNECTIONS TO RECESSED LIGHTING FIXTURES (6FT MAX). USE LINE TIGHT REXIBLE METAL CONDUIT, WITH APPROPRIATE CONNECTIONS, IN DAMP OR WET LOCATIONS, AT MOTOR OR EQUIPMENT LOCATIONS IN MECHANICAL EQUIPMENT ROOMS, AT OR NEAR PUMPS, AND WHEN INSTALLED OUTDOORS d GROUND METALLIC CONDUITS AS REQUIRED BY NEC. e. INSTALL RACEWAYS CONTINUOUS FROM OUTLET TO OUTLET BOX, OR CABINET, WITH A MAXIMUM OF 150 FEET BETWEEN PULLS. IN AREAS WHERE THERE ARE NO SUSPENDED CEILINGS, RUN ALL CONDUITS PARALLEL/1PERPENDICULAR TO BUILDING SURFACE. f IN SYSTEMS OPERATING AT MORE THAN 300 VOLTS BETWEEN PHASE CONDUCTORS, AND WHERE DIFFERENT PHASE CONDUCTORS ARE TO BE RUN TO A COMMON GANG WALL SWITCH BOX, PROVIDE SUBSTANTIAL BARRIERS BETWEEN ADJACENT SWITCHES IN THE BOX SO THAT 710 DIFFERENT PHASE WIRES WILL NOT BE IN THE SAME COMPARTMENT. 9. WHEREVER RACEWAYS PASS THROUGH FLOORS, WALLS, PENETRATIONS, OR 07HER PARTITIONS, CAREFULLY FILL ANY SPACE BETWEEN THE OUTSIDE OF THE RACEWAY AND THE BUILDING MATERIAL TID PREVENT PASSAGE OF AIR, WATER, SMOKE, AND FUMES. FILLING MATERIAL SHALL BE A UL LISTED, INTUMESCENT SEALING HAVING FIRE/SMOKE RESISTIVE RATING EQUAL TO THE BUILDING MATERIAL PENETRATE). h. CONDUITS UTILIZED THROUGHOUT THE PROJECT SHALL NOT BE SMALLER THAW 3/4 INCH FOR FEEDERS„ MULTIPLE BRANCH CIRCUIT HOMERUNS AND HOMERUNS OF CONDUCTORS LARGER THAN NO. 12. INDIVIDUAL BRANCH CIRCUIT WIRING FOR NO. 12 CONDUCTORS SHALL BE ACCEPTABLE IN 3/4' CONDUIT, I.E. 2#12, 1#12G, 3/4'C. B. COUPLINGS AND TERMINATORS 1. FOR RIGID STEEL. OR INTERMEDIATE METAL CONDUIT. FACTORY -MADE THREADED COUPLING OF SAME MATERIAL AS THE CONDUIT. 2 FOR ELECTRICAL METALLIC TUBING, USE STEEL CONFESSION COUPLING AND NYLON INSULATED GROUNDING BUSHINGS. 3. FOR FLEXIBLE METAL CONDUIT COUPLING AT CONNECTIONS BETWEEN FLEXIBLE CONDUIT AND EMT, AND NYLON INSULATED THROAT STEEL CONNECTORS AT BOX OR CABINET TERMINATIONS. 4. SCREW COUPLINGS; STEEL SET SCREW BOX CONNECTORS WITH NYLON INSULATED THROAT AND LOCKNUTS AT ALL BOXES AND CABINET TERMINATIONS OR NON-INSULATED BOX CONNECTOR. LOCKNUT AND NYLON-INSULATED GROUNDING BUSHING ON aR GROUNDING ` h ARE REQUIRED. C. JUNCTION ( PULL BOXES 1. SIZE BOXES IN ACCORDANCE WITH THE REQUIREMENTS OF THE NEC. BOXES SHALL BE UL LISTED AND NO SMALLER THAN 4 INCHES SQUARE BY 1-1/2 INCHES DEEP WITH COVERS ACCESSIBLE AT ALL TIMES. SET BOXES ON 0ONCEALED CONDUITS WITH COVERS FLUSH WITH THE FINISHED WALL OR CEILING LINE. PROVIDE 1 1 PULL BOXES OF APPROPRIATE DIMENSIONS FOR CONDUITS AND CONDUICTORS NOTED, WHERE SHOWN AND WHERE NECESSARY FOR THE INSTALLA71ON AND PULLING OF a, AND WIRES. COVERS ON JUNC71ON BOXES AND CONDULETS AFTER WRING AND CONNECTIONS ARE COMPLETED. JUNCTION Z ALL 1 PUILL BOXES FOR EMERGENCY SYST7 AND LOW VOLTAGE SY57EMS SHALL HAW COVER PLATES PAINTED. COLORS FOR COVERS SHALL BE YELLOW! RANCH), ORANGE (CRITICAL BRAl GREEN (EQUIPMENT SYSTEM), RED (FIRE ALARM), AND BRIDOIN (DATA/TELEPHONE). INSTALLATION OF 1 JUNCTION BOXES a. 0. FASTEN ALL BOXES SECURELY M THE BUILDING CONSTRUCTION, OF CONDUIT a A b. ON CONCE&ED CONDUIT SYSTEMS WHERE BOXES ARE NOT OTHEINSE ACCESSIBLE. SET BOXES FLUSH V17H FINISHED SURFACES FOR ACCESSt AND PROVIDE OVERLAPPING COVERS. C. ALL WIRING DEVICES FACEPLA7ES SHALL BE ENGRAVED VATH THE PANELBDARD DESIGNATION AND CIRWIT NUMBER SERVING THE OUTLET. .7 NOT CE D. OUTLET BOXES 1. OUTLET BOXES SHALL BE UL LISTED, AND OF SIZES ANit TYPES REQUIRED FOR THE APPLICATION. OUTLET BOXES SHALL BE SHEET STEEL, 1 LIGHTER THAN 14 GAUGE, /al AFTER r FABRICATION. SET BOX SO FACE OF BOX WILL FINISH FLUSH WITH BUILDING SURFACE. CL FOR LIGHTING FIXTURE 1 U11ETS:- 4 INCH SQUARE PLASTER 1/2 INCHES DEEP WITH RAW FIXTURE RING. b. FOR WALL SWITCHESt RECEPTACLES, AND COMMUNICATION USE 4 INCH SQUARE. BY 1-1/2 INCHES DEEP. USE BOXES WITH RINGS IN ALL PLASTERED WALLS WHERE WALL THICKNESS • r. BOXES LESS CANNOT INCH DEEP ONLY IN LOCATIONS WHERE DEEP BOXES • «I 11 a► BY CONSTRUCTION. 16120 - SYSTEM OF CONDUCTORS A. CONDUCTORS SHALL BE 98% CONDUC71MTY SOFT DRAWN ANNEALED COPPER, 600 VOLT, 1HHN/THWN INSULATK% #10 AND Smmm - SOLID, iAND LARGER STRANDED. B. NO CONDUCTORS ` T THAN NO. 12, EXCEPT F1' SIGNAL OR CONTROL CIRCUITS AND FOR INDIVIDUAL LIGHTING FIXTURE TAPS AS PERWMO BY NEC. FEET, C. FOR HOME RUNS ON 120-VOLT, 20-AMPERE BRANCH CIRCUITS, WHERE LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 100 LINEAR ` 1 10 • f 1 • •w WHERE LENGTH OF 1 LINEAR FEET OR LESS, USE 1 12 •f 1 O D. FOR HOME RUNS ON 1 LT, 20-AWPERE BRANCH CIRCUITS, ER LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 200 LINEEAR FEEL USE NO. 10 CONDUCTORS. WHERE LENGTH OF 11 LINEAR FEET OR LESS, 1 12 •t 1 OR& E. RUN DEDICATED NEUTRAL CONDUCTOR WITH EACH t CIRCUIT. SHARING OF NEUTRAL CONDUCTORS WOULD NECESSITATE THE USE OF MUL11PLE POLE OR TIED CIRCUIT BREAKERS TO ALLOW SIMULTANEOUS DISCONNECTING OF CURIF0T CARRYING CONDUCTORS IN OIRDER TO COMPLY 1 REQUIREMENTS AN1 THEREFORE F. RWM% CODEID CABLE SYSTEM APPROVED BY OMER. IF NONE REQUIRED OWNER, PROVIDE THE FOLLOWING COLOR - CODING: :► 208V/120 BROWN A PHASE BLACK ORANGE B PHA` •.al NEUTRAL - r� f PHASE NEUTRAL - WHITE GROUND 1 r•a7 GROUND r•aa COLOR CODING SHALL BE CONTINUOUS ON S • FOR #6 AWIG OR SMALLER AND CONTINUOUS OR MARKED WITH COLOR TAPE AT ALL CONNECTIONS i' CONDUCTORS LA' E INSTALLATION THAN 06 AWG. G. OF CONDUCTORS WHICH 1. PULL NO CONDUCTORS INTO CONDUITS UNTIL ALL WORK OF A NATURE 1 CONDUCTORS S COMPLETED. Z RUN FEEDERS IN CONTINUOUS UMMS, • I i • • SPLICES, INSOFAR 3. RUN CONDUITS 1' EMERGENCY POWER CONDUCTORS SEPARATE '1 ALL OTHER WIRING. 4. CABLE TYPE AC 1 • MC IS NOT • 7/ FOR HOMERUN AND FEDER r INSTALLATIONS. A. ALL WRING DEVICES SHALL BE UL LISTED. COOPER. C. RECEPTACLES 1. RECEPTACLES HOSPITAL ► STANDARD STYLE THEY SIALL 21 • 1 7 .1 • CONFORATION, ► ► r ./ 1 7 ► 71 ► ► Z GFCI RECEPTACLES SHALL BE A FEED THROUGH TYPE WIRED FOR SINGLE RECEPTACLE PROTECTION THUS NOT AFFECTING RECEPTACLES DOWNSTREAM • CIRCUIT. ` al CLASS WITH 5rnA GROUND 1 •, • a II ► aal • 1 r RATING 1 a 1• CONFIGURATION. 3. RECEPTACLE COLOR IVORY. ` •al a CONNECTED • EMERGENCY CIRCUIT. 4. PEDIATRIC LOCATIONS - ALL RECEPTACLES LOCATED IN PATIENT CARE AREAS SHALL BE LISTED TAMPER RESISITANT. D. SWITCHES 1. SWITCHES SHALL BE SPECIFICATION GRADE, 20A, 120/277V, HOIWOW RATED, BACK AND SIDE WIRED. SWITCHES SHALL INCLUDE GREEN r• ♦ 1 `••, • al 1 MOUNTING Z WHERE LIGHTING CIRCUITS ARE SHOWN TO BE LINE VOLTAGE SWITCHED, PROVIDE 1 SPECIFICATION GRADE, RATED, LISTED, BACK- AND SIDE-WIRED, TOGGLE SWITCHES RATED 20A, 120V OR 277 VOLTS. SWITCHES SHALL BE SPST. DPST, 3-WAY OR 4-WAY, WITH OR 1 / r INDICATED t 1.• h & SWITCH COLOR SHALL BE IVOIRY OR RED WHEN CONNECTED TO AN EMERGENCY 7 CIRCUIT. E WALL PLATES PLATES 1. WALL ` PROVIDED t• « '1 !a' • a. 7 a' 1 ► 1 SPECIAL PURPOSE Q OUTLETS. PLATES SHALL BE OF SUITABLE CONFIGURATION FOR THE DEVICE FOR WHICH t COVER COLOR • MOUNTING SCREWS. COLOR 1 a. ` « 1 « U.N.O. 2. WALL PLATES THERMOPLASTIC, 1 N 1 HIGH-IMPACT RESISTANT. THEY SHALL BE P-LINE SMOOTH PLATES. THEY SHALL, BE + •a• DEVICE IT IS TO COVER. I WEATHERPROOF. WRING DEVICE IN WET LOCATIONS SHALL BE INSTALLED WITH A HINGED t tt 7' 7 • /S •, CLEARLY MARKED FOR LOCATIONS ` 1 S al a'1 SHALL A GASKET BETWEEN THE COVER/MCLOSURE AND THE MOUNTING SURFACE, 1 BETWEEN r71 COVER 1 1 ` TO S.` PROPER COVER/ENCLOSURE SPECIFICATION GRADIE AS MANUFACTURED BY TAYMAC COI;FORATION OR EQUAL N. CONTRACTOR SHALL KEEP A CLEAN SET OF DRAWING AT THE SITE, NOTING DAILY ALL CHANGES MADE IN THESE DRAWING IN CONNECTION I. r t ` 1 al I r :f • WITH THE FINAL INSTALLATION INCLUDING EXACT DIMENSIONED LOCATIONS •!a• •a• « a• r r7 a• a •{ t- OF ALL NEW AND UNCOVERED EXISTING UTILITIES TURN OVER A CLEAN, NEATLY MARKED SET OF REPRODUCIBLE MYLARS SHOWING 'AS INSTALLED' WORK TO THE ARCHITECT FOR SUBSEQUENT REVIEW AND TRANSMITTAL TO THE OWNER. CONTRACTOR SHALL NOTE ALL CONSTRUCTION CHANGES, DATE EACH SHEET AND LABEL 'AS- BUILTS' IN THE REVISION BLOCK ON 1 t 'ii ` •� t ► 71 T� • THE DRAWINGS. CONTRACTOR SHALL ALSO FURNISH ONE (1) SET OF • la. t 1a. I! •, `: a ; 'AS- BUILT" BLUELINE PRINTS. 0. IN ADDITION TO THE ABOVE, CONTRACTOR SHALL ACCUMULATE DURING THE ;1 IN 1104 JOB'S PROGRESS, THE FOLLOWING DATA, IN TRIPLICATE, PREPARED IN A + •1 •a' « a. 1 1 ! N 7• 1 1 1 NEAT BROCHURE OR PACKET FOLDER AND TURNED OVER TO THE ARCHITECT h ` - •1 •17 + 1 {. 71 .1 t- i r•;7a. FOR REVIEW AND SUBSEQUENT DELIVERY TO THE OWNER. ! >, 1 1 « •7 a• 1 • 1 11 1 • 1 1. ALL WARRANTIES AND GUARANTEES AND MANUFACTURER'S 1 •+ 1 • - / 1 ► 1 1 r'17a. !1 1 • -w 11 1 DIRECTIONS ON EQUIPMENT AND MATERIAL COVERED BY THE ", 1 1 CONTRACT INCLUDING THE NAMES, ADDRESSES AND TELEPHONE NUMBERS OF THE MANUFACTURER'S REPRESENTATIVE ell I we .111 I 2 APPROVED FIXTURE BROCHURES, WIRING DIAGRAMS AND CONTROL DIAGRAMS (ORIGINAL DATA, NO COPIES). ' ! 7 11 1 t '•1 1! r•77 • 7 1 I COPIES OF APPROVED SHOP DRAWINGS. 1 '', , .'•'; 1.7• t f « 1•a• 1 1 4. OPERATING INSTRUCTIONS FOR ALL ELECTRICAL SYSTEM EQUIPMENT. OPERATING INSTRUCTIONS SHALL ALSO INCLUDE RECOMMENDED MAINTENANCE PROCEDURES.. 5. TEST REPORTS REQUIRED BY THESE SPECIFICATIONS. 7 . • Ire 1' 1. 7 1 1 6. ANY AND ALL OTHER DATA AND/OR DRAWING REQUIRED DURING CONSTRUCTION. •t al 7. REPAIR PARTS LISTS OF ALL MAJOR ITEMS OF EQUIPMENT 1• 1 tf r 1 7 + 71 a' + + INCLUDING NAME, ADDRESS AND TELEPHONE NUMBERS OF LOCAL +•a' 1 r• + :t • SUPPLIER OR AGENT. P. ALL OF THE ABOVE DATA SHALL BE SUBMITTED TO THE ENGINEER FOR HIS G REVIEW AT SUCH TIME AS THE CONTRACTOR SUBMITS HIS LAST ESTIMATE I.- PRIOR TO HIS FINAL PAYMENT, BUT IN NO CASE, LESS THAN TWO WEEKS 9 BEFORE FINAL INSPECTION. 16020 - ELECTRICAL WORK IN EXISTING FACILITIES A. THE CONTRACT DOCUMENTS DO NOT PROPOSE TO SHOW ALL EXISTING SYSTEMS MATERIAL OR EQUIPMENT. OBTAIN INFORMATION RELATED TO EXISTING FACILITIES FROM EXISTING DOCUMENTS. MEASUREMENTS, NOTATIONS, PHOTOGRAPHS, SURVEYS, AND OTHER OBSERVATIONS AT THE SITE B. SINCE THE BUILDING WILL CONTINUE IN USE THROUGHOUT THE CONSTRUCTION PERIOD. CARRY OUT THE WORK UNDER THIS DIVISION IN SUCH A MANNER AS TO MINIMIZE DISTURBANCE TO THE OCCUPANTS. C. REMOVE EXISTING WIRE, CONDUIT, EQUIPMENT, FIXTURES AND OTHER ITEMS TO PROVIDE ACCESS FOR WORK IN EXISTING FACILITIES. REINSTALL AND REFINISH ITEMS REMOVED, OR OTHERWISE DAMAGED, TO MATCH EXISTING ADJACENT SURFACED UPON COMPLETION OF THE WORK D. WHERE EXISTING FUNCTIONS TO REMAIN IN USE ARE DISRUPTED. THEY SHALL BE FULLY RESTORED AFTER DISRUPTION, IN FULL COMPLIANCE WITH THIS DIVISION OF THE SPECIFICATIONS FOR NEW WORK. E MODIFY, REMOVE OR RELOCATE MATERIALS AND ITEMS INDICATED ON THE DRAWINGS OR REQUIRED BY THE INSTALLATION OF NEW WORK. F. WORKING JOINTLY WITH THE ARCHITECT, ESTABLISH AND MARK SALVAGE AND DEMOLITION ITEMS BEFORE COMMENCING WORK; REPORT ITEMS SCHEDULE FOR RELOCATION, REINSTALLATION OR REUSE, WHICH ARE FOUND TO BE IN DAMAGED CONDITION; AWAIT FURTHER INSTRUCTIONS FROM THE ARCHITECT BEFORE COMMENCING WITH WORK. G. DEMOLITION EQUIPMENT, DEVICES AND MATERIAL SHALL BE REMOVED FROM THE SITE AND DISPOSED OF BY THE CONTRACTOR. SALVAGED EQUIPMENT AND DEVICES SHALL BE THE PROPERTY OF THE OWNER UNLESS NOTED OTHERWISE H. MAKE MINOR RELOCATIONS NECESSITATED BY THE CONDITIONS AT THE SITE OR AS DIRECTED BY THE ARCHITECT, WITHOUT ADDITIONAL COST TO THE OWNER. REPAIR AND RESTORE TO GOOD FUNCTIONAL CONDITION, EQUIPMENT, MATERIALS AND ITEMS SCHEDULED FOR RELOCATION, WHICH ARE DAMAGED DURING DISMANTLING OR REASSEMBLY OPERATIONS. NEW MATERIALS AND ITEMS OF SIMILAR DESIGN AND QUALITY MAY BE SUBSTITUTED FOR MATERIALS AND ITEMS INDICATED TO BE RELOCATED UPON APPROVAL OF SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. REMOVE CAREFULLY, IN REVERSE ORDER TO ORIGINAL ASSEMBLY OR PLACEMENT, ITEMS WHICH ARE TO BE RELOCATED. PROTECT ITEMS UNTIL RELOCATION IS COMPLETE. CLEAN AND REPAIR 11EMS TO BE RELOCATED, AND PROVIDE NEW MATERIALS, FITTINGS AND APPURTENANCES REQUIRED TO COMPLETE THE RELOCATIONS AND TO RESTORE TO GOOD OPERATING ORDER. PERFORM THE RELOCATION WORK IN ACCORDANCE WITH APPLICABLE PORTIONS OF THESE SPECIFICATIONS, UTILIZING SKILLED WORKERS. 1. RELOCATING DEVICES: REMOVE AND REINSTALL IN LOCATIONS DESIGNATED BY THE ARCHITECT TEMPERATURE CONTROL SYSTEM DEVICES, RELAYS, WIRE, CONDUIT, FIXTURES, EQUIPMENT AND OTHER DEVICES REQUIRED FOR THE OPERATION OF THE VARIOUS SYSTEMS THAT ARE INSTALLED IN EXISTING- TO-BE- REMOVED CONSTRUCTION. 16084 - THROUGH - PENETRATION FIR57OLPPING FOR ELECTRICAL SYSTEMS A. ONLY TESTED FIRESTOP SYSTEMS SHALL BE USED IN SIPEanc LoCAnoNs AS FOLLOWS: 1. PENETRATIONS FOR THE PASSAGE OF CONDUIT AND OTHER ELECTRICAL EQUIPMENT THROUGH FIRE -RATED VERTICAL BARRIERS (WALLS AND PARTITIONS), HORIZONTAL BARRIERS (FLOOR /CEILING ASSEMBLIES), AND VERTICAL SERVICE SHAFT WALLS AND PARTITIONS. 2. COMPLETION OF FIRESIOP INSTALLATIONS TO MAINTAIN THE RATING INTEGRITY OH= THE BARRIER PENETRATED. B. INSTALLER SHALL CONSULT THE STRUCTURAL ENGINEER PRIOR TO PENETRATING ANY LOAD BEARING ASSEMBLY. C. ACCEPTABLE MANUFACTURERS: HILT INC., TREMCO SEALANTS do COATINGS, 3M FIRE PROTECTION PRODUCTS, JOHN - MANVILLE FIRETEMP, OR OTHER MANUFACTURERS LISTED IN THE UL FIRE RESISTANCE DIRECTORY - VOLUME 2. D. CONTRACTOR IS RESPONSIBLE FOR PROVIDING FIRESTOPPING BARRIER AT ALL ELECTRICAL BOXES (EXISTING AND NEW) AND PENETRATIONS FOR ANY EXISTING FIRE WALLS IN THE SCOPE OF WORK AREA AND/OR FOR ANY NEW FIRE WALLS. FOR NEW FIRE WALLS IN WHICH ONE SIDE OF THE WALL FALLS OUTSIDE OF THE SCOPE OF WORK AREA AND OTHER DOES NOT, CONTRACTOR SHALL PROVIDE FIRSTOPPING BARRIER FOR ALL PENETRATIONS AND ELECTRICAL BOXES ON THE WALL SIDE NOT IN THE SCOPE OF WORK AREA. 16110 - SYSTEMS OF RACEWAYS A CONDUIT I. RIGID STEEL CONDUIT (CITE - GALVANIZED RIGID CONDU17j. CONSTRUCTED OF MILD STEEL PIPING, GALVANIZED INSIDE AND OUTSIDE, CONFORMING WITH FED. SPEC. WW- C -581E, ANSI CBO.1 AND UL 6. 2. INTERMEDIATE METAL CONDUIT I CONSTRUCTED OF ZINC COATED STEEL TUBING MANUFACTURED IN ACCORDANCE WITH FED. SPEC. WW- C- 5814, UL -1242 AND MEETING THE REQUIREMENTS OF THE NEC. 3• ELECTRIC METALLIC TUBING (EMT): CONSTRUCTED OF HIGH GRADE STEEL MANUFACTURED SPECIFICALLY TO STANDARDS ASSURING MAXIMUM WELDING CHARACTERISTICS AND DUCTILITY, AND SHALL CONFORM TO FED. SPEC. WW-C-563 -A, ANSI C80-3, AND UL 797. 4. LIQUIDTIGHT FLEXIBLE CONDUIT: FLEXIBLE METAL CONDUIT AS SPECIFIED HEREIN WITH A COPPER GROUNDING STRAND AND FACTORY - APPLIED NEOPRENE JACKET. LIQUID TIGHT FLEXIBLE CONDUIT SHALL BE UL LISTED, EQUIVALENT TO ANACONDA 'SEAL 711r. TYPE UA. 56 INSTALLATION OF BUILDING CONDUIT a ALL INTERIOR RACEWAYS SHALL BE BAT. RACEWAYS IN DAMP OR WET LOCATIONS, OR IN HAZARDOUS LOCATIONS, SHALL BE GRC OR IMC. b. CONDUITS SHALL BE OF SUCH SIZE AND SO INSTALLED THAT THE CONDUCTORS MAY BE DRAWN THROUGH WITHOUT INJURY OR EXCESSIVE STRAIN, SHALL BE SECURED AT CABINETS AND BOXES WITH GALVANIZED LOCKNNUIS, BOTH INSIDE AND OUTSIDE, AND SHALL HAVE APPROPRIATE BUSHING INSIDE BUSHING SHALL BE INSULATING TYPE WITH BOND GROUND CLAMPS. Q USE LENGTHS OF FLEXIBLE METAL CONDUIT NOT LESS THAN 12 INCHES LONG AT FINAL CONNECTIONS TO ALL MOTORS, TRANSFORMERS AND SIMILAR DEVICES SUBJECT TO MOVEMENT BECAUSE OF VIBRATION OR MECHANICAL ADJUSTMENT. USE FLEXIBLE METAL CONDUITS TO EFFECT FINAL CONNECTIONS TO RECESSED LIGHTING FIXTURES (6FT MAX). USE LINE TIGHT REXIBLE METAL CONDUIT, WITH APPROPRIATE CONNECTIONS, IN DAMP OR WET LOCATIONS, AT MOTOR OR EQUIPMENT LOCATIONS IN MECHANICAL EQUIPMENT ROOMS, AT OR NEAR PUMPS, AND WHEN INSTALLED OUTDOORS d GROUND METALLIC CONDUITS AS REQUIRED BY NEC. e. INSTALL RACEWAYS CONTINUOUS FROM OUTLET TO OUTLET BOX, OR CABINET, WITH A MAXIMUM OF 150 FEET BETWEEN PULLS. IN AREAS WHERE THERE ARE NO SUSPENDED CEILINGS, RUN ALL CONDUITS PARALLEL/1PERPENDICULAR TO BUILDING SURFACE. f IN SYSTEMS OPERATING AT MORE THAN 300 VOLTS BETWEEN PHASE CONDUCTORS, AND WHERE DIFFERENT PHASE CONDUCTORS ARE TO BE RUN TO A COMMON GANG WALL SWITCH BOX, PROVIDE SUBSTANTIAL BARRIERS BETWEEN ADJACENT SWITCHES IN THE BOX SO THAT 710 DIFFERENT PHASE WIRES WILL NOT BE IN THE SAME COMPARTMENT. 9. WHEREVER RACEWAYS PASS THROUGH FLOORS, WALLS, PENETRATIONS, OR 07HER PARTITIONS, CAREFULLY FILL ANY SPACE BETWEEN THE OUTSIDE OF THE RACEWAY AND THE BUILDING MATERIAL TID PREVENT PASSAGE OF AIR, WATER, SMOKE, AND FUMES. FILLING MATERIAL SHALL BE A UL LISTED, INTUMESCENT SEALING HAVING FIRE/SMOKE RESISTIVE RATING EQUAL TO THE BUILDING MATERIAL PENETRATE). h. CONDUITS UTILIZED THROUGHOUT THE PROJECT SHALL NOT BE SMALLER THAW 3/4 INCH FOR FEEDERS„ MULTIPLE BRANCH CIRCUIT HOMERUNS AND HOMERUNS OF CONDUCTORS LARGER THAN NO. 12. INDIVIDUAL BRANCH CIRCUIT WIRING FOR NO. 12 CONDUCTORS SHALL BE ACCEPTABLE IN 3/4' CONDUIT, I.E. 2#12, 1#12G, 3/4'C. B. COUPLINGS AND TERMINATORS 1. FOR RIGID STEEL. OR INTERMEDIATE METAL CONDUIT. FACTORY -MADE THREADED COUPLING OF SAME MATERIAL AS THE CONDUIT. 2 FOR ELECTRICAL METALLIC TUBING, USE STEEL CONFESSION COUPLING AND NYLON INSULATED GROUNDING BUSHINGS. 3. FOR FLEXIBLE METAL CONDUIT COUPLING AT CONNECTIONS BETWEEN FLEXIBLE CONDUIT AND EMT, AND NYLON INSULATED THROAT STEEL CONNECTORS AT BOX OR CABINET TERMINATIONS. 4. SCREW COUPLINGS; STEEL SET SCREW BOX CONNECTORS WITH NYLON INSULATED THROAT AND LOCKNUTS AT ALL BOXES AND CABINET TERMINATIONS OR NON-INSULATED BOX CONNECTOR. LOCKNUT AND NYLON-INSULATED GROUNDING BUSHING ON aR GROUNDING ` h ARE REQUIRED. C. JUNCTION ( PULL BOXES 1. SIZE BOXES IN ACCORDANCE WITH THE REQUIREMENTS OF THE NEC. BOXES SHALL BE UL LISTED AND NO SMALLER THAN 4 INCHES SQUARE BY 1-1/2 INCHES DEEP WITH COVERS ACCESSIBLE AT ALL TIMES. SET BOXES ON 0ONCEALED CONDUITS WITH COVERS FLUSH WITH THE FINISHED WALL OR CEILING LINE. PROVIDE 1 1 PULL BOXES OF APPROPRIATE DIMENSIONS FOR CONDUITS AND CONDUICTORS NOTED, WHERE SHOWN AND WHERE NECESSARY FOR THE INSTALLA71ON AND PULLING OF a, AND WIRES. COVERS ON JUNC71ON BOXES AND CONDULETS AFTER WRING AND CONNECTIONS ARE COMPLETED. JUNCTION Z ALL 1 PUILL BOXES FOR EMERGENCY SYST7 AND LOW VOLTAGE SY57EMS SHALL HAW COVER PLATES PAINTED. COLORS FOR COVERS SHALL BE YELLOW! RANCH), ORANGE (CRITICAL BRAl GREEN (EQUIPMENT SYSTEM), RED (FIRE ALARM), AND BRIDOIN (DATA/TELEPHONE). INSTALLATION OF 1 JUNCTION BOXES a. 0. FASTEN ALL BOXES SECURELY M THE BUILDING CONSTRUCTION, OF CONDUIT a A b. ON CONCE&ED CONDUIT SYSTEMS WHERE BOXES ARE NOT OTHEINSE ACCESSIBLE. SET BOXES FLUSH V17H FINISHED SURFACES FOR ACCESSt AND PROVIDE OVERLAPPING COVERS. C. ALL WIRING DEVICES FACEPLA7ES SHALL BE ENGRAVED VATH THE PANELBDARD DESIGNATION AND CIRWIT NUMBER SERVING THE OUTLET. .7 NOT CE D. OUTLET BOXES 1. OUTLET BOXES SHALL BE UL LISTED, AND OF SIZES ANit TYPES REQUIRED FOR THE APPLICATION. OUTLET BOXES SHALL BE SHEET STEEL, 1 LIGHTER THAN 14 GAUGE, /al AFTER r FABRICATION. SET BOX SO FACE OF BOX WILL FINISH FLUSH WITH BUILDING SURFACE. CL FOR LIGHTING FIXTURE 1 U11ETS:- 4 INCH SQUARE PLASTER 1/2 INCHES DEEP WITH RAW FIXTURE RING. b. FOR WALL SWITCHESt RECEPTACLES, AND COMMUNICATION USE 4 INCH SQUARE. BY 1-1/2 INCHES DEEP. USE BOXES WITH RINGS IN ALL PLASTERED WALLS WHERE WALL THICKNESS • r. BOXES LESS CANNOT INCH DEEP ONLY IN LOCATIONS WHERE DEEP BOXES • «I 11 a► BY CONSTRUCTION. 16120 - SYSTEM OF CONDUCTORS A. CONDUCTORS SHALL BE 98% CONDUC71MTY SOFT DRAWN ANNEALED COPPER, 600 VOLT, 1HHN/THWN INSULATK% #10 AND Smmm - SOLID, iAND LARGER STRANDED. B. NO CONDUCTORS ` T THAN NO. 12, EXCEPT F1' SIGNAL OR CONTROL CIRCUITS AND FOR INDIVIDUAL LIGHTING FIXTURE TAPS AS PERWMO BY NEC. FEET, C. FOR HOME RUNS ON 120-VOLT, 20-AMPERE BRANCH CIRCUITS, WHERE LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 100 LINEAR ` 1 10 • f 1 • •w WHERE LENGTH OF 1 LINEAR FEET OR LESS, USE 1 12 •f 1 O D. FOR HOME RUNS ON 1 LT, 20-AWPERE BRANCH CIRCUITS, ER LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 200 LINEEAR FEEL USE NO. 10 CONDUCTORS. WHERE LENGTH OF 11 LINEAR FEET OR LESS, 1 12 •t 1 OR& E. RUN DEDICATED NEUTRAL CONDUCTOR WITH EACH t CIRCUIT. SHARING OF NEUTRAL CONDUCTORS WOULD NECESSITATE THE USE OF MUL11PLE POLE OR TIED CIRCUIT BREAKERS TO ALLOW SIMULTANEOUS DISCONNECTING OF CURIF0T CARRYING CONDUCTORS IN OIRDER TO COMPLY 1 REQUIREMENTS AN1 THEREFORE F. RWM% CODEID CABLE SYSTEM APPROVED BY OMER. IF NONE REQUIRED OWNER, PROVIDE THE FOLLOWING COLOR - CODING: :► 208V/120 BROWN A PHASE BLACK ORANGE B PHA` •.al NEUTRAL - r� f PHASE NEUTRAL - WHITE GROUND 1 r•a7 GROUND r•aa COLOR CODING SHALL BE CONTINUOUS ON S • FOR #6 AWIG OR SMALLER AND CONTINUOUS OR MARKED WITH COLOR TAPE AT ALL CONNECTIONS i' CONDUCTORS LA' E INSTALLATION THAN 06 AWG. G. OF CONDUCTORS WHICH 1. PULL NO CONDUCTORS INTO CONDUITS UNTIL ALL WORK OF A NATURE 1 CONDUCTORS S COMPLETED. Z RUN FEEDERS IN CONTINUOUS UMMS, • I i • • SPLICES, INSOFAR 3. RUN CONDUITS 1' EMERGENCY POWER CONDUCTORS SEPARATE '1 ALL OTHER WIRING. 4. CABLE TYPE AC 1 • MC IS NOT • 7/ FOR HOMERUN AND FEDER r INSTALLATIONS. A. ALL WRING DEVICES SHALL BE UL LISTED. COOPER. C. RECEPTACLES 1. RECEPTACLES HOSPITAL ► STANDARD STYLE THEY SIALL 21 • 1 7 .1 • CONFORATION, ► ► r ./ 1 7 ► 71 ► ► Z GFCI RECEPTACLES SHALL BE A FEED THROUGH TYPE WIRED FOR SINGLE RECEPTACLE PROTECTION THUS NOT AFFECTING RECEPTACLES DOWNSTREAM • CIRCUIT. ` al CLASS WITH 5rnA GROUND 1 •, • a II ► aal • 1 r RATING 1 a 1• CONFIGURATION. 3. RECEPTACLE COLOR IVORY. ` •al a CONNECTED • EMERGENCY CIRCUIT. 4. PEDIATRIC LOCATIONS - ALL RECEPTACLES LOCATED IN PATIENT CARE AREAS SHALL BE LISTED TAMPER RESISITANT. D. SWITCHES 1. SWITCHES SHALL BE SPECIFICATION GRADE, 20A, 120/277V, HOIWOW RATED, BACK AND SIDE WIRED. SWITCHES SHALL INCLUDE GREEN r• ♦ 1 `••, • al 1 MOUNTING Z WHERE LIGHTING CIRCUITS ARE SHOWN TO BE LINE VOLTAGE SWITCHED, PROVIDE 1 SPECIFICATION GRADE, RATED, LISTED, BACK- AND SIDE-WIRED, TOGGLE SWITCHES RATED 20A, 120V OR 277 VOLTS. SWITCHES SHALL BE SPST. DPST, 3-WAY OR 4-WAY, WITH OR 1 / r INDICATED t 1.• h & SWITCH COLOR SHALL BE IVOIRY OR RED WHEN CONNECTED TO AN EMERGENCY 7 CIRCUIT. E WALL PLATES PLATES 1. WALL ` PROVIDED t• « '1 !a' • a. 7 a' 1 ► 1 SPECIAL PURPOSE Q OUTLETS. PLATES SHALL BE OF SUITABLE CONFIGURATION FOR THE DEVICE FOR WHICH t COVER COLOR • MOUNTING SCREWS. COLOR 1 a. ` « 1 « U.N.O. 2. WALL PLATES THERMOPLASTIC, 1 N 1 HIGH-IMPACT RESISTANT. THEY SHALL BE P-LINE SMOOTH PLATES. THEY SHALL, BE + •a• DEVICE IT IS TO COVER. I WEATHERPROOF. WRING DEVICE IN WET LOCATIONS SHALL BE INSTALLED WITH A HINGED t tt 7' 7 • /S •, CLEARLY MARKED FOR LOCATIONS ` 1 S al a'1 SHALL A GASKET BETWEEN THE COVER/MCLOSURE AND THE MOUNTING SURFACE, 1 BETWEEN r71 COVER 1 1 ` TO S.` PROPER COVER/ENCLOSURE SPECIFICATION GRADIE AS MANUFACTURED BY TAYMAC COI;FORATION OR EQUAL 1 •+ a' ! • 1 t 1 1 1 :'1 •+ 7- 1 7 :, • • 1 ral 1 7' 1 ` 1 .1 Val la' r r 1 7 «1 1 1• 1• !f •1 `i• •1 \`: 1 r i `a. a/ ` 1 • •1 1 +• ` 71 +• t 'f 1 I • 1 •, 1 • t a r' r' f 1 1 •+ 1 7' •• 1 • •• .7- I « `a' 71 • + 1 �: :'7 '1 1 ` ',a' fal ',a' ',71 1 - + a• •1','1 71 / I 11 ` • 1 t a• •a• •1 a: 7 / t1 a • « 117 1 ••t Ia1 1 T •, a, al 1 ` • "1'7' •f 1'; 1 t 7 1 / 1 1 + • ' a' ♦/ 1' '.a:' 1 : 1' 7. a a ] 7.1 1 . •1 1• `• • 1 • - r 1.2 « Z•a. r'1 1 7 1' ] 7 1 •�. ` ♦1' 1 •_.­' - t 1 .1 13. ` `•1 - !1 1 ► 1 r 1 ]1 ► 7 7 1 71 .• 1 t1 a' •' ` 7/ t t i «1 t • •.7 ♦1 •.1 71 7' : 77 71 ••1':. `• 17 / . 1. 313: 1 311D.* 71 '.] ♦►•.171 •.�: •• • :-,r 1• r •1 1 ---.! ;• 7 r'+ 1 7 -1 I « :'Ir a 1 7 T 1 tI a• • a.�:7 t t't a .1 •J `7' • a 7 21 6•;7a •` • t . 1' 1 F.141Y.1112111WALIti r al «f f w••r «i•1 f• + a' 1 A 3•1 1 t-,7• a7 M !t f'w 0 . •, # 7 r r7 a • 7 r• + 1 a•. 71 tf t •1••7' •1 1 1• It IS: 1 7'1 I 1 I r 7 r' 1 Ill 7'1 I - 7 : 1 •11 .._ - .. - _ E .. _ _ - _ U _ - _,_ ` m . o 16475 OVERCURRENT PROTECTIVE DEVICES - a _. - , �` o A. PROVIDE DATA SHEETS SHOWING ELECTRICAL MARACTERISTICS INCLUDING - - n - o °b• rn TIME- CURRENT CURVES AS PART OF THE SHOP DRAWING SUBMITTAL - ... m cv fr► N c I ^r-1 (•1 fit m L B. FAULT CURRENT VALUES INDICATED ON THE DRAWING ARE BASED ON 0 n ko to In U) ACTUAL AVAILABLE FAULT VALUES AT EACH SWITCHBOARD, PANELBOARD AND ANY OTHER SIMILAR EQUIPMENT. EQUIPMENT MANUFACTURERS SHALL -j m m Y 3 PROVIDE EQUIPMENT AND PROTECTIVE DEVICES SUITABLY RATED FOR THE - - - � �� ) L? c v CONFIGURATIONS INDICATED RATED FOR THE AVAILABLE FAULT CURRENT - _ T W c o m o c ao INDICATED. SERIES RATING OF DEVICES IS NOT ACCEPTABLE. - , _ - J' o � _ra. c.) - 5 E u, C. CIRCUIT BREAKERS a In C7 . - o -c 10 1. CIRCUIT BREAKER MANUFACTURER SHALL BE THE SAME AS THE '-' cu Fo c w ° :LJ SWITCHBOARD ANELBOARD OTOR CONTROL. CENTER MANUFACTURER. r+ � o s m 1_ • °o D. FUSES N to U a � > x °m 1. ACCEPTABLE MANUFACTURERS BUSS MAN, GOUL SHAWMUT, OR o , . o o uJ LITTLEFUSE 2. FUSES SHALL HAVE 200,000 RMS SYMMETRICAL AMPERE INTERRUPTING co n s CL CAPACITY AT 600Y OR `r 1 _� LESS, CURRENT UNITING TYPE; TIME DELAY N a . : .- w 1-4 CHARACTERISTICS - 10 SECONDS (MINIMUM) AT 50OX RATED CURREIIT; iA m = UL CLASS RK1. *IIz _° . = E SELF - CONTAINED CIRCUIT BREAKER ENCLOSURES SHALL BE PADLOCKABLE u x. o . to 15 C In NEMA 1, EXCEPT FOR UNITS IN DAMP OR WET AREAS WHICH SHALL BE A c NEMA 3R ENCLOSURE WITH CONDUIT HUBS. ^ "` 4-i z o O � a a¢ F. ENCLOSURES FOR SELF- CONTAINED UNITS SHALL BE SECURELY MOUNTED TO WAIL. AND SHALL BE LEVEL. AND TRUE. MOUNTING HEIGHT SHALL BE PLUS 54' A.F.F. TO CENTER OF BREAKER U.N.O. G. FURNISH A NUMBER OF SPARE FUSES EQUALING 10% OF QUANTITY REVMKM INSTALLED BUT NOT LESS THAN THREE (3) FUSES OF EACH TYPE AND RATING. MA1WC; REMARKS: H. INSTALL FUSES WITH LABEL ORIENTED SUCH THAT THE MANUFACTURER, TYPE AND SIZE ARE EASILY READ. 16721 - FIRE ALARM SYSTEM (MODIFICATION) A FURNISH AND INSTALL FIRE ALARM AND DETECTION SYSTEM ADDITIONS AND RELOCATIONS AS INDICATED ON THE DRAWINGS, COMPATIBLE AND CONSISTENT WITH THE EXISTING SYSTEM. B. THE EXISTING SYSTEM OPERATION SHALL REMAIN UNCHANGED PROVIDING CONTINUA. SERVICE DURING ALL PHASES OF THE RENOVATION AND /OR EXPANSION. - G R IS THE RESPOfW TY' OF THE ELECTRICAL CONTRACTOR 70 PROVDE EXPANDABLE MODULES, POWER SUPPLIES. HARDWARE. SOFTWARE, ETC. TO THE FIRE ALAN SYSTEM N ORDER TO ACCOMMODATE THE ADDITIONAL IN ALARM DENM D. CONTRACTOR SHALL PROVIDE SENSITIVITY TEST REPORT FOR ALL NEW SMOKE DETECTORS. E THE ENTIRE SYSTEM SHALL BE TESTED TO THE OWNER'S SATISFACTION. CONTRACTOR SHALL PROVIDE A COMPLETE FIRE ALARM CERTIFICATION AND A SENSITIVITY TEST REPORT FOR ALL NEW, AND EXISTING SMOKE, DUCT AND HEAT DETECTORS. CONTRACTOR SHALL REPLACE ANY DETECTOR THAT DOES NOT MEET THE ALLOWABLE SENSITIVITY VALUES. F. WHERE REWIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED WITH THE WILDING AUTOMATION SYSTEM IN ORDER TO SEND/IZECEIVE SIGNALS FROM ALARM INITIATING DEVICES AND H -O-A SWITCHES FOR THE OPERATION OF SMOKE CONTROL SYSTEMS, FAN SHUTDOWN AND COMMUNICATIONS. COORDINATE ALL REQUIREMENTS WITH DIVISION 15. G. VISUAL STRODE DEVICES SHALL MEET THE REQUIREMENTS OF ADA, UL, AND NFPA. H. AUDIBLE DEVICES IN PUBLIC AND STAFF AREAS SHALL BE SPEAKERS WITH A PEAK OUTPUT OF 96cIB AT 10' -0'. I. ALL WIRING SHALL BE STRANDED AND IN CONDUIT. COLOR SHALL BE THE FACIUTYS STANDARD OR RED. J. PROVIDE NEW CONDUIT AND WIRING AS REWIRED FOR NEW FIRE ALARM DEVICES. CONNECT AND PROGRAM DEVICES IN EXISTING FIRE ALARM CONTROL PANEL COORDINATE EXACT LOCATION OF EXISTING FIRE CONTROL PANEL WITH OWNER. NEW DEVICES ARE TO MATCH EXISTING ONES AND BE UL LISTED WITH EXISTING FIRE ALARM SYSTEM. PROVIDE NEW POWER SUPPLIES AS NECESSARY INCLUDING EXPANSION MODULES OR ANY SOFTWARE OR HARDWARE ACCESSORIES REQUIRED FOR A COMPLETE AND FUNCTIONAL INSTALLATION. ALL DEVICES SHALL MEET ADA REQUIREMENTS. K CONTRACTOR SHALL SUBMIT SIGNED AND SEALED PLANS INDICATING EXACT LOCATION, TYPE, CABLING, AND BATTERY CALCULATIONS L ALL WIRING SHALL BE IN 3/4'C. MINIMUM. M. M3IDOR SHALL RE-CERTIFY THE SYSTEM AND PRIDI CERTIFICATION AND SMOKE DETECTOR SEIS< MTY REPORT PRIOR TD ANY IMECT ON. N. SYNCHRONIZE ALL AUDIO/VISUAL DEVICES. 0. AUDIBLE DEVICES SHALL BE ON SEPARATE CIRCUITS THAN VISUAL DEVICES. P. UPON ACTIVATION OF THE FIRE ALARM SYSTEM, THE MU SHALL SHUT DOWN WHEN IN MANUAL OR AUTOMATIC POSITION. EXHAUST FAN SHALL BE INIERLOM WITH THE AHU STARTER. LOCATE FIRE ALARM RELAY WITHIN 3' -GYP OF STARTER. 16741 - TELEPHONE AND DATA COMMUNICATIONS X AT ALL WALL DATA/VOICE OUTLET LOCATION'HS, PROVIDE A 4 11/16' SQUARE BOX WITH SINGLE -GANG ADAPTER AND BLANK COVER PLAT:. 1' MIN. EMPTY CONDUIT SHALL RUN WITH PULL CORD TO 6' ABOVE NEAREST ACCESSIBLE CORRIDOR CEILING SPACE WHERE CORRIDORS DO NOT HAVE ACCESSIBLE CEILINGS, PROVIDE CONDUIT SLEEVES AS A MINIMUM ONE PER SYSTEM COVERING THE ENTIRE LENGTH OF NON- ACCESSIBLE CEILING CAVITY. NUMBER AND SIZE OF CONDUIT/SLEEVES SHALL BE PER MANUFACTURER'S CABLING REQUIREMENTS. B. PROVIDE A MINIMUM OF A 3116' DIAMETER, TWISTED NYLON PLASTIC CORD IN ALL EMPTY RACEWAYS PROVIDE A IDENTIFICATION TAG ON EACH END INDICATING THE LOCATION OF THE OTHER END. CI INSTALL DATA /COMMUNICATIONS OUTLETS AT SAME HEIGHT SPECIFIED FOR CONVENIENCE OUTLETS U.N.O. GROUP TELEPHONE AND DATA COMMUNICATIONS OUTLETS WITH RELATED RECEPTACLE OUTLETS U.N.O. D• WHERE PLYWOOD BACKBOARDS ARE INDICATED, PROVIDE A 3/4' THICK APA A/D GRADE PLYWOOD, TREATED WITH FIRE RETARDANT, MINIMUM TWO (2) COATS OF LIGHT GRAY PANT. BACKBOARDS SHALL BE MOUNTED SIX (6' INCHES A.F.F. AND EXTEND UPWARD A FULL EIGHT (8' -0') FEET OR M THE CEILING GRID IF LESS THAN 6' -O'. 16900 - EQUIPMENT CONNECTIONS AND CONTROL WIRING A. THE FURNISHING AND INSTALLATION OF CONTROL POWER WIRING REWIRED FOR EQUIPMENT FURNISHED UNDER DIVISION 15 AND NOT SHOWN ON THE ELECTRICAL DRAWING SHALL BE FURNISHED UNDER DIVISION 15. CONTROL POWER WIRING IS DEFINED AS THE LINE VOLTAGE I POWER WIRING FOR EQUIPMENT CONTROL. CABINETS, TEMPERATURE CONTROL, ENERGY MANAGEMENT. CR BUILDING AUTOMATION SYSTEM PANELS AND LINE VOLTAGE SMOKE/FIRE DAMPERS B. THE FURNISHING AND INSTALLATION OF THE TEMPERATURE CONTROL WIRING, ENERGY MANAGEMENT SYSTEM OR BUILDING AUTOMATION WIRING NOT SHOWN ON THE ELECTRICAL DRAWING SHALL BE FURNISHED UNDER DIVISION 15. TEMPERATURE CONTROL.. ENERGY MANAGEMENT SYSTEM AND BUILDING AUTOMATION SYSTEM WIRING IS DEFINED AS THE INTERLOCK OR INTERCONNECTING WIRING REWIRED BETWEEN SYSTEM CONTROL DEVICES, APPURTENANCES AND CONTROL. PANELS TO ALLOW THE SYSTEM To FUNCTION AUTOMATICALLY. THIS INCLUDES WIRING BETWEEN THE FIRE ALARM SYSTEM, SMOKE EXHAUST SYSTEMS, DOOR ENTRY SYSTEMS AND ANY OTHER SYSTEM REQUIRING INTERFACE WITH THE TEMPERATURE CONTROL. ENERGY MANAGEMENT AND BUILDING AUTOMATION SYSTEM. C• PROVIDE POWER WIRING TO EACH MOTOR -DRIVE AND/OR ELECTRICALLY - OPERATED SYSTEM OR UNIT OF EQUIPMENT. THE WIRING SHALL ALLOW THE MOTOR(S) OR EQUIPMENT TO OPERATE IN A MANUAL MODE. D. CONTROL WIRING WILL UNLESS SPECIFICALLY NOTED OTHERWISE, WILL BE FURNISHED AND INSTALLED UNDER OTHER DIVISIONS OF THE SPECIFICATIONS. E EXCEPT FOR ITEMS THAT ARE FURNISHED WITH FACTORY- INSTALLED, INTEGRAL. MOTORS, AN ELECTRIC MOTOR OF REWIRED SIZE AND ELECTRICAL CHARACTERISTICS WILL BE PROVIDED AND INSTALLED UNDER OTHER DIVISIONS FOR EACH ITEM OF MOTOR -DRIVEN EQUIPMENT. COMPLETE THE ELECTRICAL INSTALLATION OF THESE MOTORS IN ACCORDANCE 07H APPROVED WIRING DIAGRAMS AND INSTRRUCTIOLN& F. WHERE DISCONNECT SWITCHES OR CIRCUIT BREAKERS ARE NOT PROVIDED INTEGRAL, WITH CONTROL EQUIPMENT FOR MOTORS AND OTHER ELECTRICAL APPURTENANCES. PROVIDE AND INSTALL ALL DISCONNECT SWITCHES REQUIRED BY THE NATIONAL ELECTRICAL CODE AND/OR INDICATED. G. WHERE POSSIBLE, TERMINATE CONDUITS IN CONDUIT BOXES ON MOTORS. MERE MOTORS ARE NOT PROVIDED WITH CONDUIT BOXES, TERMINATE THE CONDUITS IN CONDUIT FITTING AT THE MOTORS. Irma • is IIIIIII 412480.000 • t kiclo. 1 .. -, • - Sheet Na E&W 4- t 1 -11 1 om I. r t ` 1 al I r :f • •!a• •a• « a• r r7 a• a •{ t- 1 t 'ii ` •� t ► 71 T� • • la. t 1a. I! •, `: a ; ;1 IN 1104 + •1 •a' « a. 1 1 ! N 7• 1 1 1 1 h h ` - •1 •17 + 1 {. 71 .1 t- i r•;7a. ! >, 1 1 « •7 a• 1 • 1 11 1 • 1 1 •+ 1 • - / 1 ► 1 1 r'17a. !1 1 • -w 11 1 ", 1 1 ell I we .111 I ' ! 7 11 1 t '•1 1! r•77 • 7 1 1 '', , .'•'; 1.7• t f « 1•a• 1 1 7 . • Ire 1' 1. 7 1 1 •t al 1• 1 tf r 1 7 + 71 a' + + +•a' 1 r• + :t • a 7", t • ', •7' • a. ` r M T,-' 11 M M 1 •1 7' 7'{ 1 t M 1 "{ a . 1 / 7 • 14 •, • •• a• rl f • i • a r, 1 • a• al 171 7 a r' 171 7 7 ` 1 1 7 i', 1 1 a',' • 1 1 ' 7'/ 7 1 1 ` 171 •, . ',al 1 • 1' a/ 'l ` I I4,41,1 • • ` 9-11:14-143-111 1 1 a -,-111 •1 - 7 a 1 • •� • ► 71 «1 « 71 r 1 T T 1 • « 1 •, • -1] +• 1 71 t t t •-• 7 .1 ',1 7 7 t fti '1 1',1a' 1 t a',',I1 a'/ It r' 171 7 7 « !1 7'w • 7/ 7 171 ra. a t 1.` •,7. a 1 1• 1 al • I- I h •t 1� r71 •• 7'w • « '• I / • 7 • 1 ` + a• '1 a 1• 1 7.1 . I« 1 7 •, H 11 7 ` 7 ;7 7 « 1`•, I • :, 7 7 • 1.` '1 t 1 1 'i1 h '71 • •;a• ► •.1 a a • •1 r `+ i •la. •,r •. •.. a 1 I•f. ` ra / t• t "1 171 ♦ « 1 •; {: 1 r7•w l ` '• • +. '1 • I.171 ► ►1 1 7 a 7 ! Itil •, «• t :,, ` • 1 • al 1 t1 31 1 1 71 . • �a. + •� r i a• al ' • 1 • •, 1.1 171 f 1 a- 1 7 go • • ',al ',a' i • a • I ` • s -I 7i « a .a• t f t 1 t• `a- • 1 a .1 .T pi- a l a. • •, 171 `1 «/ •t1 i 7•w ` f 7 71 •, 1 • 1 •, `a. a t7' ! •• :v1 -r, I r7• • >, ••i r • 1- • .•...A «x,1:'1 `I ;11.1 1.....4171 ` `7. • a. 71 ` +• ••• + 1111 it 1 1 71 1 I 1- h 7 7« t►` 'la. •, 71 1 r rr `- ti ` •, • •,al r• • . f • r ` .. +. + V 1 f r r a•, • .•, al • 1 a as ' ! t ` I a►z 1 ra' '7' • t 7 a •a' !t 1 a.� 1 7' • • • « .", IT 1 ' IQ 1 a 7 • +� ',7, 1 - a• a• 1 tl 1 •1 7 1 1 1 7' • •' t ` 1 1'• a• t ` 'Y • 71 ' 1 . m ra' •,' ra 7 7 7 « 1C •{ •i a•w ` t • 1 • 7 'YQ + • 1 1 • t 1 r7'w ` 1 ` •Pia • a, 1 • • 1 : a► 1 ` a 1 1 • - • 7 7 « 1 `71 i - • .'/ la• • a. 1 1 `•1 « al + as • • �. 1 al 1 ` 1 f • I f • 1 1 • 1 r•1 ► •a • al r •,a. .. f • al • f '1 • 7 ilal f t 9'17 « 1 a •1 •• 7 ` • « / r't 1 1 t1 1 1• t •�1 •, a r• + I a► w1 •u • --4- « 1 1 I- 7 ••1• 1 r7•w •1 !1 «•; :. 1 • •'1 f •1 "7• • 1 7a r-1 1 '11 • 1 7' 1 7 7 • 1 « ( « 171 7' 1 1 ► ` r 71 1' 1 '1 a 1 a i' ` t 7 1 1: J 1 I + r'1 1 7 '11 •• 1 1' 1 r'1 1 '11 7 •; 17 1 r r•• ► a. ► • 1 1 1 1- ••1 1 •i - ';a.�`1 . Ia 1 1' f • r •w • :'t - 1 1 1~ t1 - t t7 7• a .. •O t tt 1 1'w + r• 1 ► : -1 /a" 1 f a' 7 •{ • a T' 1 1 `i 71 r' 1 1 •f 1 1 " 12 1131=# • I' a `a• ` ` I r' 1 1 ♦1 1 t'w ••• -,► • . 7, 1 1 ' f 1 1 / «1 1 • N i 1' • 7' ] ] '1 7 « 1 ` 'A. •1 71 1 `7' a • 1 ` ', 7 • '1 7 « a'w • • r- 7 171 1r 7' •.t 1 r•+ 1 N 1 f'w '1 • h 1 1 7 t IC -, « a f a- • • • i / `r r• 7a al • a r• • 1 •• 1 r. ! i' 7 a 0•,73 7'w f f 1 M 1 1 •w + IiIIII + 7' tt '. ; 71 1 ;1 1 • • • • r 7' • 7 • • ',a al 1 !1 1 1 • 17'1 71 •1 7' >+ ` 71 •1. 7 7 !1 1 1•w `a' • 1•• •.1 1 7 7i 7/ r « 2,4 • • r r' t ► •1 ► Y' • t «+ r' f 1 t t • 1 r `.! 1 N N r 1 •w f r' i / a'1 t 7 1• 1 •`••, 1 1 • la `i /171 • • f + r' • ► « t • 1 1 •+ 1 1 1 •• 7• !1 . al 1 1 1 '-« 1 •t 7' • 7 ► ►• ` +•; 7' •r a' 1 r'1 ► a '11 2311212" t 7' a► ` 71 •1' • •f 1 1' • t 7 ' ti t ' • 1 •• t t 1 a r• 71 1 XZ r • • 1 r `• 1 • • a'/ f -1 i t a. t• •, r a. ` • •41 • a1 1 `71 a a •1 �• 1 �•,• �• 71 ` •TI la -,� '7 t 1• 1 1 .+ / /a`r f >, t . •7; f'1 al >v 7 .._ - .. - _ E .. _ _ - _ U _ - _,_ ` m . o 16475 OVERCURRENT PROTECTIVE DEVICES - a _. - , �` o A. PROVIDE DATA SHEETS SHOWING ELECTRICAL MARACTERISTICS INCLUDING - - n - o °b• rn TIME- CURRENT CURVES AS PART OF THE SHOP DRAWING SUBMITTAL - ... m cv fr► N c I ^r-1 (•1 fit m L B. FAULT CURRENT VALUES INDICATED ON THE DRAWING ARE BASED ON 0 n ko to In U) ACTUAL AVAILABLE FAULT VALUES AT EACH SWITCHBOARD, PANELBOARD AND ANY OTHER SIMILAR EQUIPMENT. EQUIPMENT MANUFACTURERS SHALL -j m m Y 3 PROVIDE EQUIPMENT AND PROTECTIVE DEVICES SUITABLY RATED FOR THE - - - � �� ) L? c v CONFIGURATIONS INDICATED RATED FOR THE AVAILABLE FAULT CURRENT - _ T W c o m o c ao INDICATED. SERIES RATING OF DEVICES IS NOT ACCEPTABLE. - , _ - J' o � _ra. c.) - 5 E u, C. CIRCUIT BREAKERS a In C7 . - o -c 10 1. CIRCUIT BREAKER MANUFACTURER SHALL BE THE SAME AS THE '-' cu Fo c w ° :LJ SWITCHBOARD ANELBOARD OTOR CONTROL. CENTER MANUFACTURER. r+ � o s m 1_ • °o D. FUSES N to U a � > x °m 1. ACCEPTABLE MANUFACTURERS BUSS MAN, GOUL SHAWMUT, OR o , . o o uJ LITTLEFUSE 2. FUSES SHALL HAVE 200,000 RMS SYMMETRICAL AMPERE INTERRUPTING co n s CL CAPACITY AT 600Y OR `r 1 _� LESS, CURRENT UNITING TYPE; TIME DELAY N a . : .- w 1-4 CHARACTERISTICS - 10 SECONDS (MINIMUM) AT 50OX RATED CURREIIT; iA m = UL CLASS RK1. *IIz _° . = E SELF - CONTAINED CIRCUIT BREAKER ENCLOSURES SHALL BE PADLOCKABLE u x. o . to 15 C In NEMA 1, EXCEPT FOR UNITS IN DAMP OR WET AREAS WHICH SHALL BE A c NEMA 3R ENCLOSURE WITH CONDUIT HUBS. ^ "` 4-i z o O � a a¢ F. ENCLOSURES FOR SELF- CONTAINED UNITS SHALL BE SECURELY MOUNTED TO WAIL. AND SHALL BE LEVEL. AND TRUE. MOUNTING HEIGHT SHALL BE PLUS 54' A.F.F. TO CENTER OF BREAKER U.N.O. G. FURNISH A NUMBER OF SPARE FUSES EQUALING 10% OF QUANTITY REVMKM INSTALLED BUT NOT LESS THAN THREE (3) FUSES OF EACH TYPE AND RATING. MA1WC; REMARKS: H. INSTALL FUSES WITH LABEL ORIENTED SUCH THAT THE MANUFACTURER, TYPE AND SIZE ARE EASILY READ. 16721 - FIRE ALARM SYSTEM (MODIFICATION) A FURNISH AND INSTALL FIRE ALARM AND DETECTION SYSTEM ADDITIONS AND RELOCATIONS AS INDICATED ON THE DRAWINGS, COMPATIBLE AND CONSISTENT WITH THE EXISTING SYSTEM. B. THE EXISTING SYSTEM OPERATION SHALL REMAIN UNCHANGED PROVIDING CONTINUA. SERVICE DURING ALL PHASES OF THE RENOVATION AND /OR EXPANSION. - G R IS THE RESPOfW TY' OF THE ELECTRICAL CONTRACTOR 70 PROVDE EXPANDABLE MODULES, POWER SUPPLIES. HARDWARE. SOFTWARE, ETC. TO THE FIRE ALAN SYSTEM N ORDER TO ACCOMMODATE THE ADDITIONAL IN ALARM DENM D. CONTRACTOR SHALL PROVIDE SENSITIVITY TEST REPORT FOR ALL NEW SMOKE DETECTORS. E THE ENTIRE SYSTEM SHALL BE TESTED TO THE OWNER'S SATISFACTION. CONTRACTOR SHALL PROVIDE A COMPLETE FIRE ALARM CERTIFICATION AND A SENSITIVITY TEST REPORT FOR ALL NEW, AND EXISTING SMOKE, DUCT AND HEAT DETECTORS. CONTRACTOR SHALL REPLACE ANY DETECTOR THAT DOES NOT MEET THE ALLOWABLE SENSITIVITY VALUES. F. WHERE REWIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED WITH THE WILDING AUTOMATION SYSTEM IN ORDER TO SEND/IZECEIVE SIGNALS FROM ALARM INITIATING DEVICES AND H -O-A SWITCHES FOR THE OPERATION OF SMOKE CONTROL SYSTEMS, FAN SHUTDOWN AND COMMUNICATIONS. COORDINATE ALL REQUIREMENTS WITH DIVISION 15. G. VISUAL STRODE DEVICES SHALL MEET THE REQUIREMENTS OF ADA, UL, AND NFPA. H. AUDIBLE DEVICES IN PUBLIC AND STAFF AREAS SHALL BE SPEAKERS WITH A PEAK OUTPUT OF 96cIB AT 10' -0'. I. ALL WIRING SHALL BE STRANDED AND IN CONDUIT. COLOR SHALL BE THE FACIUTYS STANDARD OR RED. J. PROVIDE NEW CONDUIT AND WIRING AS REWIRED FOR NEW FIRE ALARM DEVICES. CONNECT AND PROGRAM DEVICES IN EXISTING FIRE ALARM CONTROL PANEL COORDINATE EXACT LOCATION OF EXISTING FIRE CONTROL PANEL WITH OWNER. NEW DEVICES ARE TO MATCH EXISTING ONES AND BE UL LISTED WITH EXISTING FIRE ALARM SYSTEM. PROVIDE NEW POWER SUPPLIES AS NECESSARY INCLUDING EXPANSION MODULES OR ANY SOFTWARE OR HARDWARE ACCESSORIES REQUIRED FOR A COMPLETE AND FUNCTIONAL INSTALLATION. ALL DEVICES SHALL MEET ADA REQUIREMENTS. K CONTRACTOR SHALL SUBMIT SIGNED AND SEALED PLANS INDICATING EXACT LOCATION, TYPE, CABLING, AND BATTERY CALCULATIONS L ALL WIRING SHALL BE IN 3/4'C. MINIMUM. M. M3IDOR SHALL RE-CERTIFY THE SYSTEM AND PRIDI CERTIFICATION AND SMOKE DETECTOR SEIS< MTY REPORT PRIOR TD ANY IMECT ON. N. SYNCHRONIZE ALL AUDIO/VISUAL DEVICES. 0. AUDIBLE DEVICES SHALL BE ON SEPARATE CIRCUITS THAN VISUAL DEVICES. P. UPON ACTIVATION OF THE FIRE ALARM SYSTEM, THE MU SHALL SHUT DOWN WHEN IN MANUAL OR AUTOMATIC POSITION. EXHAUST FAN SHALL BE INIERLOM WITH THE AHU STARTER. LOCATE FIRE ALARM RELAY WITHIN 3' -GYP OF STARTER. 16741 - TELEPHONE AND DATA COMMUNICATIONS X AT ALL WALL DATA/VOICE OUTLET LOCATION'HS, PROVIDE A 4 11/16' SQUARE BOX WITH SINGLE -GANG ADAPTER AND BLANK COVER PLAT:. 1' MIN. EMPTY CONDUIT SHALL RUN WITH PULL CORD TO 6' ABOVE NEAREST ACCESSIBLE CORRIDOR CEILING SPACE WHERE CORRIDORS DO NOT HAVE ACCESSIBLE CEILINGS, PROVIDE CONDUIT SLEEVES AS A MINIMUM ONE PER SYSTEM COVERING THE ENTIRE LENGTH OF NON- ACCESSIBLE CEILING CAVITY. NUMBER AND SIZE OF CONDUIT/SLEEVES SHALL BE PER MANUFACTURER'S CABLING REQUIREMENTS. B. PROVIDE A MINIMUM OF A 3116' DIAMETER, TWISTED NYLON PLASTIC CORD IN ALL EMPTY RACEWAYS PROVIDE A IDENTIFICATION TAG ON EACH END INDICATING THE LOCATION OF THE OTHER END. CI INSTALL DATA /COMMUNICATIONS OUTLETS AT SAME HEIGHT SPECIFIED FOR CONVENIENCE OUTLETS U.N.O. GROUP TELEPHONE AND DATA COMMUNICATIONS OUTLETS WITH RELATED RECEPTACLE OUTLETS U.N.O. D• WHERE PLYWOOD BACKBOARDS ARE INDICATED, PROVIDE A 3/4' THICK APA A/D GRADE PLYWOOD, TREATED WITH FIRE RETARDANT, MINIMUM TWO (2) COATS OF LIGHT GRAY PANT. BACKBOARDS SHALL BE MOUNTED SIX (6' INCHES A.F.F. AND EXTEND UPWARD A FULL EIGHT (8' -0') FEET OR M THE CEILING GRID IF LESS THAN 6' -O'. 16900 - EQUIPMENT CONNECTIONS AND CONTROL WIRING A. THE FURNISHING AND INSTALLATION OF CONTROL POWER WIRING REWIRED FOR EQUIPMENT FURNISHED UNDER DIVISION 15 AND NOT SHOWN ON THE ELECTRICAL DRAWING SHALL BE FURNISHED UNDER DIVISION 15. CONTROL POWER WIRING IS DEFINED AS THE LINE VOLTAGE I POWER WIRING FOR EQUIPMENT CONTROL. CABINETS, TEMPERATURE CONTROL, ENERGY MANAGEMENT. CR BUILDING AUTOMATION SYSTEM PANELS AND LINE VOLTAGE SMOKE/FIRE DAMPERS B. THE FURNISHING AND INSTALLATION OF THE TEMPERATURE CONTROL WIRING, ENERGY MANAGEMENT SYSTEM OR BUILDING AUTOMATION WIRING NOT SHOWN ON THE ELECTRICAL DRAWING SHALL BE FURNISHED UNDER DIVISION 15. TEMPERATURE CONTROL.. ENERGY MANAGEMENT SYSTEM AND BUILDING AUTOMATION SYSTEM WIRING IS DEFINED AS THE INTERLOCK OR INTERCONNECTING WIRING REWIRED BETWEEN SYSTEM CONTROL DEVICES, APPURTENANCES AND CONTROL. PANELS TO ALLOW THE SYSTEM To FUNCTION AUTOMATICALLY. THIS INCLUDES WIRING BETWEEN THE FIRE ALARM SYSTEM, SMOKE EXHAUST SYSTEMS, DOOR ENTRY SYSTEMS AND ANY OTHER SYSTEM REQUIRING INTERFACE WITH THE TEMPERATURE CONTROL. ENERGY MANAGEMENT AND BUILDING AUTOMATION SYSTEM. C• PROVIDE POWER WIRING TO EACH MOTOR -DRIVE AND/OR ELECTRICALLY - OPERATED SYSTEM OR UNIT OF EQUIPMENT. THE WIRING SHALL ALLOW THE MOTOR(S) OR EQUIPMENT TO OPERATE IN A MANUAL MODE. D. CONTROL WIRING WILL UNLESS SPECIFICALLY NOTED OTHERWISE, WILL BE FURNISHED AND INSTALLED UNDER OTHER DIVISIONS OF THE SPECIFICATIONS. E EXCEPT FOR ITEMS THAT ARE FURNISHED WITH FACTORY- INSTALLED, INTEGRAL. MOTORS, AN ELECTRIC MOTOR OF REWIRED SIZE AND ELECTRICAL CHARACTERISTICS WILL BE PROVIDED AND INSTALLED UNDER OTHER DIVISIONS FOR EACH ITEM OF MOTOR -DRIVEN EQUIPMENT. COMPLETE THE ELECTRICAL INSTALLATION OF THESE MOTORS IN ACCORDANCE 07H APPROVED WIRING DIAGRAMS AND INSTRRUCTIOLN& F. WHERE DISCONNECT SWITCHES OR CIRCUIT BREAKERS ARE NOT PROVIDED INTEGRAL, WITH CONTROL EQUIPMENT FOR MOTORS AND OTHER ELECTRICAL APPURTENANCES. PROVIDE AND INSTALL ALL DISCONNECT SWITCHES REQUIRED BY THE NATIONAL ELECTRICAL CODE AND/OR INDICATED. G. WHERE POSSIBLE, TERMINATE CONDUITS IN CONDUIT BOXES ON MOTORS. MERE MOTORS ARE NOT PROVIDED WITH CONDUIT BOXES, TERMINATE THE CONDUITS IN CONDUIT FITTING AT THE MOTORS. Irma • is IIIIIII 412480.000 • t kiclo. 1 .. -, • - Sheet Na E&W 4- 412480.000 • t kiclo. 1 .. -, • - Sheet Na E&W 4-