12-1303R-006No
m1w,
1310
ELECTRICAL SYMBOLS
ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS. SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
LIGHTING FIRE ALARM
DESCRIPTION DEVICE MM HT. SYMBOL DESCRIPTION
2'x2' / 2'x4' FLUORESCENT LIGHT FIXTURE ON NORMAL CIRCUIT.
2'x2' / 2'x4' FLUORESCENT LIGHT FIXTURE ON CRITICAL CIRCUIT.
2'x2' / 2'x4' FLUORESCENT LIGHT FIXTURE ON LIFE SAFETY CIRCUIT.
2'x4' FI UOI;EMT LIGHT FIXTURE W/INBQARD LAMPS ON LIFE SAFETY
CIRCUIT AND OUTBOARD LAMPS ON NORMAL CIRCUIT.
2'x4' FLUORESCENT LIGHT FIXTURE W/INBOARD LAMPS ON NORMAL
CIRCUIT AND OUTBOARD LAMPS ON CRITICAL CIRCUIT.
2'x4' FLUORESCENT LIGHT FIXTURE WANBOARD LAMPS ON CRITICAL
V
WALL MOUNTED FIXTURE ON NORMAL CIRCUIT.
DRAWING TITLE
WALL MOUNTED FIXTURE ON CRITICAL CIRCUIT.
do
WALL MOUNTED FIXTURE ON LIFE SAFETY CIRCUIT.
0
RECESSED /SUSPENDED DOWNLIGHT FIXTURE ON NORMAL CIRCUIT.
0
RECESSED /SUSPENDED DOWNLIGHT FIXTURE ON CRITICAL CIRCUIT.
•
RECESSED /SUSPENDED DOWINLIGHT FIXTURE ON LIFE SAM CIRCUIT.
(�
RECESSED DOWNLIGHT FIXTURE WITH WALL WASH TRIM.
8
9N T GAL ACE. ARROWS INDICATE CHEVRON DIRECTIONS. OR
SWITCHES
SYMBOL
DESCRIPTION
$
WALL SWITCH SPST, 20A. 120/277V
$Z
DOUBLE POLE TOGGLE SWITCH, 2OA/120/277V
$3
3 -WAY WALL SWITCH, 20A. 120/277V
$4
4 -WAY WALL SWITCH, 20A. 120/277V
$D
WALL Box DIMMER SWITCH
$K
KEY OPERATED WALL SWITCH
$T
WALL SWITCH WITH ADJUSTABLE COUNTDOWN TIMER
$31)
3 -WAY WALL DIMMER SWITCH, 20A. 120/277V
$3K
3-WAY, KEY OPERATED WALL SWITCH, 20A. 120/277V
$me
MOMENTARY WALL SWITCH, 20A. 120/277V
$Ly
LOW VOLTAGE WALL SWITCH
$os
WALL MOUNTED OCCUPANCY SENSOR SWITCH. REFER TO SPECIFICATIONS.
WIRING DEVICES & POWER
SYMBOL
DESCRIPTION
t3-
SINGLE RECEPTACLE - 2OA/125V /2P/3W /G NEMA 5-20R
DUPLEX RECEPTACLE - 2OA/125V/2P/3W/G NEMA 5-20R
@
DUPLEX RECEPTACLE - 2OA/125V /2P/3W /G NEMA 5-20R
DUPLEX RECEPTACLE GFI - 20A/125V/2P/3W/G NEMA 5-20R 7
_
DUPLEX RECEPTACLE GFI - 2DA/125V/2P/3W/G NEMA 5-20R
EXISTING WIRING AS REQUIRED TO MAINTAIN CONTINUITY OF EXISTING CIRCUITRY SUCH THAT NO
QUADRAPLEX RECEPTACLE TWO DUPLEX RUTS. UNDER ONE
COVERPLAIE
QUADRAPLEX RECEPTACLE TWO DUPLEX RCPTS. UNDER ONE
COVERPLATE)
•t
0
0
a
71
« 71
« 71
,, -,
71
,, -,
`« 71
« 71
71
�« 71
« 71
V,
« 2 13 1
« 71
48' AFF
4e AFF
48' AFF
4e AFF
48' AFF
48' AFF
48' AFF
48' AFF
48' AFF
48' AFF
48' AFF
48' AFF
1 « /
' 1
18' AFF U.N.O.
6' ABOVE COUNTERTOP OR
CUSTOM MOUNTING HEIGHT
18' AFF U.N.O.
6' ABOVE COUNTERTOP OR
CUSTOM MOUNTING HEIGHT
18' AFF U.N.O.
18' AFF U.N.O.
18' AFF U.N.O.
+54' U.N.O.
+54' U.N.O.
AS REWIRED
AS REWIRED
AS REWIRED
48' AFF
NOTE:
DRAWING TITLE
scaLE
O
DUPLEX RECEPTACLE - 2+ I' 7 5-20R
FLOOR MOUNTED - FLUSH MOUNTED UNO
1
DUPLEX I RECEPTACLE
MOUNTED « + MOUNTED 1 7 1
PARTIAL FIRST FLOOR PLAN - ELECTRICAL
SPECIAL PURPOSE RECEPTACLE (NEMA NO. AS INDICATED)
PRIOR TO BID AND SHALL NOTIFY THE ARCHITECT AND /OR ENGINEER IF A CONDITION EXISTS WHICH
JUNCTION BOX SZE AND MOUN71NG AS REQUIRED
NTS
PREVENTS HIM/HER FROM ACCOMPLISHING THE WORK INDICATED AND INTENDED BY THESE DRAWINGS,
DEVICE MTG. HT.
NTS
O O
I; 31=n
u +
«-« :••l 21 `N « 7 -� M L r
k 41RIL 7 1 F.11 0 7« l '� JIM&II 11 twfl;Ll
48•AFF
MOTOR STARTER FVNR UNO; NUMBER INDICATES NEWA SRE
uluu�
TO THE BOTTOM OF THE LEN BELOW
6' FINISHED
MANUAL MOTOR STARTER SWITCH WITH THERMAL 1 TR 1 1 1 PILO?
ffl
TO THE BOTTOM OF THE LEN
cam
z;0'!&fjjl 13 Wil):
■
•�7 r • 1 1 « «' « a7•w
TO THE BOTTOM OF THE LENS
REMOVE ALL DISCONNECT SWITCHES, CIRCUIT BREAKERS, MOTOR CONNECTIONS, STARTERS, ELECTRICAL
- « 1 1 - 7• •� + •a 7
« 1 «•« •-1 171 171 71
mom�.
'� -� �•�
fill 1'
-
IiIiii
INDICATED. ALSO, REMOVE ALL CONDUIT AND WIRE BACK TO POWER SOURCE. CIRCUIT SHALL REMAIN
«/ 1 it 1`71
•t
0
0
a
71
« 71
« 71
,, -,
71
,, -,
`« 71
« 71
71
�« 71
« 71
V,
« 2 13 1
« 71
48' AFF
4e AFF
48' AFF
4e AFF
48' AFF
48' AFF
48' AFF
48' AFF
48' AFF
48' AFF
48' AFF
48' AFF
1 « /
' 1
18' AFF U.N.O.
6' ABOVE COUNTERTOP OR
CUSTOM MOUNTING HEIGHT
18' AFF U.N.O.
6' ABOVE COUNTERTOP OR
CUSTOM MOUNTING HEIGHT
18' AFF U.N.O.
18' AFF U.N.O.
18' AFF U.N.O.
+54' U.N.O.
+54' U.N.O.
AS REWIRED
AS REWIRED
AS REWIRED
48' AFF
THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND
INSTALLATION OF THE NECESSARY MATERIAL AND LABOR TO ACCOIN USIH
THE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. ALL
WORK BY CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL.
STATE AND LOCAL BUILDING CODES AND STANDARDS INCLUDING BUT NOT
LIMITED To-
NOTE:
DRAWING TITLE
scaLE
IT IS THE RESPONSIBILITY OF MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION
GENERAL INFORMATION - ELECTRICAL
NTS
CONTRACTORS TO VISIT THE SITE AND EXAMINE IN DETAIL THE SCOPE OF WORK OF THIS PROJECT
PARTIAL FIRST FLOOR PLAN - ELECTRICAL
PRIOR TO BID AND SHALL NOTIFY THE ARCHITECT AND /OR ENGINEER IF A CONDITION EXISTS WHICH
ELECTRICAL ONE -LINE, SCHEDULES
NTS
PREVENTS HIM/HER FROM ACCOMPLISHING THE WORK INDICATED AND INTENDED BY THESE DRAWINGS,
DEVICE MTG. HT.
NTS
O O
RD "40
HEAT DETECTOR CEILING OR WALL MOUNTED
48•AFF
m II 1 104114 1:01i,
SCOPE OF THE WORK.
TO THE BOTTOM OF THE LEN BELOW
6' FINISHED
` 1 ; 111' « :1 1 1 « «7. \`,• «7 1 ''1 1 /
TO THE BOTTOM OF THE LEN
�i
6' BELOW FINISHED CEILING
A. ALL EQUIPMENT SHOWN DASHED IS EXISTING TO BE REMOVED. CONTRACTOR SHALL DISCONNECT AND
TO THE BOTTOM OF THE LENS
REMOVE ALL DISCONNECT SWITCHES, CIRCUIT BREAKERS, MOTOR CONNECTIONS, STARTERS, ELECTRICAL
6' BELOW FINISHED CEILING
mom�.
'� -� �•�
THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND
INSTALLATION OF THE NECESSARY MATERIAL AND LABOR TO ACCOIN USIH
THE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. ALL
WORK BY CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL.
STATE AND LOCAL BUILDING CODES AND STANDARDS INCLUDING BUT NOT
LIMITED To-
1. STATE OF FLORIDA 10. NATIONAL ELECTRICAI. SAFETY (RUDE
2. LIFE SAFETY CODE - NFPA 101 (2009) 11. REQUIREMENTS OF LOCAL UTILITY COMPANIES
3. UNDERWRITERS LABORATORIES. INC. PUBLICATIONS (UL) 12. NATIONAL. FIRE PROTECTION ASSMA71ON 72 (2007)
4. NATIONAL FIRE PROTECTION ASSOCIATION. (NFPA) 11 NATIONAL FIRE PROTECTION ASSOCIATION 99 (2005)
5. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 14 THE STATE FIRE PREVENTION CODE, 4A60 (2010)
6. NATIONAL ELECTRICAL CODE - NFPA 70 (2008) 156 BUILDING CODE: FLORIDA BUILDING CODE (2010)
7. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE) 16. GUIDELINES FOR DESIGN AND CONSTRUCTION OF
8. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) HEALTHCARE FACILITIES (2010)
9. INTERNATIONAL POWER CABLE ENGINEER'S ASSOCIATION (IPCEA) 17. NFPA 110 (2005)
INFEC11ON CONTROL •
all .1
, q1;71 1'
BID NOTE
THE DRAWINGS DO NOT INDICATE EXISTING INSTALLATIONS
OTHER THAN TO IDENTIFY MODIFICATIONS OR EXTENSIONS
THERETO VISIT THE SITE AND ASCERTAIN THE EXISTING
CONDITIONS. REVIEW CONSTRUCTION DETAILS OF THE EXISTING
PORTION OF THE BUILDING DURING THE SITE INSPECTION.
INCLUDE ALL WORK REQUIRED TO REMOVE OR MODIFY
PORTIONS OF THE EXISTING INSTALLATION IN ORDER TO
ACCOMMODATE THE NEW WORK. FAILURE TO COMPLY WITH THIS
WILL NOT BE CONSIDERED GROUNDS FOR ADDITIONAL PAYMENT
IN CONNECTION WITH REMOVING OR MODIFYING ANY PART OF
THE EXISTING INSTALLATION OR INSTALLING ANY NEW OR
TEMPORARY WORK.
I. ALL CIRCUITS SHOWN ARE FOR REFERENCE PURPOSES ONLY. CONTRACTOR SHALL VERIFY ALL
CIRCUITS TO BE REMOVED PRIOR TO COMMENCEMENT OF WORK.
J. THE CONTRACT DOCUMENTS DO NOT PROPOSE TO SHOW ALL EXISTING SYSTEMS, MATERIAL OR
EQUIPMENT. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO OBTAIN DATA RELATED TO
EXISTING CONDITIONS FROM EXISTING DOCUMENTS, NOTATIONS, PHOTOGRAPHS, SURVEYS AND OTHER
OBSERVATIONS AT THE SITE
K. REMOVE EXISTING WIRE, CONDUIT, EQUIPMENT, FIXTURES AND OTHER ITEMS TO PROVIDE ACCESS FOR
WORK IN EXISTING FACILITIES. REINSTALL AND REFINISH ITEMS REMOVED, OR OTHERWISE DAMAGED, TO
MATCH EXISTING AT NO ADDITIONAL COST TO OWNER.
L WHERE EXISTING FUNCTIONS TO REMAIN IN USE ARE DISRUPTED, THEY SHALL BE FULLY RESTORED
AFTER DISRUPTION, IN FULL COMPLIANCE WITH APPLICABLE CODES AND STANDARDS.
M. MODIFY , REMOVE, OR RELOCATE MATERIALS AND ITEMS INDICATED ON THE DRAWINGS OR REQUIRED
DUE TO THE DEMOLITION WORK.
N. WORK JOINTLY WITH THE ARCHITECT, ESTABLISH AND MARK SALVAGE AND DEMOLITION ITEMS BEFORE
COMMENCING WORK; REPORT ITEMS SCHEDULE FOR RELOCATION, REINSTALLATION OR REUSE, WHICH
ARE FOUND TO BE IN DAMAGED CONDITION; AWAIT FURTHER INSTRUCTIONS FROM THE ARCHITECT
BEFORE COMMENCING WITH WORK.
0. DEMOLITION EQUIPMENT, DEVICES AND MATERIAL SHALL BE REMOVED FROM THE SITE AND DISPOSED
OF BY THE CONTRACTOR. SALVAGED EQUIPMENT AND DEVICES SHALL BE THE PROPERTY OF THE
OWNER UNLESS NOTED OTHERWISE.
P. MAKE RELOCATION NECESSITATED BY THE CONDITIONS AT THE SITE OR AS DIRECTED BY THE
ARCHITECT, WITHOUT ADDITIONAL COST TO THE OWNER. REPAIR, REPLACE AND /OR RESTORE TO GOOD
FUNCTIONAL CONDITION, EQUIPMENT, MATERIAL AND ITEMS SCHEDULE FOR RELOCATION, WHICH ARE
DAMAGED DURING DISMANTLING OR REASSEMBLE OPERATIONS. PROVIDE NEW MATERIALS, FITTINGS AND
APPURTENANCES REQUIRED TO COMPLETE THE RELOCATION AND TO RESTORE TO GOOD OPERATING
ORDER. PERFORM THE RELOCATION WORK IN ACCORDANCE TO APPLICABLE CODES ASD STANDARDS,
USING SKILLED WORKERS.
Q. RELOCATING DEVICES: REMOVE AND REINSTALL IN LOCATIONS DESIGNATED BY THE ARCHITECT,
TEMPERATURE CONTROL SYSTEM DEVICES. RELAYS, WIRE CONDUIT, FIXTURES, EQUIPMENT AND OTHER
DEVICES REQUIRED FOR THE OPERATION OF THE VARIOUS SYSTEMS THAT ARE INSTALLED IN EXISTING
TO BE REMOVED CONSTRUCTION.
R. CONTRACTOR SHALL KEEP A CLEAN SET OF DRAWINGS ON THE JOB, NOTING DAILY, ALL CHANGES
MADE IN THESE DRAWINGS IN CONNECTION WITH THE DEMOLITION PHASE, INCLUDING EXACT
DIMENSIONED LOCATIONS OF ALL UNCOVERED EXISTING UTILITIES AND SHALL, WITH THIS, REQUEST FOR
FINAL PAYMENT. TURN OVER A CLEAN, NEATLY MARKED SET OF REPRODUCIBLE MYLARS SHOWING
'EXISTING CONDITIONS' WORK TO THE ARCHITECT FOR SUBSEQUENT REVIEW AND TRANSMITTAL TO THE
OWNER. CONTRACTOR SHALL NOTE ALL CONSTRUCTION CHANGES, DATE EACH AND LABEL 'AS- BUILTS'
IN THE REVISION BLOCK ON THE DRAWINGS. CONTRACTOR SHALL ALSO FURNISH ONE SET OF
'AS- BUILTS' BLUEPRINTS.
S. DEVICES SHOWN IN SOLID LIGHT LINES ARE EXISTING TO REMAIN.
T. CONTRACTOR SHALL UPDATE ALL ELECTRICAL PANEL SCHEDULES AFFECTED BY THIS DEMOLITION.
HAND WRITTEN SCHEDULES ARE NOT ACCEPTED. SCHEDULES SHALL BE TYPED OR COMPUTER
GENERATED.
GENERAL NOTES: FLOOR PLANS.
A. CONTRACTOR SHALL PROVIDE AND INSTALL AN IDENTIFICATION NAMEPLATE FOR EACH ELECTRICAL
EQUIPMENT /APPURTENANCES DEPICTING THE DESIGNATION INDICATED ON THE DRAWINGS.
B. ALL EMPTY CONDUITS SYSTEMS SHALL CONTAIN A PULL WIRE FOR FUTURE PULLING OF
CONDUCTORS.
C. CONTRACTOR SHALL COORDINATE ALL REQUIRED ENERGY MANAGEMENT SYSTEM POINTS AND
CONTACTS CONNECTIONS TO ENSURE THE COMPLETE AND PROPER OPERATION OF ALL SYSTEMS.
D. THE CONTRACOTR SHALL COORDINATE WITH OTHER TRADES ALL NECESSARY WIRING AND
CONNECTIONS REQUIRDE PRIOR TO PULLING CONDUCTOIRS INTO NEW CONDUITS.
E. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT AND MATERIAL NECESSARY FOR A COMPLETE AND
OPERATIONAL INSTALLATION.
F. CONTRACTOR SHALL NOT DISRUPT SERVICE TO ELECTRICAL APPURTENANCES TO REMAIN.
G. CONTRACTOR SHALL CONNECT ALL NEW FIRE ALARM DEVICES, AS INDICATED ON DRAWINGS, TO
EXISTING SYSTEM. CONTRACTOR SHALL PROVIDE NEW EXPANDABLE MODULES, CARDS, ETC. AS
REQUIRED TO EXISTING SYSTEM, IN ORDER TO ACCOMODATE NEW DEVICES.
H. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PROVIDE POWER AND CONNECT
ALL NEW FIRE /SMOKE DAMPERS AND /OR MOTORIZE DAMPERS TO THE EXISTING FIRE ALARM
SYSTEM. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT AND MATERIAL NECESSARY FOR A
COMPLETE AND OPERATIONAL INSTALLATION. REFER TO MECHANICAL DRAWINGS FOR EXACT
LOCATION OF FIRE /SMOKE DAMPERS AND /OR MOTORIZE DAMPERS.
I. ALL RECEPTACLES AND SWITCH PLATES SHALL HAVE ENGRAVED COVER PLATES TO INDICATE THE
PANEL BOARD AND CIRCUIT NUMBERS POWERING THE DEVICE.
J. ALL EMERGENCY RECEPTACLES AND LIGHT SWITCHES FACE PLATES SHALL BE RED.
K. THE ELECTRICAL CONTRACTOR SHALL. VERIFY THAT THE AIC RATING OF ALL EXISTING CIRCUIT
BREAKERS IN PANELS AFFECTED BY THIS PROJECT ARE ABOVE THE FAULT CURRENT VALUES
PROVIDED IN THE SHORT CIRCUIT CALCULATIONS. IF THE AIC RATINGS ARE BELOW THE FAULT
CURRENT VALUES, THE ELECTRICAL CONTRACTOR SHALL REPLACE ALL BREAKERS WITH NEW
BREAKERS WITH AIC RATINGS ABOVE THE FAULT CURRENT VALUES.
L CONTRACTOR SHALL UPDATE ALL ELECTRICAL PANEL SCHEDULES AFFECTED BY THIS PROJECT.
HAND WRITTEN SCHEDULES ARE NOT ACCEPTED. SCHEDULES SHALL BE TYPED OR COMPUTER
GENERATED.
M. ALL NEW INSTALLATION SHALL COMPLY WITH NEC 210.4(8). CONTRACTOR SHALL PROVIDE A DEDICATED
NEUTRAL FOR EACH CIRCUIT.
N. WITHIN 30 DAYS AFTER DATE OF SYSTEM ACCEPTANCE, CONTRACTOR SHALL SUBMIT ASBUILT RECORD
DRAWINGS OF THE ACTUAL INSTALLATIONS TO THE OWNER AND DESIGN TEAM INCLUDING ANY
APPLICABLE MARKUPS TO THE RISER DIAGRAM. REFER TO SPECIFICATIONS FOR FURTHER
REQUIREMENTS.
0. OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING OWNER PRIOR
TO OCCUPANCY, INCLUDING SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR
EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE WITH CLEARLY IDENTIFIED REQUIRED ROUTINE
MAINTENANCE ACTIONS, AND NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY.
P. PROVIDE NO. 10 AWG CONDUCTORS FOR HOME RUNS ON 120 -VOLT. 20- AMPERE BRANCH CIRCUITS,
WHERE THE CONDUCTOR LENGTH EXCEEDS 100 LINEAL FEET FROM PANELBOARD TO THE FIRST OUTLET.
ELECTRICAL SHEET LIST
NOTE:
DRAWING TITLE
scaLE
IT IS THE RESPONSIBILITY OF MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION
GENERAL INFORMATION - ELECTRICAL
NTS
CONTRACTORS TO VISIT THE SITE AND EXAMINE IN DETAIL THE SCOPE OF WORK OF THIS PROJECT
PARTIAL FIRST FLOOR PLAN - ELECTRICAL
PRIOR TO BID AND SHALL NOTIFY THE ARCHITECT AND /OR ENGINEER IF A CONDITION EXISTS WHICH
ELECTRICAL ONE -LINE, SCHEDULES
NTS
PREVENTS HIM/HER FROM ACCOMPLISHING THE WORK INDICATED AND INTENDED BY THESE DRAWINGS,
DEVICE MTG. HT.
NTS
SO NO ADDITIONAL COST IS INCURRED BY THE OWNER. AFTER CONTRACT IS AWARDED IT WILL BE
ASSUMED THAT THE SITE WAS VISITED AND EXAMINED AND ALL PARTIES ARE IN AGREEMENT WITH THE
48•AFF
SCOPE OF THE WORK.
TO THE BOTTOM OF THE LEN BELOW
6' FINISHED
DEMOLITION NOTES:
TO THE BOTTOM OF THE LEN
�i
6' BELOW FINISHED CEILING
A. ALL EQUIPMENT SHOWN DASHED IS EXISTING TO BE REMOVED. CONTRACTOR SHALL DISCONNECT AND
TO THE BOTTOM OF THE LENS
REMOVE ALL DISCONNECT SWITCHES, CIRCUIT BREAKERS, MOTOR CONNECTIONS, STARTERS, ELECTRICAL
6' BELOW FINISHED CEILING
PANELS, NURSE CALL SYSTEM EQUIPMENT, ETC. WITHIN THE AREA OF WORK, UNLESS OTHERWISE
-
INDICATED. ALSO, REMOVE ALL CONDUIT AND WIRE BACK TO POWER SOURCE. CIRCUIT SHALL REMAIN
AS SPARE OR SPACE IN THEIR RESPECTIVE PANELS, OR BE REUSED AS INDICATED ON PANEL
SCHEDULES. WHERE CONDUIT IS INACCESSIBLE, REMOVE CONDUCTORS AND CUT BACK CONDUIT FLUSH
WITH SLAB OR WALL PATCH OPENING TO MATCH EXISTING FINISH. WHERE EXISTING WIRING EXTENDS
-
OUTSIDE OF THE AREA BY NATURE OF THE ORIGINAL INSTALLATION, CONTRACTOR SHALL MODIFY
_
EXISTING WIRING AS REQUIRED TO MAINTAIN CONTINUITY OF EXISTING CIRCUITRY SUCH THAT NO
EQUIPMENT TO REMAIN IS LEFT WITHOUT SERVICE.
B. PRIOR TO BID, THE EXTENT AND UNDERSTANDING OF THE WORK TO BE PERFORMED SHALL BE
_
CLEARLY ESTABLISHED SUCH THAT NO ADDITIONAL COSTS WILL BE INCURRED BY THE OWNER. ANY
WORK, OTHER THAN AS DESCRIBED ON ANY ITEM OR SYSTEMS SHALL BE QUALIFIED WITHIN THE BID.
C. CONTRACTOR SHALL EXERCISE EXTREME CAUTION DURING DEMOLITION WORK. EXISTING FEEDERS AND
_
PANELS ARE SHOWN SCHEMATIC FOR REFERENCE PURPOSES ONLY. CONTRACTOR SHALL VERIFY IN
_
FIELD ROUTING OF ALL EXISTING FEEDERS PRIOR TO DEMOLITION.
D. CONTRACTOR SHALL PROVIDE TEMPORARY POWER, LIGHTING, COMM., ETC., WHERE REQUIRED DURING
CEILING
DEMOLITION AND CONSTRUCTION SCOPE OF WORK.
-
Ew ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR AND SHALL BE
-
COORDINATED WITH OTHER TRADES.
F. CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY
FOR THE DURATION OF THE WORK.
G. CONTRACTOR SHALL PAY FOR THE PERMITS, FEES do INSPECTIONS.
H. CONTRACTOR SHALL NOT DISRUPT SERVICE TO ELECTRICAL APPURTENANCES TO REMAIN.
1. STATE OF FLORIDA 10. NATIONAL ELECTRICAI. SAFETY (RUDE
2. LIFE SAFETY CODE - NFPA 101 (2009) 11. REQUIREMENTS OF LOCAL UTILITY COMPANIES
3. UNDERWRITERS LABORATORIES. INC. PUBLICATIONS (UL) 12. NATIONAL. FIRE PROTECTION ASSMA71ON 72 (2007)
4. NATIONAL FIRE PROTECTION ASSOCIATION. (NFPA) 11 NATIONAL FIRE PROTECTION ASSOCIATION 99 (2005)
5. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 14 THE STATE FIRE PREVENTION CODE, 4A60 (2010)
6. NATIONAL ELECTRICAL CODE - NFPA 70 (2008) 156 BUILDING CODE: FLORIDA BUILDING CODE (2010)
7. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE) 16. GUIDELINES FOR DESIGN AND CONSTRUCTION OF
8. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) HEALTHCARE FACILITIES (2010)
9. INTERNATIONAL POWER CABLE ENGINEER'S ASSOCIATION (IPCEA) 17. NFPA 110 (2005)
INFEC11ON CONTROL •
all .1
, q1;71 1'
BID NOTE
THE DRAWINGS DO NOT INDICATE EXISTING INSTALLATIONS
OTHER THAN TO IDENTIFY MODIFICATIONS OR EXTENSIONS
THERETO VISIT THE SITE AND ASCERTAIN THE EXISTING
CONDITIONS. REVIEW CONSTRUCTION DETAILS OF THE EXISTING
PORTION OF THE BUILDING DURING THE SITE INSPECTION.
INCLUDE ALL WORK REQUIRED TO REMOVE OR MODIFY
PORTIONS OF THE EXISTING INSTALLATION IN ORDER TO
ACCOMMODATE THE NEW WORK. FAILURE TO COMPLY WITH THIS
WILL NOT BE CONSIDERED GROUNDS FOR ADDITIONAL PAYMENT
IN CONNECTION WITH REMOVING OR MODIFYING ANY PART OF
THE EXISTING INSTALLATION OR INSTALLING ANY NEW OR
TEMPORARY WORK.
I. ALL CIRCUITS SHOWN ARE FOR REFERENCE PURPOSES ONLY. CONTRACTOR SHALL VERIFY ALL
CIRCUITS TO BE REMOVED PRIOR TO COMMENCEMENT OF WORK.
J. THE CONTRACT DOCUMENTS DO NOT PROPOSE TO SHOW ALL EXISTING SYSTEMS, MATERIAL OR
EQUIPMENT. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO OBTAIN DATA RELATED TO
EXISTING CONDITIONS FROM EXISTING DOCUMENTS, NOTATIONS, PHOTOGRAPHS, SURVEYS AND OTHER
OBSERVATIONS AT THE SITE
K. REMOVE EXISTING WIRE, CONDUIT, EQUIPMENT, FIXTURES AND OTHER ITEMS TO PROVIDE ACCESS FOR
WORK IN EXISTING FACILITIES. REINSTALL AND REFINISH ITEMS REMOVED, OR OTHERWISE DAMAGED, TO
MATCH EXISTING AT NO ADDITIONAL COST TO OWNER.
L WHERE EXISTING FUNCTIONS TO REMAIN IN USE ARE DISRUPTED, THEY SHALL BE FULLY RESTORED
AFTER DISRUPTION, IN FULL COMPLIANCE WITH APPLICABLE CODES AND STANDARDS.
M. MODIFY , REMOVE, OR RELOCATE MATERIALS AND ITEMS INDICATED ON THE DRAWINGS OR REQUIRED
DUE TO THE DEMOLITION WORK.
N. WORK JOINTLY WITH THE ARCHITECT, ESTABLISH AND MARK SALVAGE AND DEMOLITION ITEMS BEFORE
COMMENCING WORK; REPORT ITEMS SCHEDULE FOR RELOCATION, REINSTALLATION OR REUSE, WHICH
ARE FOUND TO BE IN DAMAGED CONDITION; AWAIT FURTHER INSTRUCTIONS FROM THE ARCHITECT
BEFORE COMMENCING WITH WORK.
0. DEMOLITION EQUIPMENT, DEVICES AND MATERIAL SHALL BE REMOVED FROM THE SITE AND DISPOSED
OF BY THE CONTRACTOR. SALVAGED EQUIPMENT AND DEVICES SHALL BE THE PROPERTY OF THE
OWNER UNLESS NOTED OTHERWISE.
P. MAKE RELOCATION NECESSITATED BY THE CONDITIONS AT THE SITE OR AS DIRECTED BY THE
ARCHITECT, WITHOUT ADDITIONAL COST TO THE OWNER. REPAIR, REPLACE AND /OR RESTORE TO GOOD
FUNCTIONAL CONDITION, EQUIPMENT, MATERIAL AND ITEMS SCHEDULE FOR RELOCATION, WHICH ARE
DAMAGED DURING DISMANTLING OR REASSEMBLE OPERATIONS. PROVIDE NEW MATERIALS, FITTINGS AND
APPURTENANCES REQUIRED TO COMPLETE THE RELOCATION AND TO RESTORE TO GOOD OPERATING
ORDER. PERFORM THE RELOCATION WORK IN ACCORDANCE TO APPLICABLE CODES ASD STANDARDS,
USING SKILLED WORKERS.
Q. RELOCATING DEVICES: REMOVE AND REINSTALL IN LOCATIONS DESIGNATED BY THE ARCHITECT,
TEMPERATURE CONTROL SYSTEM DEVICES. RELAYS, WIRE CONDUIT, FIXTURES, EQUIPMENT AND OTHER
DEVICES REQUIRED FOR THE OPERATION OF THE VARIOUS SYSTEMS THAT ARE INSTALLED IN EXISTING
TO BE REMOVED CONSTRUCTION.
R. CONTRACTOR SHALL KEEP A CLEAN SET OF DRAWINGS ON THE JOB, NOTING DAILY, ALL CHANGES
MADE IN THESE DRAWINGS IN CONNECTION WITH THE DEMOLITION PHASE, INCLUDING EXACT
DIMENSIONED LOCATIONS OF ALL UNCOVERED EXISTING UTILITIES AND SHALL, WITH THIS, REQUEST FOR
FINAL PAYMENT. TURN OVER A CLEAN, NEATLY MARKED SET OF REPRODUCIBLE MYLARS SHOWING
'EXISTING CONDITIONS' WORK TO THE ARCHITECT FOR SUBSEQUENT REVIEW AND TRANSMITTAL TO THE
OWNER. CONTRACTOR SHALL NOTE ALL CONSTRUCTION CHANGES, DATE EACH AND LABEL 'AS- BUILTS'
IN THE REVISION BLOCK ON THE DRAWINGS. CONTRACTOR SHALL ALSO FURNISH ONE SET OF
'AS- BUILTS' BLUEPRINTS.
S. DEVICES SHOWN IN SOLID LIGHT LINES ARE EXISTING TO REMAIN.
T. CONTRACTOR SHALL UPDATE ALL ELECTRICAL PANEL SCHEDULES AFFECTED BY THIS DEMOLITION.
HAND WRITTEN SCHEDULES ARE NOT ACCEPTED. SCHEDULES SHALL BE TYPED OR COMPUTER
GENERATED.
GENERAL NOTES: FLOOR PLANS.
A. CONTRACTOR SHALL PROVIDE AND INSTALL AN IDENTIFICATION NAMEPLATE FOR EACH ELECTRICAL
EQUIPMENT /APPURTENANCES DEPICTING THE DESIGNATION INDICATED ON THE DRAWINGS.
B. ALL EMPTY CONDUITS SYSTEMS SHALL CONTAIN A PULL WIRE FOR FUTURE PULLING OF
CONDUCTORS.
C. CONTRACTOR SHALL COORDINATE ALL REQUIRED ENERGY MANAGEMENT SYSTEM POINTS AND
CONTACTS CONNECTIONS TO ENSURE THE COMPLETE AND PROPER OPERATION OF ALL SYSTEMS.
D. THE CONTRACOTR SHALL COORDINATE WITH OTHER TRADES ALL NECESSARY WIRING AND
CONNECTIONS REQUIRDE PRIOR TO PULLING CONDUCTOIRS INTO NEW CONDUITS.
E. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT AND MATERIAL NECESSARY FOR A COMPLETE AND
OPERATIONAL INSTALLATION.
F. CONTRACTOR SHALL NOT DISRUPT SERVICE TO ELECTRICAL APPURTENANCES TO REMAIN.
G. CONTRACTOR SHALL CONNECT ALL NEW FIRE ALARM DEVICES, AS INDICATED ON DRAWINGS, TO
EXISTING SYSTEM. CONTRACTOR SHALL PROVIDE NEW EXPANDABLE MODULES, CARDS, ETC. AS
REQUIRED TO EXISTING SYSTEM, IN ORDER TO ACCOMODATE NEW DEVICES.
H. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PROVIDE POWER AND CONNECT
ALL NEW FIRE /SMOKE DAMPERS AND /OR MOTORIZE DAMPERS TO THE EXISTING FIRE ALARM
SYSTEM. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT AND MATERIAL NECESSARY FOR A
COMPLETE AND OPERATIONAL INSTALLATION. REFER TO MECHANICAL DRAWINGS FOR EXACT
LOCATION OF FIRE /SMOKE DAMPERS AND /OR MOTORIZE DAMPERS.
I. ALL RECEPTACLES AND SWITCH PLATES SHALL HAVE ENGRAVED COVER PLATES TO INDICATE THE
PANEL BOARD AND CIRCUIT NUMBERS POWERING THE DEVICE.
J. ALL EMERGENCY RECEPTACLES AND LIGHT SWITCHES FACE PLATES SHALL BE RED.
K. THE ELECTRICAL CONTRACTOR SHALL. VERIFY THAT THE AIC RATING OF ALL EXISTING CIRCUIT
BREAKERS IN PANELS AFFECTED BY THIS PROJECT ARE ABOVE THE FAULT CURRENT VALUES
PROVIDED IN THE SHORT CIRCUIT CALCULATIONS. IF THE AIC RATINGS ARE BELOW THE FAULT
CURRENT VALUES, THE ELECTRICAL CONTRACTOR SHALL REPLACE ALL BREAKERS WITH NEW
BREAKERS WITH AIC RATINGS ABOVE THE FAULT CURRENT VALUES.
L CONTRACTOR SHALL UPDATE ALL ELECTRICAL PANEL SCHEDULES AFFECTED BY THIS PROJECT.
HAND WRITTEN SCHEDULES ARE NOT ACCEPTED. SCHEDULES SHALL BE TYPED OR COMPUTER
GENERATED.
M. ALL NEW INSTALLATION SHALL COMPLY WITH NEC 210.4(8). CONTRACTOR SHALL PROVIDE A DEDICATED
NEUTRAL FOR EACH CIRCUIT.
N. WITHIN 30 DAYS AFTER DATE OF SYSTEM ACCEPTANCE, CONTRACTOR SHALL SUBMIT ASBUILT RECORD
DRAWINGS OF THE ACTUAL INSTALLATIONS TO THE OWNER AND DESIGN TEAM INCLUDING ANY
APPLICABLE MARKUPS TO THE RISER DIAGRAM. REFER TO SPECIFICATIONS FOR FURTHER
REQUIREMENTS.
0. OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING OWNER PRIOR
TO OCCUPANCY, INCLUDING SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR
EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE WITH CLEARLY IDENTIFIED REQUIRED ROUTINE
MAINTENANCE ACTIONS, AND NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY.
P. PROVIDE NO. 10 AWG CONDUCTORS FOR HOME RUNS ON 120 -VOLT. 20- AMPERE BRANCH CIRCUITS,
WHERE THE CONDUCTOR LENGTH EXCEEDS 100 LINEAL FEET FROM PANELBOARD TO THE FIRST OUTLET.
ELECTRICAL SHEET LIST
ML
DRAWING TITLE
scaLE
EO.00
GENERAL INFORMATION - ELECTRICAL
NTS
E1.00
PARTIAL FIRST FLOOR PLAN - ELECTRICAL
E200
ELECTRICAL ONE -LINE, SCHEDULES
NTS
E3.00
ELECTRICAL SPECIFICATIONS
NTS
� Q
� � c
a�
r �a O a fu t
Akt0 tL c to
LL o to
.4uaq to
in 0 co
rym . � ° ro M` m E In
n. M ^0 c n
a� c 0
N :- �.
rl 0 0 L X 4. O
NNU a4°_ > xm
Cl 12 ccW
CD ° 0 0
a
�0.
N
En
o Utz
C o Q
COL a
KEYPLAN
Job NCI
412480.000
Dots
11 -05 -2012
t� •
Shmt No-
E0.00"'
-
�i
KEYPLAN
Job NCI
412480.000
Dots
11 -05 -2012
t� •
Shmt No-
E0.00"'