12-1303R-002MECHANICAL SYMBOLS
ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.
SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
- CHWS
, CHS
CHILLED WATER SUPPLY PIPE
E CHR-
CHILLED WATER RETURN PIPE
SYMBOL
DESCRIPTION
CWS-
CONDENSER WATER SUPPLY PIPE
A
�V
NEW EQUIPMENT DESIGNATION
(TOP - EQUIP. ABBREV., BOTTOM - MARK)
CWR-
CONDENSER WATER RETURN PIPE
/.A./
NEW DIFFUSER DESIGNATION
(TOP - SCHEDULE DESIG., BOTTOM - CFM)
RL
REFRIGERANT LIQUID PIPE
RG
REFRIGERANT GAS PIPE
3250
NEW EQUIPMENT
HWS-
HEATING WATER SUPPLY
HWR-
HEATING WATER RETURN
UNEW
EXISTING EQUIPMENT
DUCT
-HPS
-HPR
HIGH PRESSURE STEAM
HIGH PRESSURE CONDENSATE RETURN
- - -LPS - --
LOW PRESSURE STEAM
BV
EXISTING DUCT TO REMAIN
- -LPR - --
LOW PRESSURE CONDENSATE RETURN
- -- 1
EXISTING DUCT TO BE REMOVED OR RELOCATED
-PCT
PUMPED CONDENSATE RETURN
CD
CONDENSATE DRAIN
®
NEW SUPPLY DIFFUSER
��
DIRECTION OF SLOPE
R
®
DI
EXISTING SUPPLY DIFFUSER TO REMAIN
�"-
DIRECTION OF FLOW
DO
EXPANSION LOOP
F _,1_
EXISTING SUPPLY DIFFUSER TO BE REMOVED OR RELOCATED
_0 4 _
GATE VALVE
RLA
NEW RETURN GRILLE
�-
BUTTERFLY VALVE
�-
BALL VALVE
EDH
EEXISTING
UH
RETURN GRILLE TO REMAIN
-►N-
GLOBE VALVE
r- -m
Ic_J
®
EXISTING RETURN GRILLE TO BE REMOVED OR RELOCATED_
NEW EXHAUST GRILLE
EF
AUTOMATIC 2 -WAY CONTROL VALVE
AUTOMATIC 3-WAY CONTROL VALVE
WHP
EEXISTING
SF
EXHAUST GRILLE TO REMAIN
PLUG VALVE/BALANCING COCK
I-
CHECK VALVE
_
JEXISTING
EXHAUST GRILLE TO BE REMOVED OR RELOCATED
NEW SLOT DIFFUSER
Q
--E?+F
HYDRAULIC SHOCK ARRESTOR
VALVE IN VERTICAL
FMB
EXISTING SLOT DIFFUSER
{{F-
UNION
- - --
EXISTING SLOT DIFFUSER TO BE REMOVED OR RELOCATED
- VV-
VACCUUM BREAKER
--
FLEXIBLE DUCT
DO
P -TRAP
O
SENSOR
:
FLOOR DRAIN W/ P -TRAP
Q
THERMOSTAT
SV
HUB DRAIN
T,
EXISTING THERMOSTAT TO BE REMOVED OR RELOCATED
io
FLOOR CLEANOUT OR GRADE CLEANOUT
Mvp -
AiR TRANSFER QUANTITY (CFM)
I
CLEANOUT OR WALL CLEANOUT
�••�
CONICAL TAP WITH VOLUME DAMPER
+
PETE'S PLUG
♦--
CONICAL TAP W/O VOLUME DAMPER
-i•1
GAUGE COCK
SQUARE TO ROUND DUCT TRANSITION
y
THERMOMETER
J
MANUAL VOLUME DAMPER
--'
FIRE DAMPER
IF
THERMOMETER WELL
-�"
SMOKE DAMPER
STRAINER WITH BLOW -OFF VALVE
- -4
FIRE /SMOKE DAMPER
F & T STEAM TRAP
-�
MOTORIZE) DAMPER
�-
STEAM BUCKET TRAP
CONNECT TO EXISTING
ELECTRIC PNEUMATIC SWITCH
6 :1 :1 W1 I A, A
AC
ABOVE CEILING
EOM
END OF MAIN DRIP
AFF
ABOVE FINISHED FLOOR
F CU
FAN COIL UNIT
Al
ANALOG INPUT
FPB
FAN POWERED BOX
AO
ANALOG OUTPUT
FPI
FINS PER INCH
BFC
BELOW FINISHED CEILING
GC
GENERAL CONTRACTOR
3250
120/1/60
GEF
GENERAL EXHAUST FAN
BF
BELOW FLOOR, BUND FLANGE
MERV 14
EXISTING
BG
BELOW GRADE
GSF
GENERAL SUPPLY FAN
BV
BUTTERFLY VALVE
MVD
MANUAL VOLUME DAMPER
CRAC
COMPUTER ROOM UNiT
N
NEW
CRU
CONDENSATE RETURN UNIT
OBD
OPPOSED BLADE DAMPER
CU
CONDENSING UNIT
R
RELOCATED
DI
DIGITAL INPUT
RA
RETURN AIR
DO
DIGITAL OUTPUT
RCA
RECIRCULATED (RETURN) AIR
DS
DISCONNECT SWITCH
RLA
RELIEF AIR
E
EXISTING
SA
SUPPLY AIR
EDH
ELECTRIC DUCT HEATER
UH
UNIT HEATER
EUH
ELECTRIC UNIT HEATER
WH
WATER HEATER
EF
EXHAUST FAN
WHP
WATER - SOURCE HEAT PUMP
SF
SUPPLY FAN
CAV
CONSTANT AIR VOLUME
EA
EXHAUST AiR
FMB
FILTER MIXING BOX
OA
OUTSIDE AIR
IN HG
INCHES MERCURY (PRESSURE)
C HW
CHILLED WATER
IN WC
INCITES WATER COLUMN (PRESSURE)
UNO
UNLESS NOTED OTHERWISE
IBT
INVERTED BUCKET TRAP
PRV
PRESSURE RELIEF VALVE
TAV
THERMOSTATIC AiR VENT
SV
SAFETY VALVE
MA
(STEAM SYSTEM)
MIXED AIR
N.I.C.
NOT IN CONTRACT
LE
LAUNDRY EQUIPMENT
Sealant
IWI MM
EME52OMD
wNnlwnal
Flange Frerrpvm_- \�"
EXTERIOR
Notes:
1. The installation shown herein must be followed
strictly to ensure compliance with Miami -Dade
NOA.
2. Continuous installation angles and fasteners are
shipped loose and require installation in the field.
3. Anchors or fasteners into the all are not
required.
4, Ruskin is not responsible for determining the
suitability of the structure.
S. Shims may be required to achieve con5istenl
clearance between louver and opening on all
sides (shims not included)..
6. NIRC - Not in Ru5Wn's Contract,
Main- Wall Depth
-10"(2S4) • UFFie -le{
95 "(381 (]91)UFflS If
Continuous Angles arid
Fasteners (shipped loose).
Fasteners to be installed 3' [75y
q ♦ mac from ends end 12° (305)
maa. IK
yy (e Mumon Support,.
4h .y� ? 5- (127) deep• at
a r' muRiseclton
pints -ly.
J,
PI [.
_ley` p UFF skew.
condrwous
°. at perimeter
LL UFF Sleeve Depth
/2 ^(30S)- UFF10- r..
17- (432) • UFfl 5
• DETAIL-
5NO SCALE
PUMP SCHEDULE
DESIG.
SERVES
TYPE
FF•
GPM
TDH
(FT")
ELECTRICAL
MANUFACIURER/iuIODEL NO.
REMARKS/NOTES
HP
RPM
VOLT/PHASE
HP- RHC -1S -8
RHC -1S -8
CIRCULATOR
N/A
1.3
6.9
0.04
3250
120/1/60
TACO L0515
MATCH EXISTING COIL PUMPS
7.1 � OW 1 « 7 -, 771 «1 1103
REHEAT
C01 L
SCHEDULE
MARK
CFM
COIL SIZE
FACE VEL.
(MAX)
BTUH
EAT 'F
LAT 'F
�i1
MANUFACTURER ODE. NO.
APD -IN
(MAX)
EWT
&F
WATER
ATF
GPM
WATER
dP -FT (MAX)
OUTSIDE
AHU -1 -3
GENERAL ADMIN
2920
1825
1095
0,3275
1840
1435
MERV 7
MERV 14
EXISTING
350
RHC -1 S-8
300
10x8
500
13000
55
85
0.3
125.8
105.8
1.3
5
EXIST. EF SCHEDULE
MARK
SERVICE
PRE T +B
NEW DESIGN
EF -1 -3
GENERAL
1120
1050
FINAL
FiLT.
�i1
MANUFACTURER ODE. NO.
TOTAL
CFM
RETURN
CFM
% NOTES:
1. FAN TO SHUT DOWN ON FIRE ALARM.
2 VERIFY INTERLOCK WITH AHU -1 -3, IF NOT INTERLOCKED, PRO
A2 '
EXISTING AHU SCHEDULE
DESIG.
SERVICE
PRE
T&B CFM
EW
DESIGN CFM
MOTOR DATA
PRE
FiLT.
FINAL
FiLT.
�i1
MANUFACTURER ODE. NO.
TOTAL
CFM
RETURN
CFM
OUTSIDE
AIR CFM
L
RETURN
OUTSIDE
AHU -1 -3
GENERAL ADMIN
2920
1825
1095
0,3275
1840
1435
MERV 7
MERV 14
EXISTING
350
-
120/60/1
NO
G REENHECK /CSP -A700
39
ALL
3
NOIM,
.
1. AM TO SHUT DOWN ON FIRE ALARM.
THREADED ROD
I SIZE PER SMACNA (TYP)
al:
I1 01I
TYPICAL
1/Y ALL THREADED STEEL HANGER
ROD, SECURE TO STRUCTURE WITH
DOUBLE NUTS,TYPICAL(MIN. OF 4).
`1 1'
1 " «1
1. `a
GENERALNOTES: mm 0 0
A. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE FLORIDA UNIFOPW ry �r --I rn
STATEWIDE BUILDING CODE STATE AND LOCAL CODES IBC, AIA, IMC, NEC THE NATIONAL FIRE R m " no c
PROTECTION ASSOCIATION (NFPA). AND THE LOCAL AUTHORITIES HAVING JURISDICTION. AIL-1- - _ r6
EQUIPMENT, MATERIALS, CONTROLS, ETC. SHALL BE NEW UNLESS NOTED OTHERWISE AND J J pj pj a
SHALL MATCH ALL FACILITY STANDARDS OR IF APPROVED BY THE OWNER, BE OF THE SAME of U- w to
QUALITY AS REPRESENTED BY THE SCHEDULED ITEM. - - - w c
B CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS, PAY ALL FEES, AND COMPLY W:74 -
ALL NATIONAL, STATE, AND MUNICIPAL LAWS, CODES, AND ORDINANCES RELATING TO - w °, � M m 0 00
BUILDING AND PUBLIC SAF:iY. a c? "o _.. n o Z
C. CONTRACTOR SHALL FURNISH ALL MATERIALS, EQUIPMENT, AND LABOR REQUIRED FOR A r+ 4) - c = " o
COMPLETE WORKING AND COORDINATED SYSTEM. � � `a s x °o
D. COORDINATE THE EXACT LOCATION OF MECHANICAL. AND PLUMBING EQUIPMENT WITH THE N In u a 1m > ,x m
LOCATIONS OF LIGHT FIXTURES, PIPING, CONDUIT, AND OTHER CONSTRUCTION, TO ALLOW FOR c In C E W
PROPER ACCESS TO SERVICE EQUIPMENT. °o • ♦ = p o
L COORDINATE THE LOCATION OF DUCiWORK AND PIPING NTH OTHER TRADES AND PROVIDE o W • a
CC)
OFFSETS IN DUCTWORK AND PIPING AS REQUIRED. N _ M
F. IT IS THE INTENT OF THESE DOCUMENTS TO ALLOW ALL CEILING CONSTRUCTION AND HEIGHTS .� h
TO BE AS SHOWN. COORDINATE THE LOCATION OF DUCiWOORK AND PIPING AND PROVIDE o
ar
OFFSETS IN DUCTWORK AND PIPING AS REQUIRED TO MEET THIS INTENT.
G. CONDUIT, PIPING, AND DUCTWORK SHALL BE INDEPENDENTLY SUPPORTED, AND EACH v
SUPPORT SHALL BE INDEPENDENT OF PARTITION AND CEILING SYSTEM SUPPORTS. WHERE in z
INDEPENDENT SUPPORT IS NOT POSSIBLE AN ENGINEERED SUPPORT SYSTEM SHALL BE nom`. a
UTiLIZ:•D.
H. ALL WORK SHALL BE SCHEDULED AND PERFORMED IN STRICT COORDINATION WITH
ARCHITECTURAL PHASING PLANS AND WITH HOSPITAL SCHEDULES, OCCUPANCIES, AND WORK.
L PROTECT EQUIPMENT AND WORK FROM DAMAGE DURING HANDUNG AND INSTALLATION UN11L REVOOM
COMPLETION OF CONSTRUCTION.
J. REMOVE ALL EXCESS MATERIAL AND DEBRIS AND CLEAN ALL EQUIPMENT UPON COMPLETION
OF WORK. TOUCH UP WITH PAINT WHERE REQUIRED. MARK: REMARKS:
K ACONNECTION BETWEEN PIPES OF DISSIMILAR MATERIALS SHALL BE MADE WITH DIELECTRIC
UNIONS
ANCA COMMENT 11 /�l 2 , 9/
L DUCT SIZES ARE NET FREE AREA. 1
M. PROVIDE ROUND DUCTS TO ALL AIR DEVICES UNLESS NOTED OTHERWISE DUCT SIZE SHALL 1 12/17/2D12 MATCH AIR DEVICE NECK Si2E OR THE TABLE IN AIR DEVICE SCHEDULE, WHICHEVER IS 2
LARGER. FLEXIBLE DUCTS SHALL BE SIZED SIMILARLY.
N. INSTALL SPACE SENSOR ADJACENT TO LATCH SiDE OF DOOR IN SPACE INDICATED. U.N.O. Q WO CHANGES 3/08/2013 INDICATED LOCATIONS ARE APPROXIMATE. AVOID HEAT PRODUCING EQUIPMENT, 3
0. INSTALL TURNING VANES IN ALL 90 DEGREE SQUARE ELBOWS IN SUPPLY, RETURN, AND
EXHAUST DUCTS. (NONE ALLOWED IN COMBIJS110N AIR DUCTS).
P. MULTi -BLADE DAMPERS OF ANY TYPE INSTALLED WITHIN Was OF AN ELBOW OR OTHER
FITTING SHALL BE INSTALLED WITH THE DAMPER BLADE SHAFTS PARALLEL TO THE
AIRSTREAM FLOW DIRECTION UPSTREAM OF THE FITTING.
Qe FIRE, SMOKE, AND FIRE/SMOKE DAMPERS WiLL BE REQUIRED AT ALL DUCT PENETRATIONS
THRRU RATED WALLS. COORDINATE WITH LIFE - SAFETY RA.
R. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PRICING ALL FIRE, SMOKE, AND
FIRE/SMOKE DAMPERS REQUIRED BY CODE MECHANICAL CONTRACTOR SHALL REPORT
EXISTING FIRE, SMOKE, FIRE/SMOKE DAMPERS TO THE ENGINEER BEFORE PRICING.
�1S DEMONSTRATE TO OWNERS RREPRMTATiVE THAT ALL INSTALLED CONTROLS ARE WORKING
PROPERLY WITHOUT ERRORS PRIOR TO RELEASING SYSTEM TO OWNER.
T, MAKE RELOCATION AND /OR REPAIRS NECESSITATED BY THE CONDITIONS AT THE SITE OR AS
DIRECTED BY THE OWNER, WITHOUT ADDITIONAL COST TO THE OWNER. REPAIR, PAINT
AND /OR RESTORE TO GOOD FUNCTIONAL CONDITION SUCH AS EQUIPMENT, MATERIAL, WALLS,
CEILING, FINISHES, CEILING GRID AND ITEMS SCHEDULE FOR RELOCATION AND /OR EXISTING TO
REMAIN, WHICH ARE DAMAGED DURING DISMANTLING OR REASSEMBLE OPERATIONS PROVIDE
NEW MATERIALS, FITTINGS AND APPURTENANCES REQUIRED TO COMPLETE THE RELOCATION
AND TO RESTORE TO GOOD OPERATING ORDER. PERFORM THE RELOCATION WORK IN
ACCORDANCE TO APPLICABLE CODES ASD STANDARDS, USING SKILLED WORKERS.
GENERAL PIPING NOTES
A. CONTRACTOR TO PROVIDE ACCESS DOORS IF REQUIRED FOR ACCESS TO CAN'S AND ANY
VALVES THAT ARE NOT ACCESSIBLE. VERIFY SIZE AND LOCATIONS WITH MECHANICAL
CONTRACTOR.
B. HWC BRANCH PIPING SHALL BE A MINIMUM OF 3/4' U.N.O.
NJ1/�;,��, /I ►/. ..II 1 1 •11 I :i� • 7-1 1 •i 71 ' . 1 ... 1 1 .� / 1 .
t�t•D 1 - ` I «11 • 1 • �• `7 1 `« ' r 1 • 71 1 1 «I 1' '1 1 :� `71 '1
� ; � , � 1 • 7 M l '/ 1 «I 7'171 7
A JAM
« « 1 •r7' I a1 1.7 1 1
`« 71 >, / «« «3. 1 1', •1 1' «11•,1
Ic• •,r -,3: �
1� • •17' •/7: �
"� 1 1 1 • � • � � «/ 1 '11 71 f • 1 � •/ • / • 7' f 1 � 1 1
«1 1 1 �` 1' 71 1 - / 1 1 t7' •/ • •171
�� 7 �__- '17 1 1 al : • « •' • 1 1 / i 1 / r7' '1 . •AI
1'
'1 / •171 `: •11 '17 1 1 1-1 � / 1 r71 1
1
1 1 1 • 7' « /
• � 1 «1 1 :+ •17 1 71 1
�' / 1 • 7' 1 ' 7'
is •/7 F1 - 1 "7• / i 7• 1 •171 •17 f 7/
•
•1r °13:7
`;; I al «7 11 `7' •� `71 '17 / 71 1 1',71 /-
1« 1 `• 1 `71 1 1 '1 71 1 7- •17•':•13: 7
' 1 N r• a4 i / •, 1
r / � 1 7 •, 1 . 7 •
►1 ` / ` 1 1
►1 MI 1 A ', 1'', :J ► 1
+ 17' ►/ i 1 : 1 / ( «1 al 1 r71 - / 1 • 1 1 • '/7 1 7/
«11.'1 •« 1' h 1
7• « ` 1 1 1' 1
FAN SCHEDULE
DESIG.
DESIG.
AREA SERVE
LOCATION
CFM
EBXPT••
DATA
MOTOR DATA
MANUFACTURER/MODEL NO.
WEIGHT
REMARKS/NOTES
TYPE
RPM
DRIVE
TS (FPM)
WATTS
B.H.
VOL
FIRE STOPPING
EF- -1 -38
GENERAL
CEILING 1
400
0.5
INLINE
1090
DIRECT
1976
350
-
120/60/1
NO
G REENHECK /CSP -A700
39
ALL
.. NOTES,
1. PROVIDE DISCMNET
2. BACK DRAFT DAMPER.
3. FAN 1 SHUT DOWN ON '1 ALARM
4. PROVIDE `•771 CONTROL
5. INTERLOCK « EXISTING
6. MAX .4TA
n
U
HVAC DESIGN REQUIRES
YES
NO
DUCT SMOKE DETECTOR
X
FIRE DAMPER(S)
X
SMOKE DAMPER(S)
X
FIRE RATED ENCLOSURE
X
FIRE RATED ROOF/ FLOOR CEILING ASSEMBLY
X
FIRE STOPPING
X
SMOKE CONTROL
X
APPLICABLE CODES
1. FLORIDA BUILDING CODE 2010 EDITION
2. FLORIDA MECHANICAL CODE, 2010 EDITION
3. FLORIDA PLUMBING CODE, 2010 EDITION
4. GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITAL AND HEALTH
CARE FACILITIES (GUIDELINES 2010 EDITION)
5. NFPA 101 (2006)
6. NFPA 99 (2005)
7. STATE FIRE PROVEIMON CODE 4A60 (2001)
& ALA GUIDELINES (2010)
9. FIRE MARSHALL'S RULE 4A3.012 F.A.C. (JANUARY 1, 2001)
10. NFPA 70 (2008)
11. NFPA 110 (2005)
.. .
i
i
All
i
/