12-1303-0090 G J a ELECTRICAL SPECIFICATIONS 16010 - BASIC ELECTRICAL REQUIREMENTS A. THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND . INSTALLATION OF THE NECESSARY MATERIAL AND LABOR TO ACCOMPLISH THE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. ALL WORK BY CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL, STATE AND LOCAL BUILDING CODES AND STANDARDS INCLUDING BUT NOT LIMITED TO:REFER TO SHEET EO.00 B. CODES AND STANDARDS REFERRED TO ARE MINIMUM. WHERE THE REQUIREMENTS OF THE DRAWINGS OR SPECIFICATIONS EXCEED THOSE OF THE CODES AND REGULATIONS, THE DRAWINGS AND SPECIFICATIONS GOVERN. C. THE CONTRACTOR SHALL OBTAIN AND PAY FOR PERMITS, PLAN CHECKS, INSPECTIONS, AND APPROVALS APPLICABLE TO THE WORK AS REQUIRED BY THE REGULATORY AUTHORITIES. FEES AND COSTS OF ANY NATURE WHATSOEVER INCIDENTAL TO THESE PERMITS, INSPECTIONS AND APPROVALS SHALL BE ASSUMED AND PAID BY THE CONTRACTOR THE PRO -RATA COSTS, IF ANY, FOR UTILITIES SERVING THIS PROPERTY WILL BE PAID FOR BY THE OWNER AND SHALL NOT BE INCLUDED AS PART OF THIS CONTRACT. D. SPACE ALLOCATIONS FOR MATERIALS, EQUIPMENT AND DEVICES HAVE BEEN MADE ON THE BASIS OF PRESENT AND KNOWN FUTURE REQUIREMENTS AND THE DIMENSIONS OF ITEMS OF EQUIPMENT OR DEVICES OF A PARTICULAR MANUFACTURER WHETHER INDICATED OR NOT. THE CONTRACTOR SHALL VERIFY THAT ALL MATERIALS, EQUIPMENT AND DEVICES PROPOSED FOR USE ON THIS PROJECT ARE WITHIN THE CONSTRAINTS OF THE ALLOCATED SPACE E ALL DOSTING SYSTEMS, EQUIPMENT OR MATERIAL CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING THE EXISTING CONDITIONS AT THE JOB SITE BEFORE SUBMITTING PROPOSALS SUBMISSION OF PROPOSALS SHALL BE TAKEN AS EVIDENCE THAT SUCH INSPECTION HAS TAKEN PLACE THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE COMPLETE SET OF CONSTRUCTION DOCUMENTS, AND THE LACK OF SPECIFIC INFORMATION ON THE DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR OF ANY RESPONSIBILITY. F EQUIPMENT SHALL BE NEW AND SHALL BEAR THE U.L LABEL WHERE APPLICABLE, UNLESS NOTED OTHERWISE ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR AFTER COMPLETION AND ACCEPTANCE BY THE OWNER G. CONTRACTOR SHALL INSTALL ELECTRICAL SYSTEMS WITHOUT INTERFERENCE AND IN STRICT COORDINATION WITH OTHER TRADES H. MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE CONTRACT DOCUMENTS AND APPLICABLE CODES AND STANDARDS IN CASE OF DIFFERENCE BETWEEN APPLICABLE CODES AND STANDARDS AND THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL PROMPTLY NOTIFY THE ARCHITECT/ENGINEER IN WRITING OF SUCH DIFFERENCE SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE REQUIREMENTS OF APPLICABLE CODES AND STANDARDS, HE /SHE SHALL BEAR ALL COSTS ARISING IN CORRECTING SUCH DEFECTS APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL ORDINANCES, UTILITY COMPANY REGULATIONS, AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS SHOULD THE CONTRACTOR SUPPLY EQUIPMENT DIFFERING FROM THE SPECIFIED ITEMS IN THE CONTRACT DOCUMENTS WITHOUT NOTIFICATION TO THE ENGINEER, HE SHALL BEAR ALL COSTS TO UPGRADE DEFICIENCIES ARISING FROM SUCH. I. WHERE ONLY ONE MANUFACTURER'S NAME IS LISTED IN THE EQUIPMENT SPECIFICATION, OTHER MANUFACTURERS OF SIMILAR CHARACTERISTICS AND OF EQUAL OR BETTER PERFORMANCE CAPACITIES MAY BE CONSIDERED FOR 'OR EQUAL' ACCEPTANCE BY THE ENGINEER. SUBSTITUTION REQUESTS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL WHERE MORE THAN ONE MANUFACTURER IS LISTED IN THE NOTES AND EQUIPMENT SPECIFICATIONS, ONLY THOSE NAMED MANUFACTURERS WILL BE CONSIDERED FOR ACCEPTANCE SHOULD A SUBSTITUTION BE ACCEPTED, AND SHOULD THE SUBSTITUTE MATERIAL PROVE DEFECTIVE. OR OTHERWISE UNSATISFACTORY FOR THE SERVICE INTENDED WITHIN THE GUARANTEE PERIOD, THIS MATERIAL OR EQUIPMENT SHALL BE REPLACED NTH THE MATERIAL OR EQUIPMENT SPECIFIED AT NO COST TO THE OWNER J. PROVIDE ACCESS, INCLUDING NECESSARY ACCESS DOORS, FOR NEW AND EXISTING EQUIPMENT REQUIRING OPERATION AND /OR MAINTENANCE. RELOCATE E)aSTING AND LOCATE ALL NEW EQUIPMENT SUCH THAT OPERATION OR MAINTENANCE IS NOT RESTRICTED. K INSTALL EQUIPMENT WITH WORKING CLEARANCES COMPLYING WITH NEC 110 -26 AND 110 -34. L SHOP DRAWING SUBMITTALS 1. CONTRACTOR SHALL PREPARE AND SUBMIT SEVEN COPIES OF ALL SUBMITTALS FOR ALL PERTINENT ELECTRICAL EQUIPMENT AND DEVICES INDICATED IN THE SCOPE OF WORK 2. COMPLETE LIST OF MATERIALS TO BE FURNISHED UNDER EACH SPECIFIC SECTION. 3. MANUFACTURERS' SPECIFICATIONS AND OTHER DATA REQUIRED TO ASSURE SPECIFICATION COMPLIANCE, 4. CATALOG SHEETS, CLEARLY MARKED FOR IDENTIFICATION OF ITEMS TO BE PROVIDED, INCLUDING DISCONNECT SWITCHES, BREAKERS, FUSES, STARTERS, LIGHTING FIXTURES, TRANSFORMERS, OR OTHER MATERIAL NOT REQUIRING SPECIALLY PREPARED SHOP DRAWINGS 5. ALL SHOP DRAWING CUT SHEETS SHALL CLEARLY IDENTIFY THE SPECIFIC PRODUCT TO BE REVIEWED AND APPROVED, INCLUDING MANUFACTURER GENERIC CUT SHEETS. INCOMPLETE CUT SHEETS AND CUT SHEETS SUBMITTED WITHOUT IDENTIFYING THE SPECIFIC PRODUCT PROVIDED, WILL BE AUTOMATICALLY REJECTED. 6. AS PART OF EQUIPMENT SHOP DRAWINGS, PROVIDE DETAILED DIMENSIONED LAYOUT DRAWINGS FOR ALL LARGE ELECTRICAL EQUIPMENT AND ELECTRICAL. ROOMS WHERE NEW EQUIPMENT IS BEING INSTALLED. M. EACH CONDUIT, REGARDLESS OF MATERIAL. WHICH PASSES THROUGH A CONCRETE SLAB, MASONRY WALL. OR ROOF OR PORTION OF THE BUILDING STRUCTURE SHALL BE FREE FROM THE STRUCTURE AND SHALL PASS THROUGH A SLEEVE. ALL SLEEVES SHALL BE CONSTRUCTED FROM ELECTRIC - METALLIC TUBING OR EQUIVALENT WEIGHT GALVANIZED STEEL TUBING AND SHALL BE FLUSH ON BOTH SIDES OF THE SURFACE PENETRATED, U.N.O. ALL SLEEVES PENETRATING THE ROOF AREAS SHALL EXTEND A MINIMUM 10 INCHES ABOVE THE ROOF WITH APPROVED WEATHERPROOF COUNTERFLASHING ATTACHED TO THE CONDUIT ABOVE THE ROOF. ALL SLEEVES PENETRATING FLOORS SHALL EXTEND A MINIMUM OF 6 INCHES A.F.F. THE SLEEVES SHALL BE SIZED TO ALLOW FREE PASSAGE OF THE CONDUIT TO BE INSERTED. SLEEVES PASSING THROUGH WALLS OR FLOORS ON OR BELOW GRADE OR IN MOIST AREAS SHALL BE CONSTRUCTED OF GALVANIZED RIGID STEEL AND SHALL BE DESIGNED WITH A SUITABLE FLANGE INT HE CENTER TO FORM A WATERPROOF PASSAGE AFTER THE CONDUIT HAS BEEN INSTALLED IN SLEEVES, THE VOID SPACE AROUND THE CONDUIT SHALL BE CAULKED AND FILLED WITH AN ASPHALT -BASE COMPOUND TO INSURE A WATERPROOF PENETRATION. JUTE TWINE CAULKING SHALL NOT BE USED. N. CONTRACTOR SHALL KEEP A CLEAN SET OF DRAWINGS AT THE SITE. NOTING DAILY ALL CHANGES MADE IN THESE DRAWINGS IN CONNECTION WITH THE FINAL INSTALLATION INCLUDING EXACT DIMENSIONED LOCATIONS OF ALL NEW AND UNCOVERED EXISTING UTILITIES TURN OVER A CLEAN, NEATLY MARKED SET OF REPRODUCIBLE MYLARS SHOWING 'AS INSTALLED' WORK TO THE ARCHITECT FOR SUBSEQUENT REVIEW AND TRANSMITTAL TO THE OWNER CONTRACTOR SHALL NOTE ALL CONSTRUCTION CHANGES, DATE EACH SHEET AND LABEL 'AS- BUILTS' IN THE REVISION BLOCK ON THE DRAWINGS CONTRACTOR SHALL ALSO FURNISH ONE (1) SET OF 'AS- BUILT' BLUELINE PRINTS 0. IN ADDITION TO THE ABOVE, CONTRACTOR SHALL ACCUMULATE DURING THE JOB'S PROGRESS, THE FOLLOWING DATA, IN TRIPLICATE. PREPARED IN A NEAT BROCHURE OR PACKET FOLDER AND TURNED OVER TO THE ARCHITECT FOR REVIEW AND SUBSEQUENT DELIVERY TO THE OWNER 1. ALL WARRANTIES AND GUARANTEES AND MANUFACTURER'S DIRECTIONS ON EQUIPMENT AND MATERIAL COVERED BY THE CONTRACT INCLUDING THE NAMES, ADDRESSES AND TELEPHONE NUMBERS OF THE MANUFACTURER'S REPRESENTATIVE 2. APPROVED FIXTURE BROCHURES, TIRING DIAGRAMS AND CONTROL DIAGRAMS (ORIGINAL DATA. NO COPIES). 3. COPIES OF APPROVED SHOP DRAWINGS 4. OPERATING INSTRUCTIONS FOR ALL ELECTRICAL SYSTEM EQUIPMENT. OPERATING INSTRUCTIONS SHALL ALSO INCLUDE RECOMMENDED MAINTENANCE PROCEDURES 5. TEST REPORTS REQUIRED BY THESE SPECIFICATIONS 6. ANY AND ALL OTHER DATA AND /OR DRAWINGS REQUIRED DURING CONSTRUCTION. 7. REPAIR PARTS LISTS OF ALL MAJOR ITEMS OF EQUIPMENT INCLUDING NAME, ADDRESS AND TELEPHONE NUMBERS OF LOCAL SUPPLIER OR AGENT. P. ALL OF THE ABOVE DATA SHALL BE SUBMITTED TO THE ENGINEER FOR HIS REVIEW AT SUCH TIME AS THE CONTRACTOR SUBMITS HIS LAST ESTIMATE PRIOR TO HIS FINAL PAYMENT, BUT IN NO CASE, LESS THAN TWO WEEKS BEFORE FINAL INSPECTION. 16020 - ELECTRICAL WORK IN EXISTING FACILITIES A. THE CONTRACT DOCUMENTS DO NOT PROPOSE TO SHOW ALL EXISTING SYSTEMS MATERIAL OR EQUIPMENT. OBTAIN INFORMATION RELATED TO EXISTING FACILITIES FROM E)aSTING DOCUMENTS, MEASUREMENTS, NOTATIONS, PHOTOGRAPHS, SURVEYS, AND OTHER OBSERVATIONS AT THE SITE. B. SINCE THE BUILDING WILL CONTINUE IN USE THROUGHOUT THE CONSTRUCTION PERIOD, CARRY OUT THE WORK UNDER THIS DIVISION IN SUCH A MANNER AS TO MINIMIZE DISTURBANCE TO THE OCCUPANTS. C. REMOVE EXISTING WIRE, CONDUIT, EQUIPMENT, FIXTURES AND OTHER ITEMS TO PROVIDE ACCESS FOR WORK IN EXISTING FACILITIES. REINSTALL AND REFINISH ITEMS REMOVED, OR OTHERWISE DAMAGED, TO MATCH E)aSTING ADJACENT SURFACED UPON COMPLETION OF THE WORK. D. WHERE EXISTING FUNCTIONS TO REMAIN IN USE ARE DISRUPTED, THEY SHALL BE FULLY RESTORED AFTER DISRUPTION, IN FULL COMPLIANCE WITH THIS DIVISION OF THE SPECIFICATIONS FOR NEW WORK E MODIFY, REMOVE OR RELOCATE MATERIALS AND ITEMS INDICATED ON THE DRAWINGS OR REQUIRED BY THE INSTALLATION OF NEW WORK. F. WORKING JOINTLY WITH THE ARCHITECT, ESTABLISH AND MARK SALVAGE AND DEMOLITION ITEMS BEFORE COMMENCING WORK; REPORT ITEMS SCHEDULE FOR RELOCATION, REINSTALLATION OR REUSE, WHICH ARE FOUND TO BE IN DAMAGED CONDITION; AWAIT FURTHER INSTRUCTIONS FROM THE ARCHITECT BEFORE COMMENCING WITH WORK. G. DEMOLITION EQUIPMENT, DEVICES AND MATERIAL SHALL BE REMOVED FROM THE SITE AND DISPOSED OF BY THE CONTRACTOR SALVAGED EQUIPMENT AND DEVICES SHALL BE THE PROPERTY OF THE OWNER UNLESS NOTED OTHERWISE. H. MAKE MINOR RELOCATIONS NECESSITATED BY THE CONDITIONS AT THE SITE OR AS DIRECTED BY THE ARCHITECT, WITHOUT ADDITIONAL COST TO THE OWNER REPAIR AND RESTORE TO GOOD FUNCTIONAL CONDITION. EQUIPMENT, MATERIALS AND ITEMS SCHEDULED FOR RELOCATION, WHICH ARE DAMAGED DURING DISMANTLING OR REASSEMBLY OPERATIONS NEW MATERIALS AND ITEMS OF SIMILAR DESIGN AND QUALITY MAY BE SUBSTITUTED FOR MATERIALS AND ITEMS INDICATED TO BE RELOCATED UPON APPROVAL OF SHOP DRAWINGS, PRODUCT DATA AND SAMPLES REMOVE CAREFULLY, IN REVERSE ORDER TO ORIGINAL ASSEMBLY OR PLACEMENT, ITEMS WHICH ARE TO BE RELOCATED. PROTECT ITEMS UNTIL RELOCATION IS COMPLETE. CLEAN AND REPAIR ITEMS TO BE RELOCATED, AND PROVIDE NEW MATERIALS, FITTINGS AND APPURTENANCES REQUIRED TO COMPLETE THE RELOCATIONS AND TO RESTORE TO GOOD OPERATING ORDER. PERFORM THE RELOCATION WORK IN ACCORDANCE WITH APPLICABLE PORTIONS OF THESE SPECIFICATIONS, UTILIZING SKILLED WORKERS I. RELOCATING DEVICES: REMOVE AND REINSTALL IN LOCATIONS DESIGNATED BY THE ARCHITECT TEMPERATURE CONTROL SYSTEM DEVICES, RELAYS, WIRE. CONDUIT, FIXTURES, EQUIPMENT AND OTHER DEVICES REQUIRED FOR THE OPERATION OF THE VARIOUS SYSTEMS THAT ARE INSTALLED IN EXISTING- TO-BE- REMOVED CONSTRUCTION. 16084 - THROUGH- PENETRATION FIRESTOPPING FOR ELECTRICAL SYSTEMS A. ONLY TESTED FIRESTOP SYSTEMS SHALL BE USED IN SPECIFIC LOCATIONS AS FOLLOWS: 1. PENETRATIONS FOR THE PASSAGE OF CONDUIT AND OTHER ELECTRICAL EQUIPMENT THROUGH FIRE -RATED VERTICAL BARRIERS (WALLS AND PARTITIONS), HORIZONTAL BARRIERS (FLOOR /CEILING ASSEMBLIES), AND VERTICAL SERVICE SHAFT WALLS AND PARTITIONS 2. COMPLETION OF FIRESTOP INSTALLATIONS TO MAINTAIN THE RATING INTEGRITY OF THE BARRIER PENETRATED. B. INSTALLER SHALL CONSULT THE STRUCTURAL ENGINEER PRIOR TO PENETRATING ANY LOAD BEARING ASSEMBLY. C. ACCEPTABLE MANUFACTURERS: HILTI INC., TREMCO SEALANTS & COATINGS, 3M FIRE PROTECTION PRODUCTS, JOHN- MANVILLE FIRETEMP, OR OTHER MANUFACTURERS LISTED IN THE U.L FIRE RESISTANCE DIRECTORY - VOLUME 2. D. CONTRACTOR IS RESPONSIBLE FOR PROVIDING FIRESTOPPING BARRIER AT ALL ELECTRICAL BOXES (EXISTING AND NEW) AND PENETRATIONS FOR ANY EXISTING FIRE WALLS IN THE SCOPE OF WORK AREA AND /OR FOR ANY NEW FIRE WALLS FOR NEW FIRE WALLS IN WHICH ONE SIDE OF THE WALL FALLS OUTSIDE OF THE SCOPE OF WORK AREA AND OTHER DOES NOT, CONTRACTOR SHALL PROVIDE FIRSTOPPING BARRIER FOR ALL PENETRATIONS AND ELECTRICAL BOXES ON THE WALL SIDE NOT IN THE SCOPE OF WORK AREA. 16110 - SYSTEMS OF RACEWAYS A. CONDUIT 1. RIGID STEEL CONDUIT (GRC - GALVANIZED RIGID CONDUIT): CONSTRUCTED OF MILD STEEL PIPING, GALVANIZED INSIDE AND OUTSIDE, CONFORMING WITH FED. SPEC. WW- C -581E. ANSI C80.1 AND UL 6. 2. INTERMEDIATE METAL CONDUIT (IMC): CONSTRUCTED OF ZINC COATED STEEL TUBING MANUFACTURED IN ACCORDANCE WITH FED. SPEC. WW-C- 581 -E, UL -1242 AND MEETING THE REQUIREMENTS OF THE NEC. 3. ELECTRIC METALLIC TUBING (EMT): CONSTRUCTED OF HIGH GRADE STEEL MANUFACTURED SPECIFICALLY TO STANDARDS ASSURING MAXIMUM WELDING CHARACTERISTICS AND DUCTILITY, AND SHALL CONFORM TO FED. SPEC. MV-C- 563 -A. ANSI C80-3, AND UL 797. 4. LIQUIDTIGHT FLEMBLE CONDUIT: FLEXIBLE METAL CONDUIT AS SPECIFIED HEREIN WITH A COPPER GROUNDING STRAND AND FACTORY - APPLIED NEOPRENE JACKET. LIQUID TIGHT FLEXIBLE CONDUIT SHALL BE UL LISTED, EQUIVALENT TO ANACONDA 'SEALTITE', TYPE UA. 5. INSTALLATION OF BUILDING CONDUIT a. ALL INTERIOR RACEWAYS SHALL BE EMT. RACEWAYS IN DAMP OR WET LOCATIONS, OR IN HAZARDOUS LOCATIONS, SHALL BE GRC OR IMC. b. CONDUITS SHALL BE OF SUCH SIZE AND SO INSTALLED THAT THE CONDUCTORS MAY BE DRAWN THROUGH WITHOUT INJURY OR EXCESSIVE STRAIN, SHALL BE SECURED AT CABINETS AND BOXES WITH GALVANIZED LOCKNUTS, BOTH INSIDE AND OUTSIDE, AND SHALL HAVE APPROPRIATE BUSHINGS INSIDE BUSHINGS SHALL BE INSULATING TYPE WITH BOND GROUND CLAMPS a USE LENGTHS OF FLEXIBLE METAL CONDUIT NOT LESS THAN 12 INCHES LONG AT FINAL CONNECTIONS TO ALL MOTORS, TRANSFORMERS AND SIMILAR DEVICES SUBJECT TO MOVEMENT BECAUSE OF VIBRATION OR MECHANICAL ADJUSTMENT. USE FLEXIBLE METAL CONDUITS TO EFFECT FINAL CONNECTIONS TO RECESSED LIGHTING FIXTURES (6FT MAX). USE LIQUID TIGHT FLEXIBLE METAL CONDUIT, WITH APPROPRIATE CONNECTIONS, IN DAMP OR WET LOCATIONS, AT MOTOR OR EQUIPMENT LOCATIONS IN MECHANICAL EQUIPMENT ROOMS, AT OR NEAR PUMPS, AND WHEN INSTALLED OUTDOORS d. GROUND METALLIC CONDUITS AS REQUIRED BY NEC. e. INSTALL RACEWAYS CONTINUOUS FROM OUTLET TO OUTLET BOX, OR CABINET, WITH A MAXIMUM OF 150 FEET BETWEEN PULLS IN AREAS WHERE THERE ARE NO SUSPENDED CEILINGS, RUN ALL CONDUITS PARALLEL/PERPENDICULAR TO BUILDING SURFACE f IN SYSTEMS OPERATING AT MORE THAN 300 VOLTS BETWEEN PHASE CONDUCTORS, AND WHERE DIFFERENT PHASE CONDUCTORS ARE TO BE RUN TO A COMMON GANG WALL SWITCH BOX, PROVIDE SUBSTANTIAL BARRIERS BETWEEN ADJACENT SWITCHES IN THE BOX SO THAT TWO DIFFERENT PHASE WIRES WILL NOT BE IN THE SAME COMPARTMENT. 9. WHEREVER RACEWAYS PASS THROUGH FLOORS, WALLS, PENETRATIONS, OR OTHER PARTITIONS, CAREFULLY FILL ANY SPACE BETWEEN THE OUTSIDE OF THE RACEWAY AND THE BUILDING MATERIAL TO PREVENT PASSAGE OF AIR, WATER, SMOKE, AND FUMES FILLING MATERIAL SHALL BE A UL LISTED, INTUMESCENT SEALING HAVING FIRE /SMOKE RESISTIVE RATING EQUAL TO THE BUILDING MATERIAL PENETRATED. h. CONDUITS UTILIZED THROUGHOUT THE PROJECT SHALL NOT BE SMALLER THAN 3/4 INCH FOR FEEDERS, MULTIPLE BRANCH CIRCUIT HOMERUNS AND HOMERUNS OF CONDUCTORS LARGER THAN NO. 12. INDIVIDUAL BRANCH CIRCUIT WIRING FOR NO. 12 CONDUCTORS SHALL BE ACCEPTABLE IN 314' CONDUIT, I.E. 2#12, 1#12% 314'C. B. COUPLINGS AND TERMINATORS 1. FOR RIGID STEEL OR INTERMEDIATE METAL CONDUIT. FACTORY -MADE THREADED COUPLINGS OF SAME MATERIAL AS THE CONDUIT. 2. FOR ELECTRICAL METALLIC TUBING, USE STEEL COMPRESSION COUPLINGS AND NYLON INSULATED GROUNDING BUSHINGS 3. FOR FLEXIBLE METAL CONDUIT. COUPLINGS AT CONNECTIONS BETWEEN FLEXIBLE CONDUIT AND EMT, AND NYLON INSULATED THROAT STEEL CONNECTORS AT BOX OR CABINET TERMINATIONS 4. SCREW COUPLINGS; STEEL SET SCREW BOX CONNECTORS NTH NYLON INSULATED THROAT AND LOCKNUTS AT ALL BOXES AND CABINET TERMINATIONS OR NON - INSULATED BOX CONNECTOR, LOCKNUT AND NYLON- INSULATED GROUNDING BUSHING ON ALL TUBING WHERE GROUNDING BUSHINGS ARE REQUIRED. C. JUNCTION AND PULL BOXES 1. SIZE BOXES IN ACCORDANCE WITH THE REQUIREMENTS OF THE NEC. BOXES SHALL BE UL LISTED AND NO SMALLER THAN 4 INCHES SQUARE BY 1 -1/2 INCHES DEEP WITH COVERS ACCESSIBLE AT ALL TIMES. SET BOXES ON CONCEALED CONDUITS WITH COVERS FLUSH WITH THE FINISHED WALL OR CEILING LINE. PROVIDE JUNCTION AND PULL BOXES OF APPROPRIATE DIMENSIONS FOR CONDUITS AND CONDUCTORS NOTED, WHERE SHOWN AND WHERE NECESSARY FOR THE INSTALLATION AND PULLING OF CABLES AND WIRES INSTALL COVERS ON JUNCTION BOXES AND CONDULETS AFTER WIRING AND CONNECTIONS ARE COMPLETED. 2. ALL JUNCTION AND PULL BOXES FOR EMERGENCY SYSTEMS AND LOW VOLTAGE SYSTEMS SHALL HAVE COVER PLATES PAINTED. COLORS FOR COVERS SHALL BE YELLOW (LIFE SAFETY BRANCH), ORANGE (CRITICAL BRAMCH), GREEN (EQUIPMENT SYSTEM), RED (FIRE ALARM). AND BROWN (DATA/TELEPHONE). 3. INSTALLATION OF PULL AND JUNCTION BOXES CL FASTEN ALL BOXES SECURELY TO THE BUILDING CONSTRUCTION, INDEPENDENT OF CONDUIT SYSTEMS. b. ON CONCEALED CONDUIT SYSTEMS WHERE BOXES ARE NOT OTHERWISE ACCESSIBLE. SET BOXES FLUSH WITH FINISHED SURFACES FOR ACCESS, AND PROVIDE OVERLAPPING COVERS C. ALL WIRING DEVICES FAMEPLATES SHALL BE ENGRAVED WITH THE PANELBOARD DESIGNATION AND CIRCUIT NUMBER SERVING THE OUTLET. LABEL TAPE WILL NOT BE ACCEPTABLE. D. OUTLET BOXES 1. OUTLET BOXES SHALL BE UL LISTED, AND OF SIZES AND TYPES REQUIRED FOR THE APPLICATION. OUTLET BOXES SHALL BE SHEET STEEL, NO LIGHTER THAN 14 GAUGE, GALVANIZED AFTER FABRICATION. SET BOX SO FACE OF BOX WILL FINISH FLUSH WITH BUILDING SURFACE. CL FOR LIGHTING FIXTURE OUTLETS: 4 INCH SQUARE BY 1- 1/2 INCHES DEEP WITH RAISED FIXTURE RING. b. FOR WALL SWITCHES, RECEPTACLES, AND COMMUNICATION USE 4 INCH SQUARE, BY 1 -1/2 INCHES DEEP. USE BOXES WITH PLASTER RINGS IN ALL PLASTERED WALLS WHERE WALL THICKNESS PERMITS USE BOXES LESS THAN 1 -1/2 . INCH DEEP ONLY IN LOCATIONS WHERE DEEP BOXES CANNOT BE ACCOMMODATED BY CONSTRUCTION. 16120 - SYSTEM OF CONDUCTORS A CONDUCTORS SHALL BE 98X CONDUCTIVITY SOFT DRAWN ANNEALED COPPER, 600 VOLT, THHN/THWN INSULATION, #10 AND SMALLER - SOLID, #8 AND LARGER - STRANDED. B. NO CONDUCTORS SHALL BE SMALLER THAN NO. 12, EXCEPT FOR SIGNAL OR CONTROL CIRCUITS AND FOR INDIVIDUAL LIGHTING FIXTURE TAPS AS PERMITTED BY NEC. C. FOR HOME RUNS ON 120 -VOLT, 20- AMPERE BRANCH CIRCUITS, WHERE LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 100 LINEAR FEET, USE No. 10 CONDUCTORS WHERE LENGTH OF RUN IS 100 LINEAR FEET OR LESS, USE NO. 12 CONDUCTORS D. FOR HOME RUNS ON 277 -VOLT, 20- AMPERE BRANCH CIRCUITS, WHERE LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 200 LINEAR FEET, USE NO. 10 CONDUCTORS WHERE LENGTH OF RUN IS 100 LINEAR FEET OR LESS, USE NO. 12 CONDUCTORS E RUN DEDICATED NEUTRAL CONDUCTOR WITH EACH BRANCH CIRCUIT. SHARING OF NEUTRAL CONDUCTORS WOULD NECESSITATE THE USE OF MULTIPLE POLE OR TIED CIRCUIT BREAKERS TO ALLOW SIMULTANEOUS DISCONNECTING OF CURRENT CARRYING CONDUCTORS IN ORDER TO COMPLY WITH NFPA 70 REQUIREMENTS AND THEREFORE IS F. YUNRPM CODED CABLE SYSTEM APPROVED BY OWNER IF NONE IS REQUIRED BY OWNER, PROVIDE THE FOLLOWING COLOR CODING: a. 48OV/277 b. 208V/120 A PHASE - BROWN A PHASE - BLACK B PHASE - ORANGE B PHASE - RED C PHASE - YELLOW C PHASE - BLUE NEUTRAL - GREY NEUTRAL - WHITE GROUND - GREEN GROUND - GREEN COLOR CODING SHALL BE CONTINUOUS ON INSULATION FOR 06 AWG OR SMALLER AND CONTINUOUS OR MARKED WITH COLOR TAPE AT ALL CONNECTIONS FOR CONDUCTORS LARGER THAN #6 AWG. G. INSTALLATION OF CONDUCTORS 1. PULL NO CONDUCTORS INTO CONDUITS UNTIL ALL WORK OF A NATURE WHICH MAY CAUSE INJURY TO CONDUCTORS IS COMPLETED. 2. RUN FEEDERS IN CONTINUOUS LENGTHS, WITHOUT JOINTS OR SPLICES, INSOFAR AS PRACTICABLE 3. RUN CONDUITS FOR EMERGENCY POWER CONDUCTORS SEPARATE FROM ALL OTHER WIRING. 4. CABLE TYPE AC OR MC IS NOT ALLOWED FOR HOMERUN AND FEEDER INSTALLATIONS. 16140 - WIRING DEVICES A. ALL WIRING DEVICES SHALL BE UL LISTED. B. ACCEPTABLE MANUFACTURERS PASS do SEYMOUR, HUBBEL, LEVITON, AND COOPER C. RECEPTACLES 1. RECEPTACLES SHALL BE HOSPITAL GRADE STANDARD STYLE THEY SHALL 20A, 125V, 2 -POLE, 3- WIIIfE. NEMA 5-208 CONFIGURATION, BACK AND WIRED IMTH A GREEN EQUIPMENT GROUND SCREW OR AN AUTOMATIC GROUNDING SYSTEM ATTACHED TO THE STRAP U.N.O. 2. GFCI RECEPTACLES SHALL BE A FEED THROUGH TYPE WIRED FOR SINGLE RECEPTACLE PROTECTION THUS NOT AFFECTING RECEPTACLES DOWNSTREAM ON THE SAME CIRCUIT. THEY SHALL BE UL RATED CLASS 1 WITH 5mA GROUND FAULT TRIP LEVEL AND A 20A FEED- THROUGH RATING AND HAVE A NEMA 5-20R CONFIGURATION. 3. RECEPTACLE COLOR SHALL BE IVORY. THEY SHALL BE RED WHEN CONNECTED TO AN EMERGENCY CIRCUIT. 4. PEDIATRIC LOCATIONS - ALL RECEPTACLES LOCATED IN PATIENT CARE AREAS SHALL BE LISTED TAMPER RESISITANT. D. SWITCHES I. SWITCHES SHALL BE SPECIFICATION GRADE, 20A. 120/277V, HORSEPOWER RATED, BACK AND SIDE WIRED. SWITCHES SHALL INCLUDE A GREEN GROUND SCREW ATTACHED TO THE MOUNTING STRAP. 2. WHERE LIGHTING CIRCUITS ARE SHOWN TO BE LINE VOLTAGE SWITCHED, PROVIDE WITH SPECIFICATION GRADE, HORSEPOWER RATED, UL LISTED, BACK - AND SIDE - WIRED, TOGGLE SWITCHES RATED 20A, 120V OR 277 VOLTS. SWITCHES SHALL BE SPST, DPST, 3-WAY OR 4-WAY, WITH OR WITHOUT PILOT LIGHT AS INDICATED ON THE DRAWINGS 3. SWITCH COLOR SHALL BE IVORY OR RED WHEN CONNECTED TO AN EMERGENCY CIRCUIT. E WALL PLATES 1. WALL PLATES SHALL BE PROVIDED FOR ALL SWITCHES, RECEPTACLES, BLANKS, TELEPHONE/1DATA, AND SPECIAL PURPOSE OUTLETS. THE WALL PLATES SHALL BE OF SUITABLE CONFIGURATION FOR THE DEVICE FOR WHICH IT IS TO COVER WITH COLOR MATCHING MOUNTING SCREWS. COLOR OF THE WALL PLATES SHALL MATCH THE DEVICE, U.N.O. 2. WALL PLATES SHALL BE THERMOPLASTIC, NON - COMBUSTIBLE, AND HIGH - IMPACT RESISTANT. THEY SHALL BE P-LINE SMOOTH PLATES. THEY SHALL BE OF THE SAME MANUFACTURER AS THE WIRING DEVICE IT IS TO COVER 3. WEATHERPROOF: WIRING DEVICE IN WET LOCATIONS SHALL BE INSTALLED WITH A HINGED OUTLET COVER/ENCLOSURE CLEARLY MARKED 'SUITABLE FOR WET LOCATIONS WHILE IN USE' AND 'UL LISTED'. THERE SHALL BE A GASKET BETWEEN THE COVER/ENCLOSURE AND THE MOUNTING SURFACE. AND BETWEEN THE HINGED COVER AND MOUNTING PLATE/BASE TO ASSURE PROPER SEAL THE COVER/ENCLOSURE SHALL BE SPECIFICATION GRADE AS MANUFACTURED BY TAYMAC CORPORATION OR EQUAL F. INSTALLATION OF TIRING DEVICES 1. EACH WIRING DEVICE SHALL BE MOUNTED IN A METALLIC OUTLET BOX. IN GENERAL, DEVICES IN FINISHED SPACES SHALL BE FLUSH MOUNTED DEVICES AND DEVICES IN UNFINISHED SPACES SUCH AS ELECTRICAL AND MECHANICAL ROOMS SHALL BE SURFACE MOUNTED. VERIFY THE REQUIREMENTS OF ALL SPACES WITH ARCHITECT. 2. MOUNT RECEPTACLES A.F.F. TO THE DEVICE CENTERLINE, U.N.O. MOUNT SWITCHES A.F.F. TO THE DEVICE CENTERLINE AND 6' FROM A DOOR STRIKE, U.N.O. 3, MAINTAIN GROUNDING CONTINUITY BETWEEN DEVICES AND METALLIC RACEWAY SYSTEM IN ADDITION TO PROVIDING A GREEN EQUIPMENT GROUNDING CONDUCTOR RUN WITH ALL CIRCUIT CONDUCTORS AS INDICATED ON THE DRAWINGS. 4. MOUNT RECEPTACLES THROUGHOUT THE PROJECT WITH GROUND POLE AT THE TOP OF THE CONFIGURATION WHEN MOUNTED VERTICALLY AND ON THE RIGHT WHEN MOUNTED HORIZONTALLY. 5. ALL EXTERIOR RECEPTACLES SHALL BE GFCI WITH A WEATHERPROOF COVER/ENCLOSURE 16160 - CABINETS AND ENCLOSURES A. CABINETS SHALL BE GALVANIZED STEEL WITH GRAY BAKED ENAMEL FINISH AND SHALL BE SIZED AS REQUIRED OR INDICATED. FRONTS SHALL BE STEEL, FLUSH OR SURFACE TYPE INDICATED WITH CONCEALED HINGE, AND FLUSH LOCK KEYED TO MATCH BRANCH CIRCUIT PANELBOARD. FINISH WITH GRAY BAKED ENAMEL B. ENCLOSURES SHALL BE NEMA 250, TYPE 1 OR 3R. AS INDICATED ON DRAWINGS THEY SHALL HAVE CONTINUOS HINGED COVERS. PROVIDE INTERIOR METAL PANEL FOR MOUNTING TERMINAL BLOCKS AND ELECTRICAL COMPONENTS; FINISH WITH WHITE ENAMEL. ENCLOSURE FINISH SHALL BE MANUFACTURER'S STANDARD ENAMEL 16190 - SUPPORTING DEVICES A. ACCEPTABLE MANUFACTURERS: UNISTRUT CORP., B-LINE SYSTEMS, INC., AND MIDLAND ROSS- KNDORF. B. FURNISH AND INSTALL ALL HANGERS AND SUPPORTS REQUIRED BY RACEWAY SYSTEMS C. HANGERS SHALL BE SUPPORTED BY MEANS OF UNCOATED SOLID STEEL RODS WHICH ARE THREADED TO ALLOW VERTICAL ADJUSTMENTS LOCK NUTS SHALL BE PROVIDED IN SUFFICIENT NUMBER AND LOCATION TO LOCK ALL ROD ADJUSTMENTS PERMANENTLY AT THE ADJUSTED HEIGHT. TWO LOCH( NUTS SHALL BE USED UNLESS THE NUT TIGHTENS AGAINST A THREADED SOCKET. MINIMUM ROD DIAMETERS SHALL BE AS FOLLOWS: NOMINAL CONDUIT SIZE ROD DIAMETER 1/2' THROUGH 2' 1/4' 2 -1/2' THROUGH 3' 3/8' 4' AND 5' 1/2' D. HANGER SPACING SHALL BE AS REQUIRED FOR PROPER SUPPORT OF RACEWAY, BUT IN NO CASE SHALL BE LESS THAN ONE HANGER PER 8' -0' OF RACEWAY LENGTH EXCEPT THAT CONDUIT LESS THAN 1' DIAMETER SHALL BE SUPPORTED AT LEAST EVERY 6' -0'. E WHERE NUMEROUS CONDUITS ARE RUN PARALLEL TO ONE ANOTHER, THEY MAY BE SUPPORTED FROM A TRAPEZE TYPE HANGER ARRANGEMENT WITH STRUT BOTTOM. F. SUPPORT OF HANGERS SHALL BE BY MEANS OF SUFFICIENT QUANTITIES OF INDIVIDUAL AFTER SET STEEL EXPANSION SHIELDS, OR BEAM CLAMPS ATTACHED TO STRUCTURAL STEEL G. STIFF -LEGS SHALL BE FURNISHED AND INSTALLED IN CASES WHERE SUPPORT FROM OVERHEAD STRUCTURE IS NOT POSSIBLE H. CEILING MOUNTED LIGHT FIXTURES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AT TWO OPPOSITE CORNERS THE CONTRACTOR SHALL PROVIDE FIXTURE HANGERS TO PROPERLY INTERFACE WITH THE CEILING SYSTEM. I. FURNISH AND INSTALL COMPLETE ANY ADDITIONAL STRUCTURAL SUPPORT STEEL, BRACKETS. FASTENERS, ETC. AS REQUIRED TO ADEQUATELY SUPPORT ALL RACEWAY AND EQUIPMENT. J. SUPPORT OF HANGERS FROM CONCRETE SLABS SHALL BE BY MEANS OF SUFFICIENT QUANTITY OF 'U' BRACKETS ATTACHED WITH AFTER SET EXPANSION SHIELDS AND BOLTS 16195 - ELECTRICAL IDENTIFICATION A. PROVIDE ELECTRICAL IDENTIFICATION FOR THE FOLLOWING: 1. SWITCHGEARS, SWITCHBOARDS, MOTOR CONTROL CENTERS, PANELBOARDS, MOTOR STARTERS, CONTACTORS, DISCONNECT SWITCHES, CIRCUIT BREAKERS, AND OTHER ELECTRICAL EQUIPMENT WITH NAMEPLATE IDENTIFYING THE ITEM OF EQUIPMENT SERVING THE SAME 2. RACEWAYS, JUNCTION BOXES, AND PULL BOXES 3. WIRING DEVICES, WRING, AND THREE PHASE MOTOR ROTATION. B. PROVIDE THE FOLLOWING COLOR CODING FOR ALL EQUIPMENT NAMEPLATES: NORMAL SYSTEM - BLACK W/ WHITE LETTERS CRITICAL BRANCH - RED W/ WHITE LETTERS LIFE SAFETY BRANCH - YELLOW W/ WHITE LETTERS EQUIPMENT SYSTEM - GREEN W/ WHITE LETTERS C. ALL NAMEPLATES SHALL INCLUDE VOLTAGE, PHASE. WIRE, BRANCH OF POWER CONNECTED TO, AND SOURCE OF POWER EQUIPMENT IS FED FROM. NAMEPLATES SHALL BE LAMINATED, WHITE CORE, PLASTIC WITH BEVELED EDGES, MINIMUM 1/16' THICK. LETTERING SHALL BE MACHINE ENGRAVED, NOT LESS THAN 1/4' HIGH, CUT THROUGH THE SURFACE TO THE WHITE CORE NAMEPLATES SHALL BE SECURELY ATTACHED TO THE EQUIPMENT USING GALVANIZED SCREWS. ADHESIVES SHALL NOT BE USED. D. ALL NAMEPLATES SHALL INCLUDE VOLTAGE. PHASE, WIRE, BRANCH OF POWER CONNECTED TO, AND SOURCE OF POWER EQUIPMENT IS FED FROM. NAMEPLATES SHALL BE LAMINATED, WHITE CORE, PLASTIC WITH BEVELED EDGES, MINIMUM 1/16' THICK LETTERING SHALL BE MACHINE ENGRAVED, NOT LESS THAN 1/4' HIGH, CUT THROUGH THE SURFACE TO THE WHITE CORE NAMEPLATES SHALL BE SECURELY ATTACHED TO THE EQUIPMENT USING GALVANIZED SCREWS. ADHESIVES SHALL NOT BE USED. !E E IDENTIFICATION OF JUNCTION AND PULL BOXES SHALL BE WITH A BLACK SIDE PERMANENT MARKING PEN ON THE TOP OF THE 4' X 4' JUNCTION BOX COVER OR ON THE BACK OF THE OUTLET BOX COVER PLATE IDENTIFYING THE BRANCH CIRCUITS AND SYSTEMS WITHIN THE CONDUIT. PULL BOXES SHALL BE PROVIDED WITH A NAMEPLATE STATING VOLTAGE AND SYSTEM SERVED. F. ON THE FACE OF THE WIRING DEVICE WALL PLATE, MACHINE ENGRAVE THERMOPLASTIC PLATES WITH THE PANELBOARD AND BRANCH CIRCUIT NUMBER THE DEVICE IS SERVED FROM. ADHESIVE LABELS ARE NOT ALLOWED. G. RACEWAY IDENTIFICAIINN SHALL BE PROVIDED AT A MINIMUM OF EVERY 50'. AT EACH END IF LESS THAN 50', AND A MINIMUM OF ONCE PER ROOM OR SPACE THROUGH WHICH IT PASSES. H. CONDUIT, RACEWAYS AND BOXES SHALL BE SPOT PAINTED. CONDUIT SHALL BE IDENTIFIED WITHIN 6 INCHES OF THE BOX OR ENCLOSURE THE ENTIRE BOX AND COVERPLATE SHALL BE PAINTED. USE THE FOLLOWING COLOR CODING SCHEME- NORMAL SYSTEM - WHITE FIRE ALARM - RED CRITICAL BRANCH - BRIGHT ORANGE COMMUNICATIONS -BROWN LIFE SAFETY BRANCH - BRIGHT YELLOW TELEPHONE /COMPUTER - BLACK EQUIPMENT SYSTEM - KELLY GREEN NURSE CALL - ROYAL BLUE TV - LIGHT PINK IN EVENT THAT THERE IS A DISCREPANCY BETWEEN THESE COLORS AND THE FACILITY STANDARD. CONTRACTOR SHALL SUBMIT AN RFI REQUESTING CLARIFICATION. 16440 - DISCONNECT SWITCHES A. ACCEPTABLE MANUFACTURERS: CUTLER HAMMER, GENERAL ELECTRIC, OR SQUARE D. B. SWITCHES SHALL BE HEAVY DUTY TYPE AND UL LISTED.. C. SWITCHES SHALL HAVE SWITCHBLADES WHICH ARE VISIBLE WHEN THE SWITCH IS OFF AND THE COVER IS OPEN. D. LUGS SHALL BE FRONT REMOVABLE AND UL LISTED 60 OR 75 DEGREES C FOR CONDUCTOR 30 -100A, AND 75 DEGREES C CONDUCTORS 200A AND UP. E. SWITCH OPERATING MECHANISM SHALL BE WICK -BREAK SUCH THAT, DURING NORMAL OPERATION OF THE SWITCH, THE OPERATION OF THE CONTACTS SHALL NOT BE CAPABLE OF BEING RESTRAINED BY THE OPERATING HANDLE AFTER THE CLOSING OR OPENING ACTION OF THE CONTACTS HAS STARTED. F. THE OPERATING HANDLE SHALL BE AN INTEGRAL PART OF THE BOX, NOT THE COVER. G. SWITCHES SHALL HAVE A DUAL COVER INTERLOCK MECHANISM TO PREVENT UNINTENTIONAL OPENING OF THE SWITCH COVER WHEN THE SWITCH IS ON AND PREVENT TURNING THE SWITCH ON WHEN THE COVER IS OPEN. THE COVER INTERLOCK MECHANISM SHALL HAVE AN EXTERNALLY OPERATED OVERRIDE BUT THE OVERRODE SHALL NOT PERMANENTLY DISABLE THE INTERLOCK MECHANISM. THE TOOL USED TO OVERRIDE THE COVER INTERLOCK MECHANISM SHALL NOT BE REQUIRED TO ENTER THE ENCLOSURE IN ORDER TO OVERRIDE THE INTERLOCK. H. SWITCH COVERS SHALL BE ATTACHED WITH WELDED PIN -TYPE HINGES (SECURABLE IN)THEE OPPEENHIPO�TION (TAYPPEED 3R) WITH REMOVABLE SCREWS AND I. THE ENCLOSURE SHALL HAVE ON AND OFF MARKINGS STAMPED TO THE COVER. J. SWITCHES SHALL HAVE PROVISIONS TO ACCEPT UP TO 318' HASP PADLOCKS TO LOCK THE HANDLE IN THE OFF POSITION. K TANGENTIAL KNOCKOUTS SHALL BE PROVIDED TO FACILITATE EASE OF CONDUIT ENTRY (NEMA TYPE 1). TYPE 3R ENCLOSURE SHALL CONTAIN NO KNOCKOUTS. SUPPLY WATERTIGHT HUBS L SWITCHES SHALL BE HORSEPOWER RATED. M. INSTALL FUSES IN FUSIBLE DISCONNECT SWITCHES AS INDICATED OR AS REQUIRED BY MANUFACTURER OF EQUIPMENT THAT THE SWITCH IS SERVING. N. FUSIBLE SWITCHES: FOR 600 AMPERE AND SMALLER SWITCHES, PROVIDE UL LISTED REJECTION CLIPS TO REJECT ALL FUSES EXCEPT O ASS R; FOR 800 AMPERE AND LARGER SWITCHES, PROVIDE FUSE CLIPS FOR CLASS L FUSES ALL SWITCHES UL LISTED SHORT CIRCUIT RATING OF 200.00 AMPERES RMS SYMMETRICAL 0. ENCLOSED CIRCUIT BREAKER ENCLOSURES: NEMA 1 OR NEMA 31? AS INDICATED ON THE DRAWINGS NEMA 1 ENCLOSURES: FURNISHED WITH KNOCKOUTS WHERE PRACTICAL; FABRICATED FROM SHEET STEEL, GALVANIZED AFTER FORMING; ELECTRODEPOSITED, GRAY BAKED ENAMEL FINISH. PROVIDE PADLOCKING PROVISIONS TO ALLOW LOCKING THE CIRCUIT BREAKER IN THE 'OFF' POSITION. NEMA 31R ENCLOSURES FOR CIRCUIT BREAKERS RATED THRU THE 225 AMPERE FRAME SIZE FURNISHED WITH PROVISIONS FOR INTERCHANGEABLE. BOLT -ON HUBS NEMA 3R ENCLOSURE COVERS SECURABLE IN THE OPEN POSITION. PROVIDE PADLOCKING PROVISIONS TO ALLOW LOCKING THE ENCLOSURE COVER CLOSED. P. ALL ENCLOSED CIRCUIT BREAKER, FUSIBLE SWITCHES, AND DISCONNECT SWITCHES INSTALLED OUTSIDE OR IN WET OR DAMP LOCATIONS. SHALL BE IN A NEMA 3R ENCLOSURE 16450 - GROUNDING A. DIM METALLIC PARTS OF THE ELECTRICAL SYSTEM WHICH ARE NOT INTENDED TO CARRY CURRENT, INCLUDING SYSTEM COMPONENTS SUCH AS BUSDUCTS, SWITCHBOARDS, PANELBOARDS AND RACEWAY SYSTEMS, AND INCLUDING GROUNDING AND NEUTRAL CONDUCTORS OF THE VARIOUS TIRING SYSTEMS, SHALL BE GROUNDED IN ACCORDANCE WITH NEC REQUIREMENTS., B. PROVIDE COPPER (LAD STEEL GROUND RODS 3/4 INCH DIAMETER 10 FEET LONG DESIGNED FOR DRIVEN INSTALLATION. C. PROVIDE EXOTHERMIC TYPE CHEMICAL WELDED TYPE CONNECTORS FOR JOINING OF GROUNDING ELECTRODE CONDUCTORS TO GROUND RODS, GROUNDING PLATES AND SPLICING OF CONDUCTORS PROVIDE COMPRESSION AND BOLTED TYPE CONNECTORS FOR JOINING OF GROUNDING ELECTRODE CONDUCTORS TO GROUND BARS D. PROVIDE MECHANICAL TYPE CONNECTORS FOR JOINING OF ALL EQUIPMENT AND ISOLATED GROUND CONDUCTORS E SIZE GROUNDING CONDUCTORS IN ACCORDANCE WITH TABLES 250 -66 AND 250 -122 OF THE NEC. F. PROVIDE GROUNDING BUSHINGS ON ALL RACEWAYS TERMINATING WITHIN ALL ELECTRICAL ENCLOSURES CONSTRUCTED OF SEPARATE ENCLOSURE PANELS WHICH ARE NOT INTEGRALLY WELDED TOGETHER PROVIDE GROUNDING CONDUCTORS FROM SUCH BUSHINGS TO THE FRAME OF THE ENCLOSURE, GROUND BUS AND EQUIPMENT GROUNDING STRAP WHERE ONE OCCURS. G. PROVIDE A SEPARATE GREEN- INSULATED EQUIPMENT GROUNDING CONDUCTOR, WITH INSULATION OF THE SAME RATING AS THE PHASE CONDUCTORS, FOR ALL FEEDERS AND BRANCH CIRCUITS. INSTALL THE GROUNDING CONDUCTORS IN THE RACEWAY WITH RELATED PHASE AND NEUTRAL CONDUCTORS. WHERE PARALLEL CONDUCTORS IN SEPARATE RACEWAYS OCCUR, PROVIDE A GROUNDING CONDUCTOR IN EACH RACEWAY. CONNECT ALL GROUNDING CONDUCTORS TO GROUND TERMINALS AT EACH END OF THE RUN, TO THE END THAT THERE WILL BE NO UNINTERRUPTED GROUNDING CIRCUIT FROM THE POINT OF GROUND FAULT BACK TO A POINT OF CONNECTION OF THE EQUIPMENT GROUND AND SYSTEM NEUTRAL H. CONNECT THE SECONDARY NEUTRAL POINT AND THE ENCLOSURE IN EACH DRY TYPE TRANSFORMER TOGETHER AND RUN A GROUNDING ELECTRODE CONDUCTOR FROM THEIR COMMON POINT OF CONNECTION TO THE BUILDING GROUNDING ELECTRODE SYSTEM. I. PERFORM THE FOLLOWING TESTS: 1. TEST THE CONTINUITY OF, AND THE PROPER CONNECTION OF, EACH GROUND CONDUCTOR AND SYSTEM. TO ASSURE THAT THE GROUNDING SYSTEM IS COMPLETE AND UNINTERRUPTED. TESTING SHALL BE PERFORMED USING LABORATORY- ACCURACY TEST INSTRUMENTS OF SUITABLE DESIGN FOR THE TESTS TO BE PERFORMED. TEST INSTRUMENTS SHALL BE PROVIDED UNDER DIVISION 16. 2. TEST GROUNDING CONDUCTORS, PHASE CONDUCTORS AND NEUTRAL CONDUCTORS FOR CONTINUITY AND FOR POSSIBLE DAMAGE TO INSULATION. EACH CONDUCTOR SHALL BE TESTED FOR INSULATION FROM GROUND AND FROM OTHER CONDUCTORS. 3. ANY PORTIONS OF THE INSTALLATIONS WHICH FAIL TO PASS THESE TESTS SHALL BE REPLACED, REPAIRED OR OTHERWISE CORRECTED TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE, AND COMPLETELY RETESTED TO SHOW PROPER CONFORMITY. 4 CONTRACTOR IS RESPONSIBLE FOR TESTING THE EFFECTIVENIESS OF THE GROOFING SYSEEN FOR ALL ELSCCTTRICAI. DEVICES N THE SCOPE OF WORK AREA BY VOLTAGE AND IMPEDANCE MFASUMANES AS INDICATED N NFPA 99, 43.3.1.3 & 433,1.4 RESPECTIVELY. THE RESULTS SHALL BE RECORDED WITH A METER THAT HAS BEEN CALIBRATED UM THE LAST 12 MONTHS THE METER AND TYPED OR PRINTED RECORDED RESULTS SHALL BE MADE AVAI AEILE AT TIME OF FINAL INSPECTION. J. THE EQUIPMENT GROUNDING TERMINAL BUSES OF THE NORMAL AND ESSENTIAL BRANCH-CIRCUIT PANELBOARDS SERVING THE SAME INDIVIDUAL PATIENT VICINITY SHALL BE BONDED TOGETHER WITH AN INSULATED CONTINUOUS COPPER CONDUCTOR NOT SMALLER THAN 10 AWG. WHERE TWO OR MORE PANELBOARDS SERVING THE SAME INDIVIDUAL PATIENT VICINITY ARE SERVED FROM SEPARATE TRANSFER SWITCHES ON THE EMERGENCY SYSTEM, THE EQUIPMENT GROUNDING TERMINAL BUSES OF THOSE PANELBOARDS SHALL BE BONDED TOGETHER WITH AN INSULATED CONTINUOUS COPPER CONDUCTOR NOT SMALLER THAN 10 AWG. THIS CONDUCTOR SHALL BE PERMITTED TO BE BROKEN IN ORDER TO TERMINATE ON THE EQUIPMENT GROUNDING TERMINAL BUS IN EACH PANELBOARD. 16475 - OVERC URRENT PROTECTIVE DEVICES A. PROVIDE DATA SHEETS SHOWING ELECTRICAL CHARACTERISTICS INCLUDING TIME - CURRENT CURVES AS PART OF THE SHOP DRAWING SUBMITTAL B. FAULT CURRENT VALUES INDICATED ON THE DRAWINGS ARE BASED ON ACTUAL AVAILABLE FAULT VALUES AT EACH SWITCHBOARD, PANELBOARD AND ANY OTHER SIMILAR EQUIPMENT. EQUIPMENT MANUFACTURERS SHALL PROVIDE EQUIPMENT AND PROTECTIVE DEVICES SUITABLY RATED FOR THE CONFIGURATIONS INDICATED RATED FOR THE AVAILABLE FAULT CURRENT INDICATED. SERIES RATING OF DEVICES IS NOT ACCEPTABLE. C. CIRCUIT BREAKERS 1. CIRCUIT BREAKER MANUFACTURER SHALL BE THE SAME AS THE SWITCHBOARD/PANELBOARD/MOTOR CONTROL CENTER MANUFACTURER D. FUSES I. ACCEPTABLE MANUFACTURERS. BUSSMAN, GOUL SHAWMUT, OR LITTLEFUSE 2. FUSES SHALL HAVE 200,000 RMS SYMMETRICAL AMPERE INTERRUPTING CAPACITY AT 600V OR LESS, CURRENT LIMITING TYPE; TIME DELAY CHARACTERISTICS - 10 SECONDS (MINIMUM) AT 50OX RATED CURRENT; UL CLASS RK1. E. SELF- CONTAINED CIRCUIT BREAKER ENCLOSURES SHALL BE PADLOCKABLE NEMA 1, EXCEPT FOR UNITS IN DAMP OR WET AREAS WHICH SHALL BE A NEMA 3R ENCLOSURE WITH CONDUIT HUBS. F. ENCLOSURES FOR SELF - CONTAINED UNITS SHALL BE SECURITY MOUNTED TO WALL AND SHALL BE LEVEL. AND TRUE MOUNTING HEIGHT SHALL BE PLUS 54' A.F.F. TO CENTER OF BEAKER U.N.O. G. FURNISH A NUMBER OF SPARE FUSES EQUALING 1OX OF QUANTITY INSTALLED BUT NOT LESS THAN THREE (3) FUSES OF EACH TYPE AND RATING. H. INSTALL FUSES WITH LABEL ORIENTED SUCH THAT THE MANUFACTURER, TYPE AND SIZE ARE EASILY READ. 16721 - FIRE ALARM SYSTEM (MODIFICATION) A. FURNISH AND INSTALL FIRE ALARM AND DETECTION SYSTEM ADDITIONS AND RELOCATIONS AS INDICATED ON THE DRAWINGS, COMPATIBLE AND CONSISTENT WITH THE EXISTING SYSTEM. B. THE EXISTING SYSTEM OPERATION SHALL REMAIN UNCHANGED PROVIDING CONTINUAL SERVICE DURING ALL PHASES OF THE RENOVATION AND /OR EXPANSION. C. R IS THE RESPONSBIJTY OF THE ELECTRICAL CONTRACTOR TO PROVIDE EXPANDABLE MODULES. POWER SUPPLIES, HARDWARE, SOFTWARE, ETWw 70 THE FIRE ALARM SYSTEM N ORDER TO ACCOMMODATE THE ADDITIONAL FIRE ALARM DEVICES D. CONTRACTOR SHALL PROVIDE SENSITIVITY TEST REPORT FOR ALL NEW SMOKE DETECTORS E. THE ENTIRE SYSTEM SHALL BE TESTED TO THE OWNER'S SATISFACTION. CONTRACTOR SHALL PROVIDE A COMPLETE FIRE ALARM CERTIFICATION AND A SENSITIVITY TEST REPORT FOR ALL NEW, AND EXISTING SMOKE, DUCT AND HEAT DETECTORS CONTRACTOR SHALL REPLACE ANY DETECTOR THAT DOES NOT MEET THE ALLOWABLE SENSITIVITY VALUES F WHERE REQUIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED WITH THE BUILDING AUTOMATION SYSTEM IN ORDER TO SEND/RECEIVE SIGNALS FROM ALARM INITIATING DEVICES AND H -O-A SWITCHES FOR THE OPERATION OF SMOKE CONTROL SYSTEMS, FAN SHUTDOWN AND COMMUNICATIONS COORDINATE ALL REQUIREMENTS WITH DIVISION 15. G. VISUAL STROBE DEVICES SHALL MEET THE REQUIREMENTS OF ADA, UL, AND NFPA. H. AUDIBLE DEVICES IN PUBLIC AND STAFF AREAS SHALL BE SPEAKERS WITH A PEAK OUTPUT OF 96dB AT 10'-0'. I. ALL WIRING SHALL BE STRANDED AND IN CONDUIT. COLOR SHALL BE THE FACILITYS STANDARD OR RED. J. PROVIDE NEW CONDUIT AND WIRING AS REQUIRED FOR NEW FIRE ALARM DEVICES CONNECT AND PROGRAM DEVICES IN EXISTING FIRE ALARM CONTROL PANEL COORDINATE EXACT LOCATION OF E)aSTING FIRE CONTROL PANEL WITH OWNER. NEW DEVICES ARE TO MATCH EXISTING ONES AND BE UL LISTED WITH EXISTING FIRE ALARM SYSTEM. PROVIDE NEW POWER SUPPLIES AS NECESSARY INCLUDING EXPANSION MODULES OR ANY SOFTWARE OR HARDWARE ACCESSORIES REQUIRED FOR A COMPLETE AND FUNCTIONAL INSTALLATION. ALL DEVICES SHALL MEET ADA REQUIREMENTS K CONTRACTOR SHALL SUBMIT SIGNED AND SEALED PLANS INDICATING EXACT LOCATION, TYPE. CABLING, AND BATTERY CALCULATIONS L ALL WIRING SHALL BE IN 3/4'C. MINIMUM. M. VENDOR SHALL RE- CERTIFY THE SYSTE]I AND PROVIDE CERTIFICATION AND SIM DETECTOR SENSITIVITY REPORT PRIOR TO ANY INSPECTION. N. SYNCHRONIZE ALL AUDIOVISUAL DEVICES 0. AUDIBLE DEVICES SHALL BE ON SEPARATE CIRCUITS THAN VISUAL DEVICES P. UPON ACTIVATION OF THE FIRE ALARM SYSTEM, THE AHU SHALL SHUT DOWN WHEN IN MANUAL OR AUTOMATIC POSITION. EXHAUST FAN SHALL BE INTERLOCKED WITH THE AHU STARTER LOCATE FIRE ALARM RELAY WITHIN 3' -0' OF STARTER 16741 - TELEPHONE AND DATA COMMUNICATIONS A. AT ALL WALL DATA/VOICE OUTLET LOCATIONS, PROVIDE A 4 11/16' SQUARE BOX WITH SINGLE -GANG ADAPTER AND BLANK COVER PLATE 1' MIN. EMPTY CONDUIT SHALL RUN WITH PULL CORD TO 6' ABOVE NEAREST ACCESSIBLE CORRIDOR CEILING SPACE WHERE CORRIDORS DO NOT HAVE ACCESSIBLE CEILINGS, PROVIDE CONDUIT SLEEVES AS A MINIMUM ONE PER SYSTEM COVERING THE ENTIRE LENGTH OF NON- ACCESSIBLE CEILING CAVITY. NUMBER AND SIZE OF CONDUIT/SLEEVES SHALL BE PER MANUFACTURER'S CABLING REQUIREMENTS B. PROVIDE A MINIMUM OF A 3116' DIAMETER, TWISTED NYLON PLASTIC CORD IN ALL EMPTY RACEWAYS PROVIDE A IDENTIFICATION TAG ON EACH END INDICATING THE LOCATION OF THE OTHER END. C. INSTALL DATA /COMMUNICATIONS OUTLETS AT SAME HEIGHT SPECIFIED FOR CONVENIENCE OUTLETS U.N.O. GROUP TELEPHONE AND DATA COMMUNICATIONS OUTLETS WITH RELATED RECEPTACLE OUTLETS U.N.O. D. WHERE PLYWOOD BACKBOARDS ARE INDICATED, PROVIDE A 3/4' THICK APA A/D GRADE PLYWOOD, TREATED WITH FIRE RETARDANT, MINIMUM TWO (2) COATS OF LIGHT GRAY PAINT. BACKBOARDS SHALL BE MOUNTED SIX (6') INCHES A.F.F. AND EXTEND UPWARD A FULL EIGHT (8' -0l FEET OR TO THE CEILING GRID IF LESS THAN 8' -O'. 16900 - EQUIPMENT CONNECTIONS AND CONTROL WIRING A. THE FURNISHING AND INSTALLATION OF CONTROL POWER WIRING REQUIRED FOR EQUIPMENT FURNISHED UNDER DIVISION 15 AND NOT SHOWN ON THE ELECTRICAL DRAWINGS SHALL BE FURNISHED UNDER DIVISION 15. CONTROL POWER WIRING IS DEFINED AS THE LINE VOLTAGE (12OV) POWER WIRING FOR EQUIPMENT CONTROL CABINETS, TEMPERATURE CONTROL. ENERGY MANAGEMENT, OR BUILDING AUTOMATION SYSTEM PANELS AND LINE VOLTAGE SMOKE/I IRE DAMPERS B. THE FURNISHING AND INSTALLATION OF THE TEMPERATURE CONTROL TIRING, ENERGY MANAGEMENT SYSTEM OR BUILDING AUTOMATION WIRING NOT SHOWN ON THE ELECTRICAL DRAWINGS SHALL BE FURNISHED UNDER DIVISION 15. TEMPERATURE CONTROL. ENERGY MANAGEMENT SYSTEM AND BUILDING AUTOMATION SYSTEM WIRING IS DEFINED AS THE INTERLOCK OR INTERCONNECTING WIRING REQUIRED BETWEEN SYSTEM CONTROL DEVICES, APPURTENANCES AND CONTROL PANELS TO ALLOW THE SYSTEM TO FUNCTION AUTOMATICALLY. THIS INCLUDES WIRING BETWEEN THE FIRE ALARM SYSTEM, SMOKE EXHAUST SYSTEMS, DOOR ENTRY SYSTEMS AND ANY OTHER SYSTEM REQUIRING INTERFACE WITH THE TEMPERATURE CONTROL. ENERGY MANAGEMENT AND BUILDING AUTOMATION SYSTEM. C. PROVIDE POWER WIRING TO EACH MOTOR -DRIVE AND /OR ELECTRICALLY - OPERATED SYSTEM OR UNIT OF EQUIPMENT. THE WIRING SHALL ALLOW THE MOTOR(S) OR EQUIPMENT TO OPERATE IN A MANUAL MODE. D. CONTROL WIRING WILL, UNLESS SPECIFICALLY NOTED OTHERWISE, WILL BE FURNISHED AND INSTALLED UNDER OTHER DIVISIONS OF THE SPECIFICATIONS. E EXCEPT FOR ITEMS THAT ARE FURNISHED WITH FACTORY- INSTALLED, INTEGRAL MOTORS, AN ELECTRIC MOTOR OF REQUIRED SIZE AND ELECTRICAL CHARACTERISTICS WILL BE PROVIDED AND INSTALLED UNDER OTHER DIVISIONS FOR EACH ITEM OF MOTOR -DRIVEN EQUIPMENT. COMPLETE THE ELECTRICAL INSTALLATION OF THESE MOTORS IN ACCORDANCE WITH APPROVED WIRING DIAGRAMS AND INSTRUCTIONS F. WHERE DISCONNECT SWITCHES OR CIRCUIT BREAKERS ARE NOT PROVIDED INTEGRAL WITH CONTROL EQUIPMENT FOR MOTORS AND OTHER ELECTRICAL APPURTENANCES, PROVIDE AND INSTALL ALL DISCONNECT SWITCHES REQUIRED BY THE NATIONAL ELECTRICAL. CODE AND /OR INDICATED. G. WHERE POSSIBLE. TERMINATE CONDUITS IN CONDUIT BOXES ON MOTORS. WHERE MOTORS ARE NOT PROVIDED NTH CONDUIT BOXES, TERMINATE THE CONDUITS IN CONDUIT FITTINGS AT THE MOTORS -- I -- - _ _ - - I- - - - -- - _ = -_I - - E 2 ` -- - - ICJ m . p - W - - c 0- - - - 0 a'o - o - 'IT - m m - M -I M U1 C rrnrn cos En W M J 4 J-1 (o :: J J c1 6 Y - -4�,Lo to . • Ln Ln c 13 - oL = -MM = Eul a o n MC7 c .c i _ N .wi CO • O . -Ioos� v Oo NcnU aJ- Xm R ••cpo cu cu CD = • s �., a co �, y • N : ­_ d y f0 a� 15: _ `° , � F � a�s °c`n u M aa)i vi�Z .o ., a L o` Q a a REVISIONS MARK: REMARKS: a: w 3: 0 O> 2 �mm cf) 0 < m t, V) 24 ubmin W 0) 0) H Z W gm W (a) Z Q 2 Z W O's.:: � S cc'•;,�' <Z)."', x7832 : �C3, Lo. W = • T �'% R?r - �.� - Ot A - , `,�. ° c 1% 111; �,, A `,J : a. "__-J_ h.z =t I lz[*4 :4 r X�K t _^P1t , , i = a 4A ;'t" ''Jx'v ti', u ,� .- , ." ' `7U,5,.� " 3 x 'A 4., m _= = ', i ''4 -; - -b J'A-�, .� ' J 4 2012 KEYPLAN Job No: 412480.000 ate: 11 -05 -2012 Sheet Tine: -01, � *� I -0 • Sheet No: E3.00 o .�, t,, Pln y ';� I k -ji F �a M- .A .� r� . N '. � - - If .,u y