Loading...
12-1139-029N ,L d o_ v_ �U 0 .q C 0 rn M N N Industry Standards and Code Bodies are intended to indicate the latest volume or publication of the Standard. All equipment, materials and details of installation shall comply with the requirements and latest revisions of the following Bodies, as applicable: ANSI American National Standards Institute ASTM American Society of Testing Materials AWG American Wire Gouge FM Factory Mutual NEMA National Electrical Manufacturers Association UL Underwriters' Laboratories NETA National Electrical Testing Association IEEE Institute of Electrical and Electronic Engineers 3. All materials and workmanship shall comply with all applicable Codes, Specifications, Local and State Ordinances, Industry Standards and Utility Company Regulations, latest Editions. C. Scope of Work 1. Cooperate with all trades to assure the steady progress of all work under the contract, as well as providing temporary power at project site for all others. 2. It shall be the responsibility of the contractor to study all drawings and details so that the installation of all new work can be fully coordinated. The contractor shall visit the site to satisfy himself that all provisions have been made for all aspects of this project. If discrepancies exist between drawings and /or site conditions, the contractor shall notify the general contractor in writing prior to signing of the contract for consideration and decision before proceeding. Failure to do so will not be allowed as a basis for additional compensation to correct a difficulty of difference from conditions inferred or indicated on the drawings. 3. Prepare and submit shop drawings of pertinent electrical equipment, devices, etc., as are indicated in the scope of work, and record for all work provided under this contract to the architect /engineer's review. Provide seven (7) copies of all submittals as noted hereinafter. 4. The contractor, for the work in his scope of work, shall give all necessary notices, obtain all permits, pay all governmental taxes, fees, inspections, and other costs in connection with his work; file for necessary approvals with the jurisdiction under which the work is to be performed. Electrical contractor shall obtain all required certificates of inspection for his respective work and deliver same to the general contractor before request for acceptance of his portion of work is made and before final payrnent. 5. Cut all openings, chases and patching required to accommodate the work under this division, seal with acoustical caulk and /or blowout patch, and repair all floors, walls, etc., damaged by such cuttings. All work done under this heading must conform in every respect to finish and quality of materials and workmanship specified under appropriate sections for the building. All cutting, core drilling, etc. required for the installation of the electrical equipment shall be by the contractor. Approved by the owner. 6. Verify equipment sizes, voltage and current characteristics, etc, before the ordering of any equipment and before roughing -in for equipment to be supplied by others, and provide ready accessibility of system required to be reached for maintenance and operations. 7. Check other sections of the specifications for equipment to be connected under this contract. 8. The electrical contractor shall make all requests for systems shut downs to the owner 72 hours in advance and shall restore all systems to normal operation by 3:30 pm every work day. 9. The entire area shall be brought up to meet code requirements including existing conditions. 10. All abandoned utilities shall be removed. D. The following general systems and equipment shall be provided as a minimum, but not be limited to the following: Normal distribution system. Emergency distribution system. Grounding. Lighting fixtures including lamps. Connections to HVAC, plumbing, elevators. Empty conduit system for telephone /communications systems. Hoisting, rigging, setting of all conduit, cable and equipment. Testing, cleaning and adjusting. SECTION 16020 - TEST & PERFORMANCE VERIFICATION A. Equipment and applications shall be per NEMA standards. B. Cables, motors, grounds, transformers, and the emergency system shall be thoroughly tested. Contractor shall provide a report indicating the results of all tests. C. Provide equipotential ground certification report in accordance with NFPA 99. The report shall state that the items have been tested and that they conform to the specified standard. SECTION 16110 - RACEWAYS A. Raceways shall be as follows: 1. Raceways for feeders and branch circuits shall be metallic, rigid metal conduit, intermediate metal conduit (IMC) or electrical metallic tubing (EMT) subject to the restrictions of the National Electrical Code, minimum size 3/4 ". EMT shall not be used in concrete construction or where subjected to mechanical damage. 2. Flexible metal conduit shall be used only for connection to motors, pumps, air handling units and transformers, and shall be waterproof type, with an interwoven ground conductor. Separate ground conductor shall be installed in all flexible conduit sizes. Flexible conduit non - waterproof type can be used for connecting to lighting fixtures only. Maximum length of all flexible conduit allowed shall be 5' -0 ". 3. Expansion fittings shall be used where conduit passes through building expansion joints, weatherproof telescopic type. The expansion fitting shall permit a minimum movement of 4 ". 4. Set screw type connectors and couplings will not be allowed, except for emt type conduit. Emt fittings shall be ansi c80.4 steel type, insulated throat, gland compression type or set screw type. Diecost fittings are also acceptable. 5. Raceways shall not be allowed in any concrete floor slabs. 6. All emergency system wiring shall be installed in conduit. 7. Provide all materials, devices, hangers, clamps, etc. And labor required to properly support all conduits /boxes installed under this contract in accord with nec. Provide minimum of 1" separation between all conduits racked together. 8. Conduit and boxes in ceiling spaces shall be supported from structure. 9. Provide nylon pull strings in all empty conduits. 10. Conduit and tubing shall be manufactured by one of the following: Anaconda Metal Hose, Republic Steel Corp., Allied Tube & Conduit Co., or Russell & Stoll. 11. Flexible conduit shall be manufactured by one of the following: Anaconda Metal Hose, Russell & Stoll, or Allied Tube & Conduit. SECTION 16120 - CONDUCTORS Fees, permits, royalties, guarantees. DIVISION 16 - ELECTRICAL Firestopping, smokeproofing, waterproofing. SECTION 16010 - GENERAL ELECTRICAL PROVISIONS Shop Drawings, Record Drawings, Coordination Drawings. A. General Fire alarm system. 1. Transportation, insurance, temporary protection, supervision Connections to Owner furnished equipment. and incidental items essential for proper installation and operation, though not specifically mentioned or indicated but which Access doors, are usually provided or are essential for proper installation and following color coding: operation of all systems related to this Section, as specified Boxes - junction. herein. Black (2 B Phase: Boxes - outlet. 2. All materials shall be new and bear a UL label. Blue 4 Neutral: Boxes - pull. 3. All conduits, wireways or other electrical raceways passing Green through fire partitions, fire walls or floors shall have a fire Conductors - 600V. stop installed providing an effective barrier against the spread of Brown fire, smoke and gases, maintaining the required fire rating. Conduit - metallic. B. Codes and Regulations Disconnect switches. 1. Installation shall conform to the following codes and Hangers and supports. regulations. Green 59A -3: FLORIDA ADMINISTRATIVE CODE HOSPITAL LICENSURE - 2003 Empty conduits for television system. NFPA -70: National Electrical code - 2008 Mechanical suspension channel. NFPA -101: Life Safety Code - 2009 larger than #6 AWG. AIA Guidelines for Design and Construction of Health Care Facilities - 2010 Motor disconnect devices. Florida Americans With Disabilities Accessibility Implemetaion Act - 2012 4A -3 FAC: State of Florida Fire Prevention code - 2010 Panelboards - lighting and distribution. NFPA 90A Standard for Installation of A/C and Ventilating Systems - 2002 NFPA -72: National Fire Alarm Code - 2007 Wiring devices and device plates. Florida Building Code - 2010 Florida Existing Building Code - 2010 Submittals and approvals of all State and Local Authorities, NFPA -99: Standard for Health Care Facilities - 2005 Dimmers. 2. In these specifications, references made to the following Lighting control systems. Industry Standards and Code Bodies are intended to indicate the latest volume or publication of the Standard. All equipment, materials and details of installation shall comply with the requirements and latest revisions of the following Bodies, as applicable: ANSI American National Standards Institute ASTM American Society of Testing Materials AWG American Wire Gouge FM Factory Mutual NEMA National Electrical Manufacturers Association UL Underwriters' Laboratories NETA National Electrical Testing Association IEEE Institute of Electrical and Electronic Engineers 3. All materials and workmanship shall comply with all applicable Codes, Specifications, Local and State Ordinances, Industry Standards and Utility Company Regulations, latest Editions. C. Scope of Work 1. Cooperate with all trades to assure the steady progress of all work under the contract, as well as providing temporary power at project site for all others. 2. It shall be the responsibility of the contractor to study all drawings and details so that the installation of all new work can be fully coordinated. The contractor shall visit the site to satisfy himself that all provisions have been made for all aspects of this project. If discrepancies exist between drawings and /or site conditions, the contractor shall notify the general contractor in writing prior to signing of the contract for consideration and decision before proceeding. Failure to do so will not be allowed as a basis for additional compensation to correct a difficulty of difference from conditions inferred or indicated on the drawings. 3. Prepare and submit shop drawings of pertinent electrical equipment, devices, etc., as are indicated in the scope of work, and record for all work provided under this contract to the architect /engineer's review. Provide seven (7) copies of all submittals as noted hereinafter. 4. The contractor, for the work in his scope of work, shall give all necessary notices, obtain all permits, pay all governmental taxes, fees, inspections, and other costs in connection with his work; file for necessary approvals with the jurisdiction under which the work is to be performed. Electrical contractor shall obtain all required certificates of inspection for his respective work and deliver same to the general contractor before request for acceptance of his portion of work is made and before final payrnent. 5. Cut all openings, chases and patching required to accommodate the work under this division, seal with acoustical caulk and /or blowout patch, and repair all floors, walls, etc., damaged by such cuttings. All work done under this heading must conform in every respect to finish and quality of materials and workmanship specified under appropriate sections for the building. All cutting, core drilling, etc. required for the installation of the electrical equipment shall be by the contractor. Approved by the owner. 6. Verify equipment sizes, voltage and current characteristics, etc, before the ordering of any equipment and before roughing -in for equipment to be supplied by others, and provide ready accessibility of system required to be reached for maintenance and operations. 7. Check other sections of the specifications for equipment to be connected under this contract. 8. The electrical contractor shall make all requests for systems shut downs to the owner 72 hours in advance and shall restore all systems to normal operation by 3:30 pm every work day. 9. The entire area shall be brought up to meet code requirements including existing conditions. 10. All abandoned utilities shall be removed. D. The following general systems and equipment shall be provided as a minimum, but not be limited to the following: Normal distribution system. Emergency distribution system. Grounding. Lighting fixtures including lamps. Connections to HVAC, plumbing, elevators. Empty conduit system for telephone /communications systems. Hoisting, rigging, setting of all conduit, cable and equipment. Testing, cleaning and adjusting. SECTION 16020 - TEST & PERFORMANCE VERIFICATION A. Equipment and applications shall be per NEMA standards. B. Cables, motors, grounds, transformers, and the emergency system shall be thoroughly tested. Contractor shall provide a report indicating the results of all tests. C. Provide equipotential ground certification report in accordance with NFPA 99. The report shall state that the items have been tested and that they conform to the specified standard. SECTION 16110 - RACEWAYS A. Raceways shall be as follows: 1. Raceways for feeders and branch circuits shall be metallic, rigid metal conduit, intermediate metal conduit (IMC) or electrical metallic tubing (EMT) subject to the restrictions of the National Electrical Code, minimum size 3/4 ". EMT shall not be used in concrete construction or where subjected to mechanical damage. 2. Flexible metal conduit shall be used only for connection to motors, pumps, air handling units and transformers, and shall be waterproof type, with an interwoven ground conductor. Separate ground conductor shall be installed in all flexible conduit sizes. Flexible conduit non - waterproof type can be used for connecting to lighting fixtures only. Maximum length of all flexible conduit allowed shall be 5' -0 ". 3. Expansion fittings shall be used where conduit passes through building expansion joints, weatherproof telescopic type. The expansion fitting shall permit a minimum movement of 4 ". 4. Set screw type connectors and couplings will not be allowed, except for emt type conduit. Emt fittings shall be ansi c80.4 steel type, insulated throat, gland compression type or set screw type. Diecost fittings are also acceptable. 5. Raceways shall not be allowed in any concrete floor slabs. 6. All emergency system wiring shall be installed in conduit. 7. Provide all materials, devices, hangers, clamps, etc. And labor required to properly support all conduits /boxes installed under this contract in accord with nec. Provide minimum of 1" separation between all conduits racked together. 8. Conduit and boxes in ceiling spaces shall be supported from structure. 9. Provide nylon pull strings in all empty conduits. 10. Conduit and tubing shall be manufactured by one of the following: Anaconda Metal Hose, Republic Steel Corp., Allied Tube & Conduit Co., or Russell & Stoll. 11. Flexible conduit shall be manufactured by one of the following: Anaconda Metal Hose, Russell & Stoll, or Allied Tube & Conduit. SECTION 16120 - CONDUCTORS � 0-) A. Feeders W 00 W Cn 1, 600V feeders shall be single- conductor, 600V rated with XHHW or XHHW -2 insulation, feeders shall be color coded using color tape at all connections and in all pull and junction boxes. All feeders shall be installed in conduit. All wiring #8 AWG and larger shall be stranded. 2. Provide color coded cable system approved by Owner. If none is required by Owner, provide the following color coding: a. 208/120V _ O (1 ) A Phase: Black (2 B Phase: Red 3 C Phase: Blue 4 Neutral: White (((5 Ground: Green b. 480/277V (1) A Phase: Brown B Phase: Orange 3 C Phase: Yellow 4 Neutral: 121 Grey 5 Ground: Green Note: Color coding shall be continuous on insulation for #6 AWG or smaller and continuous or marked with color tape at all connections for conductors larger than #6 AWG. B. Branch Circuits 1. Branch circuit conductors shall be single- conductors 600V rated with THWN or THHN insulation with continuous color coding. 2. Branch circuit conductor shall be designed to utilize the advantage of multi -wire distribution, however, no more than (5) conductors (3- phase, 1 neutral and 1 ground) shall be installed in a common conduit. 3. Minimum size wire for branch circuit and power wiring shall be #12 AWG, for remote control signal circuit and interlock wiring can be #14 AWG. For 20A branch circuit runs exceeding 100' -0' in length from the panelboard to the first outlet, the entire branch circuit run shall be #10 AWG or larger. For runs over 175' -0" to the first outlet, use #8 AWG or larger for the entire branch circuit run. 4. Multiconductor armored cable (Hospital grade) may be used for normal power, general purpose 20A branch circuit wiring for receptacles and lighting fixtures only, 60OV, copper, with an insulated green grounding conductor run with the phase wires. Bare bonding wire conductor or the metal sheathing of cable shall not be used as the grounding conductor, but shall be used as a second path for grounding per NEC, to bond metallic sheathing to other wiring methods. All armored cables where installed shall be run concealed. This wiring method using armored cable or any other assembled cable(s) shall not be used for emergency system branch /feeder circuits. Armored cable shall be UL listed for Hospital use and shall comply with Federal Specification J -C -30 and shall be manufactured by AFC or approved equal. Armored clad cable conductors shall be color coded, continuous on insulation as called for hereinbefore. 5. Branch circuit and feeder conductors shall be manufactured by one of the following: Carol Cable, Okonite, Pirelli or Rome Cable Corp. C. All wire and cable shall be annealed, coated copper per astm b 33 or b 189 with conductivity of not less than 98 percent. All wire shall be stranded, unless size 8 or smaller, class b per astm b8. D. All wire shall have 600 volt insulation, ul listed and complying with ul 83, icea s -61 -402 or ieea s -66 -524 for respective insulation type and shall be color coded. 16130 - BOXES A. Boxes shall be as follows: 1. Galvanized steel outlet boxes conforming to UL Standard No. 514 will be used for concealed outlets. 2. Exposed outlet boxes shall be cast -metal conduit type FS or FD with threaded hubs. 3. Pull and junction boxes shall conform to UL Standard 50, constructed of code gouge galvanized steel and be sized per the requirements of the National Electric Code. 4. Provide pull and junction boxes as required. 5. All junction and pull boxes for emergency systems and low voltage systems shall have cover plates painted. Colors for covers shall be as indicated below: Life safety branch yellow Critical branch orange Equipment branch green Fire alarm red Data /telephone system brown 16140 - WIRING DEVICES A. Light Switches 1. Switches shall be full size, heavy duty, ac type, rated for 120/277 volts, hubbell #1221 -1, #1223 -i, #1224 -i. 2. Dimmers shall be 120 volts, 600, 1000 and 1500 watts with slider control, color selected by architect, manufactured by lutron n2000 series or approved equal. Wattage of connected load to the dimmer shall not exceed 80 percent of dimmer rating. B. Duplex, receptacles 1. Duplex receptacles shall be HOSPITAL grade, u- ground, rated for 120 volts, 20 amperes. Catalog numbers are as follows: hubbell #8300. C. Device plates 1. Switch device plates shall be manufactured of nylon, Color shall be as selected by the architect, Device plates shall be nylon and of the some manufacturer as wiring devices. Device plate screws shall match plates. D. Receptacles and light switches on emergency power shall be red in color with red device plates. SECTION 16170 - CIRCUIT AND MOTOR DISCONNECTS A. Disconnect switches shall be as follows: 1. Furnish and install disconnect switches for disconnecting means for all equipment. Disconnect switches shall be of the Type "A ", quick -make, quick -break construction. Disconnect switches shall have interlocking doors. Cabinets shall be bonderized and finished in gray enamel. NEMA Type 3R enclosures shall be used where the disconnect switch is exposed to the weather or in wet areas. 2. Disconnect devices shall be one of the following manufacturers: Square D, General Electric or Westinghouse. 3. All equipment shall be provided with the proper size /rating disconnect switch whether indicated on the drawings or not to comply with NEC. Also, install and connect disconnect switches furnished by other Trades. 16190 - SUPPORTS A. Provide supports as follows: 1. All supports required to properly support all equipment, devices, raceways, etc. to be installed under this contract, 2. Provide supports as required by the NEC. 16195 - IDENTIFICATION A. Equipment Identificaiton 1. Provide engraved laminated phenolic nameplates to identify panelboards disconnects and all major equipment. 2 Nameplates shall include the panel and circuit designation and shall be laminated, Bakelite with 1/4" high, recessed letters. Nameplates shall be securely attached to the equipment with galvanized screws. Adhesives or cements shall not be used. 3. Nameplate for equipment on normal power shall be black in color with white recessed letters. 4. Nameplates for devices on emergency power shall be "red" in color with white recessed letters. 5. Furnishing ands installing permanent identification markers for all electrical equipment and raceways installed under this contract. 6. Nameplates shall include the following information: a. Equip ml'ent Identification: Service voltage- phase -wire, branch' of power connected to, and source of power ITe equipment is fed from. 7. All panelboards shall be provided with new written directories. All directories shall indicate loads served as well as breaker ratings and pole space requirements for each load. This requirement applies to all new or revised panelboards. Provide copy of all directories to engineer of record. 8. The contractors shall be responsible for tracing out existing branch circuits and updating panel directories as required to insure proper directory listings. B. Conduit Identification 1. Provide manufacturer's standard pre - printed, flexible or semi - rigid, permanent, plastic -sheet conduit markers, extending 360 degrees around conduits; designed for attachment to conduit by adhesive, adhesive 'flap joint of marker, matching adhesive plastic tape at each end of marker, or pretensioned snap -on. Except as otherwise indicated,) provide lettering which indicates voltage of conductor(s) in conduit. Provide minimum 8 inch length for 2 inch and smaller conduit) 12 inch length for larger conduit. 2. Paint conduits for emergency systems and low voltage systems in accord with table 1 of this section. Spacing of paint markings shall be 10' -0" on centers for entire length of conduit. C. Color -Code Tape 1. Colored tape shall be polyvinyl chloride, self- adhesive not less than 3 mils thick and 1 1/2 inch wide, suitable for use on 90 degree C conductors, ul listed and shall be furnished in colors as specified herein. SECTION 16198 TESTING A. All low voltage 1600V equipment, cable, motors, dry type transformers, etc. shall be field tested per NETA Standards. B. The contractor', shall provide testing and documentation for equipotential grounding system to meet AHCA standards by an approved meter and must be available for testing at final survey. C. Testing shall be as stipulated per NFPA 99, 2002, section 4.3.3. SECTION 16450 - GROUNDING A. A complete equipment grounding system shall be provided such that all metallic structures, enclosures, raceways, junction boxes, outlet boxes, cabinets, machine frames, metal fences, and all other conductive items operate continuously at ground potential and provide a low impedance path to ground for possible fault currents. B. A separate inslulated green grounding conductor shall be provided for each single and 3 -phase feeder and branch circuit. Grounding conductor' shall be run with the related phase and neutral conductors. Panel feeders installed in more than (1) raceway shall have individual, full 'sized, green grounding conductor in each raceway. The equipment grounding system shall not rely on the metallic raceways for grounding continuity. C. Provide bonding of all equipment in accrodance with NFPA -70. SECTION 16471 - DISTRIBUTION AND BRANCH CIRCUIT PANELBOARDS A. Distribution, lighting and receptacle panelboards shall be deadfront construction utilizing thermal magnetic bolt on circuit breakers. Panels over 225A shall be fully rated for the available short circuit current) All trims shall be door -in -door type. B. Panelboards shall be manufactured by Westinghouse, General Electric, or Square '1D ". C. All panelboard land individually mounted circuit breakers shall have short circuit ratings as follows, unless otherwise noted on drawings: 1. 208V Class Parcels /Breakers a. 10 kAIC!, where shown fed via 150 <VA transformer and less b. 22 kAIC iwhere shown fed via 225 kVA transformer C. 42 kAIC where shown fed via 300 kVA transformer d. 65 kAIC where shown fed via 500 kVA transformers 2, 480V Class Panels /Breakers a. 65 kAIC for all 480V breakers. D. All panelboard (,bussing shall be copper, including ground. Section 16500 - LIGHTING 1. Light fixtures provided under this Division shall be provided complete with lamps and all 'necessary trim and mounting hardware, and installed as shown on the drawings. Light fixtures shall be neatly and firmly mounted, using standard supports for outlets and fixtures. Lamps shall be included in the system guarantee for a period of 90 days after final acceptance of the building. 2. Shop Drawings shall include computer generated lighting calculations, showing compliance with the minimum criteria. 3. The contractor shall provide fixture trims and supports as required to match type of ceiling system. No ceiling fixture shall be ordered until the Ceiling System installer has given written acceptance of the method and location'( of fixture hanging and fixture type. 4. Provide ten extra lamps for every fluorescent lamp type. 5. Ballasts shall have a minimum "A" sound rating. They shall be high power factor rated at ninety five percent (95 %) minimum power factor. 6. Coordinate all fixtures with piping and ductwork prior to installation and relocate fixtures as required to provide proper illumination. Coordinate significant changes to engineer prior to installation. SECTION 16721 - FIRE ALARM AND DETECTION SYSTEM A. The contractor shall provide connection to the owners existing fire alarm system. Provide all necessary system components such as, power supplies, micro - controllers, keyboard displays, led displays, batteries, peripheral devices, voice evacuation systems, etc. for a complete and functioning system. Fire alarm system components shall match existing. B. The system shall comply with all current, applicable codes including the following: 1. National Electrical Code (NEC) - 2005 2. National Fire Protection Agency a. NFPA 72 Edition 2007 b. NFPA 101 Life Safety Code - 2009 C. NFPA 90A Standard for the Installation of Air Conditioning and Ventilation Systems - 2002 3. All applicable UL standards 4. Americans with Disabilities Act (ADA) - 2012 5. Local Code Requirements C. Control Panel 1. The contractor shall provide all necessary hardware and software programming necessary to accommodate modifications to the existing system by adding new devices indicated on plans. D. Building Automation System Interface 1. Where required, the fire alarm system shall be interfaced with the building automation system (automatic temperature control system) to send and receive signals from alarm initiating devices and H -O -A switches for the operation of smoke control systems, fan shutdown and communications. Coordinate all requirements with division 15000. E. Alarm Initiating Devices 1. Provide all alarm initiating devices as indicated on floor plans. Devices shall match existing. F. Alarm Indicating Devices 1. Visual strobe units shall meet the requirements of ADA, UL and N FPA, 2. Audible units in public and staff spaces shall be speakers with a peak output of 96 dB at 10' -0 3. Audible units in mechanical areas or other areas with high ambient noise shall be trumpet type suitable for such locations. G. Wiring 1. All fire alarm wiring shall be supervised. All wire and cable shall be suitable for fire alarm use and shall be installed in conduit. 2. All wiring shall be stranded and color coded per the Hospital's Standards. H. Testing The entire system shall be 100% tested and certified in accordance with NFPA72 and shall provide NFPA 72 Record of Completion Form 1-6.2.1 In addition to the satisfaction of the Owner, a final acceptance test shall be witnessed by the local authority, the Owner's Building Construction Department and AHCA. Perform voltage activation sensitivity test with required range on new smoke & duct detectors and record results. Present recorded data at the formal inspection for verification. Approved copies shall become part of the operations and maintenance manuel for the fire alarm system. SECTION 16740 - EMPTY RACEWAY SYSTEM A. An empty raceway system shall be provided for use by the telecommunication vendor for the pulling in of telecommunications wiring and equipment. The raceway system shall meet the EIA /TIA -569 Standards. B. Telecommunications Outlets 1. Each telecommunication outlet shall consist of a 4 11/16" square outlet box with single -gang adaptor and blank cover plate. 3/4" Conduit shall run from the outlet to nearest accessible corridor ceiling. C. Furnish and install empty conduit outlets and mounting boards for MAN and security systems. D. Outlet boxes for all systems shall be 4 11/16" square (no rounded corner) with raised cover and faceplates (consult Owner for the appropriate faceplate), similar to wiring device plates. E. Provide power requirements such as duplex outlets and ground terminal connections for the telephone empty conduit system, as required by the vendor. F. ' A minimum 3/16" diameter, twisted nylon plastic fish cord shall be furnished and installed in all empty raceways. Provide a tag on each end of fish cord indicating the location of the other end. Conduits shall be of a size not smaller than 3/4 ". G. All empty conduit runs from outlets shall terminate above an accessible corridor suspended ceiling. H. Where corridors have non - accessible ceilings, provide conduit sleeves as a minimum one (1) per system, covering the entire length of non- accessible ceiling cavity. Number and size of conduit /sleeves shall be per equipment manufacturers' cabling requirements. �►-oJec� CAI N Ni�10N�IVE /N�INfiNIN� I ALL DIMENSIONS ARE APPROXIMATE. CONTRACTOR TO 'VERIFY DIMENSIONS IN EIELD. "TYPICAL" MEANS THAT ALL SIMILAR ITEMS ARE TO BE HANDLES SIMILAR TOTHE ONE MARKED "- TYPICAL„ W 0 I F/ J W lrnW V J O Bufi u q ®uqfiwks 58�2��4�,,„Sf,R�.1 obar I nn oAd v FL 7 YO21 954.9874206 Puajem Numb DATE �spBaorso�� 8, 04/30/12 DMWN By 00, RT8 ®1�I,MOON /ORAT�C C 1;AREN L. WARSECK, AIA DENSE # AR 13228 376 B LDING DIAGNOSMS AISOCIATES, PA a% j' LI ENSE # AAF000114 tq+ ° Z O rr ° u nuewo Nuvhn rid° °� es� E-6 / �� e+ A � 0-) W 00 W Cn C) d O - O J U W o W O _ O k 60 N Q0 :f� Bufi u q ®uqfiwks 58�2��4�,,„Sf,R�.1 obar I nn oAd v FL 7 YO21 954.9874206 Puajem Numb DATE �spBaorso�� 8, 04/30/12 DMWN By 00, RT8 ®1�I,MOON /ORAT�C C 1;AREN L. WARSECK, AIA DENSE # AR 13228 376 B LDING DIAGNOSMS AISOCIATES, PA a% j' LI ENSE # AAF000114 tq+ ° Z O rr ° u nuewo Nuvhn rid° °� es� E-6 / �� e+ A