CENTERED BETWEEN INFECTION CONTROL RISK ASSESSMENT (ICRA)
DOOR k CEILING ALL WORK SHALL CONFORM WITH THE OWNER'S INFECTION CONTROL AND CONSTRUCTION POLICIES,
(COORDINATE WITH PROCESSES AND OWNER'S PROJECT- SPECIFIC INFECTION CONTROL RISK ASSESSMENT PLAN,
ARCHITECT) - — -
— _
ICRA MATRIX
- _
CLOCK OUTLET FIRE HORN (OR CHIME) k LIGHT IC F2ISK CONSIRIJCIICN ACTIVITY TYPE
_._
EXIT
80" AFF FROM BOTTOM OF DEVICE LEVEL. TYPE A TYPE B TYPE C YPE p
LX
WALL MOUNTED LIGHT FIXTURES F GROUP 1 CLASS I CLASS IT CLASS TI CLASS TII /IV
AS NOTED ON PLANS GROUP 2_ CLASS T CLASS IT CLASS III CLASS IV
— ...._..._
REMOTE TEST _ -
GROUP 3 CLASS I CLASS IT CLASS
TELEVISION T III /TV CLASS IV
OUT _......... _ -
VOLUME CONTROL GRf JP 4 CLASS III CLASS III /T \/ CLASS III/IV CLASS IV
PANELBOARD �. _..... ...
Q — ..._
— .
CENTERED OVER DOOR 80" -- -- - -4W
8 g0" (WHERE APPLICABLE) FA PULL .. INFECTION CONTROL RISK LEVELS
DUPLEX RECEPTACLE f STATIO
E v _ G 1 R U OP - CROUP ..4
W \EaT MEDIUM MEDIUM HIGH TGHEST TELE.OUTLET
I __
OFFICE AREAS ALL PATIENT CARE UNITS EMERGENCY ROOM TRANSPLANT CLINIC
6" AF SWITCH 54" CONFERENCE ROOMS WAITING ROOMS* RADIOLOGY AREAS SURGERY SUITES
4i" ®9 PUBLIC BATHROOMS RECOVERY ROOMS
� J rl ROCP
COMPUTER ,. - -- --
)811 MAX• WAITING ROOMS*
TOOUTLET
TOP DEVICE LABOR AND DELIVERY LABOR k DELIVERY OR3/4
TO O
TELE. OUTLET NURSERIES CARDIAC CATH / ANGTO
36" C _ -._ —
AFF PEU ATRICS CVTCU
RTO SURGERY OUTPATIENT UNITS
q—o 1 - ALL INTENSIVE CARE AREAS DIA'. -YSIS AND TRANSPLANT
AFF NUCLEAR MEDICINE ONCOLOGY / BONE MARROW
ADMISSION / DISCHARGE AREA CARDIOLOGY
O1 42" A.F.F. W/ 36" COUNTER, f PHYSICAL THERAPY TANK AREA HYPERI3ARIC MEDICINE
39" A.F.F. W/ 30" COUNTER, d FINISHED FLOOR -- -- _ _
43" A.F.F, WITHOUT COUNTER DUPLEX RECEPTACLE CAFETERIA ENDOSCOPY
OR AS NOTED ON PUNS SPECIAL POWER OUTLET - - - -__ --
ECHOCARDIOGRAPHY PHARMACY ADMIXTURE
- L-ABORATORIES
PHARMACY
*DEPENDENT ON LOCATION
MOUNTING HEIGHTS CONSTRUCTION ACTIVITY TYPES
3 � -- - ....
NO Scale INSPECTIONS AND NON- INVASIVE ACTIVITIES. INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF CEILING TILES FOR VISUAL INSPECTION LIMITED TO 1
TYPE A TILE PER 50 SQUARE FEET, PAINTING (BUT NOT SANDING) WALL COVERING, ELECTRICAL TRIM WORK, MINOR PLUMBING, AND ACTIVITIES WHICH DO NOT
GENERATE DUST OR REQUIRE CUTTING OF WALLS OR ACCESS TO CEILINGS OTHER THAN FOR VISUAL INSPECTION.
......... --
TYPE B SMALL SC'L' SHORT DURATION ACTIVITIES WHICH CREATE MINIMAL DUST. INCLUDES, BUT IS NOT LIMITED TO, INSTALLATION OF TELEPHONE AND
COMPUTER CABLING, ACCESS TO CHASE SPACES, CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION CAN BE CONTROLLED,
MY WORK YMICH GENERATES A MODERATE TO HIGH LEVEL OF DUST OR REQUIRES DEMOLITION OR REMOVAL OF ANY FIXED BUILDING COMPONENTS OR
TYPE C ASSEMBLIES. INCLUDES, BUT IS NOT LIMITED TO, SANDING OF WALL FOR PAINTING OR WALL COVERING, REMOVAL OF FLOOR COVERINGS, CEILING TILES
AND CASEWORK, NEW WALL CONSTRUCTION, MINOR DUCTWORK OR ELECTRICAL WORK ABOVE CEILINGS, MAJOR CABLING ACTIVITIES, AND ANY ACTIVITY
WHICH CANNOT BE COMPLETED WITHIN A SINGLE WORKSHIFT.
TYPE D MAJOR DEMOLITION AND CONSTRUCTION PROJECTS. INCLUDES, BUT IS NOT LIMITED TO, ACTIVITIES WHICH REQUIRE CONSECUTIVE WORK SHIFTS,
REQUIRE HEAVY DEMOLITION OR REMOVAL OF A COMPLETE CEILING SYSTEM, AND NEW CONSTRUCTION.
ICRA CLASSIFICATION SCHEDULE
CLASS I 1. EXECUTE WORK QY METHODS TO MINIMIZE RAISING DsJST FROM CONSTRUCTION OPERATIONS. _
❑ 2. IMMEDIATELY REPLACE ANY CEILING TTI_E DISPLACED FOR VISUAL INSPECTION_
3. NOR DEMOLITION ON FOR REMODELING.
I. PROVIDES ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING INTO ATMOSPHERE.
2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING.
3, SEAL UNUSED DOORS WITH DUCT TAPE.
CLASS II 4. BLOCK OFF AND SEAL AIR VENTS,
5. WIPE SURFACES WITH DISINFECTANT.
El 6. CONTAIN CONSTRUCTION WASTE QLFORE TRANSPORT IN TIGHTLY COV-.RED CONTAINERS.
7. WET MOP AND /OR VACI.'UN WITH HERA FILTERED VACUUM BEFORE LEAVING WORK AREA•
i. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA.
9, REMOVE OR ISOLATE HVAC SY`;TEM IN AREAS WHERE WORK IS 6EING PERFORMED.
1. CRTAIN INFECTION CONTROL PERMIT PEFOE CONSTRUCTION BEGINS
2. ISOLATE HVAC SYSTEM IN AREA WHERE WORK TS BFING DONE TO PFEV£NT CONTAMINATION OF THE DUCT SYSTEM.
3. COMPLE7- ALL CRITICAL CARRIERS OR IMPLEMENT CONTROL CURE METHOD BEFORE CONSTRUCTION BEGINS.
4. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING EPA EQUIPPED AIR FILTPn�ION UNITS AND MONITOR WITH MAGNEHELIC GAUGES.
5. DO NOT REMOVE RARRIERS FROM WORK AREA UNTIL.. COMPLETE PROJECT IS THOROUGHLY CLEANED BY ENVIRONMENTAL SERVICES DEPARTMENT.
CLASS III 6, VACUUM WORK WITH HERA FILTERED VACUUMS.
❑ 7. WET MOP WITH DISINFECTANT.
E. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING QE DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION.
9. CONTAIN CONSTRUCTION WAS-1- BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
10. COVER TRANSPORT RECEPTACLES OR CARTS, TAPE COVERING.
11. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED,
1. OBTAIN INFECTION CONTROL PERMIT BEFORE CONSTRUCTION BEGINS.
2. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF THE DUCT SYSTEM.
3. COMPLETE ALL CRITICAL BARRIERS OR IMPLEMENT CONTROL CUBE METHOD BEFORE CONSTRUCTION BEGINS.
4. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HERA EQUIPPED AIR FILTRATION UNITS AND MONITOR WITH MAGNEHELIC GAUGES.
5, SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
6. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING A HERA VACUUM CLEANER
BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE.
CLASS IV 7. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS.
i. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS THOROUGHLY CLEANED BY THE ENVIRONMENTAL SERVICES DEPARTMENT AND
RELEASED BY SAFETY AND INFECTION CONTROL.
9. VACUUM WORK AREA WITH HERA FILTERED VACUUMS.
10. WET MOP WITH DISINFECTANT.
11. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION.
12, CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
13. COVER TRANSPORT RECEPTACLES OR CARTS, TAPE COVERING.
14, REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE CONSTRUCTION IS BEING DONE.
1
! 1
(- - - _ -2
..............
....
JI
I
1�
JNOTES:
1 Q1 WALL ASSEMBLY - THE 1, 2, 3, OR 4 HOUR FIRE-RATED GYPSUM WALLBOARD /STUD WALL
J ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE
INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE
DIRECTORY.
U2 CONDUIT - NOM 4" DIA OR SMALLER STEEL ELECTRICAL METALLIC TUBING, A MAX OF ONE
CONDUIT IS PERMITTED IN THE FIRESTOP SYSTEM. CONDUIT TO BE INSTALLED NEAR CENTER OF
STUD CAVITY WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
O3 FILL VOID OR CAVITY MATERIAL - CAULK FILL MATERIAL BEARING THE UL CLASSIFICATION MARKING
INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND GYPSUM
WALLBOARD AND WITH A MIN 1/4" DIAM BEAD OF CAULK APPLIED TO PERIMETER OF CONDUIT AT
ITS EGRESS FROM THE WALL CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL
ASSEMBLY. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY
i FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING
TABLE. THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE
OF THE CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS
INSTALLED, AS TABULATED BELOW:
MAX CONDUIT ANNULAR SPACE, F RATING, HR. T RATING, HR.
DIAM, IN. IN.
1 0 TO 3/16 1 OR 2 0, 1 OR 2
1 1/4 TO 1/2 3OR4 3OR4
4 0 TO 1 -1/2 1 OR 2 0
6 1/4 TO 1/2 3 OR 4 0
12 3/16 TO 3/8 1 OR 2 0
CONDUIT PENETRATION OF FIREWALL 1
UL SYSTEM NO. W -L -1001
CADDY J- HOOKS,
FINISHED CEILING -
/ / VOICE CABLE
DATA CABLE
II
1" CONDUIT STUD I I I I
ABOVE CEILING. CONDUIT IN WALL.
II
II
II
II
II
SINGLE GANG BOX WITH
OUTLET PLATE AND
I JACKS
Q Q REVIEW EACH LOCATION FOR
4 4 HEIGHT REQUIREMENT.
44
TYPICAL VOICE / DATA OUTLET 2
No Scale
r•.r ••• • a •r•r• ••r
• u •• ur • U U
•ey V n • • • au
• u 4 0 •
• • W•••e U
• . • U
Per rc• • • • too* 0
of
u
••
•
••
y
ENGINEERING .
FOR ARCHITECTURE
255 S. Orange Avenue
Suite 1600
Orlando, Florida 32801
PH: 407.841.9050
www.tic- engineers.com
EB #0000015
(D Copyright 2009 TLC Engineering for Architecture, Inc.
V)
Awk
LU
D
J
U
RCVIS14n3:
No. Date Description
4
t—
rr0
L
C7
"
LU
^'
W T
U
�' M
co
LLI
Cn ca
C'7
L
Seal
_O
n [-
James FerNs;r6. &,
jj�)
V
N
Z
o
vJ
E OF
rrLL
VJ
J
MT
>
W
08/31/2011
L L1
Approved By: TLC
J
Scale: AS NOTED
l
Awk
RCVIS14n3:
No. Date Description
Seal
James FerNs;r6. &,
Florida A1
° ,
�„j',��t # §51;56 �,
,
k e
E OF
Project No.: 111377
Issue Date:
08/31/2011
Drawn By: TLC
Approved By: TLC
Scale: AS NOTED
Drawing Title:
ELECTRICAL
DETAILS