11-962-001
r ELECTRICAL SYMBOL LEGEND GENERAL NOTES: DIVISION 16 SPECIFICATIONS BASIC MATERIALS TELEPHONE /COMPUTER RACEWAY SYSTEM SYMBOL DESCRIPTION SYMBOL DESCRIPTION 1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED. Sa SINGLE POLE SWITCH TELEPHONE do DATA OUTLETS, FOUR PORT 2. RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, (SUBSCRIPT INDICATES ITEM CONTROLLED) 4Q VOICE (2) do DATA OUTLETS (2) UNLESS OTHERWISE NOTED. ABOVE COUNTER RECEPTACLES SHALL BE MOUNTED ABOVE BACK 1. THE WORK REQUIRED UNDER THIS DIVISION SHALL INCLUDE ALL MATERIALS, LABOR AND 13, WHERE THE REQUIREMENTS OF ANOTHER DIVISION, SECTION, OR PART OF THESE SPECIFICATIONS S3 THREE -WAY SWITCH C = ABOVE THE COUNTER SPLASH TO CENTERLINE OF DEVICE. AUXILIARIES REQUIRE TO INSTALL A COMPLETE AND PROPERLY OPERATING ELECTRICAL SYSTEM. EXCEED THE REQUIREMENTS OF THIS DIVISION, THOSE REQUIREMENTS SHALL GOVERN, SD DIMMER SWITCH TTB 3. THE EQUIPMENT GROUNDING TERMINAL BARS OF THE NORMAL AND ESSENTIAL ELECTRICAL SYSTEM THE ELECTRICAL SYSTEM REQUIRED UNDER THIS DIVISION CONSISTS BASICALLY OF, BUT IS NOT (1500 WATTS UNLESS OTHERWISE INDICATED) TELEPHONE /COMPUTER TERMINAL BOARD PANELBOARDS SERVING THE SAME PATIENT VICINITY SHALL BE BONDED TOGETHER WITH AN LIMITED TO THE FOLLOWING: LIGHTING SYSTEM, POWER SYSTEM, ALARM SYSTEM, POWER 14, THE ENTIRE INSTALLATION SHALL BE IN ELECTRIC METALLIC TUBING, UNLESS SPECIFICALLY NOTED INSULATED, CONTINUOUS, COPPER CONDUCTOR NOT SMALLER THAN NUMBER 10, OTHERWISE. ELECTRIC METALLIC TUBING SHALL HAVE STEEL COMPRESSION TYPE COUPLINGS AND BE SO WALL MOUNTED DUAL TECHNOLOGY DISTRIBUTION, EQUIPMENT CONNECTIONS, ACCESS PANELS, EMPTY CONDUIT SYSTEMS AND ALL OCCUPANT SENSOR. MANUFACTURER: GREENGATE TTC 4. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH REQUIRED WIRING. USED INSIDE OF BUILDINGS AND ONLY IN DRY AREAS WHERE NOT EXPOSED TO MECHANICAL. a t� TELEPHONE TERMINAL CABINET DAMAGE. MINIMUM CONDUIT SIZE FOR ALL SYSTEMS SHALL BE 3/4 ". PROVIDE INSULATED BUSHINGS ONW -D- 1001- MV -N -W, THEY ARE TO BE INSTALLED. 2. INSTALL IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE AND THE REGULATIONS OF AT ENDS OF ALL CONDUITS, ALL CONDUITS AND BACKBOXES SHALL BE COLOR CODED TO MATCH OO CEILING MOUNTED DUAL TECHNOLOGY o_ 5. A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC 110. GOVERNING LOCAL, STATE, COUNTY AND OTHER APPLICABLE CODES. PAY FOR ALL REQUIRED EXISTING HOSPITAL STANDARDS, SUPPORT CONDUIT IN ACCORDANCE WITH THE NEC. OCCUPANT SENSOR. MANUFACTURER: GREENGATE COMPUTER TERMINAL CABINET LICENSES, FEES AND INSPECTIONS. OMC -DT- 2000 -R with SP20 -MV POWER PACK. B. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL CEILING WITH 3. ALL WORK AND EQUIPMENT UNDER THIS DIVISION SHALL BE IN STRICT COMPLIANCE WITH THE 15, BRANCH CIRCUIT AND FEEDER CONDUCTORS FOR ELECTRIC POWER SHALL BE COPPER TYPE DUPLEX RECEPTACLE T A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, THHN /THWN INSULATION FOR BRANCH CIRCUITS AND THWN INSULATION FOR FEEDERS. /� �� TELEPHONE SYSTEM RACEWAY DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL APPLICABLE PROVISIONS OF THE FOLLOWING CODES AND STANDARDS: NO ALUMINUM WIRING SHALL BE PERMITTED. ALL WIRE SHALL BE SIZE SHOWN ON THE APPURTENANCES IN ACCORDANCE WITH NEC 384. DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER A. LIFE SAFETY CODE - NFPA 101 (2006 EDITION). DRAWINGS, IF NO SIZE IS SHOWN, WIRE SHALL BE MINIMUM N0, 12, EXCEPT THAT BRANCH CM 6. CRITICAL AND LIFE SAFETY LIGHT SWITCHES SHALL BE ROUTED IN CONDUIT AND BOXES OTHER B. FLORIDA BUILDING CODE - (2007 EDITION W/2009 REVISIONS) " HOMERUNS" OVER 50 FT. IN LENGTH SHALL BE MINIMUM NO. 10. WIRE IN VICINITY OF CFI RECEPTACLE MOUNTED ABOVE COUNTER COMPUTER SYSTEM RACEWAY THAN THAT FOR THE NORMAL BRANCH. ESSENTIAL SYSTEM SWITCHES SHALL BE RED IN COLOR. HEAT - PRODUCING EQUIPMENT SHALL BE TYPE XHHW INSULATION. ALL WIRING SHALL BE C. NATIONAL ELECTRICAL CODE - NFPA 70 (2008 EDITION). MANUFACTURED IN THE USA. WIRING SHALL BE COLOR CODED ACCORDING TO EXISTING HOSPITAL TWO DUPLEX RECEPTACLES WITH COMMON COVER 7• PATIENT CARE AREAS SHALL BE PROVIDED WITH GROUNDING IN ACCORDANCE WITH NEC 517. D. STANDARD FOR HEALTH CARE FACILITIES -NFPA 99 (2005 EDITION). STANDARDS. WHEN BOXES ARE E. NATIONAL FIRE PROTECTION CODE - NFPA 72 (2002 EDITION) TWO DUPLEX RECEPTACLES WITH COMMON COVER TELEVISION RACEWAY DISTRIBUTION SYSTEM 8, FIRE /SMOKERANDL SMOKE PARTITONS),DTHEY SHALL BEIRINSTALLEDVWITHOUMAFFECTING THIEIEIRES F. AIA GUIDELINES FOR HEALTHCARE CONSTURCTION (2006 EDITION) 16. ALL RECEPTACLES SHALL BE 20 AMP HOSPITAL GRADE, STANDARD DUPLEX GROUNDING TYPE. MOUNTED ABOVE COUNTER CLASSIFICATION, ALL OF THE FOLLOWING CONDITIONS SHALL BE MET: SWITCHES SHALL BE SPECIFICATION GRADE, 20 AMP, 120/277 VOLT AND SHALL BE OF THE 4A. ALL MATERIALS SHALL BE NEW AND FREE OF DEFECTS, AND SHALL BE U.L. LISTED, BEAR THE U.L. SILENT OPERATING TYPE. GFCI RECEPTACLES SHALL BE HOSPITAL GRADE, UL RATED CLASS A, DUPLEX RECEPTACLE ❑D TELEVISION OUTLET FOR ANTENNA A. ALL ELECTRICAL BOXES SHALL BE METALLIC. LABEL OR BE LABELED OR LISTED WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL GROUP 1. COVERPLATES SHALL BE NYLON FINISHED. RECEPTACLES AND SWITCHES SHALL HAVE NOTE: TV TELEVISION SIGNAL WALL OUTLET B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE., TESTING AGENCY. WHERE NO LABELING OR LISTING SERVICE IS AVAILABLE FOR CERTAIN TYPES IVORY FINISH FOR NORMAL BRANCH DEVICES AND RED FINISH FOR CRITICAL BRANCH TICK MARKS SHOWN ON ANY DEVICE REPRESENTS C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES. OF EQUIPMENT, TEST DATA SHALL BE SUBMITTED TO PROVE TO THE ENGINEER THAT EQUIPMENT DEVICES. COVER PLATES FOR THE DEVICES SHALL BE ENGRAVED WITH PANEL AND CIRCUIT RECEPTACLE CONNECTED TO THE EMERGENCY CIRCUIT FT-V-d TWO GANG BOX RECEPTACLE/ CONTROL/ ANTENNA MEETS OR EXCEEDS AVAILABLE STANDARDS. NUMBERS. (RED DEVICE) TYPICAL FOR ANY DEVICE IN LEGEND D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL 'BE COMPLETELY 4B. PROVIDE SHOP DRAWING SUBMITTALS TO THE ARCHITECT /ENGINEER FOR APPROVAL FOR ALL 17. IN GENERAL, ALL ELECTRICAL EQUIPMENT (METALLIC CONDUIT, MOTOR FRAMES, PANELBOARDS, ETC.) GN GROUND BAR f-'� TV-�� TV DISTRIBUTION SYSTEM RACEWAY FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL). MATERIAL PROVIDED UNDER THIS DIVISION. EQUIPMENT SHALL NOT BE ORDERED PRIOR TO SHALL BE BONDED TOGETHER WITH A GREEN INSULATED COPPER SYSTEM GROUNDING CONDUCTOR IN E. PROVIDE A WALL AROUND OUTLETS LARGER THAT 16 SQUARE INCHES. THE INTEGRITY APPROVAL FROM THE ARCHITECT /ENGINEER. ACCORDANCE WITH SPECIFIC RULES OF ARTICLE 250 OF THE N.E.C. BONDING CONDUCTOR THROUGH SURGE SURGE SUPRESSOR OF THE WALL RATING SHALL BE MAINTAINED, THE RACEWAY SYSTEM SHALL BE CONTINUOUS FROM EACH WIRING DEVICE OR EQUIPMENT TO PANEL C3 = SERVICE ENTRANCE DEVICE F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE 4C. COORDINATION NUF CTRERSSPEECIFEDL HEREIN, AND ASDINDICATED ON HE DRAWINGS AND COORDINATION PANELS WITHOUT A PROVIDE GROUND MAR BOLTED TO THE CAN OF EXISTING HAVE AN INSULATED COPPER SYSTEM B3 = DISTRIBUTION BOARD DEVICE A3 - PANELBOARD DEVICE SYSTEM FIRE ALARM/DETECTION Y INCHES PER 100 SQUARE FEET. . STUDY. ANY DISCREPANCIES OR CONFLICTS IN THE SPECIFIED EQUIPMENT SHALL BE BROUGHT GROUND CONDUCTOR THROUGHOUT THE ENTIRE LENGTH OF CIRCUIT INSTALLED WITHIN CONDUIT G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL TO THE ATTENTION OF THE ENGINEER DURING BID FOR FORMAL CLARIFICATION. PER NEC 517 -13. GROUNDING CONDUCTOR SHALL BE INCLUDED IN TOTAL FILL IN DETERMINING ST SHUNT -TRIP BUTTON - FLUSH MOUNTED UNLESS MANUAL PULL STATION BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES. NO SUBSTITUTIONS ARE ALLOWED FOR PANELS, CIRCUIT BREAKERS, TRANSFORMERS, ETC. SUBMIT CONDUIT SIZES, EVEN THOUGH NOT INCLUDED OR SHOWN ON DRAWINGS. THE CONTRACTOR SHALL OTHERWISE NOTED NEMA 313 FOR EXTERIOR LOCATIONS H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS. EQUIPMENT AS SPECIFIED, PROVIDE EQUIPOTENTIAL GROUND TESTING IN THE PROJECT AREAS AND SUBMIT TEST REPORT, PRIOR TO THE 100 % AHCA INSPECTION, IN COMPLIANCE WITH NFPA 99. MAGNETIC MOTOR STARTER OR CONTACTOR CEILING SMOKE DETECTOR, PHOTO- ELECTRIC I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH 5. PROVIDE AND INSTALL ALL ELECTRICAL SYSTEMS AND ANY NECESSARY ACCESSORIES AS PER NEC ® SIZE AS NOTED E = ELEVATOR WITH RECALL CONTACTS BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING. AND LOCAL CODES WHETHER SPECIFIED HEREIN OR SHOWN ON DRAWINGS OR NOT, THE CONTENT OF 18A. PANELBOARDS: THE PANELBOARD BUS ASSEMGLY SHALL BE ENCLOSED IN A STEEL CABINET AND I = IONIZATION THESE SPECIFICATIONS (DIVISION 16) AND CONTRACT DOCUMENTS IN GENERAL ONLY REFERS TO SHALL BE SURFACE OR FLUSH MOUNTED AS SHOWN IN THE SCHEDULES. THE BOX SHALL BE MOTOR CONNECTION, NUMBER DENOTES HORSEPOWER DUCT SMOKE DETECTOR 9, NON- METALLIC RACEWAYS SHALL NOT BE USED TO SERVE ANY PATIENT CARE SPACE. ALL WORK REQUIRED ABOVE AND BEYOND THE REQUIREMENTS OF THE NEC AND LOCAL CODES. FABRICATED FROM GALVANIZED STEEL WITH STANDARD BAKED ENAMEL FINISH, PANELBOARD FRONT WIRING SHALL BE MECHANICALLY PROTECTED BY INSTALLATION IN METALLIC RACEWAYS. SHALL INCLUDE A DOOR AND SHALL HAVE A FLUSH, CYLINDER TUMBLER -TYPE LOCK WITH CATCH AND ® VARIABLE FREQUENCY DRIVE R = RETURN 6. DRAWINGS ARE DIAGRAMMATIC. COORDINATE FINAL EQUIPMENT LOCATIONS WITH GOVERNING SPRING- LOADED STAINLESS STEEL DOOR PULL. ALL PANELBOARD LOCKS SHALL BE KEYED ALIKE. ALL S = SUPPLY 10. ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS OTHERWISE NOTED. ARCHITECTURAL AND STRUCTURAL DRAWINGS. LAY OUT BEFORE INSTALLATION SO THAT ALL PANEL CABINETS SHALL BE A MINIMUM OF 20 INCHES WIDE. FRONTS SHALL HAVE ADJUSTABLE DD DIRECT DIGITAL CONTROL PANEL TYPE UNLESS OTHERWISE NOTED TRADES MAY INSTALL EQUIPMENT IN SPACES AVAILABLE. PROVIDE COORDINATION AS REQUIRED INDICATING TRIM CLAMPS WHICH SHALL BE COMPLETELY CONCEALED WHEN THE DOORS ARE CLOSED. SUPERVISED CONTROL RELAY 11. ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED UP. FOR INSTALLATION IN A NEAT AND WORKMANLIKE MANNER. DOORS SHALL BE MOUNTED WITH COMPLETELY CONCEALED STEEL HINGES. PANEL FRONT SHALL NOT TRANSFORMER DUCT SMOKE REMOTE ALARM INDICATING LAMP, 12, THE NUMBER OF ARROWHEADS ON THE HOMERUNS DENOTES THE NUMBER OF CIRCUITS. BE REMOVABLE WITH DOOR IN THE LOCKED POSITION. PANEL FACEPLATE SHALL BE HINGED TO ALLOW -� 7. CHECK SITE AND EXISTING CONDITIONS THOROUGHLY BEFORE BIDDING. ADVISE ENGINEER OF PANEL INTERIOR TO BE ACCESSED WITHOUT REQUIRING THE REMOVAL OF THE COMPLETE FRONT. W/ TEST SWITCH, WALL MOUNTED 72" AFF 13. PANELBOARD BRANCH CIRCUIT "RECIRCUITING" REQUIREMENTS: DISCREPANCIES OR QUESTIONS NOTED. 8 AUTOMATIC TRANSFER SWITCH THE REUSE OF EXISTING RACEWAYS SHALL BE PERMITTED TO THE FULLEST EXTENT POSSIBLE 8. PROVIDE FIELD SUPERINTENDENT WHO HAS HAD A MINIMUM OF FOUR (4) YEARS PREVIOUS COMBINATION AUDIBLE /VISUAL PROVIDED THAT THE RACEWAYS ARE PROPERLY SUPPORTED PER THE NEC. CONTRACTOR SHALL 18B. PANEL BUS: RATINGS AS BUS STRUCTURE AND MAIN LUGS OR MAIN CIRCUIT BREAKER SHALL HAVE NOTIFICATION DEVICE ENSURE THAT SUCH RACEWAYS ARE SUPPORTED, AND IF REQUIRED, ADD ADDITIONAL SUPPORTS. SUCCESSFUL EXPERIENCE ON PROJECTS OF COMPARABLE SIZES AND COMPLEXITY. SUPERINTENDENT 30AR NON -FUSED DISCONNECT SWITCH, SIZE AS NOTED CURRENT RATINGS AS SHOWN ON THE PANELBOARD SCHEDULE. BUS SHALL BE INSULATED AND BUS SHALL BE PRESENT AT ALL TIMES THAT WORK UNDER THIS DIVISION IS BEING INSTALLED OR NF NF DENOTES NON -FUSED COMBINATION AUDIBLE WHERE THE REUSE OF EXISTING RACEWAYS OCCURS, CONTRACTOR SHALL ENSURE THAT PROPER BAR CONNECTIONS TO THE BRANCH CIRCUIT BREAKERS SHALL BE OF THE "DISTRIBUTED PHASE" OR /VISUAL NOTIFICATION DEVICE AFFECTED. SUPERINTENDENT SHALL HAVE PASSED A PROCTORED H.H. BLOCK JOURNEYMAN EXAM ❑F-� PHASE SEQUENCE TYPE. ALL CURRENT CARRYING PARTS OF THE BUS STRUCTURE SHALL BE TIN 30AR CHIME /FLASHING "FIRE" LIGHT SEPARATION OF WIRING CLASSIFICATIONS IS MAINTAINED THROUGHOUT THE ENTIRE CIRCUIT. WHERE WITH 75% GRADE OR BETTER AND SHALL BE A LICENSED JOURNEYMAN. A RESUME OF THE � FUSED DISCONNECT PLATED COPPER. A FULL SIZE INSULATED NEUTRAL BUS BAR SHALL BE PROVIDED. PROVIDE SYSTEM 20AF 75CD CD = CANDELA RATING CO- MINGLING OCCURS, CONTRACTOR SHALL REMOVE THE NECESSARY WIRING AND REINSTALL IN SUPERINTENDENT'S EXPERIENCE SHALL BE SUBMITTED TO ENGINEER BEFORE STARTING WORK. AT GROUNDING TIN PLATED COPPER BUS BAR BONDED TO THE PANELBOARD CABINET FOR CONNECTION MCP AR DENOTES AMP RATING OF SWITCH SEPARATE RACEWAYS TO MAINTAIN THE REQUIRED SEPARATION. LEAST ONE MEMBER OF THE ELECTRICAL CONTRACTING FIRM SHALL HOLD A STATE MASTER OF SYSTEM GROUNDING CONDUCTORS. THIS BAR SHALL BE MECHANICALLY AND ELECTRICALLY SIZE AF DENOTES AMP FUSE SIZE F VISUAL SIGNALING UNIT, WALL MOUNTED ALL EXISTING JUNCTION BOXES AND RACEWAYS SHALL BE RE- IDENTIFIED WITH THE NEW BRANCH CERTIFICATE OF COMPETENCY. ISOLATED FROM THE NEUTRAL GAR EXCEPT WHERE PANELBOARD IS USED AS SERVICE ENTRANCE (NO AUDIO DEVICE � OF POLES ) CIRCUIT INDENTIFICATIONS UTILIZED AS PART OF THE RECIRCUITING PROCESS.- ALL JUNCTION BOXES 9. PROVIDE ALL REQUIRED COORDINATION AND SUPERVISION WHERE WORK CONNECTS TO OR IS EQUIPMENT. SHALL BE IDENTIFIED WITH THE BRANCH CIRCUIT AND PANEL IN WHICH THE LOAD IS SERVED. AFFECTED BY WORK OF OTHERS, AND COMPLY WITH ALL REQUIREMENTS AFFECTING THIS DIVISION. 30 3 COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED SPRINKLER TAMPER 18C. MOLDED CASE CIRCUIT BREAKERS: ALL PANELBOARD BRANCH CIRCUIT BREAKERS SHALL BE BOLT -ON � O 3R 3 POLE UNLESS OTHERWISE NOTED TS SWITCH CONNECTION 14. ALL EXISTING AND NEW BRANCH CIRCUITS SHALL BE PROVIDED WITH NEW TYPED WRITTEN PANEL 10, SUITABLY PROTECT ALL EQUIPMENT FURNISHED UNDER THIS DIVISION DURING CONSTRUCTION. THERMAL - MAGNETIC MOLDED CASE TYPE. BREAKERS SHALL BE 1, 2 OR 3 POLE WITH AN INTEGRAL SCHEDULES THAT CLEARLY IDENTIFY THE LOCATION AND THE TYPE OF LOAD SERVED, NEW PANEL RESTORE ALL DAMAGED SURFACES AND ITEMS TO "LIKE NEW" CONDITION BEFORE A REQUEST CROSSBAR TO ASSURE SIMULTANEOUS OPENING OF ALL POLES IN MULTI -POLE CIRCUIT BREAKERS. SPRINKLER WATERFLOW SCHEDULES SHALL REFLECT THE CURRENT AS -BUILT CONDITIONS IN THE AREAS, NOT THE CURRENT FOR SUBSTANTIAL COMPLETION INSPECTION. BREAKERS SHALL HAVE AN OVERCEN TER, TRIP- FREE,TOGGLE -TYPE OPERATING MECHANISM WITH QUICK- ENCLOSURE NEMA 1 UNLESS NOTED FS SWITCH CONNECTION IDENTIFICATION FOUND ON THE EXISTING SCHEDULES, MAKE, QUICK -BREAK ACTION AND ACTIVE HANDLE INDICATION. HANDLES SHALL HAVE "ON ", "OFF ", NEMA STARTER SIZE 11. THE WORK REQUIRED UNDER THIS DIVISION SHALL INCLUDE A ONE -YEAR GUARANTEE. THIS AND "TRIPPED" POSITIONS. BOLT -ON CIRCUIT BREAKERS SHALL BE ABLE TO BE INSTALLED IN THE F © 15, WHERE SPECIFICALLY REQUIRED BY THESE DOCUMENTS, CONTRACTOR SHALL PERFORM A COMPLETE _Lam_ FIRE ALARM CONTROL PANEL CIRCUIT TRACE OF ALL BRANCH CIRCUITS WITHIN A SPECIFIC PANEL. CIRCUIT TRACE SHALL BE USED GUARANTEE SHALL BE BY THE CONTRACTOR TO THE OWNER FOR ANY DEFECTIVE WORKMANSHIP OR PANELBOARD WITHOUT REQUIRING ADDITIONAL MOUNTING HARDWARE. 120/208 VOLT CIRCUIT BREAKERS MATERIAL WHICH HAS BEEN FURNISHED UNDER THIS CONTRACT AT NO COST TO THE OWNER FOR SHALL HAVE INTERRUPTING RATINGS A MINIMUM OF 10,000 RMS SYMMETRICAL AMPERES AT 240VAC. EP EMERGENCY POWER OFF STATION, SURFACE MOUNTED - TO DEVELOP AN ACCURATE SCHEDULE OF A PANELS BRANCH CIRCUITS EXISTING AS -BUILT A PERIOD OF ONE YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION OF THE WORK. AT +48" FATC CONDITIONS, INFORMATION SHALL BE FORWARDED TO THE ENGINEER FOR INCORPORATION INTO THE 19. CONTRACTOR SHALL CLOSELY COORDINATE WITH THE HOSPITAL PRIOR TO COMMENCING WORK AND z;m..-- .-- ...... FIRE ALARM TERMINAL CABINET PROJECT DOCUMENTS AND ISSUANCE OF AN ADDENDUM TO PROVIDE CLEAR DIRECTION ON THE 12A. PERFORM VERIFICATION WORK AS REQUIRED TO SHOW THAT THE SYSTEM IS OPERATING CORRECTLY DURING CONSTRUCTION FOR POWER AND /OR SYSTEM OUTAGES AS WELL AS GENERAL REQUIREMENTS. EXACT EXACT RECIRCUITING REQUIREMENTS FOR A SPECIFIC PANEL. IN ACCORDANCE WITH CONTRACT DOCUMENTS AND MANUFACTURER'S LITERATURE. ALL VERIFICATION A SEVEN (7) DAY NOTICE SHALL BE GIVEN FOR ALL POWER OUTAGES. CONTRACTOR SHALL WORK COLOR CODES FAAP SHALL BE DONE AFTER 3-DAY FULL OPERATIONAL PERIOD. ALL WORK ON THE SYSTEM SHALL BE DURING OFF HOURS (EVENINGS & WEEKENDS) WHEN DEEMED NECESSARY BY THE HOSPITAL. - AA ___ FIRE ALARM ANNUNCIATOR PLAN - FLUSH MOUNTED 16. PROVIDE EQUIP - POTENTIAL TESTING AS INDICATED UNDER "TESTING" FOR ALL SURFACES WITHIN THE COMPLETED, AND ALL FORMS AND OTHER INFORMATION SHALL BE SUBMITTED FOR APPROVAL ONE �_ 20. AT THE COMPLETION OF WORK, CONTRACTOR SHALL PROVIDE TWO SETS OF RECORD "AS- BUILT" AREA OF WORK FOR EACH PATIENT CARE SPACE, WEEK BEFORE THE REQUEST FOR FINAL INSPECTION OF THE BUILDING. COLOR CODING: COLOR CODE ALL POWER AND LIGHTING CABLE. COLOR CODE THE WIRE FIRE ALARM SYSTEM CONDUIT AND WIRING DRAWINGS IN ACCORDANCE WITH DIVISION 1, SHOWING THE ACTUAL LOCATION OF ALL EQUIPMENT BY USING COLORED PLASTIC TAPE, PAINTING THE ENDS ACCESSIBLE AT JUNCTION OR F_ 17. FIRE ALARM CONTRACTOR SHALL PROVIDE AN APPROVED CERTIFICATION FOR FIRE ALARM SYSTEM INSTALLED INCLUDING UNDERGROUND CONDUITS AND JUNCTION BOXES. PULL BOXES, OR OTHER METHOD ACCEPTABLE TO THE ENGINEER. USE THE FOLLOWING STATING SYSTEM IS WORKING PROPERLY AFTER MODIFIED WORK IS PERFORMED. SENSITIVITY TESTING CHART AS APPLICABLE; Q HALON SYSTEM MANUAL PULL STATION SHALL BE RECORDED FOR ALL HEADS AND SUBMITTED TO ENGINEER UPON COMPLETION AND TO 120/208 277/480 AHJ UPON INSPECTION, ALL WORK SHALL BE IN COMPLIANCE WITH THE APPLICABLE PROVISIONS OF CONDUCTOR VOLTS ONDC UCTOR VOLTS HALON SYSTEM SMOKE DETECTOR NFPA 72. PHASE A BLACK PHASE A BROWN H PHASE B RED PHASE B ORANGE PHASE C BLUE PHASE C YELLOW TESTING NEUTRAL WHITE NEUTRAL GRAY EQUIP.GROUND GREEN EQUIP.GROUND GREEN EQUIPOTENTIAL GROUND COLOR CODING OF ESSENTIAL CIRCUITS: ALL BOXES AND ENCLOSURES SHALL BE ELECTRICAL DRAWING INDEX A.EQUIPOTENTIAL GROUND: TEST ALL METAL CONDUCTIVE SURFACES LIKELY TO GECOME MARKED SO AS TO BE READILY IDENTIFIED AS PART OF THE ESSENTIAL SYSTEM. ENERGIZED WITHIN PATIENT CARE AREAS, TEST ALL LARGE CONDUCTIVE SURFACES LIKELY TO CONDUIT AND BOXES, INCLUDING BACK BOXES. PANELS, ETC. SHALL BE SPOT SHEET DESCRIPTION ISSUED BECOME ENERGIZED WITHIN A VOLUME DEFINED AS 6 FOOT FROM THE PATIENT BED PAINTED. CONDUITS SHALL BE IDENTIFIED TO WITHIN 6" OF THE BOX OR ENCLOSURE, HORIZONTALLY OR 7 FOOT 6 INCHES VERTICALLY. ALL OTHER COLOR CODES SHALL MATCH EXISTING COLOR CODING. E -1 ELECTRICAL LEGEND YES 11ARGE METAL SURFACES NOT LIKELY TO BE ENERGIZED, WHICH DO NOT REQUIRE TESTING: E -2 ELECTRICAL ONE -LINE DIAGRAM YES a. WINDOW FRAMES b. DOOR FRAMES E -3 PARTIAL 3RD FLOOR PLAN - POWER YES c. FLOOR DRAINS d. MOVEABLE METAL CABINETS E -4 ELECTRICAL DETAILS YES 2. TEST METHOD: a. USE IMPEDANCE AND VOLTAGE MEASUREMENTS b. UTILIZE ESTABLISHED GROUND BUS OR GROUND BAR IN PANEL SERVING AREA. c. MEASURE VOLTAGE FROM REFERENCE POINT TO CONDUCTIVE SURFACES AND ALL RECEPTACLE GROUND CONTACTS. d. MEASURE IMPEDANCE BETWEEN REFERENCE POINT AND RECEPTACLE GROUND CONTACTS. e. CHECK FOR PROPER POLARITY. f. IDENTIFY THE REFERENCE GROUND FOR EACH ROOM ON THE GROUND TEST REPORT. PROVIDE A BLUE DOT LABEL WITH A PERMANENT ADHESIVE BACKING LOCATED ON THE BOTTOM CENTER OF THE REFERENCE GROUND OUTLET COVER. 3. MAXIMUM ACCEPTABLE VALUES: a. VOLTAGE: 20 MV PLUS OR MINUS 20 PERCENT b. IMPEDANCE: 0.1 OHM PLUS OR MINUS 20 PERCENT c. QUIET GROUND IMPEDANCE: 0.2 OHM PLUS OR MINUS 20 PERCENT 4. EQUIPMENT. a. MILLIVOLT METER WITH 1 KOHM IMPEDANCE AND PROPER FREQUENCY RESPONSE, IN ACCORDANCE WITH NFPA 99. b. POLARITY TESTER 5. GROUND TEST REPORT. COMPLETE GROUND TEST REPORT INCLUDED AT THE END OF THIS SPECIFICATION SECTION, AND MAKE AVAILABLE COPIES OF SUCH TO ENGINEER AND INSPECTING AUTHORITY AT FINAL INSPECTION. NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT. ••e u • r • • ENGINEERING FOR ARCHITECTURE 255 S. Orange Avenue Suite 1600' Orlando, Florida 32801 PH: 407.841.9050 www.tic- engineers.com EB #0000015 o Copyright 2009 TLC Engineering for Architecture, Inc. U) W CO ,CO J U Q o I- EU c� W C � U o z U _ LL J W OD W J I co CD�- N M CO `a M .O r-�, LL O -. WE pe Revisions: No. Date Description's Seal 1 James Ferris, P.E. Florida License #65156 w I P. 5 5b yr ". STA F Project No.: 111377 Issue Date: 08/31/2011 Drawn By: TLC Approved By: TLC Scale: NTS Drawing Title: ELECTRICAL LEGEND Drawing No.: E -1 • • V • I p • ENGINEERING FOR ARCHITECTURE 255 S. Orange Avenue Suite 1600' Orlando, Florida 32801 PH: 407.841.9050 www.tic- engineers.com EB #0000015 o Copyright 2009 TLC Engineering for Architecture, Inc. U) W CO ,CO J U Q o I- EU c� W C � U o z U _ LL J W OD W J I co CD�- N M CO `a M .O r-�, LL O -. WE pe Revisions: No. Date Description's Seal 1 James Ferris, P.E. Florida License #65156 w I P. 5 5b yr ". STA F Project No.: 111377 Issue Date: 08/31/2011 Drawn By: TLC Approved By: TLC Scale: NTS Drawing Title: ELECTRICAL LEGEND Drawing No.: E -1