11-853R-002i S �1' r It LIFE SAFETY CALCULATIONS SMOKE COMPARTMENT SUMMARY U—) i SMOKE COMPARTMENT PRIMARY USE AREA SF OCCUPANT LOAD FACTOR PER PERSON OCCUPANT LOAD V) 1A TREATMENT 14,265 240 SF 60 U- 1B TREATMENT 15,215 240 SF 64 - HR 1 C ASSEMBLY BUSINESS SUB —TOTAL 3,758 9,209 15 SF 100 SF 250 92 12,967 342 1D TREATMENT STORAGE BUSINESS SUB —TOTAL 1,995 3,343 9,340 240 SF 300 SF 100 SF 8 11 93 14,678 112 1E KITCHEN DINING SUB —TOTAL 9,503 5,707 200 SF 11 SF 48 518 15,210 566 1F MECH. EQ. 5,330 300 SF 18 1 G TREATMENT 8,440 240 SF 35 1H TREATMENT 5,905 240 SF 25 11 TREATMENT 7,195 240 SF 30 ii TREATMENT 5,585 240 SF 24 1K TREATMENT 7,775 240 SF 33 TOTAL - FIRST LEVEL 112,565 1,309 BUILDING INFORMATION PROJECT INFORMATION PROJECT NAME: BAPTIST HEALTH SOUTH MIAMI HOSPITAL LIFE SAFETY SURVEY ADDRESS: 6200 SW 73 STREET. SOUTH MIAMI. FL 33143 PROPOSED USE: LIFE SAFETY SURVEY OWNER– CONTACT PERSON: LUIS FERNANDEZ DE CASTRO PHONE: 786- 6624660 APPLICABLE CODES – BUILDING CODE: 2007 FLORIDA BUILDING CODE W/2009 SUPPLEMENTS AND AIA GUIDELINES FOR DESIGN AND CONSTRUCTION ­OF HOSPITALS AND HEALTHCARE FACILITIES -2006 EDITION –FIRE CODE: 2006 NFPA 1.- UNIFORM FIRE CODE / FLORIDA FIRE PREVENTION CODE 2007 –LIFE SAFETY CODE: NPFA `101 – LIFE SAFETY CODE 2006 – ACCESIBILITY CODE: 2007 FLORIDA BUILDING CODE W/2009 SUPP EMENTS – CH.11 - -STATE FIRE MARSHALL'S RULE 69A3.012 FAC: NFPA 10 -2002. STANDARD FOR PORTABLE FIRE EXTINGUISHERS NFPA 13- x2002, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS NFPA 72 -2002, NATIONAL FIRE ALARM CODE NFPA 80 -1999 STANDARD FOR FIRE DOORS AND FIRE WINDOWS NFPA 99 -2005, STANDARD FOR HEALTH-- CARE FACILITIES NFPA 105-2003, SMOKE CONTROL DOOR ASSEMBLIES NFPA 221 -2006, STANDARD ON FIRE WALLS AND FIRE BARRIER WALLS BUILDING PLANNING OCCUPANCY: _INSTITUTIONAL GROUP 1 (FBC 2006) MIXED OCCUPANCY? YES / NO REQUIRED FIRE SEPARATION: 1 HR TYPE OF CONSTRUCTION CONSTRUCTION TYPE: FBC TYPE IB – NFPA 220 – TYPE II (2 -2 -2) __ LIFE & SAFETY NOTES LIFE SAFETY PLAN LEGEND 1 HR FIRE BARRIER 1 HR SMOKE BARRIER 1 HR FIRE BARRIER /SHAFT WALL 2 HR FIRE BARRIER 2 HR FSMOKE BARRIER 2 HR BARRIER /SHAFT WALL 4 HR FIRE BARRIER SMOKE PARTITION (NON RATED) NON RATED EXIT ACCESS CORRIDOR EXIT PASSAGE 2 HOUR SUITE OF ROOMS PERIMETER INSTITUTIONAL OCCUPANCY BUSINESS OCCUPANCY ASSEMBLY OCCUPANCY AREA UNDER CONSTRUCTION SMOKE COMPARTMENT WALL EXIT EXIT SIGN — HATCH INDICATES EXIT TEXT AND ARROW INDICATES DIRECTION FIRE DEPARTMENT CONNECTION FIRE EXTINGUISHER CABINET FIRE EXTINGUISHER PULL STATION STROBE LIGHT / HORN TOTAL TRAVEL DISTANCE TO AN EXIT TRAVEL DISTANCE TO ADJACENT SMOKE ZONE — iii —�— ME .�•- FDC 0 FEC FE FX 200' -0" 200' -0 " 1. THIS PLAN WAS PROVIDED BY BHSF. E.L.A. TAKES NO RESPONSIBILITY FOR ITS ACCURACY BEYOND THE LIMITS OF CONSTRUCTION AS DEFINED ON SHEET A2.0 & A3.0 2. THESE DRAWINGS HAVE BEEN DEVELOPED FROM EXISTING DRAWINGS WHICH MAY NOT REFLECT ACTUAL FIELD CONDITONS. THE CONTRACTOR SHALL VERIFY THESE DRAWINGS WITH EXISTING FIELD CONDITIONS AND IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF INCONSISTENCIES BETWEEN THESE DRAWINGS AND ACTUAL CONDITIONS BEFORE PROCEEDING WITH CONSTRUCTION. 3. THE GENERAL CONTRACTOR SHALL VERIFY THAT CONSTRUCTION OF EXISTING WALLS MEETS THE FIRE PROTECTION RATINGS DESIGNATED ON THESE DRAWINGS. HE SHALL ALSO MAKE ANY REPAIRS OR MODIFICATIONS NECESSARY TO BRING EXISTING WALLS, DOORS, DUCTS, ETC. UP TO THE PROPER INDICATED FIRE PROTECTION RATING. DOORS AND /OR FRAMES NOT MEETING RATING REQUIREMENTS OR BEARING PROPER LABELS SHALL BE REPLACED. 4. ALL CORRIDOR WALLS SHALL BE SMOKE TIGHT. THIS WILL BE ACHIEVED WITH DRYWALL TO DECK (ONE SIDE DRYWALL MINIMUM) OR USING ONE POUND PER SQUARE FOOT ACOUSTICAL CEILING TILES. 5. WALLS NOTED "PARTITION TIGHT TO DECK" WITH SOUND BATTS SHALL HAVE DRYWALL ON BOTH SIDES. SEE THE REFLECTED CEILING PLANS FOR SOUND BATTS LOCATIONS. 6. CONTRACTOR SHALL VERIFY THE LOCATION OF EXIT LIGHTS WITH OTHER LIGHTING TO ASSURE THERE ARE NO CONFLICTS OF EXIT LIGHT LOCATIONS. SEE REFLECTED CEILING PLANS. 7. WALLS DESIGNATED TO BE "ONE SIDE TO DECK" SHALL BE "TWO SIDES TO DECK" AT ROOMS WITHOUT CEILINGS. 8. CONTRACTOR SHALL STENCIL THE WALL CLASSIFICATION IN RED LETTERS ABOVE THE FINISH CEILING ON EACH SIDE OF ALL RATED PARTITIONS: FOR EXAMPLE: "TWO HOUR FIRE /SMOKE PARTITION — PROTECT ALL OPENINGS" SHALL OCCUR AT 20 "---0" O.C. BETWEEN OBSTRUCTION OR AS DIRECTED BY ARCHITECT. 20. LIFE AND SAFETY LEGEND, NOTES AND CALCULATIONS SCALE,1 /16 1 O �,. V � v V V V V JU„u uuu u (: ) PARTIAL FIRST FLOOR LIFE AND .SAFETY PLAN A &,& FIRST FLOOR LIFE AND SAFETY PLAN 3 2 - -- SCALE :1 /16" = 1' -0" SCALE :1 /32" = 1' -0" V V V V'V V V N /E /P Engineer Structural Engineer A > co V U. " C i0 0 O O W J W LL Ol E- m co r C] U. H J war, a:. Cl) J W O W W i a ti Owl ® o CO) J 2 C,:) 9 CL 3: cD O Seal , T AR000944, 7'1�l ,;,, a f'' 7 AR 57 i RED ARG Revision L1.16.12 FIELD COORDINATION 2 2.3.12 FIELD COORDINATION 3 2.21.12 FIELD COORDINATION Project Number 10 -038B Date „ MARCH, 2011 , Sheet Title'' LIFE SAFETY:­ 4 . P LAN Q S Drawn bye ELA ar;` ri w cu checked bye ELEWIS a Sheet Number L r 0 6'L -