11-853-025EXESTFJ3 SQUARE D NOW PANELBOARD
MAIN BREAKER: 150 AMPS 3 POLE
MAIN LUGS: AMPS
KA.I.C.: AMPS
SURFACE MTD: X
FLUSH MTD:
LIGHT]ING (L)
RECEPTACLES (R)
LARGEST MOTOR (M)
ALL OTHER MOTORS (M)
HEATING (H)
COOLING (C)
OTHER (0)
ELEVATOR (V)
SPARES (S)
DRYERS (D)
X-RAY(X)
KITCHEN (19
Name: RINLI
�Zum=
(NORMAL BRANM
3 PHASE
Project Name: EMPLOYEE HEALTH RELOCATKDN
4 WIRE
Project Number. 111355
X 208Y/120V
Fed From: 45KVA XFMR
4SOY/277V
2401120V
LIGHT]ING (L)
RECEPTACLES (R)
LARGEST MOTOR (M)
ALL OTHER MOTORS (M)
HEATING (H)
COOLING (C)
OTHER (0)
ELEVATOR (V)
SPARES (S)
DRYERS (D)
X-RAY(X)
KITCHEN (19
�Zum=
IDENTIFICATION
LOADIPHASE (KVA)
CIRCUIT BREAKER
LOAD/PHASE (KVA)
. . . . . . . . . . .
MEE=
21EM10
ME
no
ME
LIGHT]ING (L)
RECEPTACLES (R)
LARGEST MOTOR (M)
ALL OTHER MOTORS (M)
HEATING (H)
COOLING (C)
OTHER (0)
ELEVATOR (V)
SPARES (S)
DRYERS (D)
X-RAY(X)
KITCHEN (19
MAIN BREAKER: 150 AMPS
MAIN LUGS: AMPS
K.A.I.C.:-AMPS
SURFACE MTD: X
FLUSH MTD.
TOTAL CONNECTED LOAD: 16.1 KVA
TOTAL DEMAND LOAD: 17.3 KVA
DEMANDAMPS: 48.1 AMPS
I
Ln 1. NEW LOAD ON EXISTING CIRCUIT BREAKER. EACH CIRCUIT REQUIRES A DEDICATED NEUTRAL AND MUST BE REINSTALLED BACK TO THE SOURCE. --j
K90
DATA CAM
ARE
NOTE.
CONTRACTOR TO PROVIDE CONDUIT AND
SINGLE GANG BOX- OWNER'S IT
DEPARTMENT TO PROVIDE WIRING AND
FACE PLATES.
6 7
5 :40110,T-U-2
TYPICAL VOICE / DATA OUTLET 5
No Scale I
F(9' -o A.F.F. - VERIFY
W/AR(>L PLANS AS
PER ROOM LOCATION)
TAGGED NOTES:
(D 42- A.F.F. W/ 36- COURIER,
39- AFT. W/ 30- CDUNTER,
48* A.F.F. W W COUNTER
OR AS NOTED ON PLANS I
MOUNTING HEIGHTS
No Scale
ITC-0
(1) 3/4•C. FOR
(1) 3/4-C. FOR CABLE TV
CEILING TO ACCESSIBLE I
CORRIDOR I
E1-L A
edward lewlst Yf
architects
V" t'4
CABLE TV/ POWER OUTLET DETAIL
Vo Qi,-gle
ri °iii
9024 SW 152 STREET
PALMETTO BAY, FL 33157
PH: (305) 234-0576
EDWARD LEWIS ARCHITECTS, INC.
AAC001678
C. EDWARD LEWIS AR 0009567
m/E/F Engineer
to255 S. Orange Avenue
Suite 1600'
Orlando, Florida 32801
Phone: 407-841-9050
EN G I N E E R I N G 07-540 -0234
FOR ARCHITECTURE WWW.tic-eng,neers. orn
Q Copyright 2010 TLC Engineering for Architecture, Inc.
EB J0000015 TLC N0 :111403
Structural En*oor
2
Z
0
Z .5
M05;
a CY)
0
'4
-anew Nw—, 0
NOTES- 0 0 :2
WALL ASSEMBLY - THE 1, 2. 3, OR 4 HOUR FIRE RATED GYPSUM WALLBQM/STUD;'WALL J
ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE LU LL LE
in � -0 M -4 E
INDIVIDUAL 0300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RMISfANdE-
DIRECTORY.
cc
CONDUIT - NOM 4* DIA OR smim STEEL ELECTRICAL MEIN= TUBING. A MAX PF ONE 3:
CONDUIT IS PERMITTED IN THE FIRESTOP SYSTEM. CONDUIT TO BE INSTALLED NEAKU= _OF _--,— J
STUD CAVITY WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASS
0
FILL VOID OR CAVITY MATERIAL - CAULK FILL MATERIAL BEARING THE UL CLASSITA NG
INSTALLED To COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT M
WALLBOARD AND WITH A MIN lle DIAM BEAD OF CAULK APPLIED TO PERIMETER OF CONDUIT AT i. LLYY
ITS EGRESS FROM THE WALL CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES C WALL a)
It
ASSEMBLY. THE HOURLY F RATING OF THE nRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY w q
FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE' FOLLOWING 0
W
TABLE THE HOURLY T RATING OF THE nREsToP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE
OF THE CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH, IT IS W CV) C
INSTM, AS TABULATED BELOW: w
MAX CONDUIT ANNULAR SPACE, F RATING, HR. T RATING, HR. x 2 ;
CL
DIAM, IN. IN. L 0 <
1 0 TO 3/16 1 OR 2 0, 1 OR 2 1 J 2 =)
1 1/4 TO 1/2 3 OR 4 3 OR 4 C14
4 0 TO 1-1/2 1 OR 2 0 (0
6 1/4 TO 1/2 3 OR 0
CL
12 3/16 TO 3/8 1 OR 2 0 w
CONDUIT PENETRATION OF FIREWALL 2 0
UL SYSTEM NO. W-L-1=
0
4
2
Seal
A 65156
P
65156
NOTES: ATE ®s
Q WALL ASSEMBLY - THE 1, 2, 3, OR 4 HOUR FIRE-RATED MUM WALLBOARD/STUD WALL ASSEMBLY SHALI. BE CONSTRUCTED
OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL 0300 OR U400 SERIES WALL OR PARTITION
DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY. t ®d if
CABLES - MAX 4' DIAM TIGHT BUNDLE OF CABLES CENTERED IN CIRCULAR CUTOUTS IN GYPSUM WALLBOARD AND RIGIDLY
SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. ANY COMBINATION OF THE FOLLOWING TYPES AND SIZES OF COPPER CONDUCTOR Revision
CABLES MAY BE
USED:
A. MAX 350 KCMIL SINGLE CONDUCTOR POWER CABLES; CROSS-UNKED POLYETHYLENE (XLPE) OR
POLYVINYL CHLORIDE (PVC) INSULATION.
B. MAX 7/C NO. 12 AWG CABLES; PVC INSULATION AND JACKET.
C. MAX 3/C NO. 2/0 AWG MULTICONDUCTOR POWER AND CONTROL CABLES; XLPE OR PVC INSULATION, XLPE OR PVC JACKET.
D. MAX 200 PAIR NO. 24 AWG TELECOMMUNICATION CABLES; PVC INSULATION AND JACKET.
E MAX 6/94 FIBER OPTIC CABLE, PVC INSULATION AND JACKET.
FlU. VOID OR CAVITY MATERIAL - WRAP STRIP BEARING THE UL CLASSIFICATION MARKING -NOM 1/4* THICK INTUMESCENT
ELASTOMERIC MATERIAL FACED ON ONE SIDE WITH ALUMINUM FOIL, SUPPLIED IN NOM 2- WIDE STRIPS. NOM 2- WIDE STRIP Project Number
TIGHTLY WRAPPED AROUND CABLE BUNDLE (FOIL SIDE OUT) WITH SEAM BUTTED. WRAP STRIP LAYER SECURELY BOUND
WITH STEEL WRIE TIE AND SLID INTO ANNULAR SPACE APPROX 1-1/4- SUCH THAT APPROX 3,/4" OF THE WRAP STRIP 10-036B
PROTRUDES FROM THE WALL SURFACE ON EACH SIDE OF THE ASSEMBLY.
Date
DESIGN STANDARDS AND INTENT. IF A CONFLICT Q FILL VOID OR CAVITY MATERIAL - CAULK OR PUTTY BEARING THE UL CLASSIFICATION MARIONG - MIN i/4" DiAM
OCCURS WITH THE ARCHITECTURAL PLANS, CONTINUOUS BEAD OF CAULK OR PUTTY APPLIED TO THE WRAP STRIP/WALL INTERFACE AND TO THE EXPOSED EDGE OF THE MARCH, 2011
CONTRACTOR SHALL CONTACT ME ARCHITECT WRAP STRIP APPROX 3/4- FROM THE WALL SURFACE ON EACH SIDE OF THE WALL ASSEMBLY. CAULK OR PUTTY TO BE FORCED
INTO THE INTERSTICES OF THE CABLE BUNDLE TO THE MAX EXTENT POSSIBLE WITHIN THE
CONFINES OF THE WRAP STRIP ON EACH SIDE OF THE WALL ASSEMBLY. Sheet "Tie p4l�
CABLE PENETRATION OF FIREWALL ELEC DETAILE" *24f*
4 3 DAIS UL SYSTEM NO. W-L-=0 AND SCHEDU
Drawn by, TLC
Chocked by, TLC
ShostAumber,
�Zum=
MAIN BREAKER: 150 AMPS
MAIN LUGS: AMPS
K.A.I.C.:-AMPS
SURFACE MTD: X
FLUSH MTD.
TOTAL CONNECTED LOAD: 16.1 KVA
TOTAL DEMAND LOAD: 17.3 KVA
DEMANDAMPS: 48.1 AMPS
I
Ln 1. NEW LOAD ON EXISTING CIRCUIT BREAKER. EACH CIRCUIT REQUIRES A DEDICATED NEUTRAL AND MUST BE REINSTALLED BACK TO THE SOURCE. --j
K90
DATA CAM
ARE
NOTE.
CONTRACTOR TO PROVIDE CONDUIT AND
SINGLE GANG BOX- OWNER'S IT
DEPARTMENT TO PROVIDE WIRING AND
FACE PLATES.
6 7
5 :40110,T-U-2
TYPICAL VOICE / DATA OUTLET 5
No Scale I
F(9' -o A.F.F. - VERIFY
W/AR(>L PLANS AS
PER ROOM LOCATION)
TAGGED NOTES:
(D 42- A.F.F. W/ 36- COURIER,
39- AFT. W/ 30- CDUNTER,
48* A.F.F. W W COUNTER
OR AS NOTED ON PLANS I
MOUNTING HEIGHTS
No Scale
ITC-0
(1) 3/4•C. FOR
(1) 3/4-C. FOR CABLE TV
CEILING TO ACCESSIBLE I
CORRIDOR I
E1-L A
edward lewlst Yf
architects
V" t'4
CABLE TV/ POWER OUTLET DETAIL
Vo Qi,-gle
ri °iii
9024 SW 152 STREET
PALMETTO BAY, FL 33157
PH: (305) 234-0576
EDWARD LEWIS ARCHITECTS, INC.
AAC001678
C. EDWARD LEWIS AR 0009567
m/E/F Engineer
to255 S. Orange Avenue
Suite 1600'
Orlando, Florida 32801
Phone: 407-841-9050
EN G I N E E R I N G 07-540 -0234
FOR ARCHITECTURE WWW.tic-eng,neers. orn
Q Copyright 2010 TLC Engineering for Architecture, Inc.
EB J0000015 TLC N0 :111403
Structural En*oor
2
Z
0
Z .5
M05;
a CY)
0
'4
-anew Nw—, 0
NOTES- 0 0 :2
WALL ASSEMBLY - THE 1, 2. 3, OR 4 HOUR FIRE RATED GYPSUM WALLBQM/STUD;'WALL J
ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE LU LL LE
in � -0 M -4 E
INDIVIDUAL 0300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RMISfANdE-
DIRECTORY.
cc
CONDUIT - NOM 4* DIA OR smim STEEL ELECTRICAL MEIN= TUBING. A MAX PF ONE 3:
CONDUIT IS PERMITTED IN THE FIRESTOP SYSTEM. CONDUIT TO BE INSTALLED NEAKU= _OF _--,— J
STUD CAVITY WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASS
0
FILL VOID OR CAVITY MATERIAL - CAULK FILL MATERIAL BEARING THE UL CLASSITA NG
INSTALLED To COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT M
WALLBOARD AND WITH A MIN lle DIAM BEAD OF CAULK APPLIED TO PERIMETER OF CONDUIT AT i. LLYY
ITS EGRESS FROM THE WALL CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES C WALL a)
It
ASSEMBLY. THE HOURLY F RATING OF THE nRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY w q
FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE' FOLLOWING 0
W
TABLE THE HOURLY T RATING OF THE nREsToP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE
OF THE CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH, IT IS W CV) C
INSTM, AS TABULATED BELOW: w
MAX CONDUIT ANNULAR SPACE, F RATING, HR. T RATING, HR. x 2 ;
CL
DIAM, IN. IN. L 0 <
1 0 TO 3/16 1 OR 2 0, 1 OR 2 1 J 2 =)
1 1/4 TO 1/2 3 OR 4 3 OR 4 C14
4 0 TO 1-1/2 1 OR 2 0 (0
6 1/4 TO 1/2 3 OR 0
CL
12 3/16 TO 3/8 1 OR 2 0 w
CONDUIT PENETRATION OF FIREWALL 2 0
UL SYSTEM NO. W-L-1=
0
4
2
Seal
A 65156
P
65156
NOTES: ATE ®s
Q WALL ASSEMBLY - THE 1, 2, 3, OR 4 HOUR FIRE-RATED MUM WALLBOARD/STUD WALL ASSEMBLY SHALI. BE CONSTRUCTED
OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL 0300 OR U400 SERIES WALL OR PARTITION
DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY. t ®d if
CABLES - MAX 4' DIAM TIGHT BUNDLE OF CABLES CENTERED IN CIRCULAR CUTOUTS IN GYPSUM WALLBOARD AND RIGIDLY
SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. ANY COMBINATION OF THE FOLLOWING TYPES AND SIZES OF COPPER CONDUCTOR Revision
CABLES MAY BE
USED:
A. MAX 350 KCMIL SINGLE CONDUCTOR POWER CABLES; CROSS-UNKED POLYETHYLENE (XLPE) OR
POLYVINYL CHLORIDE (PVC) INSULATION.
B. MAX 7/C NO. 12 AWG CABLES; PVC INSULATION AND JACKET.
C. MAX 3/C NO. 2/0 AWG MULTICONDUCTOR POWER AND CONTROL CABLES; XLPE OR PVC INSULATION, XLPE OR PVC JACKET.
D. MAX 200 PAIR NO. 24 AWG TELECOMMUNICATION CABLES; PVC INSULATION AND JACKET.
E MAX 6/94 FIBER OPTIC CABLE, PVC INSULATION AND JACKET.
FlU. VOID OR CAVITY MATERIAL - WRAP STRIP BEARING THE UL CLASSIFICATION MARKING -NOM 1/4* THICK INTUMESCENT
ELASTOMERIC MATERIAL FACED ON ONE SIDE WITH ALUMINUM FOIL, SUPPLIED IN NOM 2- WIDE STRIPS. NOM 2- WIDE STRIP Project Number
TIGHTLY WRAPPED AROUND CABLE BUNDLE (FOIL SIDE OUT) WITH SEAM BUTTED. WRAP STRIP LAYER SECURELY BOUND
WITH STEEL WRIE TIE AND SLID INTO ANNULAR SPACE APPROX 1-1/4- SUCH THAT APPROX 3,/4" OF THE WRAP STRIP 10-036B
PROTRUDES FROM THE WALL SURFACE ON EACH SIDE OF THE ASSEMBLY.
Date
DESIGN STANDARDS AND INTENT. IF A CONFLICT Q FILL VOID OR CAVITY MATERIAL - CAULK OR PUTTY BEARING THE UL CLASSIFICATION MARIONG - MIN i/4" DiAM
OCCURS WITH THE ARCHITECTURAL PLANS, CONTINUOUS BEAD OF CAULK OR PUTTY APPLIED TO THE WRAP STRIP/WALL INTERFACE AND TO THE EXPOSED EDGE OF THE MARCH, 2011
CONTRACTOR SHALL CONTACT ME ARCHITECT WRAP STRIP APPROX 3/4- FROM THE WALL SURFACE ON EACH SIDE OF THE WALL ASSEMBLY. CAULK OR PUTTY TO BE FORCED
INTO THE INTERSTICES OF THE CABLE BUNDLE TO THE MAX EXTENT POSSIBLE WITHIN THE
CONFINES OF THE WRAP STRIP ON EACH SIDE OF THE WALL ASSEMBLY. Sheet "Tie p4l�
CABLE PENETRATION OF FIREWALL ELEC DETAILE" *24f*
4 3 DAIS UL SYSTEM NO. W-L-=0 AND SCHEDU
Drawn by, TLC
Chocked by, TLC
ShostAumber,