GENERAL NOTES:
1. ALL WORK MUST BE DONE IN ACCORDANCE WITH THE APPLICABLE LOCAL
BUILDING DEPARTMENT, NFPA RECOMMENDATIONS AND COMPLYINC WITH THE
RECOMMENDA11ONS OF INDUSTRIAL RISK INSURERS.
2. ALL VALVES CONTROLLING WATER SUPPLIES FOR SPRINKLER SYSTEM OR
PORTIONS THEREOF SHALL NOT BE LOCATED MORE THAN 7' -0" ABOVE THE
FLOOR.
3. SPARE SPRINKLER HEADS AND WRENCHES SHALL BE PROVIDED IN ACCORDANCE
WITH N.F.P.A. 13.
4. FITTINGS TO BE ABLE TO WITHSTAND THE WORKING PRESSURES INVOLVED BUT
NOT LESS THAN 173 PSI COLD WATER. FITTINGS SHALL COMPLY WITH ANSI
STANDARDS. ALL FITTINGS SHALL BE FROM SAME MANUFACTURER.
5. ALL CONCEALED PIPING SHALL BE XL /SCH -10 BLACK ASTM 135 PIPING OR
EQUAL
6. ALL EXPOSED PIPING SHALL BE XL /SCH -10 BLACK ASTM 135 OR EQUAL
7. ALL WORK SHALL COORDINATE WITH ALL OTHER TRADES TO AVOID
INTERFERENCE WITH THE PROGRESS OF CONSTRUC11ON AND REPORT ANY
DISCREPANCIES TO THE RCHITECT /ENGINEER.
8. ALL PIPING SHALL BE SUPPORTED BY MEANS OF HANGERS TESTED AND LISTED
AND APPROVED BY U.L AND /OR FM. SIZING, SPACING, AND INSTALLATION
SHALL BE IN ACCORDANCE WITH NATIONAL FIRE PROTECTION ASSOCIATION
STANDARD No. 13 SPRINKLER SYSTEMS, EXCEPT AS OTHERWISE SHOWN ON
DRAWINGS OR SPECIFIED HEREIN.
9. PRESSURE TEST AND FLUSH THE SYSTEM IN ACCORDANCE WITH N.F.P.A. 13
REQUIREMENTS.
10. ALL PIPE 1" XL /SCH -10 BLACK ASTM 135 UNLESS OTHERWISE NOTED.
SCOPE OF WORK:
1. INSTALLATION AND RELOCATION OF SPRINKLER HEADS TO
ACCOMODATE INTERIOR CHANGES.. DEMOLISH AND REINSTALL FIRE
MAIN IN CORRIDOC 03CO4.
LEGEND:
O NEW/RELOCATED PENDENT SPRINKLER HEAD
® EXISTING SPRINKLER HEAD TO REMAIN
EXISTING PIPING TO REMAIN
NEW PIPING tNWEMR
NO2 EDITION E ,ASPERN
MOQIC A IONS THAT P,;-: ISOLATED,
L NOT REQUIRE PIPE TO BE REMOVED AS RELOCATED DROPS WORKING PRESSURE TESTING
j"tj=SS OF SYSTEM
APPROVED
MIAMI.DAT:F COTU TY FIRE DEPARTMENT
BLOG.:'EPMIT. __ FIRE ALAAM
FIFE SU PR SIGN WAT // � EXT.
�i ! C%
DATE: O � � � SY
KEYPLAN
NOT TO SCALE
Wj_GNIS UTELA, Inc
7M5 NW 41 St
Lf" FL MID
TOO 054} M-cm
FOL SM M-MG
www.itifire.com
These drawings are prepared by Igrds Tutela for the
exdustva usa of Ignls Tutela and Its dlerd PsW below. No
use or dupllcatlon of these drwMngs Is pan tted whhout
prior written perrnlsslon from Ignla Tutela or Me dlent.
W
CO)
Z
■
•
f\ 7
■ 1.
•
•
REVISIONS DATE
Submit for Approval 6 -22 -11
FP�2.0
i vy