11-829-001GENERAL NOTES:
1. ALL WORK MUST BE DONE IN ACCORDANCE WITH THE APPLICABLE LOCAL
BUILDING DEPARTMENT, NFPA RECOMMENDATIONS AND COMPLYINC WITH THE
RECOMMENDA11ONS OF INDUSTRIAL RISK INSURERS.
2. ALL VALVES CONTROLLING WATER SUPPLIES FOR SPRINKLER SYSTEM OR
PORTIONS THEREOF SHALL NOT BE LOCATED MORE THAN 7r -0" ABOVE THE
FLOOR.
3. SPARE SPRINKLER HEADS AND WRENCHES SHALL BE PROVIDED IN ACCORDANCE
WITH N.F.P.A. 13.
I 4. FITTINGS TO BE ABLE TO WITHSTAND THE WORKING PRESSURES INVOLVED BUT
NOT LESS THAN 175 PSI COLD WATER. FITTINGS SHALL COMPLY WTI] ANSI
STANDARDS. ALL FITTINGS SHALL BE FROM SAME MANUFACTURER.
5. ALL CONCEALED PIPING SHALL BE XL /SCH -10 BLACK ASTM 135 PIP;1:G OR
EQUAL
6. ALL EXPOSED PIPING SHALL BE XL /SCH -10 BLACK ASTM 135 OR EQUAL
7. ALL WORK SHALL COORDINATE WITH ALL OTHER TRADES TO AVOID
INTERFERENCE WITH THE PROGRESS OF CONSTRUC11ON AND REPORT ANY
DISCREPANCIES TO THE RCHITECT /ENGINEER.
8. ALL PIPING SHALL BE SUPPORTED BY MEANS OF HANGERS TESTED AND LISTED
AND APPROVED BY U.L. AND /OR FM. SIZING, SPACING, AND INSTALLATION
SHALL BE IN ACCORDANCE WITH NATIONAL FIRE PROTECTION ASSOCIATION
STANDARD No. 13 SPRINKLER SYSTEMS, EXCEPT AS OTHERWISE SHOWN ON
DRAWINGS OR SPECIFIED HEREIN.
9. PRESSURE TEST AND FLUSH IdE SYSTEM IN ACCORDANCE WITH N.F.P.A. 13
REQUIREMENTS.
10. ALL PIPE 1" XL /SCH -10 BLACK ASTM 135 UNLESS OTHERWISE NOTII_C.
SPRINKLER HEAD SCHEDULE
QTY
MFR.
MODEL NO.
ORIFICE
SIZE
TEMP.
RATING
K
DESCRIPTION
13
TY3531
1/2
155
5.6
QUICK RESPONSE CONCEALED PENDENT
SPRINKLER
4
ITEMS
3�8
3/4
4 1/4
—1 1/4
1/2" THRU 2"
1
3/8" x 2 1/2" HEX HEAD
_
N
1 1/4
4 1/2
-1 1/2
"
1 1/2
4 3/4
-1 1/2
"
2
5
-1 3/4
"
1 /2
rlmsS En CEILING
SRINKLER ARMOVER (TYP)
Not to Scale
COMPONENTS
1. EYE ROD
2. FLAT WASHER
3. HEX HEAD CAP SCREW
4. ADJUSTABLE HANGER
RING
5. DROP —IN ANCHOR
6. HEX HEAD LAG SCREW
7. EXPANSION CASE
B. LOCK WASHER
9. HEX NUT
FOR BRICK
DESIGN DATA '=OR EYE ROD HANGER
NOMINAL
MINIMUM
HANGER
ROD
PIPE
A DIME14SION
TAKEOUT
DIAMETER
SIZE
INCHES
INCHES
INCHES
1/2
4
ITEMS
3�8
3/4
4 1/4
—1 1/4
1/2" THRU 2"
1
3/8" x 2 1/2" HEX HEAD
_
N
1 1/4
4 1/2
-1 1/2
"
1 1/2
4 3/4
-1 1/2
"
2
5
-1 3/4
"
1 /2
1
"
3
6 3/4
-2 1 %2
3/8" x 1" HEX HEAD
4
7 1%4
-3
"
5
8
-3 3/4
1e2
6
9
-4 1/4
8s
10 1/
-6
"
• TO COMPLY WrrH NFPA 13. THE ROD FOR AN d' HANGER IS
PROVIDED WRH A WELDED EYE.
FOR CONCRETE
• NFPA 13 SETS MINIMUM DISTANCES FOR PLACEMENT OF FASTENERS ABOVE THE BOTTOM OF REAMS OR JOISIS.
WOOD: 21/2" MINIMUM FOR BRANCH LINES (PIPE SIZES 2" SMALLER)
3" MINIMUM FOR MAINS (PIPE SIZES 2 1/2" & LARGER)
CONCRETE: DISTANCES AS REQUIRED TO PLACE THE FASTENER ABOVE THE CENTERLINE OF THE BEAM OR ABOVE THE BOTTOM
REINFORCEMENT STEEL
STANDARD FASTENERS FOR EYE ROD HANGERS
NOMINAL
WOOD
BRICK
CONCRETE
STEEL
PIPE SIZES
`
716 NW 41St
�o
u {
1
�
QTY
ITEMS
QTY
ITEMS
QTY
ITEMS
QTY
ITEMS
1/2" THRU 2"
1
3/8" x 2 1/2" HEX HEAD
1
3/8" EXPANSION CASE
1
3/8 "DROP —IN ANCHOR
1
3/8" x 1 1/2" HEX HEAD
LAG SCREW
1
3/8" x 2" HEX HEAD
—HILTI HDI 3/8"
CAP SCREW
1
3/8" FLAT WASHER
CAP SCREW
1
3/8" x 1" HEX HEAD
1
3/8" HEX NUT
1
3/8" FLAT WASHER
CAP SCREW
1
3/8" LOCK WASHER
1
3/8" FLAT WASHER
2 1/2" THRU 6
1
1/2" x 3" HEX HEAD
1
1/2" EXPANSION CASE
1
1/2 "DROP —IN ANCHOR
1
1/2" x 2" HEX HEAD
LAG SCREW
1
1/2" x 2 1/2" HEX
—HILTI HDI 1/2"
CAP SCREW
1
1/2" FLAT WASHER
HEAD CAP SCREW
1
1/2" x 1 1/4" HEX
1
1/2" HEX NUT
1
1/2" FLAT WASHER
HEAD CAP SCREW
1
1/2" LOCK WASHER
1
1/2" FLAT WASHER
B"
1
5/8"x 3" SQUARE HEAD
1
5/8" EXPANSION CASE
1
5/8-DROP—IN ANCHOR
1
5/8" x 2 1/2" HEX HEAD
LAG SCREW
1
5/8" x 2 3/4" HEX
—HILTI HDI 5/8"
CAP SCREW
1
5/8" FLAT WASHER
HEAD CAP SCREW
1
5/8" x1 1/2" HEX
1
5/8" HEX NUT
1
5/8" FLAT WASHER
HEAD CAP SCREW
1
5/8" LOCK WASHER
1
5/8" FLAT WASHER
HANGER DETAIL
Not to Scale
STRUCTURAL
STEEL
T.B.C.
A.T.R.
ADJUSTABLE
SWIVEL RING
SPRINKLER
PIPE
EYE ROD PIPE HANGER
CONCRETE DECK ' a :. '
DROP -IN ANCHOR
A.T.R.
ADJUSTABLE
SWIVEL RING
SPRINKLER
PIPE
ical Hanger Details
NOT TO SCALE
:CONCRETE DECK
POWDER DRIVEN
THREADED STUD
ROD COUPLING
A.T.R.
ADJUSTABLE
SWIVEL RING_
SPRINKLER
PIPE
INSPECTOR
AS-PER NFPA Q 2002 EOITICN SECTION 16.2.1.6
MOQIEICATIONS 1E ISOLATED, SUGH
AS, RELOCATED DROPS SHALL NOT REQUIRE TE =STING
IN•>00(QESS OF SYSTEM WORKING PRESSURE
APPROVED
MIAMI -DADE C0U'1%11`w' FIRE DEPARTMENT
BLDG. PERMI i� FIRE ALARM
FIRES
U ;7�'SION WATE
DATE: 6 ! / Er
W
co
Z
W=
8-13
co
�y
0
REVISIONS DATE
Submit for App Nyd 5 -22-:1
Fe7=7.L
C = _' •
FP -1.0
4
A
IGNIS L1TEL.A, Inc
`
716 NW 41St
�o
u {
1
�
� M
r
.1 Y:�
dtlddd
f" -Me
www.itifire.com
These drawings are prepared by IgNs Tldela far the
exclushre use of Ignis Tutela and Its dlerd Gated below. No
use or dupllcatton of these drawings Is pennGDed without
prior vmMen permisston from Ignls T ubsta Cr the Client
INSPECTOR
AS-PER NFPA Q 2002 EOITICN SECTION 16.2.1.6
MOQIEICATIONS 1E ISOLATED, SUGH
AS, RELOCATED DROPS SHALL NOT REQUIRE TE =STING
IN•>00(QESS OF SYSTEM WORKING PRESSURE
APPROVED
MIAMI -DADE C0U'1%11`w' FIRE DEPARTMENT
BLDG. PERMI i� FIRE ALARM
FIRES
U ;7�'SION WATE
DATE: 6 ! / Er
W
co
Z
W=
8-13
co
�y
0
REVISIONS DATE
Submit for App Nyd 5 -22-:1
Fe7=7.L
C = _' •
FP -1.0
4
A