Loading...
11-829-001GENERAL NOTES: 1. ALL WORK MUST BE DONE IN ACCORDANCE WITH THE APPLICABLE LOCAL BUILDING DEPARTMENT, NFPA RECOMMENDATIONS AND COMPLYINC WITH THE RECOMMENDA11ONS OF INDUSTRIAL RISK INSURERS. 2. ALL VALVES CONTROLLING WATER SUPPLIES FOR SPRINKLER SYSTEM OR PORTIONS THEREOF SHALL NOT BE LOCATED MORE THAN 7r -0" ABOVE THE FLOOR. 3. SPARE SPRINKLER HEADS AND WRENCHES SHALL BE PROVIDED IN ACCORDANCE WITH N.F.P.A. 13. I 4. FITTINGS TO BE ABLE TO WITHSTAND THE WORKING PRESSURES INVOLVED BUT NOT LESS THAN 175 PSI COLD WATER. FITTINGS SHALL COMPLY WTI] ANSI STANDARDS. ALL FITTINGS SHALL BE FROM SAME MANUFACTURER. 5. ALL CONCEALED PIPING SHALL BE XL /SCH -10 BLACK ASTM 135 PIP;1:G OR EQUAL 6. ALL EXPOSED PIPING SHALL BE XL /SCH -10 BLACK ASTM 135 OR EQUAL 7. ALL WORK SHALL COORDINATE WITH ALL OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUC11ON AND REPORT ANY DISCREPANCIES TO THE RCHITECT /ENGINEER. 8. ALL PIPING SHALL BE SUPPORTED BY MEANS OF HANGERS TESTED AND LISTED AND APPROVED BY U.L. AND /OR FM. SIZING, SPACING, AND INSTALLATION SHALL BE IN ACCORDANCE WITH NATIONAL FIRE PROTECTION ASSOCIATION STANDARD No. 13 SPRINKLER SYSTEMS, EXCEPT AS OTHERWISE SHOWN ON DRAWINGS OR SPECIFIED HEREIN. 9. PRESSURE TEST AND FLUSH IdE SYSTEM IN ACCORDANCE WITH N.F.P.A. 13 REQUIREMENTS. 10. ALL PIPE 1" XL /SCH -10 BLACK ASTM 135 UNLESS OTHERWISE NOTII_C. SPRINKLER HEAD SCHEDULE QTY MFR. MODEL NO. ORIFICE SIZE TEMP. RATING K DESCRIPTION 13 TY3531 1/2 155 5.6 QUICK RESPONSE CONCEALED PENDENT SPRINKLER 4 ITEMS 3�8 3/4 4 1/4 —1 1/4 1/2" THRU 2" 1 3/8" x 2 1/2" HEX HEAD _ N 1 1/4 4 1/2 -1 1/2 " 1 1/2 4 3/4 -1 1/2 " 2 5 -1 3/4 " 1 /2 rlmsS En CEILING SRINKLER ARMOVER (TYP) Not to Scale COMPONENTS 1. EYE ROD 2. FLAT WASHER 3. HEX HEAD CAP SCREW 4. ADJUSTABLE HANGER RING 5. DROP —IN ANCHOR 6. HEX HEAD LAG SCREW 7. EXPANSION CASE B. LOCK WASHER 9. HEX NUT FOR BRICK DESIGN DATA '=OR EYE ROD HANGER NOMINAL MINIMUM HANGER ROD PIPE A DIME14SION TAKEOUT DIAMETER SIZE INCHES INCHES INCHES 1/2 4 ITEMS 3�8 3/4 4 1/4 —1 1/4 1/2" THRU 2" 1 3/8" x 2 1/2" HEX HEAD _ N 1 1/4 4 1/2 -1 1/2 " 1 1/2 4 3/4 -1 1/2 " 2 5 -1 3/4 " 1 /2 1 " 3 6 3/4 -2 1 %2 3/8" x 1" HEX HEAD 4 7 1%4 -3 " 5 8 -3 3/4 1e2 6 9 -4 1/4 8s 10 1/ -6 " • TO COMPLY WrrH NFPA 13. THE ROD FOR AN d' HANGER IS PROVIDED WRH A WELDED EYE. FOR CONCRETE • NFPA 13 SETS MINIMUM DISTANCES FOR PLACEMENT OF FASTENERS ABOVE THE BOTTOM OF REAMS OR JOISIS. WOOD: 21/2" MINIMUM FOR BRANCH LINES (PIPE SIZES 2" SMALLER) 3" MINIMUM FOR MAINS (PIPE SIZES 2 1/2" & LARGER) CONCRETE: DISTANCES AS REQUIRED TO PLACE THE FASTENER ABOVE THE CENTERLINE OF THE BEAM OR ABOVE THE BOTTOM REINFORCEMENT STEEL STANDARD FASTENERS FOR EYE ROD HANGERS NOMINAL WOOD BRICK CONCRETE STEEL PIPE SIZES ` 716 NW 41St �o u { 1 � QTY ITEMS QTY ITEMS QTY ITEMS QTY ITEMS 1/2" THRU 2" 1 3/8" x 2 1/2" HEX HEAD 1 3/8" EXPANSION CASE 1 3/8 "DROP —IN ANCHOR 1 3/8" x 1 1/2" HEX HEAD LAG SCREW 1 3/8" x 2" HEX HEAD —HILTI HDI 3/8" CAP SCREW 1 3/8" FLAT WASHER CAP SCREW 1 3/8" x 1" HEX HEAD 1 3/8" HEX NUT 1 3/8" FLAT WASHER CAP SCREW 1 3/8" LOCK WASHER 1 3/8" FLAT WASHER 2 1/2" THRU 6 1 1/2" x 3" HEX HEAD 1 1/2" EXPANSION CASE 1 1/2 "DROP —IN ANCHOR 1 1/2" x 2" HEX HEAD LAG SCREW 1 1/2" x 2 1/2" HEX —HILTI HDI 1/2" CAP SCREW 1 1/2" FLAT WASHER HEAD CAP SCREW 1 1/2" x 1 1/4" HEX 1 1/2" HEX NUT 1 1/2" FLAT WASHER HEAD CAP SCREW 1 1/2" LOCK WASHER 1 1/2" FLAT WASHER B" 1 5/8"x 3" SQUARE HEAD 1 5/8" EXPANSION CASE 1 5/8-DROP—IN ANCHOR 1 5/8" x 2 1/2" HEX HEAD LAG SCREW 1 5/8" x 2 3/4" HEX —HILTI HDI 5/8" CAP SCREW 1 5/8" FLAT WASHER HEAD CAP SCREW 1 5/8" x1 1/2" HEX 1 5/8" HEX NUT 1 5/8" FLAT WASHER HEAD CAP SCREW 1 5/8" LOCK WASHER 1 5/8" FLAT WASHER HANGER DETAIL Not to Scale STRUCTURAL STEEL T.B.C. A.T.R. ADJUSTABLE SWIVEL RING SPRINKLER PIPE EYE ROD PIPE HANGER CONCRETE DECK ' a :. ' DROP -IN ANCHOR A.T.R. ADJUSTABLE SWIVEL RING SPRINKLER PIPE ical Hanger Details NOT TO SCALE :CONCRETE DECK POWDER DRIVEN THREADED STUD ROD COUPLING A.T.R. ADJUSTABLE SWIVEL RING_ SPRINKLER PIPE INSPECTOR AS-PER NFPA Q 2002 EOITICN SECTION 16.2.1.6 MOQIEICATIONS 1E ISOLATED, SUGH AS, RELOCATED DROPS SHALL NOT REQUIRE TE =STING IN•>00(QESS OF SYSTEM WORKING PRESSURE APPROVED MIAMI -DADE C0U'1%11`w' FIRE DEPARTMENT BLDG. PERMI i� FIRE ALARM FIRES U ;7�'SION WATE DATE: 6 ! / Er W co Z W= 8-13 co �y 0 REVISIONS DATE Submit for App Nyd 5 -22-:1 Fe7=7.L C = _' • FP -1.0 4 A IGNIS L1TEL.A, Inc ` 716 NW 41St �o u { 1 � � M r .1 Y:� dtlddd f" -Me www.itifire.com These drawings are prepared by IgNs Tldela far the exclushre use of Ignis Tutela and Its dlerd Gated below. No use or dupllcatton of these drawings Is pennGDed without prior vmMen permisston from Ignls T ubsta Cr the Client INSPECTOR AS-PER NFPA Q 2002 EOITICN SECTION 16.2.1.6 MOQIEICATIONS 1E ISOLATED, SUGH AS, RELOCATED DROPS SHALL NOT REQUIRE TE =STING IN•>00(QESS OF SYSTEM WORKING PRESSURE APPROVED MIAMI -DADE C0U'1%11`w' FIRE DEPARTMENT BLDG. PERMI i� FIRE ALARM FIRES U ;7�'SION WATE DATE: 6 ! / Er W co Z W= 8-13 co �y 0 REVISIONS DATE Submit for App Nyd 5 -22-:1 Fe7=7.L C = _' • FP -1.0 4 A