11-382-038GROUN
GROUND
HOT
NEUTRAL
NEUTRAL
HOT
r
0
Q
RESET
p
NOTE:
p
WIRE GFI DEVICE SUCH THAT
II
THE DOWNSTREAM DEVICES ARE NOT
AFFECTED BY GROUND FAULT
INTERRUPTION. IE. NON FEED THRU.
EACH GFI DEVICE SHALL BE SELF
PROTECTING ONLY.
GFIRECEPTACLE
0 WIRING DIAGRAM
NO SCALE
*REFER TO SPECIFICATIONS FOR FURTHER REQUIREMENTS
EXAMPLES ONLY:
EQUIPMENT SYSTEM
'4EQL1'
208V 120V
FED FROM 'ATS 4EOL1'
NORMAL SYSTEM
'EF -5'
120V
FED FROM '4NL1 -28'
GREEN HEX HEAD
GROUNDING SCREW
GROUNDED METAL
OUTLET BOX
BONDING JUMPER
UILDING GROUND
-REEK WIRE)
STANDARD" RECEPTACLE
02NOSCALE
GROUNDING DEI'A!L
CRITICAL BRANCH
'ATS- -4CL1'
208V/120
FED FROM '4NLD1' NORMAL
FED FROM '4ESLD1' EMERGENCY
FEEDS '4CL1'
E IPM .E I NT IDEIgTI � AT'ION LABEL DETAIL
o%5,
NO SCALE
IL
w
ry
X
I
ATTACH J-1OX TO HANGER WIRE THAT SECURED
AT THE STRUCTURE.
CEILING HANGER WIRE --
FIXTURE SUPPORT- -
HANGER WIRE MINIMUM
OF 2 PER FIXTURE, AT
OPPOSITE CORNERS.
SEPARATE FROM CEILING
SUPPORTS,
LIGHT FIXTURE OR OTHER
CEILING MOUNTED EQUIPMENT
SUPPORT CONDUIT
WITHIN 3 FT. OF J--BOX
AND AT 11D FT,
INTERVALS.
LENGTH SUPPORT WHIPS WITHIN 12 IN.
FROM J—SOX AND AT 4 1/2 FT.
INTERVAL WITH HANGER WIRE AND
APPROVED CUPS. FIXTURE SHALL NOT
BE USED AS THROUGH WIRE WATS.
LAY-11V FIXTURE I OUN ow DETAIL
03NOSCALE
\\—FINISH CEILING
I
I
IT��1 1
1 I ®M
O
FINISH FLOOR
MAM INIMEACE FJ EMICAL NOTES•
OLOCATION OF WALL MOUNTED FAUCET CONTROLLER PROVIDED UNDER DIV 22.
COORDINATE CONTROLLER LOCATION BETWEEN TRADES PRIOR TO ELECTRICAL
ROUGH —IN.
OPROVIDE GFCI RECEPTACLE FOR 6VDC PLUG —IN TRANSFORMER. TRANSFORMER
PROVIDED UNDER DIV 22. RECEPTACLE SHALL BE MOUNTED IMMEDIATLY AJACENT TO
(WITHIN 6 INCHES) FAUCET CONTROLLER TO LIMIT CORD DISTANCE. AFTER
INSTALLATION OF CONTR011 AND TRANSFORMER, COIL EXCESS CORD AND TIE INTO
A NEAT BUNDLE. CORD SHOULD NOT DRAPE TO FLOOR.
or-tTYPICAL LP!Ai4R( OR SINK SENSOR FAUCET RECEPTACLE DE141L
NO SCALE
r1111, �` "oeoo�
1212 de Leon Qlvd., Suite 350
Coral Gables, FL 33134
Professional Consulting Engineers phone: 305.569.1692
fax: 305.569.1693
Austin Dallas - Denver • Houston - Nashville
Miami Phoenix Richmond - Washington D.C.
ccrd project number: 410393.000
E- 1300007658
l PIPE PENETRATION
PIPE PENETRATION —"= FOR EXPOSED AREA
FOR EXPOSED AREA
j INTERIOR WALL
CUT SMOOTH HOLE
PACK TIGHT W /FIRE SAFING
CHROME PIPE COLLAR--,-----+— SCHEDULE 40 PIPE SLEEVE
PROVIDE 1" MINIMUM CLEARANCE
1' THICK 3M —FIRE STOP OR EQUAL
U.S. GYPSUM THFRMA —FIBER
/ Ll' OUND ALL PIPES (TYPICAL)
U.L. SYSTEM NO. W —L -1054 /
F RATING — 1 HOUR AND 2 HOUR MINIMUM
T RATING — 0 HOUR
0 FIRE PENETRATION D'��TAIL
4SCALE:NTS
OWNER
BAPTIST HEALTH SOUTH FLORIDA
6865 RED ROAD
CORAL GABLES, FLORIDA 33146
ARCHITECT
FL AA F000119
HKS ARCHITECTS, INC.
1221 BRICKELL AVENUE, SUITE 1220
MIAMI, FL 33131
M.E.P. ENGINEERS
CCRD PARTNERS
2121 PONCE DE LEON BOULEVARD
SUITE 350
CORAL GABLES, FL 33134
INTERIORS
IN.DESIGN, INC.
2080 NVV BOCA RATON BOULEVARD
SUITE 3
BOCA RATON, FL 33146
KEY PLAN
��1��»t�tuinnhf
: I`,f '. 705 ;.:1
�0
���itttttn1m110
REVISION
HKS PROJECT NUMBER
14262.000
DATE
04.11.2011
ISSUE
BIDDING 8A
PERM 1171 Ill SEI"
SHEET TITLE
DETAILS)
SHEET NO.
9)2011 HKS, INC. lg:pi w 01''
E43 11
pmmm
M
u
CZ
o
F�
V'1
r�
KEY PLAN
��1��»t�tuinnhf
: I`,f '. 705 ;.:1
�0
���itttttn1m110
REVISION
HKS PROJECT NUMBER
14262.000
DATE
04.11.2011
ISSUE
BIDDING 8A
PERM 1171 Ill SEI"
SHEET TITLE
DETAILS)
SHEET NO.
9)2011 HKS, INC. lg:pi w 01''
E43 11