11-382-025MECHANICAL SYMBOLS
MECHANICAL
ABBREVIATIONS
YES
AC
ABOVE CEILING
ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.
HIGH PRESSURE CONDENSATE RETURN
SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
LOW PRESSURE STEAM
SYMBOL
DESCRIPTION
FCU
A
NEW EQUIPMENT DESIGNATION
DOMESTIC COLD WATER
#
(TOP - EQUIP. ABBREV., BOTTOM - MARK)
FAN POWERED BOX
DOMESTIC HOT WATER RETURN
FIRE STOPPING
NEW DIFFUSER DESIGNATION
ANALOG INPUT
e
(TOP - SCHEDULE DESIG., BOTTOM - CFM)
PUMPED SANITARY LINE
- - - - - -
NEW EQUIPMENT
4,896
FPI
FINS PER INCH
DIRECTION OF FLOW
B.
AO
EL3EXISTING
GATE VALVE
NONE
EQUIPMENT
HORIZONTAL
BALL VALVE
-- - -/•� --
GC
NEW DUCT
TEMPERATURE AND PRESSURE RELIEF VALVE
C.
BFC
EXISTING DUCT
AUTOMATIC 3 -WAY CONTROL VALVE
NONE
i
- -- ��
EXISTING DUCT TO BE REMOVED OR RELOCATED
SOLENOID VALVE
—��--
_J__J
GENERAL EXHAUST FAN
HYDRAULIC SHOCK ARRESTOR
<X:I+
®
NEW SUPPLY DIFFUSER
UNION
NONE
VACCUUM BREAKER
DO
EXISTING SUPPLY DIFFUSER
E
GSF
F -7
EXISTING SUPPLY DIFFUSER TO BE REMOVED OR RELOCATED
O
BG
BELOW GRADE
CLEANOUT OR WALL CLEANOUT
F.
PETE'S PLUG
NEW R/A OR EXHAUST GRILLE
BUTTERFLY VALVE
MVD
MANUAL VOLUME DAMPER
THERMOMETER WELL
EXISTING R/A OR EXHAUST GRILLE
CRU
COMPUTER ROOM UNIT
N
EXISTING R/A OR EXHAUST GRILLE TO BE REMOVED OR RELOCATED
CRU
CONDENSATE RETURN UNIT
OBD
OPPOSED BLADE DAMPER
ELECTRIC PNEUMATIC SWITCH
NEW SLOT DIFFUSER
PARTITION AND CEILING SYSTEM SUPPORTS. WHERE INDEPENDENT SUPPORT IS NOT POSSIBLE AN ENGINEERED SUPPORT
CU
-AAr
FLEXIBLE DUCT
RELOCATED
E.
FIELD VERIFY THE EXACT SIZES AND LOCATIONS OF ALL EXISTING DUCTWORK AND PIPING
PRIOR TO DEMOLITION OF ANY EXISTING WORK. THE DEMOUTION WORK SHALL BE
EXISTING SLOT DIFFUSER
DI
DIGITAL INPUT
--
EXISTING SLOT DIFFUSER TO BE REMOVED OR RELOCATED
HOSPITAL SCHEDULES, OCCUPANCIES, AND WORK.
OT
THERMOSTAT
DIGITAL OUTPUT
RCA
T;
EXISTING THERMOSTAT TO BE REMOVED OR RELOCATED
DS
DISCONNECT SWITCH
45' PRESSURE TAP W/ VOLUME DAMPER
RELIEF AIR
CONICAL TAP WITH VOLUME DAMPER
EXISTING
SA
-
CONICAL TAP W/O VOLUME DAMPER
EDH
J
MANUAL VOLUME DAMPER
UNIT HEATER
DUCTWORK THAT HAS MISSING OR DAMAGED INSULATION PER SPECIFICATIONS.
EUH
FIRE DAMPER
VAV
VARIABLE AIR VOLUME
L
SMOKE DAMPER
EXHAUST FAN
WH
WATER HEATER
FIRE /SMOKE DAMPER
SF
SUPPLY FAN
M
❑
MOTORIZED DAMPER
EA
EXHAUST AIR
BAROMETRIC DAMPER
FILTER MIXING BOX
ALL EXISTING DIFFUSERS, EQUIPMENT AND PIPING REMOVED DURING CONSTRUCTION SHALL
— CHS —
CHILLED WATER SUPPLY PIPE
IN HG
INCHES MERCURY (PRESSURE)
— CHR —
CHILLED WATER RETURN PIPE
CHILLED WATER
IN WC
CS
CONDENSER WATER SUPPLY PIPE
UNO
UNLESS NOTED OTHERWISE
CR
CONDENSER WATER RETURN PIPE
PRV
RL
REFRIGERANT LIQUID PIPE
THERMOSTATIC AIR VENT
THE EQUIPMENT SHALL BE REPLACED OR REPAIRED TO THE SATISFACTION OF THE
RG
REFRIGERANT GAS PIPE
HS
HEATING WATER SUPPLY
SV
HR
HEATING WATER RETURN
MIXED AIR
PROVIDE MANUAL VOLUME DAMPER IN EACH AIR DEVICE RUNOUT DUCT AS FAR FROM AIR DEVICE AS POSSIBLE
MECHANICAL
ABBREVIATIONS
FIRE ALARM
SEQUENCE OF OPERATION
UPON FIRE ALARM AHU• -EN AND ASSOCIATED EXHAUST FAN(S) SHALL SHUT DOWN.
HVAC DESIGN REQUIRES
YES
AC
ABOVE CEILING
— HPR
HIGH PRESSURE CONDENSATE RETURN
- - -LPS - --
LOW PRESSURE STEAM
AFF
ABOVE FINISHED FLOOR
FCU
FAN COIL UNIT
-
DOMESTIC COLD WATER
-- —
FPB
FAN POWERED BOX
DOMESTIC HOT WATER RETURN
FIRE STOPPING
AI
ANALOG INPUT
CONDENSATE DRAIN
P
PUMPED SANITARY LINE
- - - - - -
VENT LINE
4,896
FPI
FINS PER INCH
DIRECTION OF FLOW
B.
AO
ANALOG OUTPUT
GATE VALVE
NONE
BUTTERFLY VALVE
HORIZONTAL
BALL VALVE
-- - -/•� --
GC
GENERAL CONTRACTOR
TEMPERATURE AND PRESSURE RELIEF VALVE
C.
BFC
BELOW FINISHED CEILING
AUTOMATIC 3 -WAY CONTROL VALVE
NONE
PLUG VALVE /BALANCING COCK
HORIZONTAL
SOLENOID VALVE
—��--
GEF
GENERAL EXHAUST FAN
HYDRAULIC SHOCK ARRESTOR
<X:I+
OF
BELOW FLOOR, BLIND FLANGE
UNION
NONE
VACCUUM BREAKER
DO
P -TRAP
E
GSF
GENERAL SUPPLY FAN
HUB DRAIN
O
BG
BELOW GRADE
CLEANOUT OR WALL CLEANOUT
F.
PETE'S PLUG
BV
BUTTERFLY VALVE
MVD
MANUAL VOLUME DAMPER
THERMOMETER WELL
!s
CRU
COMPUTER ROOM UNIT
N
NEW
CRU
CONDENSATE RETURN UNIT
OBD
OPPOSED BLADE DAMPER
ELECTRIC PNEUMATIC SWITCH
PARTITION AND CEILING SYSTEM SUPPORTS. WHERE INDEPENDENT SUPPORT IS NOT POSSIBLE AN ENGINEERED SUPPORT
CU
CONDENSING UNIT
R
RELOCATED
E.
FIELD VERIFY THE EXACT SIZES AND LOCATIONS OF ALL EXISTING DUCTWORK AND PIPING
PRIOR TO DEMOLITION OF ANY EXISTING WORK. THE DEMOUTION WORK SHALL BE
H.
DI
DIGITAL INPUT
RA
RETURN AIR
HOSPITAL SCHEDULES, OCCUPANCIES, AND WORK.
DO
DIGITAL OUTPUT
RCA
RECIRCULATED (RETURN) AIR
DS
DISCONNECT SWITCH
RLA
RELIEF AIR
E
EXISTING
SA
SUPPLY AIR
EDH
ELECTRIC DUCT HEATER
UH
UNIT HEATER
DUCTWORK THAT HAS MISSING OR DAMAGED INSULATION PER SPECIFICATIONS.
EUH
ELECTRIC UNIT HEATER
VAV
VARIABLE AIR VOLUME
L
ff
EXHAUST FAN
WH
WATER HEATER
SF
SUPPLY FAN
WIP
WATER - SOURCE HEAT PUMP
EA
EXHAUST AIR
FMB
FILTER MIXING BOX
ALL EXISTING DIFFUSERS, EQUIPMENT AND PIPING REMOVED DURING CONSTRUCTION SHALL
OA
OUTSIDE AIR
IN HG
INCHES MERCURY (PRESSURE)
CHW
CHILLED WATER
IN WC
INCHES WATER COLUMN (PRESSURE)
DUCT SIZES ARE NET FREE AREA.
UNO
UNLESS NOTED OTHERWISE
IBT
INVERTED BUCKET TRAP
PRV
PRESSURE RELIEF VALVE
TAV
THERMOSTATIC AIR VENT
THE EQUIPMENT SHALL BE REPLACED OR REPAIRED TO THE SATISFACTION OF THE
SIMILARLY.
(STEAM SYSTEM)
SV
SAFETY VALVE
MA
MIXED AIR
PROVIDE MANUAL VOLUME DAMPER IN EACH AIR DEVICE RUNOUT DUCT AS FAR FROM AIR DEVICE AS POSSIBLE
DISPOSED OF AS DIRECTED BY THE OWNER'S REPRESENTATIVE
LE
LAUNDRY EQUIPMENT
IL
R.
INSTALL SPACE THERMOSTAT ADJACENT TO LATCH SIDE OF DOOR IN SPACE INDICATED. U.N.O.
L
CONTRACTORS SHALL SEAL ALL LEAKS IN EXISTING DUCTWORK AND NEW DUCTWORK.
INDICATED LOCATIONS ARE APPROXIMATE AVOID HEAT PRODUCING EQUIPMENT. FINAL SPACE
THERMOSTAT /SENSOR LOCATIONS SHALL BE AS DIRECTED BY THE ARCHITECT.
M.
EXISTING EQUIPMENT AND DUCTWORK HAS BEEN LIGHTLY DRAWN TO SHOW THE
X
APPROXIMATE LOCATION. NEW EQUIPMENT AND DUCTWORK IS SHOWN BY HEAVY LINES.
S
ui
'I
AND EXHAUST DUCTS. (NONE ALLOWED IN COMBUSTION AIR DUCTS).
N.
CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND /OR DISPOSING OF ALL ITEMS
THAT ARE NOT NECESSARY IN THE COMPLETION OF THE PROJECT AND SHALL CLEAN
T.
LOCATE ISOLATION VALVES FOR EQUIPMENT AS CLOSE TO THE MAIN
THE AREA OF CONSTRUCTION AFTER THE COMPLETION OF THE PROJECT.
AS POSSIBLE
0.
J
U,
MULTI -BLADE DAMPERS OF ANY TYPE INSTALLED WITHIN 36" OF AN ELL OR OTHER FITTING SHALL
;
E_
BE INSTALLED WITH THE DAMPER BLADE SHAFTS PARALLEL TO THE AIRSTREAM FLOW DIRECTION
iii
P.
ANY EXISTING WALLS DAMAGED FROM PIPING OR DUCTWORK THAT WAS REMOVED SHALL
BE PATCHED AND SEALED TO MEET THE FULL INTEGRITY OF THE REMAINING WALL
V.
FIRE, SMOKE, AND FIRE /SMOKE DAMPERES WILL BE REQUIRED AT ALL DUCT PENETRATIONS THRU RATED WALLS. COORDINATE
z
WITH ARCHITECTURAL DRAWINGS. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PRICING ALL FIRE, SMOKE, AND
FIRE /SMOKE DAMPERS REQUIRED BY CODE MECHANICAL CONTRACTOR SHALL REPORT EXISTING FIRE, SMOKE, FIRE /SMOKE
w
W
DEMONSTRATE TO OWNER'S REPRESENTATIVE THAT ALL INSTALLED CONTROLS ARE WORKING PROPERLY WITHOUT ERRORS PRIOR
TO RELEASING SYSTEM TO OWNER.
LL
FIRE ALARM
SEQUENCE OF OPERATION
UPON FIRE ALARM AHU• -EN AND ASSOCIATED EXHAUST FAN(S) SHALL SHUT DOWN.
HVAC DESIGN REQUIRES
YES
— HPS
HIGH PRESSURE STEAM
— HPR
HIGH PRESSURE CONDENSATE RETURN
- - -LPS - --
LOW PRESSURE STEAM
- - -LPR - --
LOW PRESSURE CONDENSATE RETURN
—PCP
PUMPED CONDENSATE RETURN
-
DOMESTIC COLD WATER
-- —
DOMESTIC HOT WATER
— - -- —
DOMESTIC HOT WATER RETURN
FIRE STOPPING
SANITARY WASTE LINE
CD
CONDENSATE DRAIN
P
PUMPED SANITARY LINE
- - - - - -
VENT LINE
4,896
DIRECTION OF SLOPE
8,422
DIRECTION OF FLOW
B.
EXPANSION LOOP
� 4
GATE VALVE
NONE
BUTTERFLY VALVE
HORIZONTAL
BALL VALVE
-- - -/•� --
GLOBE VALVE
11,265
TEMPERATURE AND PRESSURE RELIEF VALVE
C.
AUTOMATIC 2 -WAY CONTROL VALVE
—►
AUTOMATIC 3 -WAY CONTROL VALVE
NONE
PLUG VALVE /BALANCING COCK
HORIZONTAL
SOLENOID VALVE
—��--
CHECK VALVE
Q
HYDRAULIC SHOCK ARRESTOR
<X:I+
VALVE IN VERTICAL
—
UNION
NONE
VACCUUM BREAKER
DO
P -TRAP
E
FLOOR DRAIN W/ P -TRAP
otJ
HUB DRAIN
O
FLOOR CLEANOUT OR GRADE CLEANOUT
�I
CLEANOUT OR WALL CLEANOUT
F.
PETE'S PLUG
GAUGE COCK
yTHERMOMETER
ARCHITECTURAL DRAWINGS. COORDINATE THE LOCATION OF DUCTWORK AND PIPING AND PROVIDE OFFSETS IN DUCTWORK AND
- LF
THERMOMETER WELL
!s
STRAINER WITH BLOW-OFF VALVE
D.
F & T STEAM TRAP
—�—
STEAM BUCKET TRAP
G.
CONNECT TO EXISTING
IP
ELECTRIC PNEUMATIC SWITCH
FIRE ALARM
SEQUENCE OF OPERATION
UPON FIRE ALARM AHU• -EN AND ASSOCIATED EXHAUST FAN(S) SHALL SHUT DOWN.
HVAC DESIGN REQUIRES
YES
NQ
DUCT SMOKE DETECTOR
A.
X
FIRE DAMPER(S)
ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE FLORIDA UNIFORM STATEWIDE BUILDING CODE STATE AND
SMOKE DAMPER(S)
TOTAL
CFM
X
FIRE RATED ENCLOSURE
PATCHED AS PER ITEM B BELOW.
X
F1RE RATED ROOF/ FLOOR CEILING ASSEMBLY
CFM
X
FIRE STOPPING
FACILITY STANDARDS OR IF APPROVED BY THE OWNER, BE OF THE SAME QUALITY AS REPRESENTED BY THE SCHEDULED ITEM.
X
SMOKE CONTROL
NOTE 1
X
�4111-'
GENERAL DEMOLITION NOTES:
DESIG./
SERVES
GENERAL NOTES - ALL HVAC SHEETS
EXISTING DESIGN CFM
A.
ALL CARPED DUCT TAPS AND CONNECTING DUCTS THAT ARE NOT
A.
ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE FLORIDA UNIFORM STATEWIDE BUILDING CODE STATE AND
NOTES:
BEING USED ARE TO BE REMOVED BACK TO THE MAIN DUCT AND
TOTAL
CFM
LOCAL CODES IBC, AIA, IMC, NEC THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA). AND THE LOCAL AUTHORITIES HAVING
OUTSIDE
AIR CFM
PATCHED AS PER ITEM B BELOW.
16x16
JURISDICTION. ALL EQUIPMENT, MATERIALS, CONTROLS, ETC.SHALL BE NEW UNLESS NOTED OTHERWISE AND SHALL MATCH ALL
CFM
S1
24x24
FACILITY STANDARDS OR IF APPROVED BY THE OWNER, BE OF THE SAME QUALITY AS REPRESENTED BY THE SCHEDULED ITEM.
B.
PATCH OPENINGS IN EXISTING DUCTWORK THAT IS TO REMAIN
NOTE 1
AHU -EN
EAST WING
HORIZONTAL
INCLUDING OPENINGS. WHERE TAPS OR DUCTWORK ARE TO RE
4,896
2,636
8,422
REMOVED, THE FOLLOWING SHALL OCCUR:
B.
CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS, PAY ALL FEES, AND COMPLY WITH ALL NATIONAL, STATE, AND MUNICIPAL
90%
EXISTING TO REMAIN
NONE
LAWS, CODES, AND ORDINANCES RELATING TO BUILDING AND PUBLIC SAFETY.
HORIZONTAL
• OPENINGS IN THE MAIN DUCTS ARE TO BE COVERED WITH A
7,350
3,925
11,265
SHEET METAL PATCH. THE PATCH IS TO BE LARGER THAN THE
C.
CONTRACTOR SHALL FURNISH ALL MATERIALS, EQUIPMENT, AND LABOR REQUIRED FOR A COMPLETE WORKING AND COORDINATED
90%
EXISTING OPENING AND IS TO BE SECURED WITH SHEET METAL
NONE
SYSTEM
HORIZONTAL
SCREWS FOUR INCHES ON CENTERS.
D.
COORDINATE THE EXACT LOCATION OF MECHANICAL AND PLUMBING EQUIPMENT WITH THE LOCATIONS OF LIGHT FIXTURES, PIPING,
10,250
8,650
1,600
CONDUIT, AND OTHER CONSTRUCTION, TO ALLOW FOR PROPER ACCESS TO SERVICE EQUIPMENT.
909.
• A LIBERAL QUANTITY OF FIRE RESISTANT ADHESIVE IS TO BE
NONE
APPLIED TO THE EDGES OF THE METAL PATCH AND THE
E
COORDINATE THE LOCATION OF DUCTWORK AND PIPING WITH OTHER TRADES AND PROVIDE OFFSETS IN DUCTWORK AND PIPING AS
ASSEMBLY SCREWED IN PLACE.
REQUIRED.
C.
ALL WORK SHALL BE PERFORMED IN STRICT COORDINATION WITH HOSPITAL SCHEDULES,
F.
IT IS THE INTENT OF THESE DOCUMENTS TO ALLOW ALL CEILING CONSTRUCTION AND HEIGHTS TO RE AS SHOWN ON THE
OCCUPANCIES AND WORK. CONTRACTOR SHALL COORDINATE WITH HOSPITAL REPRESENTATIVE.
ARCHITECTURAL DRAWINGS. COORDINATE THE LOCATION OF DUCTWORK AND PIPING AND PROVIDE OFFSETS IN DUCTWORK AND
PIPING AS REQUIRED TO MEET THIS INTENT.
D.
ALL NECESSARY SHUTDOWNS OR OUT OF PHASE WORK SHALL BE SCHEDULED WITH THE HOSPITAL
REPRESENTATIVE.
G.
CONDUIT, PIPING, AND DUCTWORK SHALL BE INDEPENDENTLY SUPPORTED, AND EACH SUPPORT SHALL BE INDEPENDENT OF
PARTITION AND CEILING SYSTEM SUPPORTS. WHERE INDEPENDENT SUPPORT IS NOT POSSIBLE AN ENGINEERED SUPPORT
SYSTEM SHALL BE UTILIZED.
E.
FIELD VERIFY THE EXACT SIZES AND LOCATIONS OF ALL EXISTING DUCTWORK AND PIPING
PRIOR TO DEMOLITION OF ANY EXISTING WORK. THE DEMOUTION WORK SHALL BE
H.
ALL WORK SHALL BE SCHEDULED AND PERFORMED IN STRICT COORDINATION WITH ARCHITECTURAL PHASING PLANS AND WITH
COORDINATED WITH THE NEW WORK TO ASSURE PROPER LIMITS OF DEMOLITION.
HOSPITAL SCHEDULES, OCCUPANCIES, AND WORK.
1.
PROTECT EQUIPMENT AND WORK FROM DAMAGE DURING HANDLING AND INSTALLATION UNTIL COMPLETION OF CONSTRUCTION.
F.
REMOVE ALL EXISTING EQUIPMENT AND ASSOCIATED PIPING, WHETHER SPECIFICALLY
INDICATED OR NOT, THAT IS NO LONGER REQUIRED.
J.
REMOVE ALL EXCESS MATERIAL AND DEBRIS AND CLEAN ALL EQUIPMENT UPON COMPLETION OF WORK. TOUCH UP WITH PAINT
WHERE REQUIRED.
G-
REMOVE AND CAP EXISTING BRANCH PIPING AND DUCTWORK NO LONGER REQUIRED TO
REMAIN AS PART OF AN ACTIVE SYSTEM, AT THE APPROPRIATE MAIN. REINSULATE PIPING AND
K.
ALL CONNECTION BETWEEN PIPES OF DISSIMILAR MATERIALS SHALL BE MADE NTH DIELECTRIC UNIONS.
DUCTWORK THAT HAS MISSING OR DAMAGED INSULATION PER SPECIFICATIONS.
L
ARCHITECT SHALL HAVE FINAL APPROVAL OF ALL GRILLE, DIFFUSER, AND THERMOSTAT LOCATIONS.
H.
ANY PIPING AND DUCTWORK WHICH MUST REMAIN AS PART OF AN ACTIVE SYSTEM AND IS IN
CONFLICT WITH THE NEW LAYOUT SHALL BE RELOCATED AT NO ADDITIONAL COST OVER THE
M.
COORDINATE ALL AIR DEVICE LOCATIONS AND MOUNTING FRAME STYLES WITH LIGHTING PLANS AND ARCHITECTURAL REFLECTED
CONTRACT AMOUNT.
CEILING PLANS.
I.
ALL EXISTING DIFFUSERS, EQUIPMENT AND PIPING REMOVED DURING CONSTRUCTION SHALL
N.
COORDINATE ALL WALL MOUNTED DEVICE LOCATIONS WITH ARCHITECTURAL INTERIOR ELEVATIONS.
REMAIN THE PROPERTY OF THE OWNER AND SHALL BE STORED, REMOVED FROM THE JOB
SITE OR DISPOSED OF AS DIRECTED BY THE OWNER'S REPRESENTATIVE.
0.
DUCT SIZES ARE NET FREE AREA.
J.
WHERE EXISTING EQUIPMENT IS TO BE RELOCATED, EXTREME CARE SHALL BE TAKEN TO
P.
PROVIDE ROUND DUCTS TO ALL AIR DEVICES UNLESS NOTED OTHERWISE. DUCT SIZE SHALL MATCH AIR DEVICE
PREVENT DAMAGE DURING THE REMOVAL AND REINSTALLATION. WHERE DAMAGE OCCURS,
NECK SIZE OR THE TABLE IN AIR DEVICE SCHEDULE, WHICHEVER IS LARGER. FLEXIBLE DUCTS SHALL BE SITED
THE EQUIPMENT SHALL BE REPLACED OR REPAIRED TO THE SATISFACTION OF THE
SIMILARLY.
ARCHITECT, AT NO ADDITIONAL COST TO THE OWNER.
K.
ALL EXISTING CEILING DIFFUSERS SHALL BE REUSED, REMOVED AND STORED OR
Q.
PROVIDE MANUAL VOLUME DAMPER IN EACH AIR DEVICE RUNOUT DUCT AS FAR FROM AIR DEVICE AS POSSIBLE
DISPOSED OF AS DIRECTED BY THE OWNER'S REPRESENTATIVE
R.
INSTALL SPACE THERMOSTAT ADJACENT TO LATCH SIDE OF DOOR IN SPACE INDICATED. U.N.O.
L
CONTRACTORS SHALL SEAL ALL LEAKS IN EXISTING DUCTWORK AND NEW DUCTWORK.
INDICATED LOCATIONS ARE APPROXIMATE AVOID HEAT PRODUCING EQUIPMENT. FINAL SPACE
THERMOSTAT /SENSOR LOCATIONS SHALL BE AS DIRECTED BY THE ARCHITECT.
M.
EXISTING EQUIPMENT AND DUCTWORK HAS BEEN LIGHTLY DRAWN TO SHOW THE
APPROXIMATE LOCATION. NEW EQUIPMENT AND DUCTWORK IS SHOWN BY HEAVY LINES.
S
INSTALL TURNING VANES IN ALL 90 DEGREE SQUARE ELLS IN SUPPLY, RETURN,
AND EXHAUST DUCTS. (NONE ALLOWED IN COMBUSTION AIR DUCTS).
N.
CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND /OR DISPOSING OF ALL ITEMS
THAT ARE NOT NECESSARY IN THE COMPLETION OF THE PROJECT AND SHALL CLEAN
T.
LOCATE ISOLATION VALVES FOR EQUIPMENT AS CLOSE TO THE MAIN
THE AREA OF CONSTRUCTION AFTER THE COMPLETION OF THE PROJECT.
AS POSSIBLE
0.
THE MECHANICAL CONTRACTOR SHALL ADJUST AND REBALANCE THE AIR CONDITIONING
U,
MULTI -BLADE DAMPERS OF ANY TYPE INSTALLED WITHIN 36" OF AN ELL OR OTHER FITTING SHALL
SYSTEM AND EXHAUST SYSTEM TO PROPER DESIGN VOLUME AS SHOWN ON PLAN.
BE INSTALLED WITH THE DAMPER BLADE SHAFTS PARALLEL TO THE AIRSTREAM FLOW DIRECTION
UPSTREAM OF THE FITTING.
P.
ANY EXISTING WALLS DAMAGED FROM PIPING OR DUCTWORK THAT WAS REMOVED SHALL
BE PATCHED AND SEALED TO MEET THE FULL INTEGRITY OF THE REMAINING WALL
V.
FIRE, SMOKE, AND FIRE /SMOKE DAMPERES WILL BE REQUIRED AT ALL DUCT PENETRATIONS THRU RATED WALLS. COORDINATE
COORDINATE WITH ARCHITECTURAL PLANS FOR RATINGS OF WALLS.
WITH ARCHITECTURAL DRAWINGS. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PRICING ALL FIRE, SMOKE, AND
FIRE /SMOKE DAMPERS REQUIRED BY CODE MECHANICAL CONTRACTOR SHALL REPORT EXISTING FIRE, SMOKE, FIRE /SMOKE
DAMPERS TO THE ARCHITECT AND ENGINEER BEFORE PRICING.
W
DEMONSTRATE TO OWNER'S REPRESENTATIVE THAT ALL INSTALLED CONTROLS ARE WORKING PROPERLY WITHOUT ERRORS PRIOR
TO RELEASING SYSTEM TO OWNER.
EXISTING AHU SCHEDULE
DESIG./
SERVES
UNIT TYPE
EXISTING DESIGN CFM
NEW DESIGN CFM
PRE
FILT.
FINAL
FILT.
MANUFACTURER /MODEL N0.
NOTES:
TOTAL RETURN OUTSIDE
CFM CFM AIR CFM
TOTAL
CFM
RETURN
CFM
OUTSIDE
AIR CFM
CFM
16x16
451 -800
CFM
S1
24x24
YES
WHITE
4 -WAY U.N.O
NOTE 1
AHU -EN
EAST WING
HORIZONTAL
7,532
4,896
2,636
8,422
5,831
2,591
30%
90%
EXISTING TO REMAIN
NONE
AHU -NE
NORTH WING
HORIZONTAL
11,275
7,350
3,925
11,265
7,340
3,825
30%
90%
EXISTING TO REMAIN
NONE
AHU -SE
SOUTH WING
HORIZONTAL
10,250
5,650
1,600
10,250
8,650
1,600
307:
909.
EXISTING TO REMAIN
NONE
AIR DEVICE SCHEDULE
DESIG.
FRAME SIZE
OBD
FINISH
THROW
NECK SIZE
MANUFACTURER /MODEL NO.
REMARKS/NOTES
351 -560 CFM
14-"0_1561-S50
CFM
361 -450
CFM
16x16
451 -800
CFM
S1
24x24
YES
WHITE
4 -WAY U.N.O
NOTE 1
TITUS / TDC -AA
ALUMINUM LOUVERED SUPPLY DIFFUSER /3,4,5,6,7,8
S2
24x24
YES
WHITE
3 -WAY U.N.O
NOTE 1
TITUS / TDC -AA
ALUMINUM LOUVERED SUPPLY DIFFUSER /3,4,5,6,7,8
R1
24x24
YES
WHITE
N/A
NOTE 2
TITUS / 350FL
ALUMINUM RETURN GRILLE/3,4,5,6,7,8,9
S3
SEE PLANS
YES
WHITE
ADJUSTABLE
DOUBLE
DEFLECTION
NOTE 1
TAUS / 300FL
ALUMINUM SIDEWALL REGISTER /3,7,8
R2
SEE PLANS
YES
WHITE
N/A
I NOTE 2
TITUS / 350FL
ALUMINUM SIDEWALL REGISTER /3,7,8,9
►N 1
NECK*
AIRFLOW
6 "0
0 -99 CFM
8 "o
100 -200 CFM
10 "0
201 -350 CFM
12 "40
351 -560 CFM
14-"0_1561-S50
CFM
*AND /OR DUCT RUNOUT
2.
NECK*
AIRFLOW
6x6
0 -100
CFM
8x8
101 -230
CFM
10x10
231 -360
CFM
12x12
361 -450
CFM
16x16
451 -800
CFM
22x22
801 -1200 CFM
*AND /OR DUCT RUNOUT
3, DIFFUSER RUNOUT SIZE SHALL BE DIFFUSER NECK SIZE, UNLESS OTHERWISE
NOTED ON PLANS
4. PROVIDE SURFACE MOUNT HARDWARE IN ALL INACCESSABLE CEILING SYSTEMS
5. PROVIDE LAY -IN MOUNT HARDWARE IN ALL SUSPENDED CEILING SYSTEMS
6. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOC. OF DIFFUSERS
7. PROVIDE SELECTION BASED ON A MAXIMUM RADIATED NOISE OF NC-2-5
S. PROVIDE DIFFUSERS, GRILLES, AND REGISTERS MANUFACTURED FROM ALUMINUM
UNLESS NOTED OTHERWISED.
9. 35 DEGREE BLADES, 3/4" SPACING.
-XI <S
2121 Ponce de Leon Blvd., Suite 350
Coral Gables, FL 33134
phone: 305.569.1692 OLYNER
professional Consulting Engineers fax: 305.56?. 1693 SF,F TIST HEALTh SC U H FLORIDA
Austin Dallas • Denver - Houston • Nashville 6865 RED ROAD
Miami Phoenix Richmond - Washington D.C. CORAL GABLES, FLORIDA 33146
cord project number: 410393.000 ARCHITECT
EB00007658 FL AA F000119
HKS ARCHITECTS, INC.
1221 BRICKELL AVENUE, SUITE 1220
MIAMI, FL 33131
M.E.P. ENGINEERS
CCRD PARTNERS
2121 PONCE DE LEON BOULEVARD
SUITE 350
CORAL GABLES, FL 33134
INTERIORS
IN.DESIGN, INC.
2080 NW BOCA RATON BOULEVARD
SUITE 3
BOCA RATON, FL 33146
M
O
0
.j
� L
O
PROJECT
DESIGN CRITERIA
LOCATION:
CITY /STATE
MIAMI , FLORIDA
APPLICABLE CODES:
BUILDING
2007 FBC
NTS
W/ 2008, 2009 REV.
MECHANICAL
2007 FMC W/ REV.
PLUMBING
2007 FPC W/REV.
HOSPITAL AND
2006 AIA
HEALTH CARE GUIDELINES
NTS
LATITUDE:
THIRD FLOOR MECHANICAL ICRA PLAN
DEG. N. LAT.
25.8
LQNGITUDE:
DEG. W. LONG.
80.3
ELEVATION:
FT. ABOVE SEA LEVEL
13.0
ASHRAE SUMMER DESIGN CONDITIONS
0.4% DB MWB
91/78
ASHRAE WINTER DESIGN CONDITIONS
99% DB
47
BUILDING SPACE DESIGN TEMPERATURES
SUMMER DB
72
WINTER DB
68
ROOF:
U FACTOR
-
WALL
U FACTOR
-
SUPPLY AIR TEMPERATURE:
DEG. F. DRY BULB
55
MECHANICAL SHEET LIST
DWG No.
DRAWING TITLE
SCALE
MO.00
GENERAL INFORMATION — MECHANICAL
NTS
MD2.30
THIRD FLOOR DEMOLITION PLAN — MECHANICAL
M2.30
THIRD FLOOR PLAN — MECHANICAL
M7.00
MECHANICAL DETAILS
NTS
M.ICRA
THIRD FLOOR MECHANICAL ICRA PLAN
1/a "-1'
h+�
it
i
I
KEY PLAN
GH
C O
1A GL
REVISION
HKS PROJECT NUMBER
14262.000
DATE
04.11.2011
ISSUE
BIDDING &
PERMITTING SET
SHEET TITLE
MECHANICAL
LEGEND, NOTES,
& SCHEDULES
SHEET NO.
02011 HKS, INC.