11-293-015PLUMBING NOTES
1. CONTRACTOR SHALL VISIT THE SITE AND THOROUGHLY FAMILIARIZE
HIMSELF WITH AND VERIFY ALL EXISTING CONDITIONS AND REPORT ANY
DISCREPANCIES TO THE ARCHITECT/ ENGINEER PRIOR COMMENCING WORK.
2. THE CONTRACTOR SHALL COORDINATE THE WORK OF THIS TRADE WITH ALL
OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF
CONSTRUCTION AND REPORT ANY DISCREPANCIES TO THE ARCHITECT/
ENGINEER.
3. REQUIRED INSURANCE SHALL BE PROVIDED BY THIS CONTRACTOR FOR
PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE
DURATION OF WORK.
4. ALL PERMITS, FEES, INSPECTIONS AND TESTS SHALL BE THE
RESPONSIBILITY OF THE PLUMBING CONTRACTOR.
5. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS WITH THE
ARCHITECTURAL PLANS.
6. ALL MATERIALS SHALL BE NEW AND OF AN AMERICAN MANUFACTURER,
FREE FROM DEFECTS, INDELIBLY MARKED WITH NAME OF MANUFACTURER,
WEIGHT AND/ OR CLASS.
7. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR
IN A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL
BE FULLY OPERATIVE.
8. VERIFY LOCATION, SIZE AND ELEVATION OF ALL UTILITIES PRIOR TO
BEGINNING CONSTRUCTION. ADVISE ARCHITECT/ ENGINEER OF ANY
DISCREPANCIES.
9. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS FOR THE EXACT
LOCATION OF FIXTURES AND PIPING.
10. FIRESTOPS SHALL BE PROVIDED AT ALL PLUMBING FIXTURES.
11. PROVIDE DIELECTRIC UNIONS WHERE DISSIMILAR METALS ARE JOINED.
12. ESCUTCHEONS SHALL BE CHROME PLATED BRASS WITH LOCKING SCREWS
WHERE PIPES PASS THROUGH FINISHED WALLS.
13. ALL 3" OR BIGGER HORIZONTAL BRANCHES, SEWER AND DRAIN LINES SHALL
BE SLOPED A MINIMUM OF 1/8 IN /FT. AND 2" OR SMALLER SHALL BE
SLOPPED AT 1/4 IN /FT. UNLESS OTHERWISE INDICATED ON PLANS.
18. CONTRACTOR SHALL GUARANTEE ALL WORK FREE FROM DEFECTS OF
WORKMANSHIP AND/ OR MATERIALS FOR A PERIOD OF ONE YEAR FROM
DATE OF ACCEPTANCE.
19. ALL HOT WATER PIPES SHALL BE INSULATED. WITH 1" THICK GLASS FIBER
MOLDED INSULATION. WITH PRE -SIZED FACTORY APPLIED FRJ JACKET OF
GLASS CLOTH WITH LONGITUDINAL LAP AND BUTT JOINT STRIPS WITH SELF
SEALING ADHESIVE.
20. ALL A/C CONDENSATE DRAIN LINES SHALL BE INSULATED
WITH 1/2' ARMAFLEX PIPE INSULATION.SEAL ALL SEAMS WITH
INSULATION MANUFACTURER'S SOLVENT. NO TAPES ARE ALLOWED.
21. INSULATE ALL HANDICAPPED LAVATORIES, EXPOSED DRAINS AND WATER
PIPING TO PROTECT AGAINST BURNING AND OR CUSHION IMPACT. PIPING AS
UNDER LAVATORIES PER FPC 404.6.4 USE HANDI LAV- GUARD' INSULATION KIT
OR APPROVED EQUAL COORDINATE COLOR WITH ARCHITECT.
22. ALL PLUMBING WORK SHALL BE DONE IN ACCORDANCE WITH THE FLORIDA
BUILDING CODE PLUMBING 2007.
23. PIPING MATERIALS
SANITARY, GREASE /OIL WASTE, STORM AND CONDENSATE DRAINAGE:
PVC:
PVC, SCHEDULE 40
SWEAT PROOFING:
SWEAT PROOF HORIZONTAL STORM DRAINAGE PIPING BETWEEN DRAIN AND VERTICAL
LEADER RUNNING IN CONDITIONED AIR SPACE OR PLENUMS WITH 1/2" THICK
GLASS FIBER SECTIONAL PIPE COVERING WITH FLAME RETARDANT VAPOR
BARRIER JACKET.
COPPER TUBING: (2' AND SMALLER)
TYPE "K" OR" L': SEAMLESS HARD DRAWN OR ANNEALED, ASTM B88.
TYPE DWV: SEAMLESS HARD DRAWN, ASTM 8306.
DOMESTIC WATER SUPPLY PIPING:
A. ABOVE GROUND: COPPER TUBING TYPE "L" WITH BRONZE OR WROUGHT
COPPER SOLDER JOINT FITTINGS WITH 95/5 SOLDER.
14. EVERY FIXTURE CONNECTED TO THE DRAINAGE SYSTEM SHALL BE 24. PROVIDE WATER HAMMER ARRESTORS FOR QUICK CLOSING VALVES AS PER FPC 604.9
EQUIPPED WITH A WATER SEAL TRAP.
25. PROVIDE PIPE LABELING SYSTEM FOR ALL UNDERGROUND PIPES UNDER SLAB
15. ALL EXPOSED PIPING WITHIN TOILET ROOMS SHALL BE CHROME -
PLATED.
16. PLUMBING FIXTURES SHALL COMPLY WITH WATER CONSUMPTION
CONTRACTOR TABLE 604.4
CONNECT D WASTE TO EQUIPME
REQUIRED FURNISHED BY OTHERS AS FOR COMPLETE OPERATI01
PLUMBING LEGEND
SYMBOL
DESCRIPTION
- ---
SANITARY WASTE PIPE (SAN)
SANITARY VENT PIPE
SYM.
DOMESTIC COLD WATER
HOT WATER
••
REMARKS
HOT WATER
FD
FLOOR DRAIN W/
1/2' TRAP RESEAL
-191 FCO
FLOOR CLEAN OUT
-- it WCO
WALL CLEAN OUT
1r-- am-
'P" TRAP
3+ HB
HOSE BIBB W/VAC. BREAKER
F.U.
FIXTURE UNIT
C==IWH -#
INSTANT WATER HEATER # X
TP
TRAP PRIMER
Y.T.R.
VENT THROUGH ROOF
A.F.F.
ABOVE FINISHED FLOOR
AG
ABOVE GROUND
UG
UNDERGROUND
FD
FLOOR DRAIN
FIXTURE CONNECTION SCHEDULE
SANITARY
SYM.
FIX
CW
HW
REMARKS
WASTE
HLAY
HANDICAP
2"
1/2'
_
VITREOUS CHINA WALL MOUNTED, ONE HOLE. 0.5 GPM FLOW CONTROL AERATOR, INFRA -RED SENSOR
LAVATORY
ACTIVATED FAUCET. BASICS OF DESIGN: TOTO LT307 WITH TEL3GSIO #CP FAUCET.
HANDICAP
VITREOUS CHINA, ELONGATED BOWL, SEAT LESS OPEN, 1.6GPF, WALL MOUNTED, ADA COMPLIANT. BATTERY
HWC
WATER
4"
in
-
POWERED. BASIS OF DESIGN: AMERICAN STANDARD AFWALL 3351.160 WITH SLOAN OPTIMA 111 FLUSH
CLOSET
VALVE.
FD
FLOOR DRAIN
2"
-
-
FLOOR DRAIN WITH 1/2" GRAVITY TRAP PRIMER CONNECTION.
HB
HOSE BIBBS
-
1 3/4'
-
CHICAGO FAUCET MODEL 1387 -RCF VANDAL RESISTANT
;.
1. ALL PLUMBING FIXTURES FURNISHED ANPINSTALLED BY : t O•
red de'
,.,.rchitecture interiors planning
CONSULTANTz
A &B I
.•
Consulting MEP g
7205 NW 19th Street, Suite 501
Florida
Sae-. Fatemian
CA !W •
• ZOILA MORALES, P.E. #64981 ELECTRICAL
• RAUL S. MASTRAPA, P.E. #40182 MECHANICAL
Sheet Information
Date 03-18-11
•a 08024/1574-02
Scale ASSHOWN
M1