11-215-0143/8" GALVANIZED STEEL,
SELF TAPPING EYEBOLT
(TOTAL OF 4)
ELECTRIC CONDUIT GUIDE
ROOFING �-
SECURE CURB TO ROOF USING
FASTENERS AT 4" O.C. BEFORE
APPLYING ROOFING AND
INSULATION (IF REQUIRED)
REFER TO "CURB ATTACHMENT
TO CONCRETE SLAB ROOF"
DETAIL ON THIS SHEET.
WIRING BY OTHERS
DUC
i ALL WELDED CONSTRUCTION
1/8" stainless steel cable w/ turnbuckle (see note #2) A
PROVIDE RUBBER GASKET
SEAL BETWEEN FAN AND
m
"R"
SP
GA.
SMALL
SUPPORT FRAME
p
24
LARGE
4"
U_
22
MODEL NUMBER
365VX126
SECURE FAN TO CURB WITH
U
-
NO. 14 S/S SCREWS, 8" O.C.
va
V Vy JJV
ALL AROUND
0
Z
w
M
UP -BLAST
SIDE DISCHARGE
4 V V U
AREA SERVED
- FACTORY FABRICATED
KITCHEN
V
VENTED ROOF CURB
8000
6400
- FLASHING AND COUNTER
E.S.P. (INCHES OF WATER)
3
FLASHING INTO ROOFING
V
V V V
V
SONES
SHEET METAL EXHAUST DUCT
TYPICAL KITCHEN HOOD UPBLAST
EXHAUST FAN
N.T.S.
j NOTES:
1. KITCHEN HOOD EXHAUST FAN MUST BE U.L. 762 LISTED WITH HINGED & VENTED ROOF CURB, PER NFPA 96.
i
2. FANS SHALL BE SECURED WITH CROSS - CONNECTED CABLES OVER THEM, REGARDLESS OF HEIGHT.
SCREWS FOR ALL CURB MOUNTED EQUIPMENT SHALL BE SIZE NO. 14 WITH GASKETED WASHERS,
3. ALL ROOF MOUNTED EQUIPMENT AND ANCHORING /STRAPPING SHALL COMPLY WITH THE WIND DESIGN DATA
AS INDICATED ON FBC 2007, 1603.1.4 AND FBC MECHANICAL 2007, 301.12 (3- SECOND GUST, 146 MPH, 1.15 WIND
IMPORTANCE, CATEGORY "C" EXPOSURE).
SHEET METAL RUNNER TOP AND BOTTOM
SINGLE VANE SCHEDULE
STEELSTRENGTH
"R"
SP
GA.
SMALL
2"
1\2"
24
LARGE
4"
31/4'
22
' SECURED TO DUCT WITH SHEET METAL SCREWS
l"
• I
! SHEET METAL SINGLE THICKNESS � TYPICAL FABRICATED SHEET
QUARTER ROUND TURNING VANES METAL ELBOW
T�
SECURE FAN TO CU
NO. 14 S/S SCREWS,
ALL AROUND
PROVIDE RUBBER C
SEAL BETWEEN FAP
SUPPORT FRAME
FACTORY FABRICATE[
CANT STRI
SECURE CURB i u nvvr vawm,
FASTENERS AT 4" O.C. BEFORE
APPLYING ROOFING AND
INSULATION (IF REQUIRED)
SUPPLY FAN DETAIL
N.T.S.
HING AND COUNTER
HIND INTO ROOFING
NOTES:
1. FANS SHALL BE SECURED WITH CROSS - CONNECTED CABLES OVER THEM, REGARDLESS OF HEIGHT.
SCREWS FOR ALL CURB MOUNTED EQUIPMENT SHALL BE SIZE NO. 14 WITH GASKETED WASHERS.
2. ALL ROOF MOUNTED EQUIPMENT AND ANCHORING /STRAPPING SHALL COMPLY WITH THE WIND DESIGN
DATA AS INDICATED ON FBC 2007, 1603.1.4 AND FBC MECHANICAL 2007, 301.12 (3- SECOND GUST, 146 MPH,
1.15 WIND IMPORTANCE, CATEGORY "C" EXPOSURE).
1 1/2 "x1 1/2" (MIN) ANGLE IRON FRAME
INSULATION
DUCT
a
OPERATOR/ACTUATOR
BREAKAWAY POINT
1 6'
SHEET METAL SINGLE THICKNESS
TURNING VANES WITH FLANGED
FASTENERS TOP AND BOTTOM
I
SHEET METAL RUNNER FASTENED TO
DUCT WITH SHEET METAL SCREWS
l
e`
VN
NOTE: SINGLE THICKNESS TURNING VANES SHOWN. PROVIDE DOUBLE
I THICKNESS WHERE SPECIFIED.
¢9
DUC-r TURNING VANE DETAIL
i
NTS
i
c
'I
PREFABRICATED FAN
CURB W /FLANGE. (SEE N, CANT STRIP (BY ROOFER)
FAN SCHEDULE FOR
ROOF CURB.) ROOFING GALVANIZED ROOF CURB
PRESSURE TREATED WOOD BLOCKING
ILI
ROOF INSULATION SEALING COMPOUND
d
FUSIBLE
ACCESS DOOR—/
14 "X14" MIN.
ZONED AS REQUIRED
WALL
1/4" CLEARANCE PER FOOT ALL AROUND
r SLEEVE r DUCT
CAULKING
NEGATOR SPRIN
- 6 (MI
BOTH SI
TT AIR FLOW
CAULKING FULL PERIMETER
OF DAMPER (TYPICAL BOTH SIDES)
COMBINATION FIRE /SMOKE DAMPER DETAIL_
N.T.S.
NOTES:
1. DAMPER: "RUSKIN." FSD 60 WIYH 165 F FUSIBLE LINK OR APPROVED EQUIVALENT.
2. INSTALLATION OF THE DAMPER SHALL BE IN STRICT ACCORDANCE WITH
THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND UL555S.
ROOF 8"
as
a
!" CONCRETE ROOF SYSTEM
' 1/2" DIA. EXPANSION BOLT, WITH 2" EMBEDMENT,
4" O.C. ALL AROUND
I.
CURB ATTACHMENT TO
I CONCRETE SLAB ROOF
N.T.S.
r,
FLASHING TO BE MECHANICALLY
FASTENED & SOLDERED TO
DUCT ALL AROUND
FLASHING &
COUNTER FLASHING
p
ANCHOR TO ROOF
DUCTWORK TO SYSTEM
HIGH PRESSUF
CONNECTION
SLAB
SLEEV'
ACCESIE
RECTANGL,.,,
OR ROUND DUCT.
M
STAINLESS STEEL BOLT CARBON STEEL BOLT
2" x 2" x 1/4" STEEL ANGLES
W /LENGTH AS REQ'D
STEELSTRENGTH
STEELSTRENGTH
IN TENSION = 5980 LB
IN TENSION = 6500 LB
STEELSTRENGTH
STEELSTRENGTH 2"0 STANDARD PIPE (TYP.)
IN SHEAR = 4870 LB
IN SHEAR = 3595 LB
HILTI EXPANSION ANCHOR
KWIK BOLT TZ DETAIL
N.T.S.
SCREWS
SCREWS MAY BE
OMITTED IF
HANGERLOOPS
STRAP HANGERS
N.T.S.
NOTE:
REFER TO SMACNA FOR ADDITIONAL
DUCT SUPPORT REQUIREMENTS.
-1 1/2" x 1 1/2" x 12 GA.
VITH 1/4" BOLTS a0 8" O.C.
JP TO 48" DUCT DIMENSION) AND
-2 " x 2" x 12 GA. WITH 1/4"
;OLT @a 6" O.C. (ABOVE 48"
)UCT DIMENSION) (TYP.)
" HIGH CURB COORDINATE
OCATION AND DIMENSIONS.
J.L. RATED FIRE DAMPER
SPRING OPERATED FOR
IERTICAL AIR FLOW)
BLADE AWAY FROM AIR
;TREAM)
NOTE:
1. INSTALL FIRE DAMPERS IN STRICT ACCORDANCE WITH UL 555
AND FBC -M 2007 SECTION 607.2/607.3.
2. FIRE DAMPER MANUFACTURER AND FIRE DAMPER INSTALLATION
INSTRUCTIONS SHALL COMPLY WITH FBC -M 2007 SECTION 607.2, 607.3.1.1
AND REQUIREMENTS OF UL 555.
TYPICAL CURB DUCT DETAIL HORIZONTAL FIRE DAMPER DETAIL
N.T.S. N.T.S.
DUCT DEPTH
WELDED TO BASE PLATE I
4" x 4" x 1/2" PL. SET IN PITCH PANS.
PLACE SUPPORTS SO THAT BEARING
PLATES ALWAYS REST ON RIB PORTIONS OF
THE ROOF & SECURE TO ROOF WITH LAG SCREWS
& EXPANSIONS SHIELDS. SUPPORTS SHALL
BE A MAX. OF 4' -0" ON CENTERS.
DETAIL OF ROOF DUCT SUPPORT
24" MIN.
N.T.S.
NOTES:
1. FLASH AND COUNTER FLASH AROUND PIPE SUPPORTS.
2. ALL OUTDOOR STEEL SUPPORT COMPONENTS FOR DUCTS SHALL BE HOT
DIP GALVANIZED AFTER FABRICATION.
FA N S C H E D U L E
DESIGNATION
KEF - 1
KSF - 1
yf
Vy
MANUFACTURER
LOREN COOK
LOREN COOK
Vy
WEIGHT (LBS.)
684
646
4
MODEL NUMBER
365VX126
180ASP
,
B.H.S.F.
CENTRIFUGAL
ROOF SUPPLY FAN
V Vy JJV
TYPE
y:)U V
V N V
w
M
UP -BLAST
SIDE DISCHARGE
4 V V U
AREA SERVED
KITCHEN
KITCHEN
V
C.F.M.
8000
6400
4
UJ
E.S.P. (INCHES OF WATER)
3
1.5
V
V V V
V
SONES
28
26
V V
R.P.M.
1053
819
H. P.
7.5
5
vV�
VOLT - PH - HZ
480 -3 -60
480 -3 -60
Id EE_ E 644759
DRIVE
BELT
BELT
DETAILS AND
BACKDRAFT DAMPER
NO
YES
V
REMARKS
1, 2, 3, 4
1, 2, 5, 6, 7
')
IN
HOOD SWITCH
KITCHEN HOOD /KEF - 1
REMARKS:
1. PROVIDE WITH BIRDSCREEN.
2. PROVIDE WITH INSULATED FACTORY CURB (1 1/2 ", 3LBS DENSITY), 13.5" HIGH, CONTINUOUSLY WELDED
CORNERS, VENTED EXTENSION, HINGED SUB BASE, KEYWAY GREASE THROUGH STAINLESS
HARDWARE TIE -DOWN EYELETS (4) .I,,jTy
U
3. SHALL BE ALUMINUM CONSTRUCTION.
- •_
ONNECTION '" ''{
4. UPBLAST UL 762 LISTED, VENTED AND HINGED ROOF CURB, GREASE TRAP WITH DRAIN CONNECTION."
SHALL CONTINUE RUNNING WHEN GREASE HOOD'S FIRE EXTINGUISHING SYSTEM ACTIVATES.
5. SHALL STOP RUNNING UPON ACTIVATION OF GREASE HOOD'S FIRE EXTINGUISHING SYSTEM. "I'R 'ULU
6. PROVIDE WITH WASHABLE ALUMINUM FILTERS.
7. FAN INTAKE SHALL BE AT 36" ABOVE FINISHED ROOF.
KITCHEN HOOD AND DUCT SYSTEM NOTES
1. SUPPLY AND EXHAUST FANS ARE INTERLOCKED WITH A PILOT LIGHT IN KITCHEN AREA.
2. FIRE MODE REQUIRES THE EXHAUST FAN TO CONTINUE TO OPERATE, SUPPLY FAN STOPS AND
ACTIVATES BUILDING ALARM SYSTEM.
3. HOOD EXHAUST FAN SHALL OPERATE WHENEVER THE EXTINGUISHING SYSTEM IS ACTIVATED.
4. FIXED PIPE EXTINGUISHING SYSTEM IN A SINGLE HAZARD AREA SHALL BE ARRANGED FOR
SIMULTANEOUS AUTOMATIC OPERATION UPON ACTIVATION OF ANY OF THE SYSTEMS.
5. KITCHEN GREASE DUCTS AND EXHAUST EQUIPMENT SHALL CONFORM TO FBCM -2007, CHAPTER 5,
SECTION 506 AND NFPA 96.
6. A SIGN SHALL BE PLACED ON ALL ACCESS PANELS STATING, "ACCESS PANEL - DO NOT OBSTRUCT ", IN
A LETTER SIZE AT LEAST 1" INCH HIGH.
7. EXHAUST GREASE DUCT SHALL BE CONSTRUCTED OF BLACK STEEL 16 GA., (OR 18 GA. STAINLESS
STEEL), CONTINUOUS LIQUID -TIGHT WELD MADE ON THE EXTERNAL SURFACE OF THE DUCT SYSTEM.
8. NEGATIVE PRESSURE IN COOKING AREA SHALL NOT EXCEED 0.02" W.G.
9. FIRE SUPPRESSION SYSTEM SEQUENCE OF OPERATION:
UPON ACTIVATION OF THE KITCHEN HOOD FIRE SUPPRESSION SYSTEM (FIRE ALARM OR PULL
STATION) THE FOLLOWING IS TO OCCUR.
SOLENOID GAS MAIN SHUT -OFF VALVE CLOSES TO TURN OFF ALL GAS APPLIANCES.
- ELECTRICAL APPLIANCES TURN OFF.
- SEND SIGNAL TO BUILDING FIRE ALARM SYSTEM.
-OUTSIDE AIR SUPPLY FAN SKF -1 TURNS OFF,
THE HOOD EXHAUST FAN KEF -1 SHALL OPERATE WHENEVER THE EXTINGUISHING SYSTEM IS
ACTIVATED.
?JVVV
V
VVU'JV
UVV
yf
Vy
V UV UV
U
V 4�
Vy
a u v
U
W
4
u V U
U
Vti V V`hv
,
B.H.S.F.
6200 S.W. 73 RD. street
Miami, FL. 33143
V Vy JJV
V V V
y:)U V
V N V
w
M
. X
y
4 V V U
J
V
V
U
U
k
V J V
•J
4
UJ
u V
V U
U
U V
V
V V V
V
V
KEY PLAN
V
V
V V
r ,
U
uuu
LOCATION
OF WORK
UUV4`
uUUVU
vV�
t 1sMEGNANIGAL.
Q UA EZ, RE,
Id EE_ E 644759
Sheet Title:
DETAILS AND
VV JF�V
V
HVAC
J
V
Scale: AS NOTED
VVVV
V UyUVV
')
U VVVM
(:
s SOUTH MIAN
U51I N G�t� it PT.
'TUR //i.1. ;Fc-rloN
s'r:
LOUIS J. AGUIRRE & ASSOCIATES, P.A.
Consulting Engineers
9150 South Dodeland Blvd. Suite 900
Miami @ Florida 33156 m CA 924
Telephone 305.670.0141
Facsimile 305.670.0144
www.ljoapa.com
Project No.: 20046
Revised:
------ -- -
a
Client
South Miami Hospital
B.H.S.F.
6200 S.W. 73 RD. street
Miami, FL. 33143
0 z
H
LU
w
M
. X
Cn
M
M
LU
LL_
F_ -
N ■ 0
a�j Q
z
_0 °
M o
cv
4
UJ
c�
Q)
KEY PLAN
?rte! S.M.H.
r
r ,
LOCATION
OF WORK
Seal
•per
t 1sMEGNANIGAL.
Q UA EZ, RE,
Id EE_ E 644759
Sheet Title:
DETAILS AND
SCHEDULES
HVAC
Project No.. 20046
Date: 02.18.2011
Scale: AS NOTED
Drawn by: J. H., F.P.,J.B.
Checked by: V.A.,E.Z.
Sheet Number:
�ii17.00