Loading...
11-215-010GENERAL NOTES ... .r• . .... f f DEMOLITION NOTES:,i . • r v Y • �r •. 1. AREA OF CONSTRUCTION SHALL BE MAINTAINED UNDER NEGATIVE • Y • • u� . W 4 PRESSURE IN RELATION TO SURROUNDING AREAS. THE CONSTRUCTION AREAS TO BE TESTED WEEKLY TO ASSURE A NEGATIVE PRESSUf. &QF uir• - 0.02 INCHES WATER GAUGE IN BEING MAINTAINED WHEN ALL DOOR-!;'ANQ WINDOWS ARE CLOSED. ALL AIR OUTLETS AND WALL PENETRATIONS , r' r »... ' » Y'• W i . SHALL BE BLOCKED OF TO MAINTAIN NEGATIVE PRESSURE IN THE SPACE: CONTRACTOR WILL PROVIDE A TEMPORARY EXHAUST FAN TO MAINTAIN p C NEGATIVE PRESSURE IN THE SPACE. LOUIS J. AGUIRRE & ASSOCIATES, P.A. 2. WORK SHALL SCHEDULE TO MINIMIZE IMPACT TO THE NORMAL C o n 5 U I t I n g Engineers OPERATION OF THE HOSPITAL SEE ARCHITECTURAL DRAWING PLAN. 9150 South Dadeland Blvd. • Suite 900 COORDINATE WITH THE AUTHORIZED SMH HOSPITAL REPRESENTATIVE Miami • Florida 33156 • CA 924 MINIMUM OF 72 HOURS PRIOR TO ANY SHUTDOWN REQUIRED TO Telephone 305.670.0141 PERFORM WORK ON H.V.A.C. SYSTEMS, Facsimile 305.670.0144 www.liaapa.com 3. PROVIDE VISUAL NEGATIVE PRESSURE GAUGE TO MONITOR THE Project No.: 20046 PRESSURE RELATIONSHIP BETWEEN THE CONSTRUCTION AREA AND THE ADJACENT SPACE TO PROVIDE NEGATIVE PRESSURE OF 0.02" W.G. WITHIN THE SPACE, I EQUIPMENT SPECIFICATIONS: SUPPLY, RETURN, TRANSFER, AND EXHAUST AIR DUCTWORK: SHALL BE GALVANIZED SHEET STEEL, DESIGNED, CONSTRUCTED AND INSTALLED PER SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS- METAL AND FLEXIBLE" MANUAL, LATEST EDITION. STATIC PRESSURE CLASSIFICATION AS FOLLOWS: 3" STATIC PRESSURE: SUPPLY AIR AND RETURN AIR DUCTWORK: 2" STATIC PRESSURE: OUTSIDE AIR, TRANSFER DUCTS AND EXHAUST AIR DUCTWORK. _ - - - FLEXIBLE DUCTWORK: SHALL BE CLASS 1, UL STANDARD 181, INSULATED Revised: ' ROUND DUCT BY THERMAFLEX MKE OR FLEXMASTER 8M; R -6 MINIMUM. - FACTORY FABRICATED WITH AN OUTER JACKET ENCLOSING 1 -1/2 INCH THICK r TELE 11 GLASS- REINFORCED SINSULATION AROUND A CONTINUOUS METAL INNER LINER. MYLA OUTER JACKET WITH A CONTINUOUS PREP. & PACKAGING HANGING TAB. IT _ __� RECTANGULAR MANUAL VOLUME DAMPERS: SHALL BE RUSKIN MODEL MD35 OR EQUAL. MULTIPLE OPPOSED BLADE OR SINGLE BLADE, FURNISHED �a OFFICE - - -:_ _ _._. INSTALL TEMPORARY CAP COMPLETE WITH FACTORY FABRICATED LOCKING HAND QUADRANT. . IN EXHAUST AIR DUCT r �`, PROVIDE WITH 2" STAND -OFF WHEN INSTALLED ON EXTERNALLY INSULATED AND SEAL AIR TIGHT. \, DUCT. REMOVE AT END OF CONSTRUCTION. PURCHASING MAILROOM MECHANICAL OFFICE Client 75 CFM I, - -- ❑ 1. 1 -- ❑ INFECTION CONTROL RISK ASSESSMENT TEMPORARY PARTITITION (SEE DETAIL - -� - O CEO. , - - -- 4 r' I ON ON SHEET MI.00) MAILROOM 1. TO THE EXTEND THAT IT IS REQUIRED BY THE ICRA, THE CONTRACTOR } V6 _ IOX8 W/ VOLUME 75 CFM TO BE EXHAUSTED TO THE OUTSIDE. THE SHALL MAINTAIN EXISTING LEVELS OF INDOOR AIR QUALITY IN IOXIO DAMPER. 225 CFM EXHAUST CFM AMOUNT TO BE INCREMENTALLY SURROUNDING AND ADJACENT AREAS TO THE CONSTRUCTION AREA, AND RECIRCULATING AIR. MODULATED IN THE FIELD IN ORDER TO SATISFY ICRA ELSEWHERE IN THE FACILITY, IT SHOULD BE ANTICIPATED THAT THE ICRA 28X36 EXHAUST DUCT G REQUIREMENT OE 0.02 W.G. STATIC PRESSURE. REPORT WILL REQUIRE ERECTION OF CONSTRUCTION ZONE BARRIERS RECEIVIN • DUCT UP TO EXHAUST REMOVE FLEXIBLE DUCT AFTER AND PROVISION OF NEGATIVE PRESSURE IN THE CONSTRUCTION ZONE South Mlaml Hospital FAN ON ROOF ABOVE CLO• 2 RELATIVE TO SURROUNDING AREAS. , n DEMOLITION IS COMPLETED. HEPA FILTER x It I MAIL ROOM B.H.S.F. (99.99% EFF.) �'� 2. IN ADDITION TO MEETING THE REQUIREMENTS OF THE ICRA REPORT, THE MAGNETIC OFFIC DRAFT TEMPORARY WALL CAP. CONTRACTOR SHALL PROVIDE THE EQUIPMENT NECESSARY TO CREATE A GAUGE NEGATIVE PRESSURE IN THE CONSTRUCTION AREA, RELATIVE TO THE 6200 S.W. 73 RD. Street MAIL ROOM ADJACENT AREA. EXISTING HVAC SYSTEM AND COMPONENTS SHALL NOT Miami, FL. 33143 ❑� 60 TEMPORARY BE USED FOR THIS FUNCTION, UNLESS SPECIFICALLY APPROVED BY THE CORRIDOR INSULATED FLEXIBLE OWNER'S INFECTION CONTROL OFFICER. THE CONCEPT AND ALL ASPECTS - - -- DUCT (UL 181 CLASS I). OF THIS WORK SHALL BE DONE IN ACCORDANCE WITH THE ICRA 75 CFM REQUIREMENTS AND AS A MINIMUM THE FOLLOWING: Oz LLJ EXCH. CART ROOM PATCH AND REPAIR WALL OPENING A. VERIFY ALL EXISTING DUCTWORK WHICH PASSES THROUGH THE LU AFTER DEMOLITION IS COMPLETED CONSTRUCTION ZONE, AND IS TO REMAIN, IS SEALED AND (SEE DEMOLLITION NOTES). PROTECTED DURING CONSTRUCTION. ' cn O.R. STOR. UTILITY FAN WITH HEPA FILTER AND _ STOR. �CLO. B. AIR REMOVED FROM THE CONSTRUCTION ZONE SHALL BE FILTERED n p ch ,. � SPEED CONTROL (300 CFM) TO CLEAN AND /OR DISCHARGED AS DIRECTED BY THE ICRA REPORT. W AND RECIRCULATE THE AIR IN THE C. PRESENT THE NEGATIVE AIR PRESSURE PLAN TO THE OWNER FOR �"� CONSTRUCTION AREA, MAINTAINING A - - - -- APPROVAL BY THE INFECTION CONTROL OFFICER. UJ NEGATIVE PRESSURE OF 0.02' W.G. D. PROVIDE MEANS TO MONITOR AND VERIFY NEGATIVE PRESSURE IS ❑ , Q . T BETWEEN CONSTRUCTION AREA AND BEING MAINTAINED IN ACCORDANCE WITH THE ICRA REPORT, AND E � i J ADJACENT SPACES (SEE DEMOLITION LINEN PROVIDE DOCUMENTS TO THE OWNER AS REQUIRED 0 c co NOTES ON THIS DRAWING.) Z a N LU i CODES AND STANDARDS: LINEN APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL STATE LAWS, KEY PLAN LOCAL ORDINANCES, UTILITY COMPANY REGULATIONS AND THE -r ; S.M.H. STAR = APPLICABLE REQUIREMENTS OF THE FOLLOWING ACCEPTED CODES AND r - STANDARDS, WITHOUT LIMITING THE NUMBER, AS FOLLOWS. . >7 - 1. FLORIDA BUILDING CODE - 2007 W/ 2009 SUPPLEMENTS. 2. GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH �` *f zj DEPARTMENT CARE FACILITIES 2006 EDITION. ❑ ❑ a LOCATION OF WORK 3. NATIONAL ELECTRICAL CODE (NEC 2008). L 4. .ENVIRONMENTAL PROTECTION AGENCY (EPA). V, 5. DEPT. OF ENVIRONMENTAL REGULATION MANAGEMENT (DERM). Seel CODED NOTES: 6. LOCAL ORDINANCES, REGULATIONS OF THE BUILDING DEPTS. AND FIRE :����� °` '� •, DEPTS. Ykti �,.• '" tx REMOVE DOOR DURING CONSTRUCTION PHASE. .,. 7. RECOMMENDATIONS OF NFPA, IN GENERAL AND IN PARTICULAR: INSTALL DOOR AFTER Y ICRA - 2ND FLOOR -- HVAC LIFE SAFETY, NFPA 101(2006, ri W. DEMOLITION /CONSTRUCTION IS COMPLETED. B. HVAC, NFPA 90A, (2002) X ; IICI -INIAL t,^ • " �� C. HVAC, NFPA 90B, (2006) EEOAI� 0 A. SUA 'PEZ P,E; SCALE. 1/8 = 1 —O REMOVE WALL AS REQUIRED TO ALLOW .; EXHAUST DUCT REMOVAL AND INSTALLATION OF D. HVAC, NFPA 96 (2004) ;- N+I�LySr 64'759 NEW KITCHEN HOOD EXHAUST AND MAKE UP AIR E. ( ) HOSPITALS, NFPA 99, 2005 DUCTS. PATCH AND REPAIR WALL OPENING 1 AFTER DEMOLITION /CONS RUCTION IS T COMPLETED. RELATIVE PRESSURE (0) EQUAL PRESSURE ( -) = NEGATIVE PRESSURE ( +) = POSITIVE PRESSURE Sheet Title: ICRA- SECOND FLOOR PLAN HVAC Project No.: 20046' Dater 02.18.2011 Scale: AS NOTEDI Drawn by: J. H., F.P.,J.B.' Checked by: V.A., E. Z. Sheet Number: M1 001