South Miami Hospital
B.H.S.F.
DEMOLITION PLAN - IST FLOOR - ELECTRICAL DEMOLITION ROOF PLAN -- ELECTRICAL
6200 S.W. 73 RD. Street
SCALE: 1/8» 1 �_8» SCALE: 1/8" = 1,_099 Miami, FL. 33143
a z w
w
. W
W
c a Cn �.
■ W J
M
LL.
ti
w
z
V a C.0
I„I„I
0
:
Y
DEMOLITION NOTES:
KEY PLAN
1O DISCONNECT AND REMOVE EXISTING SERVICE FOR EXISTING KITCHEN S.M.H.
HOOD EXHAUST FAN, INCLUDING WIRING FROM MCC IMCC -F LOCATED
4
IN MAIN ELECTRICAL ROOM IN THE FIRST FLOOR.s[
2� DISCONNECT AND REMOVE EXISTING HOOD LIGHTING CIRCUIT FROM'
a e +C
PANEL 11-6 -9 AND RECONNECT SAME CIRCUIT 11-6 -9 TO NEW HOOD
CONTROL PANEL FOR HOOD LIGHTS, AS INDICATED IN NEW PLANS. =r LOCATION
OF WORK
�t
DISCONNECT EXISTING LIFE SAFETY SYSTEM CIRCUIT 1E5 -25 FROM �, z
EXISTING KITCHEN FIRE SUPPRESSION SYSTEM CONTROL PANEL AND
RECONNECT SAME CIRCUIT 1E5 -25 TO NEW KITCHEN FIRE
SUPPRESSION SYSTEM CONTROL PANEL, AS INDICATED IN NEW PLANS.
DISCONNECT EXISTING LIFE SAFETY SYSTEM CIRCUIT 1E5 -23 FROM
EXISTING CO2 SWITCH AND REUSE THIS CIRCUIT 1E5 -25 TO PROVIDE
POWER TO NEW FIREISMOKE DAMPER AS INDICATED IN NEW PLANS.
5O DISCONNECT AND REMOVE EXISTING LIGHTNING PROTECTION SYSTEM
CONNECTION TO EXISTING KITCHEN HOOD EXHAUST FAN AND REWORK
SYSTEM TO CONNECT NEW KEF -1 AND KSF -1 TO EXISTING LIGHTNING
PROTECTION SYSTEM. NEW CONNECTION SHALL BE CERTIFIED AND
PROVIDED WITH A MASTER LABEL.
........
Seal
tit c, « CIL
1.° + x ^
Villa F.= <IONNSON P. *.'
icErvsE x 7I36-5
Sheet Title:
DEMOLITION
PLANS
ELECTRICAL
Project No.: 20046
Date: 02.18.2011
Scale: AS NOTED
Drawn by: S.Z.,J.B.
Checked by: P. A, D. J.
Sheet Number:
E100