11-122-002ELECTRICAL GENERAL NOTES
1. The work shall comply with the latest a plicable requirements of the National Electrical Code, O.S.H.A. FI rida
Building Code (2007 Edition with 2009 supplements)), National Fire Protection Association (NFPA) Code 101 2006 edition), 44. The Electrical Contractor shall furnish a complete set of as -built drawings, showing all changes and deviations to
AIA Guidelines for Design & Construction of Health Care Facilities (2006 edition), National Electrical Code (2008 edition), the Architect /Engineer prior to completion of the project.
Standards for Health Dare Facilities NFPA -99 (2005 edition) & other applicable Codes, Statues & Regulations governing
this installation, as a minimum standard, unless specifications listed herein or shown on plans require a higher standard.
2. All materials shall be new and bear underwriters' labels where applicable.
3. The work included consists of all supervision, labor, materials, equipment facilities, and installation required for the
complete satisfactory and approved electrical and communication systems as indicated on the drawings and called
for in this specification, or as may be reasonably implied by either.
4. Conductors shall consist of 98% conductivity copper, type THNN/THWN, sizes are AWG.
5. All conductors shall be stranded copper.
6. Contractor shall verify all equipment nameplate data for wiring and overcurrent protection requirements before
performing rough -in work.
7. All equipment shall be mounted on galvanized steel unistrut.
8. All EMT fittings shall be steel compression type.
9. All lugs shall be for copper conductors.
10. Label all equipment (disconnect switches, circuit breakers, controls, etc.) with engraved laminated plastic name
plates -screw attached to equipment.
11. Label all electrical outlets and light switches using engraved labels.
12. Contractor shall pay for all permits, fees, inspections and testing. Contractor to obtain permit and approved
submittals prior to beginning work or ordering equipment.
13. Electrical Contractor shall visit job site and familiarize himself with all conditions affecting electrical and
communications installation and make provisions as to the cost thereof. Existing conditions of electrical equipment,
light fixtures, etc... that are part of the final system shall be verified by the Contractor prior to submitting his bid.
14. Outlet boxes shall be pressed steel in dry locations. Cast alloy with threaded hubs in wet or damp locations
and special enclosures for other classified areas.
15. Electrical system shall be complete and effectively grounded as required by the latest edition of the N.E.C. or
local codes.
16. All required insurance shall be provided for protection against public liability and property damage for the
duration of the work.
17. Contractor shall submit shop drawings or cut sheets of lighting fixtures, switches and other electrical items for
approval by Engineer /Architect.
18. Contractor shall be responsible for all cutting and patching required of his work.
19. Label all panels w /typewritten directories (hand written is not acceptable).
20. Panelboards: Update panel directory showing any modification done in the panel for all existing electrical panels.
21. The term "Provide" used in the construction documents and specifications indicates the Contractor shall furnish
and install.
22. The minimum bend radius for grounding installation, shall be 8 inches for #6 wire and smaller, 12 inches for
wire larger than #6.
24. Panelboards: All current carrying buss shall be copper. All ground bus bars shall be copper. A.I.C. ratings shall
be as indicated on panelboard schedules.
25. Once construction is completed, as -built drawings shall be provided to the Architect duly signed by the Electrical
Contractor.
26. PFOVide, post amd up a hand fMOFked eepy of the single lime diagfem depietimg edffent eemelitiem e
45. Prepare and affix a type written directory to the inside cover of each new and or existing (revised) panelboard
indicating loads controlled by each circuit.
46. Provide temporary electrical service for use by all trades during construction and remove same at completion of
project. Temporary power is to be done per code.
47. All fuses she" be eUFFent limiting, peF U.6., Fated 690 yelts, unless etheFWiSe Met
48. Electrical contractor shall verify circuit protective devices rating for equipment prior to construction.
49. Contractor shall coordinate all work under his or her supervision and between work which is not under his
supervision but affects his work.
52. Provide one year guarantee for all material and workmanship.
53. Contractor shall use 3M Fire Barrier CP -25WB+ Caulk, for any metal conduit penetration trhough a fire wall.
56. Only metallic conduit shall be used for all above ground applications (exposed or concealed) in this project.
57. Contractor shall investigate and trace carefully any existing conduit before removing or disconnecting it in
order to make sure no existing equipment or system will be left without power. Contractor shall notify owner and
engineer if the removal of any existing conduit will leave any existing equipment without power.
58. Contractor shall prepare and submit to engineer 1/4" or 1/2" scale shop drawings of any electrical equipment
room (closet), UPS room, Engine /Generator Room, House Service Panel Room, etc. showing in detail actual room layout,
equipment actual dimensions and actual conduit runs and sizes.
59. All conductors which are not terminated and have the potential to become energized during this project shall
have their ends insulated. Conductors up to #6 shall be protected by screwing on a wire -nut, sized for that conductor,
on the ends of the conductors. Conductors #4 and larger shall require a heat shrink rubber boot type fitting.
Electrical tape will not be an acceptable form of insulating the ends of conductors.
60. Contractor shall run 3/4" conduit with pullwire from data outlet to ceiling space (if there is ceiling) or to
10' A.F.F. if there is no ceiling. Provide plastic bushing at stub -up conduit.
Telephone /data wiring by Telephone Contractor. Coordinate this work with Telephone Contractor before submitting bid.
61. Drawings are diagrammatic and shall not be scaled. Refer to architectural plans and elevations for exact
location of all equipment. Electrical Contractor shall furnish and install all items required for a complete and acceptable
working installation.
62. The electrical system shall be completely and effectively grounded as required in Article 250 of the National
Electrical Code.
63. The electrical, telephone and cable television installations shall meet all requirements by the local utility companies.
64. Location of electrical equipment shown is approx. contractor shall field verify exact dimensions and field conditions
before installing equipment to make sure installation comply with NEC.
65. Documentation for Equipotential Grounding in all patient care areas shall be provided. This documentation and an
approved meter for testing shall be readily available at final survey. (NFPA 99 4.3.3).
28. Contractor shall coordinate any power interruption of the building with Owner and submit a Request of Power Shutdown. 66. tiaise eall 5rite, s to be e ceitified ut the end of this project aiid said certification eport shall be available
29. Prior to any power interruption, Contractor shall submit MOP for Owner approval.
30. The temperature rating associated with the ampacity of a conductor shall be so selected and coordinated as to
not exceed the lowest temperature rating of connected termination, conductor or device.
31. It shall not be the intent of these plans and /or specifications to show every minor detail of construction. The
Electrical Contractor shall be expected to furnish and install items for a complete electrical system and provide all
requirements necessary for equipment to be placed in proper working order.
32. The electrical Contractor shall keep all areas in which work is being performed free from debris at all items and
areas shall be left broom clean at the end of each working day.
33. The Electrical Contractor shall be responsible to repair to original conditions any and all damages to building
surfaces, equipment and furnishings caused during performance of work.
34. Where core drilling of floor /walls is required, Contractor shall seal openings watertight after utilities have been
installed. Location of cored holes shall be coordinated with location of equipment in a manner to be clean and
functional. The Contractor shall install only one conduit per hole and seal the opening around the conduit as
specified. Coordinate this with Owner representative.
35. Provide fire retardant U.L. approved sealant on all penetrations of fire rated partitions, walls and structural slabs.
It shall be the responsibility of the Electrical Contractor to verify, prior to submitting bid, locations of all such fire
rated partitions, wall and structural slabs.
36. Phase eFF8AgeFR@Rt Sh011 be PF9peFIy d@t0FFAiAed 6A GGG9FdQA6@ with AFt. 43Q.9:7 (13) ef N.E.G. wee of phese
37. Electrical Contractor shall demolish all remaining conduit, outlets, lighting fixtures, any electrical device and their
associated wiring that will not be re -used in this project and that is in the project area. Remove wiring back to
power source. If conduit part cannot be removed, abandon it in place duly capped at both ends.
38. Commission the electrical system free from grounds, tested for insulation integrity, voltage drop, and circuit
balanced as indicated on plan prior to final acceptance.
39. It shall be understood that all work performed shall be done by a licensed Electrical Contractor and in a first
class workmanlike manner. Said Contractor shall meet all requirements set forth by any local ordinance and /or
governing authorities.
40. Unless noted as existing, all equipment, wiring, devices, etc. shall be new and as specified. Equipment is to be
listed.
41. Contractor shall guarantee all materials and workmanship free from defects for a period of not less than (1)
year from date of acceptance, unless indicated or specified otherwise.
42. It shall be the responsibility of the Electrical Contractor for the advanced ordering of long lead items so as not
to interfere with the production of other trades resulting in any down or lag time.
43. All electrical equipment, devices, wire, etc., shall be listed for the intended use, with Underwriter's Laboratories,
Inc. (UL) where standards have been established by UL. As a minimum, all equipment shall meet applicable
standards for the type of equipment and intended use of the following:
A. American National Standards Institute (ANSI).
B. Illuminating Engineers Society (IES).
C. America Society Testing and Materials (ASTM).
D. National Electrical Manufacturer's Association (NEMA).
NOTE: These standards are subordinate to code and standards set by UL.
DEMOLITION LEGEND
EXISTING EQUIPMENT TO REMAIN
f� EXISTING EQUIPMENT TO BE RELOCATED
EXISTING EQUIPMENT TO BE REMOVED
1 7:] NEW EQUIPMENT
COLOR CODE
YELLOW LIFE SAFETY
ORANGE CRITICAL
GREEN EQUIPMENT
RED FIRE ALARM
CONSTRUCTION WORK AREA VENTILATION NOTES
TYPE "A" HIGHEST RISK. CLASS III.
1. CONTRACTR
PREP REDOBYSOWNER FOR THISMPROJ T .ECHOCONTRACTORESHIALL POERFORM ALL WORK SINEA&C IIRDANCE
WITH SAID REQUIREMENTS. CONTRACTOR SHALL ADHERE TO THE LIMITS OF THE CONSTRUCTION AREA.
2. AS MAY BE REQUIRED BY THE ICRA, THE CONTRACTOR SHALL MAKE EVERY EFFORT TO MAINTAIN
EXIST. LEVELS OF INDOOR AIR QUALITY IN AREAS SURROUNDING CONSTRUCTION AREA.
3. IN ADDITION TO COMPLYING WITH THE REQUIREMENT OF THE I.C.R.A., THE CONTRACTOR SHALL ALSO
PROVIDE ALL THE NECESSARY COMPONENTS AND EQUIPMENT TO CREATE A NEGATIVE PRESSURE
IN THE CONSTRUCTION AREA RELATIVE TO ADJACENT AREAS, EXISTING HVAC SYSTEM(S)
SHALL NOT BE USED FOR THIS FUNCTION, UNLESS SPECIFICALLY APPROVED BY THE
OWNER'S INFECTION CONTROL OFFICER.
THE CONCEPT AND ALL ASPECTS OF THIS WORK SHALL BE DONE IN ACCORDANCE WITH THE I.C.R.A.
REQUIREMENTS AND AT A MINIMUM ARE AS FOLLOWS:
VERIFY THAT ALL EXISTING DUCTWORK WHICH PASSES THROUGH THE WORK AREA
REMAIN, IS SEALED, AND PROTECTED DURING THE CONSTRUCTION WORK. COVER ALL SUPPLY
RETURN /EXHAUST OPENINGS WITH FILTER MEDIA.
AIR REMOVED FROM THE CONSTRUCTION ZONE SHALL BE FILTERED AND /OR DISCHARGED AS
INDICATED ON THE CONSTRUCTION WORK AREAS.
MONITOR AND VERIFY NEGATIVE PRESSURE IS BEING MAINTAINED IN ACCORDANCE WITH THE ICRA
REPORT, AND PROVIDE DOCUMENTATION TO THE OWNER AS REQUIRED.
4. ANY REQUIRED EQUIP. SHUTDOWN W /THE OWNER, SHALL BE COORDINATED IN ADVANCE TO ASSURE
THA SHUTDOWN WILL NOT ADVERSALLY AFFECT AIR PRESSURE RELATIONSHIPS.
5. CONTRACTOR SHALL HAVE AIR NEGATIVE AIR MACHINES, DISCHARGE AIR DUCTS & ANT MODIFICATIONS
TO EXISTING HVAC SYSTEMS READY PRIOR TO DEMOLITION.
6. DEMOLITION WORK SHALL NOT BEGIN UNTIL CONSTRUCTION WORK AREAS) T & B REPORT HAS BEEN
REVIEWED & ACCEPTED BY THE ARCH., ENGINEER, & THE OWNER'S INFECTION CONTROL MANAGER.
7. PLASTIC ENCLOSURE CONSTRUCTION ISOLATION SHALL BE CREATED WHERE WORK IS PERMITTED IN
THE CORRIDORS. H.E.P.A. VACUUM SHALL BE USED TO CLEAN WITHIN THE CUBE AFTER THE WORK
HAS BEEN COMPLETED.
1 EQUIPMENT SPECIFICATIONS:
1. NEGATIVE AIR MACHINES - ABATEMENT TECHNOLOGIES MODEL HEPA -AIRE PAS (800- 634 -9091)
OR EQUIVALENT. PROVIDE WITH THE FOLLOWING FEATURES:
A.) U.L. OR E.T.L. LISTED,
B.) STAINLESS STEEL CABINET WITH INTEGRAL TRANSPORT DOLLY AND EXHAUST COLLAR.
C.) UP TO FOUR STAGES OF FILTRATION WITH ZERO BYPASS CABINET CONSTRUCTION.
a.) FIRST STAGE 1" PARTICULATE FILTER.
b.) SECOND STAGE 2" PLEATED FILTER.
c.) OPTION CARBON FILTER TRACK.
d.) 99.97% EFFICIENT DOP HEPA FILTER.
D.) FILTER CHANGE INDICATOR LAMP FOR PRE - FILTER AND FINAL FILTERS.
E.) POWER CORD FOR 120 VAC POWER CONNECTION, OPERATING HOUR METER, TWO SPEED OR
VARIABLE SPEED BLOWER.
2. PREDATOR 600 PORTABLE AIR SCRUBER VARIABLE SPEED MODEL - ABATEMENT TECHNOLOGIES
WITH I.C.R.A. PACKAGE (1- 888 - 634 -9091) U.L. OR E.T.L. LISTED OR EQUIVALENT SIZED FOR
MINIMUM 8 AC /HR.
ELECTRICAL SYMBOL
... .. . . - . .. . . .. . . . - . . - . M.. • .. . - . We-To ... .. ...
- MWAM . - 57.7111111 =0# -
DESCRIPTION
..
JUNCTION BOX
52. Provide one year guarantee for all material and workmanship.
53. Contractor shall use 3M Fire Barrier CP -25WB+ Caulk, for any metal conduit penetration trhough a fire wall.
56. Only metallic conduit shall be used for all above ground applications (exposed or concealed) in this project.
57. Contractor shall investigate and trace carefully any existing conduit before removing or disconnecting it in
order to make sure no existing equipment or system will be left without power. Contractor shall notify owner and
engineer if the removal of any existing conduit will leave any existing equipment without power.
58. Contractor shall prepare and submit to engineer 1/4" or 1/2" scale shop drawings of any electrical equipment
room (closet), UPS room, Engine /Generator Room, House Service Panel Room, etc. showing in detail actual room layout,
equipment actual dimensions and actual conduit runs and sizes.
59. All conductors which are not terminated and have the potential to become energized during this project shall
have their ends insulated. Conductors up to #6 shall be protected by screwing on a wire -nut, sized for that conductor,
on the ends of the conductors. Conductors #4 and larger shall require a heat shrink rubber boot type fitting.
Electrical tape will not be an acceptable form of insulating the ends of conductors.
60. Contractor shall run 3/4" conduit with pullwire from data outlet to ceiling space (if there is ceiling) or to
10' A.F.F. if there is no ceiling. Provide plastic bushing at stub -up conduit.
Telephone /data wiring by Telephone Contractor. Coordinate this work with Telephone Contractor before submitting bid.
61. Drawings are diagrammatic and shall not be scaled. Refer to architectural plans and elevations for exact
location of all equipment. Electrical Contractor shall furnish and install all items required for a complete and acceptable
working installation.
62. The electrical system shall be completely and effectively grounded as required in Article 250 of the National
Electrical Code.
63. The electrical, telephone and cable television installations shall meet all requirements by the local utility companies.
64. Location of electrical equipment shown is approx. contractor shall field verify exact dimensions and field conditions
before installing equipment to make sure installation comply with NEC.
65. Documentation for Equipotential Grounding in all patient care areas shall be provided. This documentation and an
approved meter for testing shall be readily available at final survey. (NFPA 99 4.3.3).
28. Contractor shall coordinate any power interruption of the building with Owner and submit a Request of Power Shutdown. 66. tiaise eall 5rite, s to be e ceitified ut the end of this project aiid said certification eport shall be available
29. Prior to any power interruption, Contractor shall submit MOP for Owner approval.
30. The temperature rating associated with the ampacity of a conductor shall be so selected and coordinated as to
not exceed the lowest temperature rating of connected termination, conductor or device.
31. It shall not be the intent of these plans and /or specifications to show every minor detail of construction. The
Electrical Contractor shall be expected to furnish and install items for a complete electrical system and provide all
requirements necessary for equipment to be placed in proper working order.
32. The electrical Contractor shall keep all areas in which work is being performed free from debris at all items and
areas shall be left broom clean at the end of each working day.
33. The Electrical Contractor shall be responsible to repair to original conditions any and all damages to building
surfaces, equipment and furnishings caused during performance of work.
34. Where core drilling of floor /walls is required, Contractor shall seal openings watertight after utilities have been
installed. Location of cored holes shall be coordinated with location of equipment in a manner to be clean and
functional. The Contractor shall install only one conduit per hole and seal the opening around the conduit as
specified. Coordinate this with Owner representative.
35. Provide fire retardant U.L. approved sealant on all penetrations of fire rated partitions, walls and structural slabs.
It shall be the responsibility of the Electrical Contractor to verify, prior to submitting bid, locations of all such fire
rated partitions, wall and structural slabs.
36. Phase eFF8AgeFR@Rt Sh011 be PF9peFIy d@t0FFAiAed 6A GGG9FdQA6@ with AFt. 43Q.9:7 (13) ef N.E.G. wee of phese
37. Electrical Contractor shall demolish all remaining conduit, outlets, lighting fixtures, any electrical device and their
associated wiring that will not be re -used in this project and that is in the project area. Remove wiring back to
power source. If conduit part cannot be removed, abandon it in place duly capped at both ends.
38. Commission the electrical system free from grounds, tested for insulation integrity, voltage drop, and circuit
balanced as indicated on plan prior to final acceptance.
39. It shall be understood that all work performed shall be done by a licensed Electrical Contractor and in a first
class workmanlike manner. Said Contractor shall meet all requirements set forth by any local ordinance and /or
governing authorities.
40. Unless noted as existing, all equipment, wiring, devices, etc. shall be new and as specified. Equipment is to be
listed.
41. Contractor shall guarantee all materials and workmanship free from defects for a period of not less than (1)
year from date of acceptance, unless indicated or specified otherwise.
42. It shall be the responsibility of the Electrical Contractor for the advanced ordering of long lead items so as not
to interfere with the production of other trades resulting in any down or lag time.
43. All electrical equipment, devices, wire, etc., shall be listed for the intended use, with Underwriter's Laboratories,
Inc. (UL) where standards have been established by UL. As a minimum, all equipment shall meet applicable
standards for the type of equipment and intended use of the following:
A. American National Standards Institute (ANSI).
B. Illuminating Engineers Society (IES).
C. America Society Testing and Materials (ASTM).
D. National Electrical Manufacturer's Association (NEMA).
NOTE: These standards are subordinate to code and standards set by UL.
DEMOLITION LEGEND
EXISTING EQUIPMENT TO REMAIN
f� EXISTING EQUIPMENT TO BE RELOCATED
EXISTING EQUIPMENT TO BE REMOVED
1 7:] NEW EQUIPMENT
COLOR CODE
YELLOW LIFE SAFETY
ORANGE CRITICAL
GREEN EQUIPMENT
RED FIRE ALARM
CONSTRUCTION WORK AREA VENTILATION NOTES
TYPE "A" HIGHEST RISK. CLASS III.
1. CONTRACTR
PREP REDOBYSOWNER FOR THISMPROJ T .ECHOCONTRACTORESHIALL POERFORM ALL WORK SINEA&C IIRDANCE
WITH SAID REQUIREMENTS. CONTRACTOR SHALL ADHERE TO THE LIMITS OF THE CONSTRUCTION AREA.
2. AS MAY BE REQUIRED BY THE ICRA, THE CONTRACTOR SHALL MAKE EVERY EFFORT TO MAINTAIN
EXIST. LEVELS OF INDOOR AIR QUALITY IN AREAS SURROUNDING CONSTRUCTION AREA.
3. IN ADDITION TO COMPLYING WITH THE REQUIREMENT OF THE I.C.R.A., THE CONTRACTOR SHALL ALSO
PROVIDE ALL THE NECESSARY COMPONENTS AND EQUIPMENT TO CREATE A NEGATIVE PRESSURE
IN THE CONSTRUCTION AREA RELATIVE TO ADJACENT AREAS, EXISTING HVAC SYSTEM(S)
SHALL NOT BE USED FOR THIS FUNCTION, UNLESS SPECIFICALLY APPROVED BY THE
OWNER'S INFECTION CONTROL OFFICER.
THE CONCEPT AND ALL ASPECTS OF THIS WORK SHALL BE DONE IN ACCORDANCE WITH THE I.C.R.A.
REQUIREMENTS AND AT A MINIMUM ARE AS FOLLOWS:
VERIFY THAT ALL EXISTING DUCTWORK WHICH PASSES THROUGH THE WORK AREA
REMAIN, IS SEALED, AND PROTECTED DURING THE CONSTRUCTION WORK. COVER ALL SUPPLY
RETURN /EXHAUST OPENINGS WITH FILTER MEDIA.
AIR REMOVED FROM THE CONSTRUCTION ZONE SHALL BE FILTERED AND /OR DISCHARGED AS
INDICATED ON THE CONSTRUCTION WORK AREAS.
MONITOR AND VERIFY NEGATIVE PRESSURE IS BEING MAINTAINED IN ACCORDANCE WITH THE ICRA
REPORT, AND PROVIDE DOCUMENTATION TO THE OWNER AS REQUIRED.
4. ANY REQUIRED EQUIP. SHUTDOWN W /THE OWNER, SHALL BE COORDINATED IN ADVANCE TO ASSURE
THA SHUTDOWN WILL NOT ADVERSALLY AFFECT AIR PRESSURE RELATIONSHIPS.
5. CONTRACTOR SHALL HAVE AIR NEGATIVE AIR MACHINES, DISCHARGE AIR DUCTS & ANT MODIFICATIONS
TO EXISTING HVAC SYSTEMS READY PRIOR TO DEMOLITION.
6. DEMOLITION WORK SHALL NOT BEGIN UNTIL CONSTRUCTION WORK AREAS) T & B REPORT HAS BEEN
REVIEWED & ACCEPTED BY THE ARCH., ENGINEER, & THE OWNER'S INFECTION CONTROL MANAGER.
7. PLASTIC ENCLOSURE CONSTRUCTION ISOLATION SHALL BE CREATED WHERE WORK IS PERMITTED IN
THE CORRIDORS. H.E.P.A. VACUUM SHALL BE USED TO CLEAN WITHIN THE CUBE AFTER THE WORK
HAS BEEN COMPLETED.
1 EQUIPMENT SPECIFICATIONS:
1. NEGATIVE AIR MACHINES - ABATEMENT TECHNOLOGIES MODEL HEPA -AIRE PAS (800- 634 -9091)
OR EQUIVALENT. PROVIDE WITH THE FOLLOWING FEATURES:
A.) U.L. OR E.T.L. LISTED,
B.) STAINLESS STEEL CABINET WITH INTEGRAL TRANSPORT DOLLY AND EXHAUST COLLAR.
C.) UP TO FOUR STAGES OF FILTRATION WITH ZERO BYPASS CABINET CONSTRUCTION.
a.) FIRST STAGE 1" PARTICULATE FILTER.
b.) SECOND STAGE 2" PLEATED FILTER.
c.) OPTION CARBON FILTER TRACK.
d.) 99.97% EFFICIENT DOP HEPA FILTER.
D.) FILTER CHANGE INDICATOR LAMP FOR PRE - FILTER AND FINAL FILTERS.
E.) POWER CORD FOR 120 VAC POWER CONNECTION, OPERATING HOUR METER, TWO SPEED OR
VARIABLE SPEED BLOWER.
2. PREDATOR 600 PORTABLE AIR SCRUBER VARIABLE SPEED MODEL - ABATEMENT TECHNOLOGIES
WITH I.C.R.A. PACKAGE (1- 888 - 634 -9091) U.L. OR E.T.L. LISTED OR EQUIVALENT SIZED FOR
MINIMUM 8 AC /HR.
ALL ABBREVIATIONS LISTED ABOVE ARE NOT NECESSARILY USED IN THIS PROJECT
SCOPE OF WORK NARRATIVE:
SOUTH MIAMI HOSPITAL
NORTH TOWS : (2ND FLOOR CVCU- ROOM 1, 8, 9, 10, 11 & 12)
EXISTING VISICU SYSTEM WILL BE REMOVED FROM THE ABOVE MENTIONED ROOMS AND RETURNED TO OWNER.
CAMERAS WITH MICROPHONE WILL BE RE -USED TO BE INSTALLED IN 4TH FLOOR OF PAVILION BUILDING.
PAVILION BUILDING: (4TH FLOOR- ROOM 408, 420, 423, 424, 425 & 426).
NEW VISICU SYSTEM WILL BE INSTALLED IN ABOVE MENTIONED ROOMS.
CAMERAS WITH MICROPHONE ARE BEING RELOCATED FROM SECOND FLOOR, NORTH TOWER.
CONTRACTOR SHALL COORDINATE ALL WORK WITH PROJECT MANAGER AND WITH VISICU VENDOR. ALL EQUIPMENT SHALL BE INSTALLED
AS PER MANUFACTURER SPECIFICATIONS.
ACTIONS TO BE PERFORMED DURING
CONSTRUCTION.
1- MANTAIN NEGATIVE AIR PRESSURE WITHIN WORK AREA UTILIZING
"HEPA" EQUIPPED AIR FILTRATION UNITS.
2- CONTAIN CONSTRUCTION WASTE IN TIGHTLY COVERED
CONTAINERS BEFORE TRANSPORTING.
3- COVER TRANSPORT RECEPTACLES OR CARTS. TAPE
COVERING UNLESS SOLID LID.
4- PLACE DUST MAP AT ENTRANCE AND EXIT OF WORK AREA.
ACTIONS TO BE PERFORMED UPON WORK
COMPLETION /PRIOR TO OCCUPANCY
1- VACUUM WORK AREA WITH "HEPA" FILTERED VACUUMS.
2- CONTAIN CONSTRUCTION WASTE IN TIGHTLY COVERED
CONTAINERS BEFORE TRANSPORTING.
3- COVER TRANSPORT RECEPTACLES OR CARTS. TAPE
COVERING UNLESS SOLID LID.
4- FINAL CLEANING BY ENVIRONMENTAL SERVICES PRIOR
TO OCCUPANCY.
ALL EXISTING AIR DISTRIBUTION DEVICES (WHETHER SHOWN ON THIS DWG.
OR NOT) WITHIN WORK AREAS SHALL BE SEALED AIRTIGHT DURING
CONSTRUCTION & SHALL BE RESTORED TO "AS -WAS" CONDITION "AFTER"
ALL WORK IS COMPLETED.
ELECTRICAL SYMBOL
LEGEND
SYMBOL
DESCRIPTION
JB
JUNCTION BOX
CELA -3
SINGLE RECEPTACLE. "ELA -3" INDICATES RECEPTACLE IS FED
FROM CIRCUIT #3 IN PANEL ELA.
ELA -3
DUPLEX RECEPTACLE. "ELA -3" INDICATES RECEPTACLE IS FED
FROM CIRCUIT #3 IN PANEL ELA.
ELA -3
QUADRUPLEX RECEPTACLE. "ELA -3" INDICATES RECEPTACLE IS
FED FROM CIRCUIT #3 IN PANEL ELA.
OJ JB
JUNCTION BOX
MOUNTING HEIGHT
ATS
DATA OUTLET.
MCB
®
VISICU AUDIO- VISUAL SERVER
BACKBOARD
C�CI
VISICU CAMERA W /MICROPHONE
BKR
S�
CEILING MOUNTED SPEAKER FOR VISICU SYSTEM.
METHOD OF PROCEDURE
0
VISICU MONITOR.
NEBS
10
VISICU ELERT CALL BUTTON.
BUILDING SERVICE CENTER
O
ELECTRIC PANELBOARD.
C
E
CONDUIT SLEEVE.
NATIONAL ELECTRICAL CODE
CB
CONCEALED CONDUIT.
NIC
- - - - --
COMMUNICATION CABLES.
CIRCUIT CAPACITY MANAGER
NL
ALL ELECTRICAL SYMBOLS ARE NOT NECESSARILY USED IN THIS PROJECT
ALL ABBREVIATIONS LISTED ABOVE ARE NOT NECESSARILY USED IN THIS PROJECT
SCOPE OF WORK NARRATIVE:
SOUTH MIAMI HOSPITAL
NORTH TOWS : (2ND FLOOR CVCU- ROOM 1, 8, 9, 10, 11 & 12)
EXISTING VISICU SYSTEM WILL BE REMOVED FROM THE ABOVE MENTIONED ROOMS AND RETURNED TO OWNER.
CAMERAS WITH MICROPHONE WILL BE RE -USED TO BE INSTALLED IN 4TH FLOOR OF PAVILION BUILDING.
PAVILION BUILDING: (4TH FLOOR- ROOM 408, 420, 423, 424, 425 & 426).
NEW VISICU SYSTEM WILL BE INSTALLED IN ABOVE MENTIONED ROOMS.
CAMERAS WITH MICROPHONE ARE BEING RELOCATED FROM SECOND FLOOR, NORTH TOWER.
CONTRACTOR SHALL COORDINATE ALL WORK WITH PROJECT MANAGER AND WITH VISICU VENDOR. ALL EQUIPMENT SHALL BE INSTALLED
AS PER MANUFACTURER SPECIFICATIONS.
ACTIONS TO BE PERFORMED DURING
CONSTRUCTION.
1- MANTAIN NEGATIVE AIR PRESSURE WITHIN WORK AREA UTILIZING
"HEPA" EQUIPPED AIR FILTRATION UNITS.
2- CONTAIN CONSTRUCTION WASTE IN TIGHTLY COVERED
CONTAINERS BEFORE TRANSPORTING.
3- COVER TRANSPORT RECEPTACLES OR CARTS. TAPE
COVERING UNLESS SOLID LID.
4- PLACE DUST MAP AT ENTRANCE AND EXIT OF WORK AREA.
ACTIONS TO BE PERFORMED UPON WORK
COMPLETION /PRIOR TO OCCUPANCY
1- VACUUM WORK AREA WITH "HEPA" FILTERED VACUUMS.
2- CONTAIN CONSTRUCTION WASTE IN TIGHTLY COVERED
CONTAINERS BEFORE TRANSPORTING.
3- COVER TRANSPORT RECEPTACLES OR CARTS. TAPE
COVERING UNLESS SOLID LID.
4- FINAL CLEANING BY ENVIRONMENTAL SERVICES PRIOR
TO OCCUPANCY.
ALL EXISTING AIR DISTRIBUTION DEVICES (WHETHER SHOWN ON THIS DWG.
OR NOT) WITHIN WORK AREAS SHALL BE SEALED AIRTIGHT DURING
CONSTRUCTION & SHALL BE RESTORED TO "AS -WAS" CONDITION "AFTER"
ALL WORK IS COMPLETED.
ABBREVIATIONS
oz
A.F.
AMP FRAME
JB
JUNCTION BOX
A.T.
AMP TRIP
LMS
LIGHT MOTION SWITCH
A.F.F.
ABOVE FINISHED FLOOR
L &S
LANDIS AND STAEFA
AL
ALUMINUM
MH
MOUNTING HEIGHT
ATS
AUTOMATIC TRANSFER SWITCH
MCB
MAIN CIRCUIT BREAKER
B'BD
BACKBOARD
MLO
MAIN LUGS ONLY
BKR
BREAKER
MOP
METHOD OF PROCEDURE
BLDG
BUILDING
NEBS
NETWORK EQUIPMENT BUILDING SYSTEM
BSC
BUILDING SERVICE CENTER
NF
NOT FUSIBLE
C
CONDUIT
NEC
NATIONAL ELECTRICAL CODE
CB
CIRCUIT BREAKER
NIC
NOT IN CONTRACT
CCM
CIRCUIT CAPACITY MANAGER
NL
NEW LOCATION
CH
CHILLER
OL
OVERLOAD
CKT
CIRCUIT
PB
PULL BOX
CLG
CEILING
PNL
PANEL
CT
COOLING TOWER
PVC
POLYVINYL CHLORIDE CONDUIT
COMM. CTR.
COMMUNICATION CENTER
RACCC
REMOTE ALARM CROSS CONNECT CABINET
DWG
DRAWING
RCPT
RECEPTACLE
EC
EMPTY CONDUIT
RE
EXISTING TO BE REMOVED
EF
EXHAUST FAN
RF
FREQUENCY
ELECT
ELECTRICAL
EMT
ELECTRIC METALLIC TUBING
RL
EXISTING TO BE RELOCATED
EMS
ENERGY MANAGEMENT SYSTEM
RGS
RIGID GALVANIZED STEEL CONDUIT
EX /EXIST.
EXISTING
RM
ROOM
FACP
FIRE ALARM CONTROL PANEL
SDD
SMOKE DUCT DETECTOR
FE
FIRE EXTINGUISHER
SW
SWITCH
FHC
FIRE HOSE CABINET
T
TRACK
FLUOR /F
FLUORESCENT
TEL
TELEPHONE
FPL
FLORIDA POWER & LIGHT
U01
UNLESS OTHERWISE INDICATED
GFI
GROUND FAULT CIRCUIT INTERRUPTER
VFD
VARIABLE FREQUENCY DRIVE
WP
WEATHER PROOF
GIRD
GROUND
WT
WATER TIGHT
H -O -A
HAND -OFF- AUTOMATIC
XFMR
TRANSFORMER
HP
HORSE POWER
ALL ABBREVIATIONS LISTED ABOVE ARE NOT NECESSARILY USED IN THIS PROJECT
SCOPE OF WORK NARRATIVE:
SOUTH MIAMI HOSPITAL
NORTH TOWS : (2ND FLOOR CVCU- ROOM 1, 8, 9, 10, 11 & 12)
EXISTING VISICU SYSTEM WILL BE REMOVED FROM THE ABOVE MENTIONED ROOMS AND RETURNED TO OWNER.
CAMERAS WITH MICROPHONE WILL BE RE -USED TO BE INSTALLED IN 4TH FLOOR OF PAVILION BUILDING.
PAVILION BUILDING: (4TH FLOOR- ROOM 408, 420, 423, 424, 425 & 426).
NEW VISICU SYSTEM WILL BE INSTALLED IN ABOVE MENTIONED ROOMS.
CAMERAS WITH MICROPHONE ARE BEING RELOCATED FROM SECOND FLOOR, NORTH TOWER.
CONTRACTOR SHALL COORDINATE ALL WORK WITH PROJECT MANAGER AND WITH VISICU VENDOR. ALL EQUIPMENT SHALL BE INSTALLED
AS PER MANUFACTURER SPECIFICATIONS.
ACTIONS TO BE PERFORMED DURING
CONSTRUCTION.
1- MANTAIN NEGATIVE AIR PRESSURE WITHIN WORK AREA UTILIZING
"HEPA" EQUIPPED AIR FILTRATION UNITS.
2- CONTAIN CONSTRUCTION WASTE IN TIGHTLY COVERED
CONTAINERS BEFORE TRANSPORTING.
3- COVER TRANSPORT RECEPTACLES OR CARTS. TAPE
COVERING UNLESS SOLID LID.
4- PLACE DUST MAP AT ENTRANCE AND EXIT OF WORK AREA.
ACTIONS TO BE PERFORMED UPON WORK
COMPLETION /PRIOR TO OCCUPANCY
1- VACUUM WORK AREA WITH "HEPA" FILTERED VACUUMS.
2- CONTAIN CONSTRUCTION WASTE IN TIGHTLY COVERED
CONTAINERS BEFORE TRANSPORTING.
3- COVER TRANSPORT RECEPTACLES OR CARTS. TAPE
COVERING UNLESS SOLID LID.
4- FINAL CLEANING BY ENVIRONMENTAL SERVICES PRIOR
TO OCCUPANCY.
ALL EXISTING AIR DISTRIBUTION DEVICES (WHETHER SHOWN ON THIS DWG.
OR NOT) WITHIN WORK AREAS SHALL BE SEALED AIRTIGHT DURING
CONSTRUCTION & SHALL BE RESTORED TO "AS -WAS" CONDITION "AFTER"
ALL WORK IS COMPLETED.
J
(n
oz
210 -840
M
Q
PLOT SIZE:
AS NOTED
DESIGNED /DRAWN BY:A.V.
CHECKED BY:
F.A.
SHEET No.:
E -1
SHEET 1 OF 8
.,
W
V)
cr_
W
�
M
O
06
J
I�
CIO:
Z
W
W
Z
�
z W
LLj
o C'
J
J
�QU
�
J
(n
oz
210 -840
M
Q
PLOT SIZE:
AS NOTED
DESIGNED /DRAWN BY:A.V.
CHECKED BY:
F.A.
SHEET No.:
E -1
SHEET 1 OF 8
.,
W
V)
cr_
W
M
M
oa
06
J
I�
CIO:
Z
W
W
Z
�
z W
LLj
o C'
J
FILE:
JOB NO.:
210 -840
DATE :
12 -01 -10
PLOT SIZE:
AS NOTED
DESIGNED /DRAWN BY:A.V.
CHECKED BY:
F.A.
SHEET No.:
E -1
SHEET 1 OF 8