11-1216-007THROUGH - PENETRATION FIRESTOP SYSTEMS SYSTEM NO. W- 11-2039 F RATINGS -1, 1 i , AND 2 HR T RATINGS -3 AND 1 i HR I. WALL ASSEMBLY - THE I OR 2 HR FIRE -RATED GYPSUM WALLBOARD /STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 5ERIE5 WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING MAY GON515T OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CON515T OF NOM 2 BY 4 IN. LUMBER 5PAGED 16 IN. OC. STEEL STUDS TO BE MIN 2 -1/2 IN. WIDE AND SPACED MAX 24 IN. OG. B. GYPSUM BOARD" - 5/8 IN, THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGE5. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION 5HALL BE AS SPECIFIED IN THE INDIVIDUAL 0300 OR 0400 5ERIE5 DE51614 IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING la 2 -1/8 IN. 2. THROUGH - PENETRANTS - ONE NONMETALLIC PIPE OR TUBING TO BE CENTERED WITHIN THE FIRE5TOP SYSTEM. A NOM ANNULAR SPACE OF 112 IN, 15 REQUIRED WITHIN THE FIRE5TOP SYSTEM. PIPE OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH 51DE5 OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES AND TUBING MAY BE USED: A, POLYVINYL CHLORIDE (PVG) PIPE - NOM 1 -1/2 IN. DIAM (OR SMALLER) SCHEDULE 40 PVC, PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING 5Y5TEM5, B. CHLORINATED POLYVINYL CHLORIDE ((,PV(,) PIPE - NOM I -112 IN, DIAM (OR SMALLER) 5DR 11 GVPG PIPE FOR USE IN CLOSED (PRO(E55 OR SUPPLY) PIPING SYSTEMS. G. FLAME RETARDANT POLYPROPYLENE (FRPP) PIPE - NOM 1 -112 IN. DIAM (OR SMALLER) SCHEDULE 40 FRPP PIPE FOR USE IN GL05ED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS. D, ELECTRICAL NONMETALLIC TUBING (ENT)+ - NOM 1 -112 IN, DIAM (OR SMALLER) ENT FORMED FROM POLYVINYL CHLORIDE. ENT TO BE INSTALLED IN ACCORDANCE WITH ARTICLE 331 OF THE NATIONAL ELECTRICAL CODE (NFPA NO. 10). SEE ELECTRICAL NONMETALLIC TUBING (FKHU) CATEGORY IN UL'5 ELECTRICAL CONSTRUCTION MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. THE F AND T RATINGS OF THE FIRE5TOP SYSTEM ARE DEPENDENT UPON THE HOURLY RATING OF THROUGH- PENETRANT A5 TABULATED BELOW: GENERAL NOTES MINIMUM 5TANOAR05: THESE 60145TRU6TION 006UMENT5 46HT REQUIRE LARGER SIZES, 6REATER 69JANTITIE5, MORE PROTECTION AND REQUIREMENT5 THAN THE 6OVERNIN6 BUILDING CODES, THE CONTRACTOR 15 RE5PON515LE FOR CARRYING OUT ALL OF THE PROVISIONS AND REQUIREMENT5 INCLUDED IN THESE PLANS AND SPECIFICATION5, 5M5TITUTION5, ALTERNATES OR CHANGES REQUE5TED TO MATCH LOWER STANDARDS PERMITTED BY THE BUILDING CODE WILL NOT BE ACCEPTED. NO ADDITIONAL PAYMENTS SHALL BE MADE TO THE CONTRACTOR TO CORRECT WORK THAT DOES NOT MEET ALL THE REQUIREMENT5 SET FORTH IN THESE CONSTRUCTION DOCUMENTS. A.I.A. DOCUMENT A -201: THE LATEST EDITION OF THE 'GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION ", AIA DOCUMENT A-201,15 HEREBY MADE A PART OF THESE PLANS AND SPECIFICATIONS. GOPIE5 ARE AVAILABLE FOR INSPECTION AT THE ARCHITEGT5 OFFICE. THESE 6ENERAL NOTES AND SPECIFICATIONS SHALL NOT BE CONSTRUED TO VOID ANY PORTION OF AIA DOCUMENT A -201. C4)N5TRUCTION DOCUMENTS: THESE BOUND FLAN5 AND SPEC IFICATION5 FORM A COMPLETE SET OF CONSTRUCTION DOCUMENTS AND SHOULD NOT BE SEPARATED FOR 05E BY VARIOUS SUB- TRADES EMPLOYED TO PROVIDE BID PROPOSALS OR EXECUTE TH15 PROJECT. A COMPLETE SET OF CONSTRUCTION DOCUMENTS 15 REQUIRED SO THAT EACH TRADE GAM COORDINATE THEIR BIDS AND WORK WITH THE TOTAL PROJECT. CON5TRUCTION DOCUMENT5 STAMPED 'NOT FOR CONSTRUCTION" SHALL NOT BE USED FOR BIDDING OR CONSTRUCTION AND ARE NOT PERMITTED ON THE JOB SITE. DO NOT SCALE DRAWING5. THE CONTRACTOR SHALL MAINTAIN A COMPLETE IF TO DATE SET OF CONSTRUCTION DOCUMENTS AND SHOP DRAWIN65 ON THE JOB SITE AT ALL TIMES DURING THE CONSTRUCTION PERIOD, THESE DOCUMENTS SHALL BE SECURED A6AIN5T ALL FORMS OF DAMAGE OR THEFT. C.ONSTRU(MON DOCUMENT REPRODUCTIONS: THESE PLANS ARE THE PROPERTY OF THE ARCHITECT, NO PORTION OF THESE CONSTRUCTION DOCUMENTS MAY BE REPRODUCED BY ANY MEANS OR METHODS WITHOUT THE EXPRE55 PRIOR AUTHORIZATION OF 5ALTZ MICHELSON ARCHITECTS. COPIES OF THE PLANS AND 5PECIFICATION5 ARE AVAILABLE FROM THE ARCHITECT. UNAUTHORIZED COPIE5 OF THESE PLANS MAY NOT PROVIDE CURRENT PROJECT INFORMATION AND MAY RESULT IN BID OR CONSTRUCTION DEFIGIENGIE5. SITE V151T: PRIOR TO BIDDING OR SUBMITTING ANY PROPOSAL THE GENERAL CONTRACTOR AND EACH SUBCONTRACTOR SHALL V151T THE JOB 51TE AND VERIFY ALL OF THE CONDITIONS UNDER WHICH TH15 WORK WILL BE PERFORMED, THE CONTRACTOR SHALL EXAMINE THE PLANS AMC) IT WILL BE AS5UMED THAT THE GONTRACTOR HAS INVE5TI6ATED AND 15 FULLY INFORMED AS TO THE CONDITIONS AND MATERIALS TO BE ENCOUNTERED AS TO CHARACTER, QUALITY AND QUANTITIES OF WORK TO BE PERFORMED AND MATERIALS TO BE FURNISHED AND AS TO THE REQUIREMENT5 OF THE PLANS. SUE16TITUTICIM: SUBSTITUTIONS OR DEVIATION5 FROM THE PLANS AND SPEGIFIGATIONS DURING BIDDING OR CONSTRUCTION ARE NOT PERMITTED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE OWNER AND /OR ARGHITEGT, FAILURE TO COMPLY WITH TH15 PROVISION WILL RESULT IN THE REJECTION OF THE WORK IN QUE5TION. THE CONTRACTOR WILL NOT BE COMPENSATED FOR UNAUTHORIZED 5U%TITUTION5 OR DEVIATION5 FROM THE PLANS AND WILL HAVE TO TAKE CORRECTIVE MEASURES AT HI5 OWN EXPENSE, ALTERNATES: REQUE5T5 FOR PRODUCT ALTERNATES OR 51,1I35TITUTION5 WILL ONLY BE CONSIDERED BY THE ARCHITECT WHEN SUBMITTED WITH A LETTER OF EXPLANATION. WHEN APPLICABLE THE REQUE5T SHALL INCLUDE; A COST COMPARISON, AVAILABILITY, TIME SCHEDULE COMPARISON, PRAWN05 AND /OR BROCHURE GUT SHEETS DEMON5TRATING THAT THE SUBSTITUTION OR ALTERNATE MEETS THE INTENDED PERFORMANCE AND QUALITY OF THE OR16INAL SPECIFICATION. CHANGE ORDERS: ALL CHAN6E ORDERS SHALL BE 516NED BY THE OWNER PRIOR TO COMMENCEMENT OF THE WORK TO BE GHAN6ED. THROUGH- PENETRATION FIRESTOP SYS'T'EMS SYSTEM NO. C -AJ -2168 F- RATING-3 HR T RATING -0 HR RE6IUE5T FOR PAYMENT: THE CONTRA( TQR5 'REQUEST FOR PAYMENT' SMALL INCLUDE RELEA5E5 OF LIEN FROM ALL MATERIAL SUPPLIERS AND SUBCONTRACTORS FOR 51YIPLIE5 AND WORK RELATING TO THE REQUEST FOR PAYMENT. NOTICE OF COMMENCEMENT: THE CONTRACTOR SMALL ASSIST THE OWNER IN THE PREPARATION AND FILING 05 A NOTICE OF COMMENCEMENT. HE SHALL INSURE THAT SAID NOTICE 15 PROMINENTLY POSTED ON THE PROPERTY AND PROTECTED FROM ALL FORMS DAMAGE. ALL SUBGONTRAGTOR5 AND MATERIAL SUPPLIERS SHALL BE MADE AWARE OF THE P05TIN6 OF TH15 DOCUMENT AND ARE REQUIRED TO SUBMIT A "NOTICE TO OWNER" BY CERTIFIED MAIL. HIDDEN CONDITION5: EXI5TIN6 UNOBSERVABLE COVERED, BURIED OR OTHERWISE HIDDEN CONDITIONS WHERE IN CONFLICT WITH THE CONSTRUCTION DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT AS SOON AS THEY ARE UNCOVERED, ADDITIONAL COSTS OR MODIFICATIONS OF THE WORK TO ACCOMMODATE THESE GONDITION5 SHALL BE APPROVED BY THE OWNER AND /OR ARGHITEGT PRIOR TO PERFORMANCE OF TH15 WORK. WHEN HIDDEN CONDITIONS ARE FOUND TO BE IN VIOLATION OF ANY 6OVERNIN69 CODE IN FORGE AT THE TIME OF CONSTRUCTION THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND /OR OWNER, GORREGTION OF EXI5TIN6 HIDDEN CODE VIOLATIONS SHALL BE APPROVED AND PAID FOR BY THE OWNER. 015CREPANCIES: THE GONTRACTOR SHALL FIELD GHEGK AND VERIFY ALL DIMENSIONS AND CONDITIONS AND BE RE52ON5113LE FOR SAME. WHEN IN THE OPINION OF THE CONTRACTOR A DISCREPANCY EXISTS, HE SHALL PROMPTLY REPORT IT IN WRITING TO THE AR( HITEGT PRIOR TO THE COMMENCEMENT OF THE WORK IN THE AREA OF 61UE5TION. NO ADDITIONAL PAYMENT SMALL BE MADE FOR THE GONTRAGTOR'5 FAILURE TO CORRECT GONFLIGTIN6 FIELD CONDITIONS, 5AFETY AND SECURITY: THE CONTRACTOR SHALL TAKE ALL PRECAUTIONS TO ENSURE THE SAFETY OF THE WORK FORGE AND PUBLIC, EXPOSED TO THE CONSTRUCTION PERFORMED UNDER THIS CONTRACT. HE SHALL SECURE THE WORK SITE AGAINST UNAUTHORIZED ENTRY AND MAINTAIN ALL SAFETY AND SECURITY MEA5URE5 THROUGH OUT THE DURATION OF THE WORK. 5AFE6UARD5: THE GENERAL CONTRACTOR SHALL PROVIDE 6UARDRAIL5, HANDRAILS, AND COVERS FOR ALL FLOOR, ROOF AND WALL OPENIN65. HE SHALL MAINTAIN AND RELOCATE ALL 5AFE6UARD5 AND PROTECTIVE FACILITIES AS REQUIRED BY SUBCONTRACTORS OR JOB, G0N5TRUGTI0N MEANS AND METH005: 5ALTZ MICHEL50H ARCHITECTS AND /OR ENGINEER(5) SHALL NOT HAVE CHARGE, CONTROL OR BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, 5EQUENGE5, PROCEDURES OR FOR SAFETY PRECAUTIONS AND PR06RAM5. IT 15 UNDERSTOOD AND AGREED THAT THE ARGHITEGT HAS NO CONSTRUCTIVE USE OF THE OWNERS SITE; HAS NO CONTROL OR AUTHORITY OVER THE MEANS, METHODS, AND SEQUENCES OF CONSTRUGTION; AND THEREFORE HAS NO ONGOING RESPONSIBILITY MAT50EVER FOR C,ON5TRU6TION 51TE SAFETY, A RESPONSIBILITY THAT HAS BEEN WHOLLY VESTED IN THE GENERAL CONTRACTOR. NOTWITHSTANDING THE ABOVE, THE ARGHITEGT HAS A DUTY TO PRESERVE AND PROTEGT PUBLIC HEALTH, SAFETY, AND WELFARE. ACC,ORDIN6LY, IT I5 5ALTZ M16HEL50N ARCHITECTS PROFE55IONAL RESPONSIBILITY TO TAKE WHAT HE BELIEVES ARE PRUDENT MEA5URE5 SHOULD THE ARCHITECT ENCOUNTER 51TUATIONS THAT HE BELIEVES CREATE A DANGER TO PUBLIC, HEALTH, SAFETY, OR WELFARE. THE CLIENT /OWNER UNDERSTANDS THI5 51TUATION AND A6REE5 TO DEFEND 5ALTZ MICHELSON ARCHITECTS AND HOLD THE ARCHITECT HARMLESS FROM GLAIM5 AR151N6 FROM THE ARCHITEGT5 EXERG15E OF PROFE55IONAL RESPONSIBILITY IN TH15 REGARD, LICEN5E5 AND PERMITS: THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS SHALL 5EGURE THE REQUIRED CITY, COUNTY, STATE LICENSES OR PERMITS AND 5PE6IAL PERMITS, WHEN REQUIRED, PRIOR TO COMMENCING ANY WORK ON TH15 PROJECT. PERMITS SHALL BE PROTEGTED AND DISPLAYED IN ACCORDANGE WITH THE LOCAL 60VERNIN6 AGENCY REQUIREMENT5, I. Floor or Wall Assembly - Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete. Wall may also be constructed OF any UL GIa55ified Concrete Blocks ". Max diam of opening is 5 in, See Concrete Blocks (GAZT) Category in the Fire Resistance Directory for names of manufacturers. 2, Nonmetallic Pipe - Nom 3 in. diam (or smaller) Schedule 40 polyvinyl Chloride (PVC) pipe for use in Closed (proce55 or Supply) or vented (drain, waste or vent) piping 5y5tem5. One pipe to be installed either concentrically or eccentrically within the Fire5top 595tem. The annular Space shall be min 112 in. to a max I in. Pipe to be rigidly supported on both aides of Floor or wall assembly. 3. Fill, Void or Cavity Material" - Sealant - Min 4 in. thickness of fill material applied within the annulus, Flush with top surface of floor or with both 5urfoce5 of wall. HILTI GON5TRU(TION CHEMICALS, DIV OF HILTI ING - FS -ONE Sealant "Bearing the UL CIa551ficotion Mark PERMIT FEES: IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO PAY FOR ALL BUILOIM6 PERMITS REQUIRED BY LOCAL CODE OR ORDINANCE. PERMANENT UTILITY FEES: IMPACT FEES, WATER AND SEWER CONNECTION FEES AND DEPOSITS FOR PERMANENT UTILITY 5ERVIGE5 SHALL BE PAID FOR BY THE OWNER. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT, AND /OR OWNER WHEN THESE FEES APPLY PRIOR TO THE START OF CON5TRU6TIOK TEMPORARY UTILITY FEES: FEES FOR TEMPORARY CONSTRUCTION RELATED USE OF UTILITY 5ERVICE5 SUCH AS WATER; ELECTRIC, TRA5H DISPOSAL; PORTABLE TOILETS, JOB 51TE PHONES AND OTHER SUCH 5ERVIGE5 THAT ARE PRIMARILY UTILIZED BY THE CONTRACTOR IN PERFORMANCE OF THE WORK UNDER TH15 CONTRACT SHALL BE INCLUDED IN THE C05T OF THE JOB AND PAID BY THE CONTRACTOR. INSURANCE: THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION A6AIN5T PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK, PROOF OF INSURANCE SMALL BE SUBMITTED TO THE OWNER PRIOR TO COMMENCEMENT OF WORK. THE CONTRACTOR AND H15 5UBGONTRAGTOR5 APE NOT TO COMMENCE WORK UNDER TH15 CONTRACT UNTIL REQUIRED INSURANCE 15 OBTAINED AND APPROVAL RECEIVED FROM THE OWNER. INSURANCE TYPE MINIMUM LIMITS OF LIABILITY WORKMAN'S COMPENSATION STATUTORY CONTRACTOR'5 PUBLIC LIABILITY: BODILY INJURY $100000 EACH PER50N $300,000 EACH ACCIDENT PROPERTY DAMA6E5 $10,000 EACH ACCIDENT $25000 A66RECATE CONTRACTOR'S LIAELITY FOR 5UBGONTRAGTEP WORK: BODILY INJURY VOODOO EACH PER50N $300,000 EACH ACCIDENT PROPERTY DAMAGES 410000 EACH ACCIDENT $25,DOO A66RE6ATE AUTOMOBILE PUBLIC LIABILITY: BODILY INJURY sIO0,0o0 EACH PER50N $300000 EACH ACCIDENT PROPERTY DAMA6E5 $10,000 EACH ACCIDENT INDEMNITY: CONTRACTOR SHALL PROTECT, DEFEND, SAVE HARMLESS AND INDEMNIFY OWNER; ITS EMPLOYEES, A6ENT5 AND PUBLIC, FROM CLAIMS, DEMANDS OR EXPENSE ON ACCOUNT OF INJURY TO PERSON OR DAMAGE TO PROPERTY, ALLE6ED OR REAL, AR151N6 FROM ANYTHING DONE OR NOR DONE UNDER THIS AGREEMENT BY CONTRACTOR, SUBCONTRACTOR, OR ANYONE DIREGTLY EMPLOYED BY EITHER, 6UARANTEE: THE CONTRACTOR SHALL GUARANTEE ALL WORK UNDER TH15 CONTRACT TO BE FREE FROM DEFECTS IN MATERIAL OR WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE OR CERTIFICATE OF OCCUPANCY. HE SMALL REPLACE ANY WORK THAT FAIL5 TO CONFORM TO THE DRAWN65 OR DETAILS AS SHOWN IN THESE CONSTRUCTION DOCUMENTS. HE SHALL DELIVER TO THE OWNER ALL WRITTEN WARRANTIES OR 6UARANTEE5 OFFERED BY THE MANUFACTURERS FOR ALL COMPONENTS, EQUIPMENT AND FIXTURES. COPIES OF INVOICES, BILLS OR PURCHASE ORDERS SHALL BE GIVEN TO THE OWNER MEN REQUIRED TO ENFORCE GUARANTEES AND WARRANTS. THESE PROVISIONS SMALL APPLY TO ALL VENDORS OR OTHERS WHO MAY BE EMPLOYED BY THE CONTRACTOR IN PRODUCING THIS WORK, COORDINATION OF THE TRADES: THE 6ENERAL GONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF EVERY ASPECT OF THE WORK AS DE56RIBED IN THE CONTRACT FOR GON5TRUCTION INCLUDING ALL OF THE REQUIREMENT5 OF THE '6ENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION ", AIA DOCUMENT A -201. HE SHALL VERIFY ALL DRAWINGS AND COORDINATE THE WORK OF ALL TRADES AT THE TIME THE WORK 15 PERFORMED ON TH15 STRUCTURE. NO ADDITIONAL PAYMENTS SHALL BE MADE FOR THE CONTRACTQR5 FAILURE TO COORDINATE 'THE WORK AND CORRECT CONFLICTIN6 FIELD CONDITIONS, THROUGH - PENETRATION FIRESTOP SYSTEMS SYSTEM NO, C -AJ -1003 F RATING -3 HR T RATING -0 OR a HR UL NO. W -L -1.299 THROUGH - PENETRATION FIRESTOP SYSTEMS F RATINGS - 1 AND 2 HR T RATING -0 HR I. FLOOR OR WALL ASSEMBLY - MIN 4 -112 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100 -150 PGF) CONCRETE. WALL MAY AL50 BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOGK5". MAX DIAM OF OPENING 15 8 IN. SEE CONCRETE BLO6K5 (CAZT) CATEGORY IN THE FIRE RE515TANGE DIRECTORY FOR NAMES OF MANUFACTURERS: 2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE CENTERED WITHIN THE FIRE5TOP 5Y5TEM, PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL A55EMBLY. A NOM ANNULAR 5PAGE OF 2 IN, 15 REQUIRED WITHIN THE FIRE5TOP 5Y5TEM. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, GONDUIT5 OR TUBING MAY BE USED: A. STEEL PIPE - NOM 6 IN. DIAM (OR SMALLER) SCHEDULE 5 (OR HEAVIER) STEEL PIPE. B. IRON PIPE - NOM 6 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE, G. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR NOM 6 IN. DIAM (OR SMALLER) STEEL CONDUIT. 3. FIRE5TOP SYSTEM - THE FIRE5TOP SYSTEM SHALL CON515T OF THE FOLLOWING: A. PACKING MATERIAL - MIN 6 PGF MINERAL WOOL BATT INSULATION OR L005E CERAMIC FIBER INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM, PAGKING MATERIAL TO BE RECESSED FROM TOP AND BOTTOM 5URFAGE5 OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO AG( OMMODATE THE REQUIRED THIGKNE55 OF FILL MATERIAL. THE THIGKNE55 OF PAGKING MATERIAL 15 DEPENDENT UPON THE CONSTRUCTION DETAILS OF THE FIRE5TOP SYSTEM AS TABULATED IN ITEM 313, B. FILL, VOID OR CAVITY MATERIAL" - PUTTY - FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP AND BOTTOM 5URFAGE5 OF FLOOR OR WITH BOTH 5URFAGE5 OF WALL. THE T RATING OF THE FIRE5TOP 5Y5TEM 15 DEPENDENT UPON MAX DIAM OF OPENING, THICKNESS OF PACKING MATERIAL AND THIGKNE55 OF FILL MATERIAL AS TABULATED BELOW: MAX DIAM MIN PACKING MIN FILL T OF OPENING MTL MTL RATING IN. THKNSIN, THKN5IN. HR 8 2-112 1 O 4 3 3/4 3/4 EGS NELSON FIRE5TOP -TYPE FSP PUTTY `BEARING UL 6LA551FICATION MARK. GENERAL CONTRACTOR SHALL DO ALL GUTTING AND PAT(HIN6 OF EXI5TIN6 CONCRETE 5LAB5, PARTITIONS, ETC, AS MAY BE REQUIRED FOR ALL TRADES TO ACCOMPLISH ALL WORK REGUIRED BY THESE CONTRACT DOCUMENTS. CONTRACTOR 54ALL DO ALL PATCHING AND PROVIDE NEW FINISHE5 TO MATCH EXI5TIN67 SO AS TO MAKE THE 'PATCHED AREA" INDISCERNIBLE TO THE EXISTING ADJACENT AREA. ALL EXISTING 5URFAGE5 SUCH AS WALLS, FLOORS, CEILIN66, BASES, ETC. THAT ARE AFFECTED BY THESE ALTERATIONS ARE TO HAVE NEW MATERIAL AND FINISH AS REQUIRED TO MATCH ALL ADJACENT EX15TIN6 FINISHES. DEMOLITION: TITLE TO MATERIALS: TITLE TO ALL MATERIAL AND EQUIPMENT TO BE DEMOLISHED AND REMOVED EXCEPTING ITEMS INDICATED TO BE TURNED OVER TO THE OWNER 15 VESTED IN THE CONTRACTOR AT START OF PROJECT. REMOVE ALL SPECIFIC ITEMS INDICATED ON THESE DRAWIN65 AND ALSO REMOVE ANY OTHER ITEMS OR CONSTRUCTION AS REQUIRED TO ACCOMPLISH ALL NEW WORK TO AREAS SHOWBN. ALL REMOVED ITEMS 54ALL BECOME THE PROPERTY OF THE CONTRACTOR WITH THE APPROVAL OF THE OWNER AND SHALL BE REMOVED FROM THE SITE. THE AMOUNT OF DUST RESULTIN6 FROM DEMOLITION 51ALL BE CONTROLLED TO PREVENT THE SPREAD OF DUST TO AVOID CREATION OF A NU15ANGE IN THE 5URROUNDIN6 AREA. USE OF WATER WILL NOT BE PERMITTED WHEN IT WILL RESULT IN, OR CREATE, HAZARDOUS OR OBJECTIONABLE CONDITIONS SUCH AS FLOOOIN6, LEAKING TO FLOOR BELOW AND POLLUTION. MANUFACTURER'S INSTRUCTIONS: MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION, APPLICATION, OR METHODS SHALL BE STRICTLY ADHERED TO AND BY REFERENCE ARE MADE A PART OF THESE PLANS AS IF FULLY WRITTEN HEREIN. FAILURE OF THE CONTRACTOR TO OBTAIN MANUFACTURER'S INSTRUCTIONS SHALL NOT RELIEVE HIM FROM PERFORM146 ALL OF THE REQUIREMENT5 OF THE WORK. CONTRACTOR SHALL CONFIRM ALL EQUIPMENT DIMEN51ON5, ELEGTRIGAL REQUIREMENTS AND UTILITY GONNEGTION5 PRIOR TO CONSTRUCTION WITH ACTUAL E61APMENT5 MAKE AND MODEL. WORKMAWSHIP: ALL WORK 54ALL BE PERFORMED IN A FIRST CLA55 WORKMAN LIKE MANNER IN ACCORDANCE WITH THESE PLANS AND SPECIFICATION5, THE BUILDING GORE AND THE STATE ENER6Y EFFICIENCY CODE. WORKMANSHIP QUALITY SHALL STRICTLY CONFORM TO THE INDUSTRY STANDARD AND APPLICABLE NATIONAL, STATE AND LOCAL CODES, ORDINANCES AND RULES. MATERIALS: UNLE55 SPECIFIED OTHERWISE, ALL CONTRACTOR SUPPLIED MATERIALS, FIXTURES, FITTIN65 OR COMPONENTS SHALL BE NEW AND DELIVERED TO THE JOB 51TE IN THE MANUFACTURER'5 OR16INAL SEALED CARTONS OR PACKA61N6. SHOP DRAWINGS: THE CONTRACTOR SHALL OBTAIN AR( HITE(V5 OR OWNER'S WRITTEN APPROVAL OF SHOP DRAWNC�5 PRIOR TO FABRICATION. SAMPLES SHALL 13E SUBMITTED UPON REQUEST. WHERE INSTALLATIONS REQUIRING SHOP DRAWIN65 HAVE BEEN MADE WITHOUT APPROVED DOGUMENT5 THE OWNER AND /OR ARCHITECT MAY REJECT THE WORK. REPLACEMENT ADDITIONS OR MODIFICATIONS TO ALL SUCH WORK SHALL BE MADE AT THE GONTRA(TOR5 EXPENSE. THE CONTRACTOR SHALL SUBMIT SHOP PRAWN66 FOR ALL PREFABRIGATEP ITEMS OF THE WORK. ACTIVE SERVICES: EXISTING ACTIVE SERVICES: WATER, GA5, SEWER, ELECTRIC,, ETC., WHEN ENCOUNTERED, SHALL BE PROTECTED A6AIN5T DAMAGE. DO NOT PREVENT OR DISTURB OPERATION OF ACTIVE SERVICES WHIGH ARE TO REMAIN. IF ACTIVE SERVICES ARE ENCOUNTERED WHICH REQUIRE RELOCATION, MAKE REOUE5T TO AUTHORITIES WITH ,1UR150I6TION FOR DETERMINATION OF PROCEDURES. WHERE EXISTING SERVICES ARE TO BE ABANDONED, THEY SMALL BE TERMINATED ON CONFORMANCE WITH REQUIREMENTS OF THE LANDLORD, OWNER, SPEOFIGATION5, UTILITY COMPANIES AND /OR GOVERNING AGENGIE5 HAVING JURI5DICTION. DAMAGE: THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL AREAS, INCLUDING PUBLIC, 5PAGE5, IN AND AROUND THE 517E A6AIN5T DAMAGE DURING THE CONSTRUCTION PROCESS. DAMAGE TO ANY AREA SMALL BE REPAIRED TO THE SATISFACTION OF THE OWNER AND LANDLORD AT THE CONTRACTORS EXPENSE, ����fu I i f- -_ � it f si i nA"A I. HALL ASSEMBLY - THE I OR 2 HR FIRE RATED GYPSUM BOARD /5TUD WALL A55EM13LY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U400 OR V400 SERIES WALL AND PARTITION DESIGN IN THE UL FIRE RE515TANGE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING SHALL CONSIST OF MIN 3 -1/2 IN. (N MM) WIDE STEEL CHANNEL STUDS 5PAGED MAX 24 IN. ((910 MM) OC. ADDITIONAL MIN 3 -1/2 IN. (M MM) WIDE STEEL STUDS SMALL BE USED TO COMPLETELY FRAME OPENING. B. GYPSUM BOARD" - THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND 5HEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U400 OR V400 5ERIE5 DESIGN IN THE UL FIRE RE515TANCE DIRECTORY. MAX AREA OF OPENING TO BE 182 IN,2 (1114 CM2) WITH A MAX DIMENSION OF 45 -1/2 IN. (156 MM). ALL VERTICAL 5TUD5 IN OPENING TO REMAIN INTACT. THE HOURLY F RATING OF THE FIRE5TOP SYSTEM 15 EQUAL TO THE HOURLY FIRE RATING OF THE WALL A55EMBLY IN WHICH IT IS INSTALLED. 2. THROUGH- PENETRANTS - ONE OR MORE METALLIC PIPES OR CONDUITS INSTALLED WITHIN OPENING. ANNULAR 5PAGE BETWEEN PENETRANTS AND PERIPHERY OF OPENING TO BE MIN 0 IN. (0 MM, POINT ( ONTACT) TO MAX 2 IN. (51 MM). 5PAGE BETWEEN PENETRANTS TO BE MIN 1/4 IN, ((? MM) TO MAX 2 IN. (51 MM). PENETRANTS TO BE RIGIDLY SUPPORTED ON BOTH SIDES, OF WALL. THE FOLLOWING TYPE5 AND SIZES OF PENETRANTS MAY BE U5ED: A. STEEL PIPE - NOM 3 IN. (16 MM) DIAM (OR SMALLER) 5GHEDULE 5 (OR HEAVIER) STEEL PIPE. B. CONDUIT - NOM 3 IN. (16 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT OR STEEL ELECTRICAL METALLIC TUBING. 3. FIRE5TOP SYSTEM - THE FIRE5TOP SYSTEM SHALL CONSIST OF THE FOLLOWING: A! PAGKING MATERIAL - MIN 3 -3/4 IN. 05 MM) OR 5 IN. (121 MM) THICKNESS OF MIN 4 PGF (64 KG/M3) MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING FOR I AND 2 HR RATED ASSEMBLIES, RESPECTIVELY. PA( KING MATERIAL TO BE RECE55ED FROM BOTH SIDES OF WALL A55EMBLY TO ACCOMMODATE THE REQUIRED THIGKNE55 OF FILL MATERIAL, B, FILL, VOID OR CAVITY MATERIAL" -CAULK OR SEALANT - MIN 1/2 IN. (13 MM) THI6KNE55 OF CAULK APPLIED WITHIN ANNULUS, FLUSH WITH BOTH 5URFAGE5 OF WALL. MIN 1/4 IN, (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD /PENETRANT INTERFACE AT POINT CONTACT LOCATION ON BOTH 5IDE5 OF WALL. 3M COMPANY - IC, 15WB +, GP 25WB+ CAULK OR FB -3000 WT SEALANT "BEARING THE UL GLA551FIGATION MARK SANITATION FACILITIES: THE 6ENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADEQUATE TEMPORARY TOILET FACILITIES ON THE JOB SITE, DRINKING WATER: THE GENERAL CONTRACTOR SHALL PROVIDE PORTABLE DRINKING WATER FOR THE USE OF ALL TRADESMEN. THE WATER SUPPLY SHALL 13E FREE OF CHARGE, CONVENIENTLY LOCATED AND MAINTAINED THROUGHOUT THE DURATION OF THE WORK FIRE PROTECTION: THE CONTRACTOR SMALL PROVIDE 6ENERAL FIRE PROTECTION THROUGHOUT THE JOB FOR THE DURATION OF THE WORK. EACH SUBCONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING FIRE PROTECTION FOR THEIR OWN SPECIALTY. OPERATIN6 INSTRUCTIONS: THE OWNER SHALL BE FURNISHED WITH THE ORIGINAL OPERATING INSTRUCTIONS, REPAIR AND MAINTENANCE MANUALS AS SUPPLIED BY THE MANUFACTURER FOR ALL EQUIPMENT INSTALLED UNDER THE CONTRACTORS SUPERVISION, FINAL GLEANING: THE CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL CONSTRUCTION GLEAN -UP INCLUDING THE REMOVAL OF ALL TEMPORARY CONSTRUCTION, SUPPORTS, 1_16HTIN65, BARRIERS, BARRICADES, ETC, U51146 MANUFACTURERS RECOMMENDED GLEANING AGENTS THE CONTRACTOR SHALL CLEAN AND POL15H ALL GLASS SURFACES; FINISH HARDWARE: CERAMIC AND VINYL TILE FLOORING; MIRRORS; WOODWORK; BASEBOARDS AND WALL SURFACES. REMOVE ALL FINGERPRINTS, STAINS, MARKIN65 DUST, DIRT, PUTTY AND OVER PAINTING IN PREPARATION FOR USE AND OGGUPANGY. SITE CLEAN -UP: GARBAGE REGEPTACLE5 SHALL BE ON 51TE AT ALL TIMES. THE JOB SITE SMALL BE KEPT FREE OF ACCUMULATED TRASH AND WASTE MATERIALS WHICH SHALL BE REMOVED WEEKLY. "BROOM GLEANING" SHALL BE DONE ON AN AS NEEDED OR DAILY BA515 FOR THE DURATION OF CONSTRUCTION. THE CONTRACTOR SMALL GLEAN ALL AREAS OF THE WORK AFTER CONSTRUCTION 15 COMPLETED, ALL TRASH, DEBRIS, IMPLEMENT5, AND SURPLUS MATERIALS SHALL BE REMOVED FROM THE JOB 51TE AT THE CONTRACTORS EXPENSE, ALL WASTE SHALL BE LEGALLY DISPOSED OF AT PUBLIC OR PRIVATE DUMPING FACILITIES. FINAL 149:1ECTION: THE OWNER AND CONTRACTOR SHALL PERFORM A FINAL 'WALK THROUGH' INSPECTION OF THE WORK PRIOR TO THE QWNER5 FINAL ACCEPTANCE, THE CONTRACTOR SHALL PREPARE AND SUBMIT A WRITTEN 'PUNCH LIST' TO THE OWNER OF THE ITEMS OF THE WORK THAT REQUIRE ADJUSTMENT, CORRECTION OR REPLACEMENT. PUNCH LISTED EQUIPMENT, FEATURES OR FINISHES SMALL 13E REPAIRED TO THE QWNER5 5AT15FACTION WITHIN FIVE WORKING DAYS, FINAL ACCEPTANCE: THE CONTRACTOR SHALL DEMONSTRATE TO THE OWNER THE USE AND VERIFY THE PROPER FUNCTION OF ALL OPERATING FEATURES INCORPORATED INTO THE PROJECT. THE OWNER SHALL REVIEW, VERIFY AND APPROVE THE COMPLETENESS OF ALL "PUNCH LIST' WORK, CERTIFICATE OF OCCUPANCY: UPON FINAL ACCEPTANCE AND COMPLETION THE CONTRACTOR SHALL OBTAIN AND DELIVER TO THE OWNER OR OMNER5 A6ENT A 'CERTIFICATE OF OGCUPANGY' OR "CERTIFICATE OF USE' FROM THE LOCAL 6 ./ERNIN5 AGENCY. PERMANENT ELECTRIC SERVICE: IN THE EVENT A 'CERTIFICATE OF OCCUPANCY' OR 'CERTIFICATE OF COMPLETION" 15 A PRERE619JI51TE TO OBTAINING AN ELECTRIC METER AND/OR PERMANENT ELECTRIC SERVICE THE CONTRACTOR SHALL HAVE THE LOCAL ELECTRIC UTILITY INSTALL ALL THE REQUIRED COMPONENTS TO PROVIDE THE ELECTRIC, 5ERVIGE SPECIFIED IN THE PLANS. THEREAFTER HE SHALL TEST AND DEMONSTRATE TO THE OWNER THE USE AND VERIFY THE PROPER FUNCTION OF ALL COMPONENTS AND OPERATING FEATURES OF THE ELEGTRIGAL SYSTEM. TE5TIN& ALL REQUIRED TE5T5 SHALL BE PERFORMED BY AN APPROVED TE5TIN6 LABORATORY AT THE CONTRACTORS EXPENSE. TEST RESULT5 SHALL BE SUBMITTED TO ARGHITEGT, AND /OR ENGINEER, THROUGH - PENETRATION FIRESTOP SYSTEMS UL NO" W- L-1001 F RATINGS -1,2,3 AND 4 HR T RATINGS- 0,1,2,3 AND 4 HR SEC10,0N_ I, WALL ASSEMBLY - THE I, 2, 3 OR 4 HR FIRE -RATED GYPSUM WALLBOARD /STUD WALL A55EMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RE515TANGE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING MAY GON515T OF EITHER WOOD STUDS (MAX 2 H FIRE RATED A55EMBLIE5) OR STEEL CHANNEL STUDS. WOOD 5TUD5 TO CON515T OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER 5PAGED 16 IN, (40(b MM) OG WITH NOM 2 BY 4 IN, (51 BY 102 MM) LUMBER END PLATES AND GRO55 BRACES. STEEL STUDS TO BE MIN 3 -5/8 IN, (012 MM) WIDE BY 1 -3/8 IN. (35 MM) DEEP CHANNELS 5PAGED MAX 24 IN. (610 MM) OC. B. GYPSUM BOARD" - NOM 112 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 GM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DE51ON IN THE UL FIRE RESISTANCE DIRECTORY, MAX DIAM OF OPENING 15 26 IN. (660 MM). 2. THROUGH - PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER GONGENTRIGALLY OR ECCENTRICALLY WITHIN THE FIRE5TOP 5Y5TEM. THE ANNULAR 5PAGE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN / (0 MM). (POINT CONTACT) TO MAX 2 IN. (51 MM) PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, 6ONDUIT5 OR TUBING MAY BE USED: A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE. B. IRON PIPE - NOM 24 IN. ((910 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN (305 MM) DIAM (OR SMALLER) OR 6LA55 50 (OR HEAVIER) DUCTILE IRON PRE55URE PIPE. G. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN (102 MM) DIAM (OR SMALLER) STEEL ELEGTRIGAL METALLIC TUBING D. COPPER TUBING NOM 6 IN, (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. F. THROUGH PENETRATING PRODUCT" - FLEXIBLE METAL PIPING THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL 6A5 PIPING MAY BE U5ED: I. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPIN6.1'PLA5TIG COVERING ON PIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. OMEGA FLEX INC 2. NOM I IN. (25 MM), DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING, IPLA5TIG GOVERING ON PIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. GASTITE, DIV OF TITEFLEX 3. NOM I IN. (25 MM)', DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING.I,PLA5TIG COVERING ON PIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY, WARD MFG INC 3. FILL, VOID OR CAVITY MATERIAL" - CAULK OR SEALANT - MIN 5A5., 1- 1/4,1 -1/8 AND 2 -112 IN. (16, 32, 48 AND (94 MM) THI6KNE55 OF CAULK FOR I, 2,3 AND 4 HR RATED ASSEMBLIES, RE5PEGTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL, MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD /PENETRANT INTERFACE AT POINT CONTACT LOCATION ON BOTH SIDES OF WALL. THE HOURLY F RATING OF THE FIRE5TOP SYSTEM 15 DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT 15 INSTALLED, AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING OF THE FIRE5TOP SYSTEM 15 DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL A55EMBLY IN WHICH IT IS INSTALLED, A5 TABULATED BELOW: MAX PIPE OR CONDUIT DIAM IN (MM) F RATING HR T RATING HR 1 (25) 1 OR 2 +O, 1 OR 2 1 (25) 3 OR 4 3 OR 4 4 (102) 1 OR 2 O C 6 (152) 3 OR 4 0 12 (305) 1 OR 2 0 +WHEN COPPER PIPE IS USED, T Rating IS 0 h. 3M COMPANY - GP 25WB+ or FB -3000 WT. • 1 SALTZ MICHELSON A R C H I T E C T S 3501 Griffin Road Ft. Lauderdale, FL 33312 (954) 266 -2700 Fx: (954) 266 -2701 sma @saltzmichelson.com w7 . �g Charles Michelson AR0009976 Project No.: 2011-166 0 66 Drawn By: NI I Checked. By: LS Date: 09 -12 -11 liOl � I i-���yy�,gg � iA Y E �g> Dpq is BX91 {t^��31Y 1f-� �f^Vpi LDf�,JG TRU TTURAL. ScCTiintu Project No.: 2011-166 0 66 Drawn By: NI I Checked. By: LS Date: 09 -12 -11 liOl