11-1210R-007e
A
I-KUN I VIEW SECTION A —A
SYSTEM NO. CAJ8081
F RATING - 2 HOUR
T RATING - 0 HOUR
NOTES:
1. FLOOR OR WALL ASSEMBLY: MINIMUM 2 "' THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100 -150 PCF) CONCRETE FLOOR OR MINIMUM 31" REINFORCED
LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL. WALL MAY ALSO BE
CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS *. MAXIMUM DIAMETER OF
OPENING EQUALS 8 INCHES. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE
FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. ONE STEEL PIPE OR CONDUIT TO BE CENTERED WITHIN THE FIRESTOP SYSTEM.
WITHIN THE FIRESTOP SYSTEM, A MINIMUM NOMINAL ANNULAR SPACE OF 1/4" IS
REQUIRED. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED AT ONE SIDE OF FLOOR
OR WALL ASSEMBLY. THIS ASSEMBLY IS SPECIFIC TO STEEL PIPE - NOMINAL 6"
DIAMETER (OR SMALLER) 16 GAUGE GALVANIZED STEEL TUBING.
3. UP TO FOUR 3/8" DIAMETER SHIELDED CABLES. WIRE TO BE CL2P, PLENUM
RATED, LOW VOLTAGE FOR COMMUNICATION USE. CABLE IS TIE WRAPPED TO STEEL
PIPE.
4. PACKING MATERIAL: MINIMAL 4 PCF MINERAL WOOL BATT INSULATION, FIRMLY
PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE
RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS
REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. MINIMUM
THICKNESS OF PACKING MATERIAL IN FLOORS AND WALLS TO BE 1-1/2".
5. FILL VOID OR CAVITY MATERIAL* - SEALANT: MINIMUM 1" THICKNESS OF FILL
MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR
BOTH SURFACES OF WALL. AS AN ALTERNATE, THE PERMANENT PACKING MATERIAL
(ITEM 3) MAY BE OMITTED IF THE FILL MATERIAL THICKNESS IS INCREASED TO A
MINIMUM 1-1/2 INCH.
*BEARING THE UL CLASSIFICATION MARK
HILTI, INC. - HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT
Note: According to Underwriter's Laboratories, The F and T Ratings of a firestop
system are not jeopardized if the metallic pipe penetrant passes through the
opening at an angle not to exceed 45 degrees from the perpendicular and the
annular spaces are within the requirements that have been established in the
individual firestop system. this is applicable to firestop systems incorporating fill
materials (such as sealants, putty, or mortar and packing materials.
K'1 DETAIL
PT -3.10 FLOOR PENETRATION
FIRESTOP SYSTEM CAJ8081
SCALE: NONE
Date Created: 1.27.2012
Date Plotted: 1.27.2012
FRONT VIEW SECTION A -A
SYSTEM NO. WL8023
F RATING - 1 and 2 HOUR (See Item 1)
T RATING - 0 HOUR
NOTES:
1. WALL ASSEMBLY: THE 1 OR 2 HOUR FIRE -RATED GYPSUM WALLBOARD /STUD WALL
ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIAL AND IN THE MANNER
SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS
IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING
CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL
CHANNEL STUDS. WOODS STUDS TO CONSIST OF NOMINAL 2 BY 4 INCH
LUMBER SPACED 16 INCHES ON CENTER. STEEL STUDS TO BE MINIMUM 2-1/2
INCHES WIDE AND SPACED MAXIMUM 24 INCHES ON CENTER.
B. WALLBOARD, GYPSUM *: ONE OR TWO LAYERS OF 5/8 INCH THICK GYPSUM
WALLBOARD, AS SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN.
MAXIMUM DIAMETER OF OPENING IS 7 INCHES.
2. ONE STEEL PIPE OR CONDUIT TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. A
MINIMUM ANNULAR SPACE OF 4 INCH IS REQUIRED WITHIN FIRESTOP SYSTEM. PIPE
TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THIS ASSEMBLY
IS SPECIFIC TO STEEL TUBE, NOMINAL 6" DIAMETER (OR SMALLER) 16 GAUGE
GALVANIZED STEEL TUBING 1/8" CONTINUOUS WALL THICKNESS. BENDS MAY
PENETRATE THE SYSTEM AT UP TO 45° WITHOUT COMPROMISING THE RATING.
3. UP TO THREE 3/8" DIAMETER SHIELDED CABLES. WIRE TO BE CL2P, PLENUM
RATED, LOW VOLTAGE FOR COMMUNICATION USE, TIE WRAPPED TO STEEL PIPE.
4. FILL, VOID OR CAVITY MATERIAL *: SEALANT - 1-1/4 INCH THICKNESS OF FILL
MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL.
*BEARING THE UL CLASSIFICATION MARK
HILTI, INC. - HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT
Note: According to Underwriter's Laboratories, The F and T Ratings of a firestop
system are not jeopardized if the metallic pipe penetrant passes through the
opening at an angle not to exceed 45 degrees from the perpendicular and the
annular spaces are within the requirements that have been established in the
individual firestop system. this is applicable to firestop systems incorporating fill
materials (such as sealants, putty, or mortar and packing materials.
r2"
DETAIL
t3.1 0 WALL PENETRATION
FIRESTOP SYSTEM WL8023
SCALE: NONE
SET
WITH LO.,,. ,."
$" DROP -IN ANCHOR, TYPICAL
(SUBSTITUTE BEAM CLAMP IN DETAIL
7 WHERE REQUIRED TO ANCHOR TO
STEEL BEAMS)
8" ALL THREAD
HANGER ROD AND
HARDWARE
STEEL TEAR
DROP
HANGER:
6" SYSTEMS
USE HILTI
PRODUCT CODE
00257364.
4" SYSTEMS
USE B -LINE
B3170NF -3
1/2-R $
GALV.
4" OR 6"
PNEUMATIC TUBE
TEARDROP HANGER
\
VARIES A
.
SCHEDULED MECHANICAL
SHAFT OPENING
6" O.D. STEEL
PNEUMATIC TUBE
o
1$" X 15" STRUT
---STRUT ANGLE FITTING
8" ANCHOR BOLTS
CHANNEL CLAMP
TYP. MECHANICAL SHAFT
PLAN VIEW AT EACH FLOOR
2"
File: P:1Florida \MiamilSouth Miami Hospital \M00450 NICU 3rd Floor \Drawing \M00450- PT310.dwg
1 s" OR 15" STRUT
SUPPORT, AS REQUIRED
BY INSTALLATION
6" O.D. STEEL
PNEUMATIC TUBE
1i" X till STRUT
UNISTRUT OR EQUAL
ANGLE FITTING
ANCDHOR�BOLTS
CHANNEL CLAMP
THREADED RODS TO
STRUCTURE ABOVE
16" OR 1 STRUT
SUPPORT, AS
REQUIRED BY
INSTALLATION
PLAN VIEW
J " -16 NC DROP IN
ANCHOR, TYPICAL
E CLAMP,
CAL
-a I- " -16;NC DROP
:4: —_ 1N.._ANGHO -R_
TYPICAL
TUBE CLAMP
ALTERNATE SECTION A -A: SUPPORT
8" THREADED F
& HARDWA
TYPli
SECTION A -A
SINGLE TUBE W /(2 ) RODS
a " -16 NC DROP IN
ANCHOR, TYPICAL
SECTION B -B
MULTIPLE TUBE SUPPORTS AND ALTERNATE SINGLE TUBE SUPPORTS
PENETRATION AS
REQUIRED
SCHEDULED MECHANICAL
SHAFT OPENING
TYP. MECHANICAL SHAFT
SECTION VIEW AT EACH FLOOR
6" O.D. STEEL
PNEUMATIC TUBE
1$" X 1$" STRUT'"
8" ANCHOR
BOLTS
CHANNEL CLAMP
TYP. FLOOR PENETRATION
SECTION VIEW AT EACH FLOOR
DETAIL
TYPICAL TUBE AND BEND SUPPORTS
SCALE: N.T.S.
NOTES:
1. SUBSTITUTE BEAM CLAMP WHERE REQUIRED TO
ANCHOR TO BEAMS, IN LIEU OF ANCHORS
THROUGH CONCRETE.
2. SET SCREW MUST BE TIGHTENED ONTO THE
SLOPED SIDE OF THE I -BEAM, CHANNEL OR
ANGLE IRON FLANGE AND TORQUED TO 60 INCH
POUNDS.
UM ROD
,\.,L,:TION IS 1/21)
7 DETAIL
PT -3.10 3/8" BEAM CLAMP
SCALE: N.T.S.
FIRE STOP
PENETRATION AS
REQUIRED
�...� 1$" X 1$" STRUT
In"
t.Tr :• .
R,
J
�y
r,
- STR ANGLL FIT.VN 0'*
$" AN JOR S TS'ro
< 2��
CORE DRILL g�
SLEEVED HO a , 1
H FL OR 841
30 °u A:
ii
S VAR aC S Swisslog .�
Phon
ne
www swi ' 1110 N
L C�
tn
M
As instruments of service, all designs, ideas, and information shown on these dr ings are a7I re
property of Swisslog Healthcare Solutions. No part thereof shall be copied, di closed t et Orr
connection with any work or project other than the specific project for which they hav
developed without the written consent of Swisslog Healthcare Solutions. Visual c tact with sal
constitute conclusive evidence of acceptance of these restrictions. j
SOUTH MIAMI HOSPITAL
SOUTH MIAMI, FL
CTS -630
STANDARD PENETRATION & SUPPORT DETAILS
DRAWN BY: I CHECKED BY: SHEET NUMBER:
OFFICE: CONCORD WJB CH r
h
SWISSLOG PROJECT NUMBER: PT-3.10
DATE: 2011 /Jan /27
SCALE: AS NOTED MOO 1 5 O
.. y
,0
._a•
l
-a I- " -16;NC DROP
:4: —_ 1N.._ANGHO -R_
TYPICAL
TUBE CLAMP
ALTERNATE SECTION A -A: SUPPORT
8" THREADED F
& HARDWA
TYPli
SECTION A -A
SINGLE TUBE W /(2 ) RODS
a " -16 NC DROP IN
ANCHOR, TYPICAL
SECTION B -B
MULTIPLE TUBE SUPPORTS AND ALTERNATE SINGLE TUBE SUPPORTS
PENETRATION AS
REQUIRED
SCHEDULED MECHANICAL
SHAFT OPENING
TYP. MECHANICAL SHAFT
SECTION VIEW AT EACH FLOOR
6" O.D. STEEL
PNEUMATIC TUBE
1$" X 1$" STRUT'"
8" ANCHOR
BOLTS
CHANNEL CLAMP
TYP. FLOOR PENETRATION
SECTION VIEW AT EACH FLOOR
DETAIL
TYPICAL TUBE AND BEND SUPPORTS
SCALE: N.T.S.
NOTES:
1. SUBSTITUTE BEAM CLAMP WHERE REQUIRED TO
ANCHOR TO BEAMS, IN LIEU OF ANCHORS
THROUGH CONCRETE.
2. SET SCREW MUST BE TIGHTENED ONTO THE
SLOPED SIDE OF THE I -BEAM, CHANNEL OR
ANGLE IRON FLANGE AND TORQUED TO 60 INCH
POUNDS.
UM ROD
,\.,L,:TION IS 1/21)
7 DETAIL
PT -3.10 3/8" BEAM CLAMP
SCALE: N.T.S.
FIRE STOP
PENETRATION AS
REQUIRED
�...� 1$" X 1$" STRUT
In"
t.Tr :• .
R,
J
�y
r,
- STR ANGLL FIT.VN 0'*
$" AN JOR S TS'ro
< 2��
CORE DRILL g�
SLEEVED HO a , 1
H FL OR 841
30 °u A:
ii
S VAR aC S Swisslog .�
Phon
ne
www swi ' 1110 N
L C�
tn
M
As instruments of service, all designs, ideas, and information shown on these dr ings are a7I re
property of Swisslog Healthcare Solutions. No part thereof shall be copied, di closed t et Orr
connection with any work or project other than the specific project for which they hav
developed without the written consent of Swisslog Healthcare Solutions. Visual c tact with sal
constitute conclusive evidence of acceptance of these restrictions. j
SOUTH MIAMI HOSPITAL
SOUTH MIAMI, FL
CTS -630
STANDARD PENETRATION & SUPPORT DETAILS
DRAWN BY: I CHECKED BY: SHEET NUMBER:
OFFICE: CONCORD WJB CH r
h
SWISSLOG PROJECT NUMBER: PT-3.10
DATE: 2011 /Jan /27
SCALE: AS NOTED MOO 1 5 O
.. y
,0
._a•