11-1210R-007e A I-KUN I VIEW SECTION A —A SYSTEM NO. CAJ8081 F RATING - 2 HOUR T RATING - 0 HOUR NOTES: 1. FLOOR OR WALL ASSEMBLY: MINIMUM 2 "' THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100 -150 PCF) CONCRETE FLOOR OR MINIMUM 31" REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS *. MAXIMUM DIAMETER OF OPENING EQUALS 8 INCHES. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. 2. ONE STEEL PIPE OR CONDUIT TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. WITHIN THE FIRESTOP SYSTEM, A MINIMUM NOMINAL ANNULAR SPACE OF 1/4" IS REQUIRED. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED AT ONE SIDE OF FLOOR OR WALL ASSEMBLY. THIS ASSEMBLY IS SPECIFIC TO STEEL PIPE - NOMINAL 6" DIAMETER (OR SMALLER) 16 GAUGE GALVANIZED STEEL TUBING. 3. UP TO FOUR 3/8" DIAMETER SHIELDED CABLES. WIRE TO BE CL2P, PLENUM RATED, LOW VOLTAGE FOR COMMUNICATION USE. CABLE IS TIE WRAPPED TO STEEL PIPE. 4. PACKING MATERIAL: MINIMAL 4 PCF MINERAL WOOL BATT INSULATION, FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. MINIMUM THICKNESS OF PACKING MATERIAL IN FLOORS AND WALLS TO BE 1-1/2". 5. FILL VOID OR CAVITY MATERIAL* - SEALANT: MINIMUM 1" THICKNESS OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL. AS AN ALTERNATE, THE PERMANENT PACKING MATERIAL (ITEM 3) MAY BE OMITTED IF THE FILL MATERIAL THICKNESS IS INCREASED TO A MINIMUM 1-1/2 INCH. *BEARING THE UL CLASSIFICATION MARK HILTI, INC. - HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT Note: According to Underwriter's Laboratories, The F and T Ratings of a firestop system are not jeopardized if the metallic pipe penetrant passes through the opening at an angle not to exceed 45 degrees from the perpendicular and the annular spaces are within the requirements that have been established in the individual firestop system. this is applicable to firestop systems incorporating fill materials (such as sealants, putty, or mortar and packing materials. K'1 DETAIL PT -3.10 FLOOR PENETRATION FIRESTOP SYSTEM CAJ8081 SCALE: NONE Date Created: 1.27.2012 Date Plotted: 1.27.2012 FRONT VIEW SECTION A -A SYSTEM NO. WL8023 F RATING - 1 and 2 HOUR (See Item 1) T RATING - 0 HOUR NOTES: 1. WALL ASSEMBLY: THE 1 OR 2 HOUR FIRE -RATED GYPSUM WALLBOARD /STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIAL AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOODS STUDS TO CONSIST OF NOMINAL 2 BY 4 INCH LUMBER SPACED 16 INCHES ON CENTER. STEEL STUDS TO BE MINIMUM 2-1/2 INCHES WIDE AND SPACED MAXIMUM 24 INCHES ON CENTER. B. WALLBOARD, GYPSUM *: ONE OR TWO LAYERS OF 5/8 INCH THICK GYPSUM WALLBOARD, AS SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN. MAXIMUM DIAMETER OF OPENING IS 7 INCHES. 2. ONE STEEL PIPE OR CONDUIT TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. A MINIMUM ANNULAR SPACE OF 4 INCH IS REQUIRED WITHIN FIRESTOP SYSTEM. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THIS ASSEMBLY IS SPECIFIC TO STEEL TUBE, NOMINAL 6" DIAMETER (OR SMALLER) 16 GAUGE GALVANIZED STEEL TUBING 1/8" CONTINUOUS WALL THICKNESS. BENDS MAY PENETRATE THE SYSTEM AT UP TO 45° WITHOUT COMPROMISING THE RATING. 3. UP TO THREE 3/8" DIAMETER SHIELDED CABLES. WIRE TO BE CL2P, PLENUM RATED, LOW VOLTAGE FOR COMMUNICATION USE, TIE WRAPPED TO STEEL PIPE. 4. FILL, VOID OR CAVITY MATERIAL *: SEALANT - 1-1/4 INCH THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. *BEARING THE UL CLASSIFICATION MARK HILTI, INC. - HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT Note: According to Underwriter's Laboratories, The F and T Ratings of a firestop system are not jeopardized if the metallic pipe penetrant passes through the opening at an angle not to exceed 45 degrees from the perpendicular and the annular spaces are within the requirements that have been established in the individual firestop system. this is applicable to firestop systems incorporating fill materials (such as sealants, putty, or mortar and packing materials. r2" DETAIL t3.1 0 WALL PENETRATION FIRESTOP SYSTEM WL8023 SCALE: NONE SET WITH LO.,,. ,." $" DROP -IN ANCHOR, TYPICAL (SUBSTITUTE BEAM CLAMP IN DETAIL 7 WHERE REQUIRED TO ANCHOR TO STEEL BEAMS) 8" ALL THREAD HANGER ROD AND HARDWARE STEEL TEAR DROP HANGER: 6" SYSTEMS USE HILTI PRODUCT CODE 00257364. 4" SYSTEMS USE B -LINE B3170NF -3 1/2-R $ GALV. 4" OR 6" PNEUMATIC TUBE TEARDROP HANGER \ VARIES A . SCHEDULED MECHANICAL SHAFT OPENING 6" O.D. STEEL PNEUMATIC TUBE o 1$" X 15" STRUT ---STRUT ANGLE FITTING 8" ANCHOR BOLTS CHANNEL CLAMP TYP. MECHANICAL SHAFT PLAN VIEW AT EACH FLOOR 2" File: P:1Florida \MiamilSouth Miami Hospital \M00450 NICU 3rd Floor \Drawing \M00450- PT310.dwg 1 s" OR 15" STRUT SUPPORT, AS REQUIRED BY INSTALLATION 6" O.D. STEEL PNEUMATIC TUBE 1i" X till STRUT UNISTRUT OR EQUAL ANGLE FITTING ANCDHOR�BOLTS CHANNEL CLAMP THREADED RODS TO STRUCTURE ABOVE 16" OR 1 STRUT SUPPORT, AS REQUIRED BY INSTALLATION PLAN VIEW J " -16 NC DROP IN ANCHOR, TYPICAL E CLAMP, CAL -a I- " -16;NC DROP :4: —_ 1N.._ANGHO -R_ TYPICAL TUBE CLAMP ALTERNATE SECTION A -A: SUPPORT 8" THREADED F & HARDWA TYPli SECTION A -A SINGLE TUBE W /(2 ) RODS a " -16 NC DROP IN ANCHOR, TYPICAL SECTION B -B MULTIPLE TUBE SUPPORTS AND ALTERNATE SINGLE TUBE SUPPORTS PENETRATION AS REQUIRED SCHEDULED MECHANICAL SHAFT OPENING TYP. MECHANICAL SHAFT SECTION VIEW AT EACH FLOOR 6" O.D. STEEL PNEUMATIC TUBE 1$" X 1$" STRUT'" 8" ANCHOR BOLTS CHANNEL CLAMP TYP. FLOOR PENETRATION SECTION VIEW AT EACH FLOOR DETAIL TYPICAL TUBE AND BEND SUPPORTS SCALE: N.T.S. NOTES: 1. SUBSTITUTE BEAM CLAMP WHERE REQUIRED TO ANCHOR TO BEAMS, IN LIEU OF ANCHORS THROUGH CONCRETE. 2. SET SCREW MUST BE TIGHTENED ONTO THE SLOPED SIDE OF THE I -BEAM, CHANNEL OR ANGLE IRON FLANGE AND TORQUED TO 60 INCH POUNDS. UM ROD ,\.,L,:TION IS 1/21) 7 DETAIL PT -3.10 3/8" BEAM CLAMP SCALE: N.T.S. FIRE STOP PENETRATION AS REQUIRED �...� 1$" X 1$" STRUT In" t.Tr :• . R, J �y r, - STR ANGLL FIT.VN 0'* $" AN JOR S TS'ro < 2�� CORE DRILL g� SLEEVED HO a , 1 H FL OR 841 30 °u A: ii S VAR aC S Swisslog .� Phon ne www swi ' 1110 N L C� tn M As instruments of service, all designs, ideas, and information shown on these dr ings are a7I re property of Swisslog Healthcare Solutions. No part thereof shall be copied, di closed t et Orr connection with any work or project other than the specific project for which they hav developed without the written consent of Swisslog Healthcare Solutions. Visual c tact with sal constitute conclusive evidence of acceptance of these restrictions. j SOUTH MIAMI HOSPITAL SOUTH MIAMI, FL CTS -630 STANDARD PENETRATION & SUPPORT DETAILS DRAWN BY: I CHECKED BY: SHEET NUMBER: OFFICE: CONCORD WJB CH r h SWISSLOG PROJECT NUMBER: PT-3.10 DATE: 2011 /Jan /27 SCALE: AS NOTED MOO 1 5 O .. y ,0 ._a• l -a I- " -16;NC DROP :4: —_ 1N.._ANGHO -R_ TYPICAL TUBE CLAMP ALTERNATE SECTION A -A: SUPPORT 8" THREADED F & HARDWA TYPli SECTION A -A SINGLE TUBE W /(2 ) RODS a " -16 NC DROP IN ANCHOR, TYPICAL SECTION B -B MULTIPLE TUBE SUPPORTS AND ALTERNATE SINGLE TUBE SUPPORTS PENETRATION AS REQUIRED SCHEDULED MECHANICAL SHAFT OPENING TYP. MECHANICAL SHAFT SECTION VIEW AT EACH FLOOR 6" O.D. STEEL PNEUMATIC TUBE 1$" X 1$" STRUT'" 8" ANCHOR BOLTS CHANNEL CLAMP TYP. FLOOR PENETRATION SECTION VIEW AT EACH FLOOR DETAIL TYPICAL TUBE AND BEND SUPPORTS SCALE: N.T.S. NOTES: 1. SUBSTITUTE BEAM CLAMP WHERE REQUIRED TO ANCHOR TO BEAMS, IN LIEU OF ANCHORS THROUGH CONCRETE. 2. SET SCREW MUST BE TIGHTENED ONTO THE SLOPED SIDE OF THE I -BEAM, CHANNEL OR ANGLE IRON FLANGE AND TORQUED TO 60 INCH POUNDS. UM ROD ,\.,L,:TION IS 1/21) 7 DETAIL PT -3.10 3/8" BEAM CLAMP SCALE: N.T.S. FIRE STOP PENETRATION AS REQUIRED �...� 1$" X 1$" STRUT In" t.Tr :• . R, J �y r, - STR ANGLL FIT.VN 0'* $" AN JOR S TS'ro < 2�� CORE DRILL g� SLEEVED HO a , 1 H FL OR 841 30 °u A: ii S VAR aC S Swisslog .� Phon ne www swi ' 1110 N L C� tn M As instruments of service, all designs, ideas, and information shown on these dr ings are a7I re property of Swisslog Healthcare Solutions. No part thereof shall be copied, di closed t et Orr connection with any work or project other than the specific project for which they hav developed without the written consent of Swisslog Healthcare Solutions. Visual c tact with sal constitute conclusive evidence of acceptance of these restrictions. j SOUTH MIAMI HOSPITAL SOUTH MIAMI, FL CTS -630 STANDARD PENETRATION & SUPPORT DETAILS DRAWN BY: I CHECKED BY: SHEET NUMBER: OFFICE: CONCORD WJB CH r h SWISSLOG PROJECT NUMBER: PT-3.10 DATE: 2011 /Jan /27 SCALE: AS NOTED MOO 1 5 O .. y ,0 ._a•