11-1210-0129 11/14/20113:49:54 PM !i1 I-Kull 1 vltVV acu 1 [UN n-M SYSTEM NO. CAJ8081 F RATING - 2 HOUR T RATING - 0 HOUR NOTES: 1. FLOOR OR WALL ASSEMBLY: MINIMUM 21/2" THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100 -150 PCF) CONCRETE FLOOR OR MINIMUM 31/2" REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL, WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS *. MAXIMUM DIAMETER OF OPENING EQUALS 8 INCHES. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. 2. ONE STEEL PIPE OR CONDUIT TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. WITHIN THE FIRESTOP SYSTEM, A MINIMUM NOMINAL ANNULAR SPACE OF 1/4" IS REQUIRED. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED AT ONE SIDE OF FLOOR OR WALL ASSEMBLY. THIS ASSEMBLY IS SPECIFIC TO STEEL PIPE - NOMINAL 6" DIAMETER (OR SMALLER) 16 GAUGE GALVANIZED STEEL TUBING. . 3. UP TO FOUR 3/8" DIAMETER SHIELDED CABLES. WIRE TO BE CL2P, PLENUM RATED, LOW VOLTAGE FOR COMMUNICATION USE. CABLE IS TIE WRAPPED TO STEEL PIPE. 4. PACKING MATERIAL: MINIMAL 4 PCF MINERAL WOOL BATT INSULATION, FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. MINIMUM THICKNESS OF PACKING MATERIAL IN FLOORS AND WALLS TO BE 1 -1/2 ". 5. FILL VOID OR CAVITY MATERIAL* - SEALANT: MINIMUM 1" THICKNESS OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL. AS AN ALTERNATE, THE PERMANENT PACKING MATERIAL (ITEM 3) MAY BE OMITTED IF THE FILL MATERIAL THICKNESS IS INCREASED TO A MINIMUM 1 -1/2 INCH. *BEARING THE UL CLASSIFICATION MARK HILTI INC. - HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT Note: According to Underwriter's Laboratories, The F and T Ratings of a firestop system are not jeopardized if the metallic pipe penetrant passes through the opening at an angle not to exceed 45 degrees from the perpendicular and the annular spaces are within the requirements that have been established in the individual firestop system. this is applicable to firestop systems incorporating fill materials (such as sealants, putty, or mortar and packing materials. 2 Floor Penetration Fire Stop System Not to scale FRONT VIEW SECTION A -A SYSTEM NO. WL8023 F RATING -1 and 2 HOUR (See Item 1) T RATING - 0 HOUR NOTES: 1. WALL ASSEMBLY: THE 10R 2 HOUR FIRE -RATED GYPSUM WALLBOARD /STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIAL AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR 0400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE .DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOODS STUDS TO CONSIST OF NOMINAL 2 BY 4 INCH LUMBER SPACED 16 INCHES ON CENTER. STEEL STUDS TO BE MINIMUM 2 -1/2 INCHES WIDE AND SPACED MAXIMUM 24 INCHES ON CENTER. B. WALLBOARD, GYPSUM *: ONE OR TWO LAYERS OF 5/8 INCH THICK GYPSUM WALLBOARD, AS SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN. MAXIMUM DIAMETER OF OPENING IS 7 INCHES. 2. ONE STEEL PIPE OR CONDUIT TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. A MINIMUM ANNULAR SPACE OF 1/4 INCH IS REQUIRED WITHIN FIRESTOP SYSTEM. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THIS ASSEMBLY IS SPECIFIC TO STEEL TUBE, NOMINAL 6" DIAMETER (OR SMALLER) 16 GAUGE GALVANIZED STEEL TUBING 1/8" CONTINUOUS WALL THICKNESS. BENDS MAY PENETRATE THE SYSTEM AT UP TO 450 WITHOUT COMPROMISING THE RATING. 3. UP TO THREE 3/8" DIAMETER SHIELDED CABLES. WIRE TO BE CL2P, PLENUM RATED, LOW VOLTAGE FOR COMMUNICATION USE, TIE WRAPPED TO STEEL PIPE. 4. FILL, VOID OR CAVITY MATERIAL *: SEALANT -1 -1/4 INCH THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. *BEARING THE UL CLASSIFICATION MARK HILTI. INC. - HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT Note: According to Underwriter's Laboratories, The F and T Ratings of a firestop system are not jeopardized if the metallic pipe penetrant passes through the opening at an angle not to exceed 45 degrees from the perpendicular and the annular spaces are within the requirements that have been established in the individual firestop system. this is applicable to firestop systems incorporating fill materials (such as sealants, putty, or mortar and packing materials. Wall Penetration Fire Stop System Not to scale $, m ch o w • °. `S� nob the 8 --t '4'A c a� +� U$ 0. n Z' ca E C o ra Lc "�•, < E L U—n U$°o 3g ,SS ® <S i SWI.S TRANSLOGIC Swisslog Healthcare Solutions Phone: (800) 525 -1841 www.swisslog.com As instruments of service, all designs, ideas, and information shown of these drawings are and shall remain the property of Swisslog Healthcare Solutions. No part thereof stall be copied, disclosed to others, or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of Swisslog Healthcare Solutions. Visual contact with these drawings shall constitute conclusive evidence of acceptance of these restrictions. South Miami Hospital Miami, FL Clinical Expansion CTS -630 Matrix ESP SW ISSN PROJECT NUMBER L08290 DATE 11/14/11 DRAWN BY WJD CHECKED BY li /"ELI f i SCALE Not To Scale OFFICE Concord W ru Penetration & Support Details ru Z W PT -311 1: N