SYSTEM NO. CAJ8081
F RATING - 2 HOUR
T RATING - 0 HOUR
NOTES:
1. FLOOR OR WALL ASSEMBLY: MINIMUM 21/2" THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100 -150 PCF) CONCRETE FLOOR OR MINIMUM 31/2" REINFORCED
LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL, WALL MAY ALSO BE CONSTRUCTED OF
ANY UL CLASSIFIED CONCRETE BLOCKS *. MAXIMUM DIAMETER OF OPENING EQUALS 8 INCHES.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES
OF MANUFACTURERS.
2. ONE STEEL PIPE OR CONDUIT TO BE CENTERED WITHIN THE FIRESTOP SYSTEM.
WITHIN THE FIRESTOP SYSTEM, A MINIMUM NOMINAL ANNULAR SPACE OF 1/4" IS REQUIRED.
PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED AT ONE SIDE OF FLOOR OR WALL ASSEMBLY.
THIS ASSEMBLY IS SPECIFIC TO STEEL PIPE - NOMINAL 6" DIAMETER (OR SMALLER) 16 GAUGE
GALVANIZED STEEL TUBING. .
3. UP TO FOUR 3/8" DIAMETER SHIELDED CABLES. WIRE TO BE CL2P, PLENUM RATED, LOW
VOLTAGE FOR COMMUNICATION USE. CABLE IS TIE WRAPPED TO STEEL PIPE.
4. PACKING MATERIAL: MINIMAL 4 PCF MINERAL WOOL BATT INSULATION, FIRMLY PACKED
INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP
SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE
THE REQUIRED THICKNESS OF FILL MATERIAL. MINIMUM THICKNESS OF PACKING MATERIAL IN
FLOORS AND WALLS TO BE 1 -1/2 ".
5. FILL VOID OR CAVITY MATERIAL* - SEALANT: MINIMUM 1" THICKNESS OF FILL MATERIAL
APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF
WALL. AS AN ALTERNATE, THE PERMANENT PACKING MATERIAL (ITEM 3) MAY BE OMITTED IF
THE FILL MATERIAL THICKNESS IS INCREASED TO A MINIMUM 1 -1/2 INCH.
*BEARING THE UL CLASSIFICATION MARK
HILTI INC. - HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT
Note: According to Underwriter's Laboratories, The F and T Ratings of a firestop system are not jeopardized
if the metallic pipe penetrant passes through the opening at an angle not to exceed 45 degrees from the
perpendicular and the annular spaces are within the requirements that have been established in the
individual firestop system. this is applicable to firestop systems incorporating fill materials (such as
sealants, putty, or mortar and packing materials.
2 Floor Penetration Fire Stop System
Not to scale
FRONT VIEW SECTION A -A
SYSTEM NO. WL8023
F RATING -1 and 2 HOUR (See Item 1)
T RATING - 0 HOUR
NOTES:
1. WALL ASSEMBLY: THE 10R 2 HOUR FIRE -RATED GYPSUM WALLBOARD /STUD WALL
ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIAL AND IN THE MANNER SPECIFIED IN THE
INDIVIDUAL U300 OR 0400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE
.DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL
CHANNEL STUDS. WOODS STUDS TO CONSIST OF NOMINAL 2 BY 4 INCH LUMBER SPACED 16
INCHES ON CENTER. STEEL STUDS TO BE MINIMUM 2 -1/2 INCHES WIDE AND SPACED MAXIMUM 24
INCHES ON CENTER.
B. WALLBOARD, GYPSUM *: ONE OR TWO LAYERS OF 5/8 INCH THICK GYPSUM
WALLBOARD, AS SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN. MAXIMUM
DIAMETER OF OPENING IS 7 INCHES.
2. ONE STEEL PIPE OR CONDUIT TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. A
MINIMUM ANNULAR SPACE OF 1/4 INCH IS REQUIRED WITHIN FIRESTOP SYSTEM. PIPE TO BE
RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THIS ASSEMBLY IS SPECIFIC TO
STEEL TUBE, NOMINAL 6" DIAMETER (OR SMALLER) 16 GAUGE GALVANIZED STEEL TUBING 1/8"
CONTINUOUS WALL THICKNESS. BENDS MAY PENETRATE THE SYSTEM AT UP TO 450 WITHOUT
COMPROMISING THE RATING.
3. UP TO THREE 3/8" DIAMETER SHIELDED CABLES. WIRE TO BE CL2P, PLENUM RATED, LOW
VOLTAGE FOR COMMUNICATION USE, TIE WRAPPED TO STEEL PIPE.
4. FILL, VOID OR CAVITY MATERIAL *: SEALANT -1 -1/4 INCH THICKNESS OF FILL MATERIAL
APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL.
*BEARING THE UL CLASSIFICATION MARK
HILTI. INC. - HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT
Note: According to Underwriter's Laboratories, The F and T Ratings of a firestop system are not jeopardized if
the metallic pipe penetrant passes through the opening at an angle not to exceed 45 degrees from the
perpendicular and the annular spaces are within the requirements that have been established in the individual
firestop system. this is applicable to firestop systems incorporating fill materials (such as sealants, putty, or
mortar and packing materials.
Wall Penetration Fire Stop System
Not to scale
$, m
ch
o w
• °. `S� nob the 8
--t '4'A c a�
+� U$
0.
n Z'
ca E C
o ra Lc
"�•, < E L
U—n U$°o
3g ,SS ® <S
i
SWI.S
TRANSLOGIC
Swisslog Healthcare Solutions
Phone: (800) 525 -1841
www.swisslog.com
As instruments of service, all designs, ideas, and information shown of these drawings are and shall remain the property of
Swisslog Healthcare Solutions. No part thereof stall be copied, disclosed to others, or used in connection with any work or project
other than the specific project for which they have been prepared and developed without the written consent of Swisslog
Healthcare Solutions. Visual contact with these drawings shall constitute conclusive evidence of acceptance of these restrictions.
South Miami Hospital
Miami, FL
Clinical Expansion
CTS -630 Matrix ESP
SW ISSN PROJECT NUMBER
L08290
DATE 11/14/11
DRAWN BY WJD
CHECKED BY li /"ELI
f i
SCALE Not To Scale
OFFICE Concord
W
ru Penetration & Support Details