11-1104R-003
ABBREVIATIONS /SUFFIXES ELECTRICAL SYMBOL LEGEND NOTE: 1. SYMBOLS IN DASHED LINE INDICATE EXISTING DEVICES. 2. ALL SYMBOLS MAY NOT BE USED IN THIS PROJECT. A.F.F. ABOVE FINISHED FLOOR A.F.G. ABOVE FINISHED GRADE AWG AMERICAN WIRE GAUGE BD. BOARD C. CONDUIT CAB. CABINET C.B. CIRCUIT BREAKER CKT. CIRCUIT CCTV CLOSED CIRCUIT TELEVISION CO -THW COPPER WIRE WITH THERMOPLASTIC, HEAT RESISTANT, ® MOISTURE RESISTANT CHARACTERISTICS E.A. EMPTY CONDUIT E.W.C. ELECTRIC WATER COOLER E EXISTING TO REMAIN ER EXISTING RELOCATED EMT ELECTRICAL METALLIC TUBING F.A. FIRE ALARM G.F.I. GROUND FAULT INTERRUPTER GND. GROUND HID HIGH INTENSIVE DISCHARGE HIPS HIGH PRESSURE SODIUM I.G. ISOLATED GROUND LT. LIGHT LTG. LIGHTING MCB MAIN CIRCUIT BREAKER MLO MAIN LUGS ONLY MT. MOUNT MTG. HT. MOUNTING HEIGHT N.E.C. NATIONAL ELECTRICAL CODE N.I.C. NOT IN CONTRACT NL NIGHT LIGHT NFPA NATIONAL FIRE PROTECTION ASSOCIATION NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION. LFMC LIQUID TIGHT FLEXIBLE METAL CONDUIT P.A. PUBLIC ADDRESS PNL. PANEL PTZ PAN - TILT -ZOOM CAMERA RECEPT. RECEPTACLE RMC RIGID METAL CONDUIT S.D.B.C. SOFT DRAWN BARE COPPER SW. SWITCH TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION PANEL U.O.N. UNLESS OTHERWISE NOTED V.P. VAPOR PROOF VOC VOLATILE ORGANIC COMPOUND WAP WIRELESS ACCESS POINT W.G. WIRE GUARD. W.P. WEATHER PROOF (NEMA 3R ENCLOSURE) X.P. EXPLOSION PROOF (CLASS TO MEET N.E.C.) LIGHTING FIXTURES O LIGHTING FIXTURE IDENTIFICATION. SEE SCHEDULE Q HID OR FLUORESCENT DOWN LIGHT Q ACCENT TYPE LIGHT FIXTURE Q-� HID OR FLUORESCENT WALL MOUNTED LIGHT FIXTURE 000 RECESSED / LAY -IN MOUNTED FLUORESCENT LIGHT FIXTURE ® SURFACE OR PENDANT MOUNTED FLUORESCENT LIGHT FIXTURE 0 WALL MOUNTED FLUORESCENT LIGHT FIXTURE �--e SURFACE OR PENDANT MOUNTED FLUORESCENT STRIP FP HID DOWN LIGHT ON NIGHT LIGHT CIRCUIT & EQUIPPED WITH RESTRIKE SYSTEM ® HID WALL MOUNTED LIGHT FIXTURE ON NIGHT LIGHT CIRCUIT ® RECESSED /FLUORESCENT LIGHT FIXTURE ON EMERGENCY CIRCUIT OR J EMERGENCY BATTERY PACT. ® SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE ON LIGHT CIRCUIT OR EMERGENCY BATTERY PACT e EXIT LIGHT VW WALL MOUNTED EXIT LIGHT SHADED QUADRANT INDICATES NUMBER OF FACES. S4 ARROWS AS SHOWN OR REQUIRED. © UNIT EQUIPMENT BATTERY BACKUP EMERGENCY LIGHT Sp COMBINATION EXIT / EMERGENCY LIGHT WITH BATTERY BACKUP. POWER EQUIPMENT HIGH VOLTAGE DISTRIBUTION PANELBOARD 277/480V ® LOW VOLTAGE DISTRIBUTION PANELBOARD 120/208V ® HIGH VOLTAGE PANELBOARD 277/48OV. MW LOW VOLTAGE PANELBOARD 120/208V. LQ HD FUSIBLE DISCONNECT OR CIRCUIT BREAKER. NEMA 3R WHEN OUTDOORS. 3 0 3 =N0. OF POLES, 60= SWITCH SIZE, 50 =FUSE, NF= NON - FUSED, * =FUSE SIZE AS REQUIRED BY LOAD. ® MOTOR STARTER W /CONTROL XMFR, HOA SELECTOR SW. AND RED PILOT LIGHT. NEMA SIZE BY MOTOR. PROVIDE NEMA 4 ENCLOSURE WHEN OUTDOORS L9 COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH OR CB. SAME ENCLOSURE AND ACCESSORIES AS INDICATED ABOVE © CONTACTOR. SAME ENCLOSURE AND ACCESSORIES AS STARTERS FAN MOTOR "2" WHEN SHOWN INDICATES HORSEPOWER a TRANSFORMER POWER DEVICES (�4 DUPLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.) (3H SINGLE RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.) ej PEDESTAL MOUNTED WP SINGLE RECEPT. �j DUPLEX RECEPT. MOUNTED ABOVE COUNTER - 20 AMP NEMA 5 -20R (44" A.F.F.) U.O.N. @j DUPLEX RECEPT. (UPS CONNECTION) - 20 AMP NEMA 5 -20R (18" A.F.F.) C4 POWER RECEPT. TWIST LOCK - 20 AMP NEMA 5 -20R (18" A.F.F.) QUAD - PLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.) ® DUPLEX RECEPT FLUSH FLOOR MOUNTED - 20 AMP NEMA 5 -20R ® DUPLEX RECEPT FLUSH CEILING MOUNTED - 20 AMP NEMA 5 -20R it SPECIAL PURPOSE RECEPT (18" A.F.F.) A, B, C A - 250V, 30A, 4W B - 250V, 50A, 4W. C - 250V, 50A, 5W. JUNCTION BOX a WALL MOUNTED JUNCTION BOX FLOOR MOUNTED JUNCTION BOX UNDER RAISED FLOOR FOR CONNECTION J TO WIREMOLD PLUG STRIP MOUNTED AT RACKS AND FURNITURE BY A HARDWIRE FLEXIBLE CONNECTION BY ELECTRICAL CONTRACTOR. ® PULL BOX WIRING BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO TICKS INDICATES 2 # 12 CONDUCTORS & 1 # 12 GROUND IN 3/4" CONDUIT. TICK MARKS WHEN SHOWN, INDICATES NUMBER OF # 12 CONDUCTORS IF OTHER THAN THREE, (1) INDICATES GROUND. CONDUIT LARGER THAN 3/4" & CONDUCTOR LARGER THAN # 12 SHALL BE AS INDICATED. HOME RUN TO PANEL "A" = PANEL DESIGNATION, 1,3,5 = CIRCUIT NUMBERS. U.O.N. MINIMUM SIZE OF 3/4 "C AND MAXIMUM OF THREE CIRCUITS PER A-13,5 HOMERUN. (DEDICATED NEUTRAL FOR EACH HOT WIRES MUST BE PROVIDED) FLEXIBLE CONDUIT CONDUIT RUN CONCEALED IN CEILING OR WALLS CONDUIT RUN UNDERGROUND OR IN SLAB - - - - - -- CONDUIT RUN EXPOSED [ CAPPED CONDUIT -H+ SYSTEM AND /OR EQUIPMENT GROUNDING CONDUCTOR II� GROUNDING ELECTRODE AND CONDUCTOR SYSTEM -x CONDUIT SEAL ® CABLE TRAY DATA, COMMUNICATIONS AND SECURITY GENERAL NOTES: 1. SITE INVESTIGATION: PRIOR TO BIDDING THE CONTRACTOR SHALL VISIT THE JOBSITE AND BECOME ACQUAINTED WITH ALL OF THE EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITION RESULTS IN EXTRA MATERIAL OR LABOR. THE CONTRACTOR SHALL SUBMIT IN HIS BID AN AMOUNT THAT WOULD BE SET ASIDE FOR UNIDENTIFIED ITEMS. 2. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS MANNER AND SHALL BE A COMPLETED AND FULLY OPERATIVE TO THE ACCEPTANCE OF THE OWNER, GENERAL CONTRACTOR AND ENGINEER. 3. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR THE COMPLETE INSTALLATION OF THE ELECTRICAL SYSTEMS, ALL IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL COMPLY WITH THE FLORIDA BUILDING CODE 2010 AND ALL THE STANDARDS OF CONSTRUCTION ESTABLISHED BY AHCA, NFPA CODES INCLUDING, BUT NOT LIMITED TO NFPA 70 - (2008), NFPA 72 (2007), NFPA 99 - (2005), NFPA 110 -(2005), NFPA 101 -(2009), NFPA 780 - (2011), AIA 2010, FGI - (2010) AND OSHA. 4. THIS CONTRACTOR SHALL PAY FOR ALL FEES, INSPECTIONS, TESTS, FINES, ETC., AS REQUIRED. 5. MINIMUM STANDARDS: THE MATERIAL, EQUIPMENT, INSTALLATIONS, AND WORKMANSHIP FURNISHED UNDER THIS SECTION SHALL CONFORM AT LEAST TO THE REQUIREMENTS OF THE REGULATING AGENCIES AS LISTED IN ITEM (3) ABOVE. ALL MATERIALS AND EQUIPMENT USED SHALL BE LISTED OR BEAR U.L. APPROVAL FOR THEIR INTENDED USE. 6. RESPONSIBILITIES: CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE INSTALLATION OF THE RACEWAY SYSTEM, EQUIPMENT AND WIRING IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. 7. GUARANTEE: THE CONTRACTOR/SUB- CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT ALL WORK EXECUTED UNDER THIS CONTRACT SHALL BE FREE FROM DEFECTS OF WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE AND THAT HE, AT HIS OWN EXPENSE, WILL REPAIR OR REPLACE ALL WORK WHICH BECOMES DEFECTIVE DURING THE TIME OF THE GUARANTEE. 8. ALL EQUIPMENT, SYSTEMS AND SYSTEM COMPONENTS SHALL BE FROM THE SAME MANUFACTURER AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS RECOMMENDATIONS AND SPECIFICATIONS. 9. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL PLANS PRIOR TO ANY FABRICATIONS OR INSTALLATION. 10. OBTAIN FULL INFORMATION REGARDING PECULIARITIES AND LIMITATIONS OF SPACE AVAILABLE FOR INSTALLATION OF THE EQUIPMENT AND MATERIALS UNDER CONTRACT, AND PROVIDE READY ACCESSIBILITY TO ELECTRICAL EQUIPMENT, INCLUDING ANY PART OF SYSTEM REQUIRED TO BE REACHED FOR MAINTENANCE AND OPERATIONS. 11. PROVIDE ACCURATE LAYOUT, GRADES AND ELEVATIONS. TAKE PROPER PRECAUTIONS TO PROTECT WORK AND EQUIPMENT FROM DAMAGE. 12. PROVIDE CODE APPROVED FIRE STOPPING AT ALL CONDUIT PENETRATIONS THROUGHOUT BUILDING CONSTRUCTION TO MAINTAIN FIRE, SMOKE AND SOUND RATING. FIRE SEAL ALL PENETRATIONS. SEAL TELECOMMUNICATION SLEEVES AFTER CABLES HAVE BEEN INSTALLED. 13. RACEWAYS AND FITTINGS: CONDUIT RUNS SHALL BE CONCEALED IN CEILING SPACES AND WALL PARTITIONS. NO CONDUIT SHALL BE EXPOSED IN INTERIOR SPACES EXCEPT FLEXIBLE CONNECTION TO WIRE MOLDS. CONCEALED CONDUITS ARE TO BE EMT. SURFACE MOUNTED RACEWAYS (WIRE MOLD) ARE TO BE INSTALLED IN SOLID WALLS ONLY. THE MINIMUM CONDUIT SIZE IS TO BE 3/4" FOR THE HOMERUN. ALL CONDUITS AND RACEWAYS SHALL BE METAL. 14. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHERS AS WELL AS PROVIDING TEMPORARY POWER. 15. VERIFY EQUIPMENT SIZES, VOLTAGE AND CURRENT CHARACTERISTICS, ETC., BEFORE THE ORDERING OF ANY EQUIPMENT AND PRIOR TO ROUGHING -IN FOR EQUIPMENT TO BE SUPPLIED TO OTHERS. NOTIFY ENGINEER OF ANY CONFLICT. 16. PROVIDE COMPLETE POWER CIRCUIT WIRING AND CONNECTIONS FOR EACH AND EVERY ITEM OF PERMANENT MECHANICAL EQUIPMENT. PRIOR TO ANY ROUGH -IN, COORDINATE WITH HVAC AND PLUMBING EQUIPMENT NAME PLATE TO OBTAIN CORRECT WIRE SIZE AND OVERCURRENT PROTECTION RATING. IF THE NAME PLATE LABEL REQUIRES THE OVERCURRENT PROTECTION DEVICE TO BE FUSES, PROVIDE A FUSED SWITCH WITH PROPER SIZE FUSES AT THE EQUIPMENT LOCATION. 17. CONDUCTOR: ALL CONDUCTOR WIRE AND CABLE SHALL CONSIST OF 98% CONDUCTIVITY COPPER. ALL CABLES SHALL BE SINGLE CONDUCTOR, 600 VOLT, THERMOPLASTIC INSULATION, SUITABLE FOR CONTINUOUS OPERATION AT 75 DEGREES C. CONDUCTOR TEMPERATURE IN BOTH WET AND DRY LOCATIONS. THESE CABLES SHALL BE N.E.C. INSULATION CLASSIFICATION TYPE THWN/THHN. MINIMUM SIZE SHALL BE #12. ALL CONDUCTOR INSULATION SHALL BE COLOR CODED MAINTAINING THE INTEGRITY OF THE EXISTING INSTALLATION. COLORED INSULATION SHALL BE USED FOR AWG SIZES #10 AND SMALLER AND APPROVED COLOR TAPES SHALL BE USED FOR AWG SIZES #8 AND LARGER. ALL POWER AND CONTROL CIRCUITS SHALL CARRY EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC 250 -122. 18. THE NATURE OF THIS TYPE OF CONSTRUCTION POSES SPECIAL PROBLEMS FOR THE DESIGN ENGINEER AS WELL AS THE CONTRACTOR. EVERY EFFORT HAS BEEN MADE BY THE ENGINEER TO SHOW AND VERIFY WHERE POSSIBLE THE LOCATION OF THE EXISTING ELECTRICAL SYSTEM. THE MAJOR PORTION OF THE ELECTRICAL SYSTEMS ARE AS SHOWN ON THE DRAWINGS. HOWEVER, MINOR DEVIATIONS MAY BECOME EVIDENT AS THE JOB PROGRESSES. NO ADVANTAGE IS TO BE TAKEN BY THE CONTRACTOR BECAUSE OF THESE MINOR DIFFERENCES. „ 19. CORRECTION OF ANY DEFECTS, REPAIRS OR DAMAGE DURING CONSTRUCTION AS WE4 AS J4 Y MINOR CHANGES IN OUTLET LOCATIONS SHALL BE MADE WITHOUT ADDITIONAL COST. jiip ,`.. 20. GUTTERS, PULL BOXES, ETC., SHALL BE GALVANIZED STEEL SIZED PER NATIONAL ELECTRICAL CODE, ; ARTICLE 312, MADE OF MATERIAL SUITABLE FOR THE ENVIRONMENTAL CONDITIONS PRESEt4.T. 21. ALL FLOORS, WALLS AND ROOF PENETRATIONS SHALL BE PROPERLY SEALED -OFF. ,IF FIRE - RATED, AN APPROVED FIRE RETARDANT SEAL SHALL BE USED. 22. ALL WIRING SHALL BE IN RACEWAY. A. INDOORS - USE THE FOLLOWING WIRE METHODS: • EXPOSED: EMT • CONCEALED: EMT • CONNECTION TO VIBRATION EQUIPMENT (INCLUDING TRANSFORMERS AND HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID, OR MOTOR - DRIVEN EQUIPMENT): FMC, EXCEPT IN WET OR DAMP LOCATIONS USE LFMC. • DAMP OR WET LOCATIONS: RIGID STEEL CONDUIT. • BOXES AND ENCLOSURES: NEMA 250, TYPE I, EXCEPT AS FOLLOWS: B. DAMP OR WET LOCATIONS: NEMA 250, TYPE 3R STEEL. C. DAMP OR WET LOCATIONS: 250, TYPE 4, NONMETALLIC. • UNDERGROUND RNC (SINGLE RUN OR GROUPED). D. SEALING FITTINGS SHALL BE INSTALLED AT FOLLOWING POINTS, AND ELSEWHERE AS SHOWN. • WHERE REQUIRED BY THE NEC. 23. THESE DRAWINGS ARE A GUIDE FOR THE INSTALLATION OF THE RACEWAY SYSTEM AND EQUIPMENT. THEY ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN AND EXTENT OF THE WORK AND ARE PARTLY DIAGRAMMATIC. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE AND FUNCTIONAL INSTALLATION. ----- 24. CIRCUIT NUMBERS ARE FOR IDENTIFICATION PURPOSES ONLY. THE CONTRACTOR IS RESPONSIBLE FOt; ^ CORRECTLY PHASING THE CIRCUITS IN THE PANEL AND SHALL BALANCE THE LOAD ON THE PHASE:;--- UNDER NORMAL OPERATING CONDITIONS. PROVIDE TYPE WRITTEN PANEL BOARD DIRECTORIES IN EXISTING PANEL BOARD DIRECTORIES. UPDATE ALL DIRECTORIES IN EXISTING PANEL BOARDS AFFECTED BY THIS PROJECT ELECTRONICALLY TRACING ALL CIRCUITS. 25. ANY DEVIATION FROM THESE DRAWINGS AND SPECIFICATIONS MUST BE AUTHORIZED IN WRITING FROM THE ENGINEERS OFFICE. THE CONTRACTOR SHOULD BE HELD LIABLE FOR ANY DEVIATIONS WITHOUT SUCH AUTHORIZATION. 26. ALL POWER AND LIGHTING CIRCUITS SHALL HAVE A GREEN EQUIPMENT GROUNDING CONDUCTOR SIZED AS PER NEC 250 -122. NEUTRAL CONDUCTOR SHALL BE 10 AWG (MINIMUM CU -THW) IN ALL MULTI - CIRCUIT BRANCH CIRCUITS. 27. PROVIDE NYLON PULL STRINGS IN ALL EMPTY CONDUITS FOR FUTURE USE. 28. COLOR CODING FOR CONDUCTORS: * A. WIRING FOR 120/208 VOLT SYSTEM SHALL BE CODED AS FOLLOWS: PHASE A - BLACK PHASE B - RED PHASE C - BLUE NEUTRAL - WHITE GROUND -GREEN B. WIRING FOR 277/480 VOLT SYSTEM SHALL BE CODED AS FOLLOWS: PHASE A - YELLOW PHASE B - BROWN PHASE C - ORANGE NEUTRAL -GRAY GROUND - GREEN C. COLORS ON CONDUCTOR 6 AWG AND SMALLER SHALL BE AN INTEGRAL PART OF INSULATION. ON CONDUCTOR 4 AWG AND LARGER CONDUCTORS, EITHER COLOR CODING TAPE OR PAINTED WITH TWO COATS OF CORRECT COLOR PAINT AT ALL TERMINALS AND CONNECTION POINTS. * UNLESS OTHERWISE REQUIRED BY APPLICABLE CODE. 29. ANY WORK NOT SHOWN OR SPECIFICALLY MENTIONED ON THESE PLANS BUT CONSIDERED NECESSARY FOR COMPLETION OF WORK IN THE PROPER MANNER SHALL BE PROVIDED BY THE CONTRACTOR WITHOUT ADDITIONAL CHARGE. 30. CONTRACTOR SHALL VERIFY SPACE CONDITIONS AND DIMENSIONS AT JOB SITE PRIOR TO FABRICATION AND INSTALLATION OF MATERIALS AND EQUIPMENT. ELECTRICAL CONTRACTOR IS TO COORDINATE HIS WORK WITH THE ARCHITECT BEFORE ROUGH INSTALLATION OF ALL OUTLETS (LIGHTS, RECEPTACLES, SWITCHES, PULL BOXES, ETC.) FOR EXACT LOCATION. 31. ALL ELECTRICAL EQUIPMENT SUCH AS PANELS, PULUJ- BOXES, FEEDERS, BREAKERS, ETC. SHALL BE PROPERLY IDENTIFIED WITH A PERMANENT LABEL AFFIXED TO THE EQUIPMENT. IDENTIFY BREAKERS IN PANELS BY MEANS OF A TYPED, PLASTIC COVERED DIRECTORY. CONTRACTOR SHALL PROVIDE UPDATED PANEL DIRECTORIES. 32. SPOT PAINT CONDUITS AND BOXES. IDENTIFY CONDUITS WITHIN 6 INCHES (6 ") OF BOX OR ENCLOSURE. USE ONLY COLOR CODE IN COMPLIANCE WITH USER REQUIREMENTS UPON COMPLETION. 33. ALL SERVICE INTERRUPTIONS AND ALL REMOVAL AND DISPOSAL WORK SHALL BE SCHEDULED AND COORDINATED WITH THE AUTHORIZED REPRESENTATIVE OF THE OWNER. 34. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS AND OTHER ITEMS AS REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 35. UPON COMPLETION OF THE INSTALLATION, CONTRACTOR SHALL CONDUCT A COMPLETE EQUIPOTENTIAL TEST AS DEFINED IN NFPA 99 4.3.3 (2005). CONTRACTOR SHALL SUBMIT THE RESULTS OF THE TEST TO THE OWNER AND THE A/E. THE CONTRACTOR SHALL HAVE TEST EQUIPMENT AVAILABLE FOR SPOT CHECK AT FINAL CONSTRUCTION SURVEY. CONTRACTOR SHALL USE A HAMPDEN OR BENTLEY NEVADA METER OR APPROVED EQUAL. 36. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL CHANGES AS THE CONSTRUCTION PROGRESSES. AT THE COMPLETION OF THE WORK, THE CONTRACTOR SHALL DELIVER A SET OF AS -BUILT DRAWINGS TO THE OWNER IN REPRODUCIBLE MATERIAL. CONTRACTOR SHALL STAMP AS -BUILT ON THE PLANS (EACH SHEET), PRINT, DATE, AND SIGN IN BLUE INK. 37. CONVENIENCE RECEPTACLE LIGHTING SWITCHES AND WIRING DEVICES MUST BE HOSPITAL GRADE AND SHALL BE ENGRAVED INDICATING PANEL AND CIRCUIT NUMBERS. 38. SEPARATE PERMIT APPLICATIONS ARE REQUIRED FOR FIRE ALARM, BURGLAR ALARM, TELEPHONE, TV, CCTV, COMPUTER WIRING AND ANY OTHER LOW VOLTAGE SYSTEM. COPY OF CONTRACT MUST BE SUBMITTED WITH EACH APPLICATION. 39. FIRE ALARM SHOP DRAWING AND PERMIT SHALL BE PROVIDED BY THE CONTRACTOR. UPON COMPLETION OF THE WORK, THE FIRE ALARM SYSTEM SHALL BE TESTED AND RE- CERTIFIED. CONTRACTOR MUST HAVE A COPY OF RE- CERTIFICATION AVAILABLE AT FINAL CONSTRUCTION SURVEY. 40. CONTRACTOR SHALL VERIFY AND PROVIDE NECESSARY CORRECTIVE ACTION TO COMPLY WITH PANELBOARD BONDING PER NEC 517.14. 41. CONDUIT AND BOXES COLOR CODE CHART: ORANGE - CRITICAL BRANCH YELLOW - LIFE SAFETY BRANCH GREEN - EQUIPMENT BRANCH RED - FIRE ALARM 42. CONTRACTOR IS RESPONSIBLE FOR REPLACING ALL PARTITION, FLOOR CEILING, CONDUIT PENETRATIONS, AND ANY OTHER EXISTING CONDITION AFFECTED BY THIS PROJECT. UPON COMPLETION, RE -PAINT ALL AFFECTED SURFACES MATCHING SURROUNDING COLOR. W V1 O O TOT� V1 SALTZ MICHELSON, A R C H I T E C T S 3501 Griffin Road Ft. Lauderdale, FL 33312 (954) 266 -2700 Fx: (954) 266 -2701 sma @saltzmichelson.com AA- 0002897 PROJ. No. 22046 CA 924 LOUIS J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS 9150 SOUTH DADELAND BLVD. STE 900 MIAMI, FLORIDA 33156 TELEPHONE: (305) 670 -0141 FAX: (305) 670 -0144 WWW.LJAAPA.COM LANDSCAPE LIGHT FIXTURE O� POLE MOUNTED SINGLE SITE LIGHTING FIXTURE ;-� ;,. TELEPHONE &DATA OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX) (18" A.F.F.) 000 POLE MOUNTED DOUBLE SITE LIGHTING FIXTURE ® TELEPHONE & DATA OUTLET FLUSH FLOOR MOUNTED 0 CEILING MOUNTED OCCUPANCY SENSOR. INCLUDE POWER PACK AS REQUIRED. 0 TELEPHONE OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX)(18" A.F.F.) FP OCCUPANCY SENSOR POWER PACK. ® TELEPHONE OUTLET FLUSH FLOOR MOUNTED ® LTG. TRANSFER RELAY. -P PUBLIC TELEPHONE (48" A.F.F.) S SINGLE POLE SWITCH - 20 AMP (48" A.F.F.) S3 THREE WAY SWITCH - 20 AMP (48" A.F.F.) VW WALL MOUNTED TELEPHONE OUTLET (60 "A.F.F.) S4 FOUR WAY SWITCH - 20 AMP (48" A.F.F.) © CLOCK (8' -0" AFF) Sp DIMMER SWITCH 2000 WATTS 48" A.F.F.) D TERMINAL CABINET -TYPE INDICATED SF FAN SPEED CONTROL (48" A.F.F.) ® TELEPHONE TERMINAL BACK BOARD SK KEY OPERATED SWITCH - 20 AMP (48" A.F.F.) QQ CLOSE CIRCUIT TV MONITORS SP SINGLE POLE SWITCH WITH PILOT LIGHT - 20 AMP(48" A.F.F.) Sm MOTOR RATED SWITCH (ONE, TWO OR THREE POLE AS REQUIRED) Q RADIO REMOTE ST TIME CONTROL SWITCH @ PAGER SPEAKER SOS OCCUPANCY SENSOR SINGLE POLE SWITCH - 20 AMP. (42" AFF). CCTV CCTV CAMERA SOS2 OCCUPANCY SENSOR 2 RELAY DUAL TECH SWITCH - 20 AMP. (42" AFF). is INTERCOM STATION (WALL MTD) -3GANG BOX @ 4' -0" SOR OVERRIDE SWITCH - 20 AMP. (42" AFF). iC 0 INTERCOM (DOOR STATION) SAME AS WALL MTD FIRE ALARM DEVICES FQ INTERCOM @ 4' -0" A.F.F. F❑ FIRE ALARM PULL STATION (48" A.F.F.) SEMI FLUSH MOUNTED, F0 CAN STATIONS @ 2' -6" A.F.F. (U.N.O.) PROVIDE BREAKABLE GLASS COVER. F0 WALL MOUNTED TV OUTLET. FIRE ALARM HORN WITH STROBE LIGHT (80 "A.F.F.) ADA • DOOR BELL PUSH BUTTON 04 FIRE ALARM SPEAKER WITH STROBE LIGHT (80 "A.F.F.) ADA 6 DOOR BELL CHIME Ss FIRE ALARM SPEAKER WITH STROBE LIGHT. CEILING MOUNTED © SECURITY SYSTEM KEYPAD ( FIRE ALARM MASS NOTIFICATION SPEAKER. CEILING MOUNTED Q SECURITY SYSTEM CARD READER FIRE ALARM STROBE LIGHT - 75 CANDELA MIN. - (80 " A.F.F.) OR 6" BELOW 0 SECURITY SYSTEM MOTION DETECTOR CEILING WHISHEVER IS LOWER, INSTALLATION SHALL COMPLY WITH A.D.A., ® 24V SMOKE DETECTOR (PHOTOELECTRIC TYPE). DS SECURITY SYSTEM DOOR STRIKE Q SECURITY SYSTEM DOOR CONTACT ®H SMOKE AND HEAT DETECTOR © SECURITY SYSTEM MAGNETIC LOCK 0 24V FIXED TEMPERATURE 135° F THERMAL DETECTOR. pS POWER SUPPLY ® 24V PHOTOELECTRIC DUCT DETECTOR. DOOR HOLDER FS FLOW SWITCH TS TAMPER SWITCH FACP FIRE ALARM CONTROL PANEL GENERAL NOTES: 1. SITE INVESTIGATION: PRIOR TO BIDDING THE CONTRACTOR SHALL VISIT THE JOBSITE AND BECOME ACQUAINTED WITH ALL OF THE EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITION RESULTS IN EXTRA MATERIAL OR LABOR. THE CONTRACTOR SHALL SUBMIT IN HIS BID AN AMOUNT THAT WOULD BE SET ASIDE FOR UNIDENTIFIED ITEMS. 2. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS MANNER AND SHALL BE A COMPLETED AND FULLY OPERATIVE TO THE ACCEPTANCE OF THE OWNER, GENERAL CONTRACTOR AND ENGINEER. 3. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR THE COMPLETE INSTALLATION OF THE ELECTRICAL SYSTEMS, ALL IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL COMPLY WITH THE FLORIDA BUILDING CODE 2010 AND ALL THE STANDARDS OF CONSTRUCTION ESTABLISHED BY AHCA, NFPA CODES INCLUDING, BUT NOT LIMITED TO NFPA 70 - (2008), NFPA 72 (2007), NFPA 99 - (2005), NFPA 110 -(2005), NFPA 101 -(2009), NFPA 780 - (2011), AIA 2010, FGI - (2010) AND OSHA. 4. THIS CONTRACTOR SHALL PAY FOR ALL FEES, INSPECTIONS, TESTS, FINES, ETC., AS REQUIRED. 5. MINIMUM STANDARDS: THE MATERIAL, EQUIPMENT, INSTALLATIONS, AND WORKMANSHIP FURNISHED UNDER THIS SECTION SHALL CONFORM AT LEAST TO THE REQUIREMENTS OF THE REGULATING AGENCIES AS LISTED IN ITEM (3) ABOVE. ALL MATERIALS AND EQUIPMENT USED SHALL BE LISTED OR BEAR U.L. APPROVAL FOR THEIR INTENDED USE. 6. RESPONSIBILITIES: CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE INSTALLATION OF THE RACEWAY SYSTEM, EQUIPMENT AND WIRING IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. 7. GUARANTEE: THE CONTRACTOR/SUB- CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT ALL WORK EXECUTED UNDER THIS CONTRACT SHALL BE FREE FROM DEFECTS OF WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE AND THAT HE, AT HIS OWN EXPENSE, WILL REPAIR OR REPLACE ALL WORK WHICH BECOMES DEFECTIVE DURING THE TIME OF THE GUARANTEE. 8. ALL EQUIPMENT, SYSTEMS AND SYSTEM COMPONENTS SHALL BE FROM THE SAME MANUFACTURER AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS RECOMMENDATIONS AND SPECIFICATIONS. 9. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL PLANS PRIOR TO ANY FABRICATIONS OR INSTALLATION. 10. OBTAIN FULL INFORMATION REGARDING PECULIARITIES AND LIMITATIONS OF SPACE AVAILABLE FOR INSTALLATION OF THE EQUIPMENT AND MATERIALS UNDER CONTRACT, AND PROVIDE READY ACCESSIBILITY TO ELECTRICAL EQUIPMENT, INCLUDING ANY PART OF SYSTEM REQUIRED TO BE REACHED FOR MAINTENANCE AND OPERATIONS. 11. PROVIDE ACCURATE LAYOUT, GRADES AND ELEVATIONS. TAKE PROPER PRECAUTIONS TO PROTECT WORK AND EQUIPMENT FROM DAMAGE. 12. PROVIDE CODE APPROVED FIRE STOPPING AT ALL CONDUIT PENETRATIONS THROUGHOUT BUILDING CONSTRUCTION TO MAINTAIN FIRE, SMOKE AND SOUND RATING. FIRE SEAL ALL PENETRATIONS. SEAL TELECOMMUNICATION SLEEVES AFTER CABLES HAVE BEEN INSTALLED. 13. RACEWAYS AND FITTINGS: CONDUIT RUNS SHALL BE CONCEALED IN CEILING SPACES AND WALL PARTITIONS. NO CONDUIT SHALL BE EXPOSED IN INTERIOR SPACES EXCEPT FLEXIBLE CONNECTION TO WIRE MOLDS. CONCEALED CONDUITS ARE TO BE EMT. SURFACE MOUNTED RACEWAYS (WIRE MOLD) ARE TO BE INSTALLED IN SOLID WALLS ONLY. THE MINIMUM CONDUIT SIZE IS TO BE 3/4" FOR THE HOMERUN. ALL CONDUITS AND RACEWAYS SHALL BE METAL. 14. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHERS AS WELL AS PROVIDING TEMPORARY POWER. 15. VERIFY EQUIPMENT SIZES, VOLTAGE AND CURRENT CHARACTERISTICS, ETC., BEFORE THE ORDERING OF ANY EQUIPMENT AND PRIOR TO ROUGHING -IN FOR EQUIPMENT TO BE SUPPLIED TO OTHERS. NOTIFY ENGINEER OF ANY CONFLICT. 16. PROVIDE COMPLETE POWER CIRCUIT WIRING AND CONNECTIONS FOR EACH AND EVERY ITEM OF PERMANENT MECHANICAL EQUIPMENT. PRIOR TO ANY ROUGH -IN, COORDINATE WITH HVAC AND PLUMBING EQUIPMENT NAME PLATE TO OBTAIN CORRECT WIRE SIZE AND OVERCURRENT PROTECTION RATING. IF THE NAME PLATE LABEL REQUIRES THE OVERCURRENT PROTECTION DEVICE TO BE FUSES, PROVIDE A FUSED SWITCH WITH PROPER SIZE FUSES AT THE EQUIPMENT LOCATION. 17. CONDUCTOR: ALL CONDUCTOR WIRE AND CABLE SHALL CONSIST OF 98% CONDUCTIVITY COPPER. ALL CABLES SHALL BE SINGLE CONDUCTOR, 600 VOLT, THERMOPLASTIC INSULATION, SUITABLE FOR CONTINUOUS OPERATION AT 75 DEGREES C. CONDUCTOR TEMPERATURE IN BOTH WET AND DRY LOCATIONS. THESE CABLES SHALL BE N.E.C. INSULATION CLASSIFICATION TYPE THWN/THHN. MINIMUM SIZE SHALL BE #12. ALL CONDUCTOR INSULATION SHALL BE COLOR CODED MAINTAINING THE INTEGRITY OF THE EXISTING INSTALLATION. COLORED INSULATION SHALL BE USED FOR AWG SIZES #10 AND SMALLER AND APPROVED COLOR TAPES SHALL BE USED FOR AWG SIZES #8 AND LARGER. ALL POWER AND CONTROL CIRCUITS SHALL CARRY EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC 250 -122. 18. THE NATURE OF THIS TYPE OF CONSTRUCTION POSES SPECIAL PROBLEMS FOR THE DESIGN ENGINEER AS WELL AS THE CONTRACTOR. EVERY EFFORT HAS BEEN MADE BY THE ENGINEER TO SHOW AND VERIFY WHERE POSSIBLE THE LOCATION OF THE EXISTING ELECTRICAL SYSTEM. THE MAJOR PORTION OF THE ELECTRICAL SYSTEMS ARE AS SHOWN ON THE DRAWINGS. HOWEVER, MINOR DEVIATIONS MAY BECOME EVIDENT AS THE JOB PROGRESSES. NO ADVANTAGE IS TO BE TAKEN BY THE CONTRACTOR BECAUSE OF THESE MINOR DIFFERENCES. „ 19. CORRECTION OF ANY DEFECTS, REPAIRS OR DAMAGE DURING CONSTRUCTION AS WE4 AS J4 Y MINOR CHANGES IN OUTLET LOCATIONS SHALL BE MADE WITHOUT ADDITIONAL COST. jiip ,`.. 20. GUTTERS, PULL BOXES, ETC., SHALL BE GALVANIZED STEEL SIZED PER NATIONAL ELECTRICAL CODE, ; ARTICLE 312, MADE OF MATERIAL SUITABLE FOR THE ENVIRONMENTAL CONDITIONS PRESEt4.T. 21. ALL FLOORS, WALLS AND ROOF PENETRATIONS SHALL BE PROPERLY SEALED -OFF. ,IF FIRE - RATED, AN APPROVED FIRE RETARDANT SEAL SHALL BE USED. 22. ALL WIRING SHALL BE IN RACEWAY. A. INDOORS - USE THE FOLLOWING WIRE METHODS: • EXPOSED: EMT • CONCEALED: EMT • CONNECTION TO VIBRATION EQUIPMENT (INCLUDING TRANSFORMERS AND HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID, OR MOTOR - DRIVEN EQUIPMENT): FMC, EXCEPT IN WET OR DAMP LOCATIONS USE LFMC. • DAMP OR WET LOCATIONS: RIGID STEEL CONDUIT. • BOXES AND ENCLOSURES: NEMA 250, TYPE I, EXCEPT AS FOLLOWS: B. DAMP OR WET LOCATIONS: NEMA 250, TYPE 3R STEEL. C. DAMP OR WET LOCATIONS: 250, TYPE 4, NONMETALLIC. • UNDERGROUND RNC (SINGLE RUN OR GROUPED). D. SEALING FITTINGS SHALL BE INSTALLED AT FOLLOWING POINTS, AND ELSEWHERE AS SHOWN. • WHERE REQUIRED BY THE NEC. 23. THESE DRAWINGS ARE A GUIDE FOR THE INSTALLATION OF THE RACEWAY SYSTEM AND EQUIPMENT. THEY ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN AND EXTENT OF THE WORK AND ARE PARTLY DIAGRAMMATIC. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE AND FUNCTIONAL INSTALLATION. ----- 24. CIRCUIT NUMBERS ARE FOR IDENTIFICATION PURPOSES ONLY. THE CONTRACTOR IS RESPONSIBLE FOt; ^ CORRECTLY PHASING THE CIRCUITS IN THE PANEL AND SHALL BALANCE THE LOAD ON THE PHASE:;--- UNDER NORMAL OPERATING CONDITIONS. PROVIDE TYPE WRITTEN PANEL BOARD DIRECTORIES IN EXISTING PANEL BOARD DIRECTORIES. UPDATE ALL DIRECTORIES IN EXISTING PANEL BOARDS AFFECTED BY THIS PROJECT ELECTRONICALLY TRACING ALL CIRCUITS. 25. ANY DEVIATION FROM THESE DRAWINGS AND SPECIFICATIONS MUST BE AUTHORIZED IN WRITING FROM THE ENGINEERS OFFICE. THE CONTRACTOR SHOULD BE HELD LIABLE FOR ANY DEVIATIONS WITHOUT SUCH AUTHORIZATION. 26. ALL POWER AND LIGHTING CIRCUITS SHALL HAVE A GREEN EQUIPMENT GROUNDING CONDUCTOR SIZED AS PER NEC 250 -122. NEUTRAL CONDUCTOR SHALL BE 10 AWG (MINIMUM CU -THW) IN ALL MULTI - CIRCUIT BRANCH CIRCUITS. 27. PROVIDE NYLON PULL STRINGS IN ALL EMPTY CONDUITS FOR FUTURE USE. 28. COLOR CODING FOR CONDUCTORS: * A. WIRING FOR 120/208 VOLT SYSTEM SHALL BE CODED AS FOLLOWS: PHASE A - BLACK PHASE B - RED PHASE C - BLUE NEUTRAL - WHITE GROUND -GREEN B. WIRING FOR 277/480 VOLT SYSTEM SHALL BE CODED AS FOLLOWS: PHASE A - YELLOW PHASE B - BROWN PHASE C - ORANGE NEUTRAL -GRAY GROUND - GREEN C. COLORS ON CONDUCTOR 6 AWG AND SMALLER SHALL BE AN INTEGRAL PART OF INSULATION. ON CONDUCTOR 4 AWG AND LARGER CONDUCTORS, EITHER COLOR CODING TAPE OR PAINTED WITH TWO COATS OF CORRECT COLOR PAINT AT ALL TERMINALS AND CONNECTION POINTS. * UNLESS OTHERWISE REQUIRED BY APPLICABLE CODE. 29. ANY WORK NOT SHOWN OR SPECIFICALLY MENTIONED ON THESE PLANS BUT CONSIDERED NECESSARY FOR COMPLETION OF WORK IN THE PROPER MANNER SHALL BE PROVIDED BY THE CONTRACTOR WITHOUT ADDITIONAL CHARGE. 30. CONTRACTOR SHALL VERIFY SPACE CONDITIONS AND DIMENSIONS AT JOB SITE PRIOR TO FABRICATION AND INSTALLATION OF MATERIALS AND EQUIPMENT. ELECTRICAL CONTRACTOR IS TO COORDINATE HIS WORK WITH THE ARCHITECT BEFORE ROUGH INSTALLATION OF ALL OUTLETS (LIGHTS, RECEPTACLES, SWITCHES, PULL BOXES, ETC.) FOR EXACT LOCATION. 31. ALL ELECTRICAL EQUIPMENT SUCH AS PANELS, PULUJ- BOXES, FEEDERS, BREAKERS, ETC. SHALL BE PROPERLY IDENTIFIED WITH A PERMANENT LABEL AFFIXED TO THE EQUIPMENT. IDENTIFY BREAKERS IN PANELS BY MEANS OF A TYPED, PLASTIC COVERED DIRECTORY. CONTRACTOR SHALL PROVIDE UPDATED PANEL DIRECTORIES. 32. SPOT PAINT CONDUITS AND BOXES. IDENTIFY CONDUITS WITHIN 6 INCHES (6 ") OF BOX OR ENCLOSURE. USE ONLY COLOR CODE IN COMPLIANCE WITH USER REQUIREMENTS UPON COMPLETION. 33. ALL SERVICE INTERRUPTIONS AND ALL REMOVAL AND DISPOSAL WORK SHALL BE SCHEDULED AND COORDINATED WITH THE AUTHORIZED REPRESENTATIVE OF THE OWNER. 34. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS AND OTHER ITEMS AS REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 35. UPON COMPLETION OF THE INSTALLATION, CONTRACTOR SHALL CONDUCT A COMPLETE EQUIPOTENTIAL TEST AS DEFINED IN NFPA 99 4.3.3 (2005). CONTRACTOR SHALL SUBMIT THE RESULTS OF THE TEST TO THE OWNER AND THE A/E. THE CONTRACTOR SHALL HAVE TEST EQUIPMENT AVAILABLE FOR SPOT CHECK AT FINAL CONSTRUCTION SURVEY. CONTRACTOR SHALL USE A HAMPDEN OR BENTLEY NEVADA METER OR APPROVED EQUAL. 36. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL CHANGES AS THE CONSTRUCTION PROGRESSES. AT THE COMPLETION OF THE WORK, THE CONTRACTOR SHALL DELIVER A SET OF AS -BUILT DRAWINGS TO THE OWNER IN REPRODUCIBLE MATERIAL. CONTRACTOR SHALL STAMP AS -BUILT ON THE PLANS (EACH SHEET), PRINT, DATE, AND SIGN IN BLUE INK. 37. CONVENIENCE RECEPTACLE LIGHTING SWITCHES AND WIRING DEVICES MUST BE HOSPITAL GRADE AND SHALL BE ENGRAVED INDICATING PANEL AND CIRCUIT NUMBERS. 38. SEPARATE PERMIT APPLICATIONS ARE REQUIRED FOR FIRE ALARM, BURGLAR ALARM, TELEPHONE, TV, CCTV, COMPUTER WIRING AND ANY OTHER LOW VOLTAGE SYSTEM. COPY OF CONTRACT MUST BE SUBMITTED WITH EACH APPLICATION. 39. FIRE ALARM SHOP DRAWING AND PERMIT SHALL BE PROVIDED BY THE CONTRACTOR. UPON COMPLETION OF THE WORK, THE FIRE ALARM SYSTEM SHALL BE TESTED AND RE- CERTIFIED. CONTRACTOR MUST HAVE A COPY OF RE- CERTIFICATION AVAILABLE AT FINAL CONSTRUCTION SURVEY. 40. CONTRACTOR SHALL VERIFY AND PROVIDE NECESSARY CORRECTIVE ACTION TO COMPLY WITH PANELBOARD BONDING PER NEC 517.14. 41. CONDUIT AND BOXES COLOR CODE CHART: ORANGE - CRITICAL BRANCH YELLOW - LIFE SAFETY BRANCH GREEN - EQUIPMENT BRANCH RED - FIRE ALARM 42. CONTRACTOR IS RESPONSIBLE FOR REPLACING ALL PARTITION, FLOOR CEILING, CONDUIT PENETRATIONS, AND ANY OTHER EXISTING CONDITION AFFECTED BY THIS PROJECT. UPON COMPLETION, RE -PAINT ALL AFFECTED SURFACES MATCHING SURROUNDING COLOR. W V1 O O TOT� V1 SALTZ MICHELSON, A R C H I T E C T S 3501 Griffin Road Ft. Lauderdale, FL 33312 (954) 266 -2700 Fx: (954) 266 -2701 sma @saltzmichelson.com AA- 0002897 PROJ. No. 22046 CA 924 LOUIS J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS 9150 SOUTH DADELAND BLVD. STE 900 MIAMI, FLORIDA 33156 TELEPHONE: (305) 670 -0141 FAX: (305) 670 -0144 WWW.LJAAPA.COM V N ;s x 0 0 E E 61 0 d g Project No.: 2011 -117 Drawn By: AP Checked By: AG Date: 01 -21 -13 Revisions E0.0 ;-� ;,. W .w� .%i ►- Mario D. Pazos PE52078 V N ;s x 0 0 E E 61 0 d g Project No.: 2011 -117 Drawn By: AP Checked By: AG Date: 01 -21 -13 Revisions E0.0