11-1104-013PLUMBING NEW CONSTRUCTION NOTES PLUMBING INSTALLATION OF ALL FIXTURE5, EQUIPMENT, AND PIPING SHOWN ON THESE DRAWINGS SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE STATE, LOCAL AND HEALTH CODES REQUIREMENTS. 2. CONTRACTOR SHALL FIELD VERIFY ELEVATIONS, SIZES AND LOCATIONS OF EXISTING PLUMBING PRIOR TO BIDDING. IF DISCREPANCIES ARE FOUND, THEY ARE TO NOTIFY ARCHITECT 3, ALL PLUMBING FIXTURES TO COMPLY WITH TABLE 604.3 OF THE FLORIDA BUILDING CODE - 2001 4. CONTRACTOR SHALL OOORDINATE EQUIPMENT CONNECTIONS 4 MOUNTING HEIGHTS WITH EQUIPMENT AND ARCHITECTURAL DRAWIN69 AND SUPPLIER. INSTALL EQUIPMENT AND MAKE FINAL CONNECTION5 FURNISHING CUTOFF VALVES, P- TRAPS, FITTIN65,P.R.V.5, AND PIPING AS REQUIRED. 5. CALLEDOR MATERIALS � EQUIPMENT, RRETU5ED OR FURNISHED BY BY OTHERS. EXCEPT THAT 6. PROVIDE 12 "XI2" ACCE55 PANELS FOR ALL VALVES LOCATED ABOVE HARD CEILINGS. INSTALL VALVES 50 AS TO BE WITHIN REACH OF ACCE55 DOOR. -7. CONTRACTOR SHALL PROVIDE ROUGH -IN5 AND MAKE FINAL CONNECTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING PLUMBING CONNECTION, INCLUDING TAILPIECE5, TRAPS, LINE STRAINERS, STOP VALVES, 6AU6E5, VACUUM BREAKERS, REDUCING VALVES, SPECIAL FITTINGS, INSULATION, AND ALL NEC DEVICES FOR A COMPLETE AND OPERATIVE SYSTEM. COORDINATE EXACT REQUIRED PLUMBING ROUGH -IN5 WITH VENDOR SUPPLIER DRAWINGS. 8. THE CONTRACTOR SHALL INSTALL PLUMBING PIPING IN LOCATIONS INDICATED ON THE CONTRACT DOCUMENT5. THE ONLY DEVIATION FROM TH15 WOULD BE IF ADDITIONAL OFFSETS ARE REQUIRED TO COORDINATE WITH OTHER TRADE5. q, REPAIR/REPLACE EXI5TINC VALVES WHICH DO NOT HOLD WHEREVER NEW PIPING 15 CONNECTED TO EXI5TIN6 PIPING, AND THE EXISTING VALVES ARE TO BE REUSED. 10. SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS IN ACCORDANCE WITH U.L. FIRE RE515TANCE INDEX FOR THROUGH PENETRATION FIRE STOP 5Y5TEM5. COORDINATE REQUIREMENTS WITH ARCHITECTURAL PLANS AND SPECS. 11. CONTRACTOR SHALL FURNI5H AND INSTALL SHOCK ABSORBER5 ON ALL LINES 5ERVIN6 QUICK 61-051% VALVES AND AS INDICATED ON PLUMBING PLANS AND RECOMMENDED BY THE MANUFACTURER. 12. CLEANOUT COVER5 SHALL NOT BE INSTALLED ON THE CORRIDOR SIDE OF ANY WALL. IF 015CREPENCIE5 ARE FOUND ON PLANS CONTRACTOR SHALL NOTIFY PLUMBING ENGINEER PRIOR TO INSTALLATION. 13. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS. 14. ALL EXP05ED PIPE AND FITTINGS IN FIN15HED AREAS SHALL BE CHROME PLATED. 15. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGES TO EXI5TIN6 PIPING AND FIXTURES DUE TO CONSTRUCTION AND SHALL RESTORE EXISTING WORK DISTURBED TO ITS ORIGINAL CONDITION AT NO 005T TO THE OWNER. I6. COORDINATE INSTALLATION OF PLUMBING SYSTEMS WITH ALL CASEWORK. CONTRACTOR SHALL OBTAIN ARCHITECTURAL DRAWINGS AND REVIEW PRIOR TO INSTALLATION. CHANCES IN THE DIRECTION OF SANITARY PIPING SHALL NOT BE MADE WITH FITTIN65 WHICH WILL CAU5E EXCE551VE REDUCTION IN THE VELOCITY OF FLOW OR CREATE ANY OTHER ADVERSE EFFECT UNLE55 PHYSICALLY IMP055113LE (IE: USE OF SANITARY TEE IN A HORIZONTAL CONNECTION, USE OF A DOUBLE SANITARY TEE IN A VERTICAL STACK, IN GENERAL, U5E OF SHORT - RADIUS FITTING FOR BRANCH TO HOUSE DRAIN OR STACK CONNECTION). 18. THIS CONTRACTOR SHALL BASE HIS PROPOSAL UPON THE EQUIPMENT AS SCHEDULED OR SPECIFIED, U51NC THE MANUFACTURER5 AND MODEL NUMBER AS CALLED FOR IN THE 5PECIFICATION5 AND SCHEDULED ON THE DRAWING5. IF MORE THAN ONE MANUFACTURER OF EQUIPMENT 15 SPECIFIED, ANY ONE OF THE MANUFACTURER5 OF EQUIPMENT MAY BE USED IN TH15 CONTRACTOR'S PROPOSAL. Iq. THE CONTRACTOR 15 EXPECTED TO ORDER ALL MATERIALS IN SUFFICIENT TIME TO AVOID DELAYING THE COMPLETION OF THE PROJECT. DELAY IN DELIVERIES WILL NOT BE CON51DERED A JUSTIFIABLE REA50N FOR 5UBM15510N OF SUBSTITUTE MATERIALS. 20• THE PLUMBING CONTRACTOR SHALL KEEP A SET OF MARKED UP DRAWINGS A5 THE JOB PROGRESSES. NO MAJOR CHAN6E SHALL BE MADE TO PLUMBING DE51614 ENGINEERING UNLESS IT HA5 BEEN COORDINATED, DRAWN AND SUBMITTED FOR APPROVAL. 21. CONTRACTOR 15 RESPONSIBLE FOR RELOCATING ALL EXI5TI% SANITARY, STORM, CONDENSATE, MEDICAL GAS AND WATER PIPING TO FACILITATE THE INSTALLATION OF NEW ELECTRICAL, MECHANICAL AND FIRE PROTECTION 5Y5TEM5 AND VENDOR EQUIPMENT. THIS INCLUDES ALL CEILING SPACES, 5HAFT5, WALLS, ETC. 22. CONTRACTOR SHALL COORDINATE WITH ALL 0156IPLINE5 INVOLVED AND EXISTING CONDITIONS ABOVE CEILINGS 50 AS TO AVOID ANY PIPE ROUTING PROBLEM5. PROVIDE OFF5ET5 AND FITTIN65 AS REQUIRED. 23. WARRANTY /GUARANTEE A. THE CONTRACTOR SHALL WARRANTY /60ARANTEE AND MAINTAIN THE STABILITY OF WORK AND MATERIALS AND KEEP SAME IN PERFECT REPAIR AND CONDITION FOR THE PERIOD OF ONE YEAR. B. DEFECTS OF ANY KIND DUE TO FAULTY WORK OR MATERIALS, APPEARING DURING THE ABOVE MENTIONED PERIOD, MUST BE IMMEDIATELY REPAIRED BY THE CONTRACTOR AT H15 OWN EXPENSE TO THE ENTIRE SAT15FACTION OF THE OWNER AND ARCHITECT. SUCH RECONSTRUCTION AND REPAIRS SHALL INCLUDE DAMA6E TO THE FIN15H OR FURNISHING OF THE BUILDING RESULTING FROM THE ORI6INAL DEFECT OR REPAIR THERETO. 24. PIPING SHALL NOT BE RUN OVER ANY ELECTRICAL AND PHONE PANEL5. 25• 5ERVICE5 TO BE REMOVED SHALL BE CAPPED AND PLUGGED, WHERE INDICATED ON DRAWING. 26. CONTINUITY OF SERVICE: INTERRUPTIONS OF EXISTING SERVICES OR FA ILITIE5 SHALL BE KEPT TO A MINIMUM AND THE CONTRACTOR SHALL FURNI5H ALL MATERIALS AND LABOR REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE NECE55ARY TO MAINTAIN CONTINUITY OF SERVICE. INTERRUPTION5 OF THE EXI5TI% SERVICES, THE INSTALLATION OF TEMPORARY FACILITIES, AND THE WORK OF MAKING FINAL CONNECTIONS TO NEW WORK SHALL BE DONE ONLY AT SUCH TIMES AS PERMITTED AND SCHEDULED BY THE OWNER. ALL 5" CONNECTIONS AND TIE -IN5 SHALL BE COORDINATED THROUGH THE OWNERS PROJECT MANAGER. I. THE DURATION OF EACH 5HUTOOWN SHALL BE LIMITED TO N16HT5 AND /OR WEEKENDS WITH THE TIME FRAME FOR 5HUTDOWN5 AS SPECIFIED BY THE OWNER. THE CONTRACTOR SHALL NOTIFY THE OWNER IN WRITING FORTY -EIGHT (45) HOURS IN ADVANCE OF EACH REQUIRED INTERRUPTION OF EXISTING SERVICE. 2. THE CONTRACTOR SHALL INCLUDE IN BID PRICE ALL PREMIUM TIME CHARGES FOR LABOR AND EQUIPMENT REQUIRED FOR ALL NIGHT AND WEEKEND OVERTIME WORK, AS NECESSARY, TO COMPLETE THE SCOPE OF THE CONTRACT. 3l. ALL FLOOR DRAINS AND FLOOR SINKS SHALL HAVE 0' COLD WATER RESEAL. INFECTION CONTROL MEASURES 1. CONTRACTOR SHALL OBTAIN FROM THE OWNER A COPY OF THE INFECTION CONTROL R15K ASSESSMENT (10" PREPARED FOR TH15 PROJECT. CONTRACTOR SHALL REVIEW THE REQUIREMENTS IN THE REPORT AND PERFORM ALL WORK IN ACCORDANCE WITH TH05E REQUIREMENTS. CONTRACTOR SHALL 5TRICTLY ADHERE TO THE LIMITS OF THE CONSTRUCTION AREA, AND WHERE PHASING APPLIES SHALL ADHERE TO THE PHASING PLAN. ANY WORK OUT5IDE THE CON5TRUCTION AREA SHALL BE COORDINATED WITH THE OWNER AND PERFORMED IN ACCORDANCE WITH THE ICRA REPORT, UNDER THE SUPERVISION OF THE OWNERS REPRESENTATIVE OR OTHER DESIGNATED ICRA COMMITTEE OFFICER. 2.TO THE EXTENT THAT IT 15 REQUIRED BY THE ICRA, THE CONTRACTOR SHALL ENDEAVOR TO MAINTAIN EXI5TIN6 LEVELS OF INDOOR AIR QUALITY IN AREAS 5URROUNDING AND ADJACENT TO THE CON5TRUCTION WORK ZONE, AND ELSEWHERE IN THE FACILITY. IT 5HOULD BE ANTICIPATED THAT THE ICRA REPORT WILL REQUIRE MEASURES TO THIS EFFECT INCLUDING ERECTION OF CONSTRUCTION ZONE BARRIERS AND PROVISION OF NEGATIVE AIR PRE99JRE IN THE CONSTRUCTION ZONE RELATIVE TO OTHER AREAS OF THE FACILITY. 3.IN ADDITION TO THE MEETING THE REQUIREMENTS OF THE ICRA REPORT, THE CONTRACTOR AT A MINIMUM SHALL PROVIDE EQUIPMENTAND COMPONENTS NECE55ARY TO CREATE A NEGATIVE PRESSURE IN THE CONSTRUCTION WORK ZONE RELATIVE TO ADJACENT AREA. EXISTING HVAG 5Y5TEM5 AND COMPONENTS SHALL NOT BE U5ED FOR TH15 FUNCTION, UNLE55 SPECIFICALLY APPROVED BY THE OWNER'S INFECTION CONTROL OFFICER. THE CONCEPT AND ALL ASPECTS OF THIS WORK SHALL BE DONE IN ACCORDANCE WITH THE ICRA REQUIREMENTS AND AT A MINIMUM AS FOLLOWS: VERIFY ALL EXI5TIN6 PLUMBING WHICH PASSES, THROUGH THE CONSTRUCTION ZONE, AND 15 TO REMAIN, 15 SEALED AND PROTECTED DURING THE CON5TRUCTION DURATION. AIR REMOVED FROM THE CON5TXTION ZONE SHALL BE FILTERED AND /OR DISCHARGED AS DIRECTED BY THE ICRA REPORT. PRESENT THE NEGATIVE AIR PRE55URE PLAN TO THE OWNER FOR APPROVAL BY THE INFECTION CONTROL COMMITTEE. PROVIDE MEANS TO MONITOR AND VERIFY NEGATIVE PRESSURE 15 BEIN6 MAINTAINED IN ACCORDANCE WITH THE ICRA REPORT, AND PROVIDE DOCUMENTATION TO THE OWNER AS REQUIRED. 4.000RDINATE IN ADVANCE ANY REQUIRED EQUIPMENT SHUTDOWN WITH THE OWNER, AND VERIFY BEFORE SHUTDOWN THAT EXISTING OR DESIRED AIR PRESSURE RELATION5HIP5 WILL NOT BE ADVERSALY AFFECTED. I I II I I I II \ I I I II \ I I I I I ' I! I ' I ' li I ' II I ' I ' I ' I ' II I ' J \ 1 I I ' I J � FF_, I I II li �i II li li Ii I I JI ,I I I li II it II I I 11 I I II I I I I II 1 1 I - I I I J NEW FD y I I v I I I I I I I I I I I I I I LJ__ I I \ I t � I I ` I I \ I I 1 i 4" i i I I I' ---------- JL ------------- ---- - - - - -- - - -- - - - - - -- L_ _ l _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ -- - -�_`` EXI ITNG I EXISITN�1� FD -1 FD -I EX \\ I 1 EX r � I I I I I I it I I I , I , I I L -� I I I I I J I I , EX151M FO -1 ! EX ! 015HWA5HING AREA NEW FD -3 I 4' I 1 ! L - - - -- ' I I ' :DI0 I I EXI51TN6 I C FD -2 4 ' EX ' ti I J , JI J I f 1 , I I I , I I , 1 ' , I I I I � , I ' I I I I , I � , I ' ; I I I i I ' I ! I 1 I I I I I I I ' r' I 1 ' , , I I I I e I I I ' I I I I r ' , I I I 1 I I ' I I ' , 1 I 1 I I 1 I I ' , I 1 I I i I , I ' i I I I I 1 I , I I , , I I , I ' I I I II L - - - - I rL I I J I I I I I PARTIAL FLOOR FLAN - NEW WORK N PLUMBING - DISHWASHING AREA A5.1 SCALE: 1 /8' = 1' -0' 4" 411 FD -1 411 EXI5TIN6 F19-2 EX15TINC 4'� FN FO-3 411 EXISTING NEW C � 4" 411 \\. FD -1 EXI5TIN6 (f Gyv \ 4n NEW 411 \� FD -2 4�� FO -3 EXI5TIN6 NEW SANITARY WASTE ISOMETRIC RISER SCALE: N.T.S. PLUMBING LEGEND TYPE DESCRIPTION WASTE EXISITNC GREASE WASTE NNDERCROUNO) NEW CONSTRUCTION -------- - - - - -- EXISTING TO REMAIN MANUFACTURER CONNECTION TO EXI5TIN6 AT TH15 POINT PLUMBING DEMOLITION NOTES I. EXISTING FIXTURE, EQUIPMENT, SERVICE, AND CONNECTIONS TO REMAIN AS 15 WHICH ARE DAMAGED DURING CON5TRUGTION SHALL BE REWORK OR REPLACED AS REQUIRED TO PROVIDE ORIGINAL OPERATION. 2. CONTRACTOR SHALL COORDINATE INTERRUPTION OF EXISTING SERVICE WITH OWNER BEFORE CONSTRUCTION. 3. REPAIR/REPLACE EXISTING VALVES WHICH DO NOT HOLD WHEREVER NEW PIPING 15 CONNECTED TO EXISTING PIPING, AND THE EXISTING VALVES ARE TO BE REUSED. PLUMBING GENERAL NOTES I. ALL EX15TIN6 WORK NOT SHOWN ON TH15 DRAWINGS (UNLESS NOTED OTHERWISE) SHALL REMAIN AS 15 2. THE CONTRACTOR SHALL KEEP A SET OF MARKED UP DRAWINGS AS THE JOB PROGRE%E5. NO MAJOR CHANGE SHALL BE MADE TO PLUMBING DE516N UNLE55 IT HA5 BEEN COORDINATE DRAWN. AND SUBMITTED FOR APPROVAL TO THE ARCHITECT. 3. CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINES INVOLVED 50 AS TO AVOID ANY PIPE ROUTIN6 PROBLEMS. PLUMBING SCHEDULE SYMBOL WASTE REMARK MANUFACTURER MODEL TYPE FO -1 ZURN CRATE NICKEL 4' WITH ZID23 EXISTING FLOOR DRAIN BRONZE BRONZE TOP TRAP PRIMER FD -2 ZURN �ZI910 -P FULL 6RATE 4' WITH ZI023 EXISTING FLOOR DRAIN NICKELBRONZE TOP TRAP PRIMER 170-3 ZURN ZI910 -P FULL GRATE 4' WITH ZI023 NEW FLOOR DRAIN NICKELBRONZE TOP TRAP PRIMER , > - \\ i L� /_ -\�J Rp I -A*pML �rn _ _ _ _ _ _ _ -ial�li5 �c�ii7 �11a1 I��1 7 \ ll� II II ❑ r ', �, T Y \ L.JI - - - -- `��\ Ir I -�� II IIt II II -- - -- - -- LJ�� - -/� r.l 1�JI LIII �4 VIII i..a II II I I li x i A5.1 II I 1 f� 71.111 _ 1 7. 'Q \ I +•_ 1--1 LIC- -_- -_]I I 1 r ' "Fir I ---"'I _ _ _ _ _ . •'_' `-ill �� 1 - II r• +._ � 1 II `JII Ill LL __T -- �, , �. -�_ _ _ _ _ _ _ -,1 1 Its • I.1- u ii II I� 1L 1 ' , • I III 1 II II ll \1 1 I n I IL ,I `"_Vm ,! II II I =�L, 1 II•, I I Ilr 1 ? II I I I III '-•F.• II II Y I 1 I![]I ; III 1 '`-7 Ii_ I II I I,I 1 Ir I 1�1 1 II I • 1 III I L _------ -- - " - -- III rr - y i 1 •11 1 1 II + I I II 1 1 II 'I h I I 1 Y I 1 ❑ L � fr 1 I II I� II ;I �� i • r -- - - - - -- 1 1 ------ - - - - -- •I L I u 1 I II J III 1 IL - - - - - •r-' r -'+ r - - -� r - - - -� I I JAI `� I I I I I • I,r 1 it _FF -111T 1 it 1 - -1 � �, • F �, �srdJ , -' I M • II IIII II 1 r J+ II 1G1 III qII II'' a ..�r.�Fllr�r\ �r..�q II II 3 KEY PLAN A5.1 SCALE: 1/16" = 1' -0" SALTS MICHELSON A R C H I T E C T S 3501 Griffin Road Ft. Lauderdale, FL 33312 (954) 266 -2700 Fx: (954) 266 -2701 sma @saltzmichelson.com AA- 0002897 4w 1 Charles Michelson AR0009976 a T F A .4 Project No.: 2011 -117 Drawn By: By: J1V Checked By: LS Date: 06 -30 -11 Revisions I Mel I