10-820-008r.
r
•
r
+i
C+
•
,
♦,
VA-1
a
DIVISION 16 - ELECTRICAL
SECTION 16010 - GENERAL ELECTRICAL PROVISIONS
A. General
1. Transportation, insurance, temporary protection, supervision
and incidental items essential for proper installation and
operation, though not speolfioally mentioned or indicated but which
are usually provided or are essential far proper installation and
operation of all systems related to this Section, as specified
herein.
3. AD conduits, wireways or other electrical raceways passing
through fire partitions. fire walls or floors shall have a fire
stop installed providing on effective barrier against the spread of
fire. smoke and gases. maintaining the required fire rating.
B. Codes and Regulations
INSTALLATION SHALL CONFORM TO THE FOLLOWING CODES AND REGULATIONS.
FLORIDA BUILDING CODE - 2007 WITH 2009 SUPPLEMENTS
NFPA -70: NATIONAL ELECTRIC CODE - 2008 EDITION
NFPA -72: NATIONAL FIRE ALARM CODE - 2002 EDITION
NFPA 99: HEALTH CARE FACILITIES - 2005 EDITION
NFPA iOi: LIFE SAFETY CODE - 2006 EDITION
AIA GUIDELINES - 2006 EDITION
APPLICABLE LOCAL CODES
2. In these specifications, references made to the following
Industry Standards and Code Bodies are intended to indicate the
latest volume or publication of the Standard. All equipment,
materials and details of installation shall comply with the
requirements and latest revisions of the following Bodies, cs
applicable:
ANSI American Notional Standards Institute
ASTM American Society of Testing Materials
AWG American Wire Gouge
FM Factory Mutual
NEMA National Electrical Manufacturers Association
UL Underwriters' Laboratories
NETA National Electrical Testing Association
IEEE Institute of Electrical and Electronic Engineers
3. AD materials and workmanship shall comply with all applicable
Codes. Specifications. Local and State Ordinances. Industry
Standards and Utility Company Regulations. latest Editions.
C. Scope of Work
1. Cooperate with all trades to assure the steady progress of all
work under the contract, as well as providing temporary power at
project site for all others.
2. It shall be the responsibility of the contractor to study all
drawings and details so that the installation of all new work can
be fully coordinated. The contractor shall visit the site to
satisfy himself that all provislons have been made for all ospects
of this project.1f discrepancies exist between drawings and /or
site conditions, the contractor shall notify the general contractor
in writing prior to signing of the contract for consideration and
decision before proceeding. Failure to do so will not be allowed
as a basis for additional compensation to correct a difficulty of
difference from conditions inferred or indicated on the drawings.
3. Prepare and submit shop drawings of pertinent electrical
equipment, devices. etc., as are indicated in the scope of work,
and record for ailwork provided under this contract to the
architect /engineer's review. Provide seven (7) copies of all
submittals as noted hereinafter.
4. The contractor, for the work in his scope of work. shall give
all necessary notices. obtain all permits. Pay all governmental
taxes, fees, inspections, and other costs In connection with his
work; file for neobasary approvals with the jurisdiction under
which the work is to be performed. Electrical contractor shall
obtain all required certificates of inspection for hie respective
work and deliver same to the general contractor before request for
acceptance of his portion of work Is mode and before final payment.
5. Cut all openings, chases and patching required to accommodate
the work under this division. seal with acoustlocl oaulk and /or
blowout patch. cnd repair all floore, walls, eta., damaged by such
cuttings. All work done under this heading must conform in every
respect to finish and quality of materials and workmanship
specified under cppropriate sections for the building. All
cutting. core drilling, eto. required for the installation of the
electrical equipment shcq be by the contractor. Approved by the
owner.
6. Verify equipment sizes. voltage and current characteristics,
etc. before the ordering of any equipment and before roughing -In
for equipment to be supplied by others. and provide ready
accessibility of system required to be reached for maintenance and
operations.
T. Check other sections of the specifications for equipment to be
connected under this contract.
8. The electrical contractor shall make all requests for systems
shut downs to the owner 72 hours In advance and shaiirestore all
systems to normal operation by 3 :30 pm every work day.
9. The entire area shollbe brought up to meet code requirements
including existing conditions.
It ... .. .. .: Is
SECTION 16110 - RACEWAYS
A. Raceways shallbe as follows:
1. Raceways for feeders and branch circuits ._
metal conduit. Intermediate metal conduit electrical
metallic National
Code. Electrical used In
concrete construction or where subjected to mechanical damage.
metal 2. Flexible be used only for connection to motors,
pumps. cir handling units and ..
conductor type. with on Interwoven ground conductor. Separate ground
shall be Installed In all flexible conduit sizes.
Flexible conduit non-watarproof type can be used for connecting to
lighting fixtures only. Maximum length of all flexible conduit
allowed shall be 51-0s.
Expansion 3. , .
building expansion joints, weatherproof
couplings expansion f Itting shall permit a minimum movement of 4'.
4. Set screw type conneotors and will not be allowed
except for Emt type conduit. Emt fittings shall be anal cBO.4 steel
type. type. Insulated throat, gIcnd compression type or set screw clamps, etc. And
Diecost fittings are not acceptable.
5. Raceways shall not be allowed In any concrete floor slobs.
6. All emergency system wiring shall be Installed In non-flexTble
7. labor ♦ properly ..
under this contract In accord with noo.Provide minimum of IT
separation between allcondults racked together.
8. Conduit and boxes In calling spaces sholibe supported
9. Provide nylon pullstrings In allempty conduits.
r Conduit and tubing shcllbe manufactured
Wheatland, followings Wheatland, Republic Steel Corp., Allied Tube & Conduit Co.,
or Triangle
11. Flexible conduit shallbe manufactured by one of the
followings ♦:
SECTION • - CONDUCTOR
Branch B. Branch Circuits
1. •• :.
coding. with THWN or THHN Insulation with continuous color
Phases 2. Provide color coded cable system approved by Owner.If none Is
required by Owner,provTde the following color coding:
c. 480/277V
(1) A Phase: Brown
Orange
(3) C Phas
(4) Neutrals Grey
Grounds
Color Notes .. ,
smaller AWG or color ..
larger connections for conductors
3. Minimum size wire for branch circuit and power wiring shall be 012
AWG, for remote control signal circuit and Interlock wiring can be
•14 AWG. For 20A branch circuit runs exceeding 100' -O' In length
from the ponelboard to the first outlet, the entire branch circuit
run shall be •10 AWG or larger. For runs over 175' -0' to the first
outlet, use •8 AWG or larger for the entire branch circuit run,
4. Branch circuit and feeder conductors shall be manufactured by one
of the following: Carol Cable, OkonTte, Pirelli or Rome Cable
Corp.
5. All wire and cable shall be cnnealed, coated copper per astm
b 33 or b 189 with conductivity of not less than 98 percent. All
wire shall be stranded, unless size 8 or smaller. class b per astm
b8.
6. All wire shall have 600 volt Insulation, ul listed and
complying with UL 83, Toso s -61 -402 or Toec s -66 -524 for respective
insulation type and shell be color coded.
16130 - BOXES
A. Boxes shc1l be as follows:
I. Galvanized steel outlet boxes conforming to UL Standard
No. 514 will be used for concealed outlets.
2. Exposed outlet boxes shall be cost -metal conduit type FS or FD
with threaded hubs.
3. Pull and junction boxes shall conform to UL Standard 50,
constructed of code gauge galvanized steel and be sized per the
requirements of the National Electric Code.
4. Provide pull and junction boxes as required.
5. All junction and pull boxes for emergency systems and low
voltage systems shall have cover plates pointed. Colors for covers
shall be as Indicated below:
Life safety branch yellow
Critical branch orange
Equipment branch green
Fire claret red
Datc /telephone system brown
SECTION 16170 - CIRCUIT AND MOTOR DISCONNECTS
A. Disconnect switches shop be as follows:
1. Furnish and Install disconnect switches for disconnecting
means for all equipment. Disconnect switches shall be of the Type
'A', quick -make, quick -break construotion. DTsconnect switches
shod have interlocking doors. Cabinets shall be bonderized and
finished in gray enamel. NEMA Type 3R enclosures shall be used
where the disconnect switch Is exposed to the weather or in wet
areas. Provide two normally open and two normally closed auxiliary
contacts for disconnect switches used to serve flan system motors
Including supply fans. return fans. exhaust fans, make -up air fans
and relief air fans for electrical Interlock with mechanical controls.
2. Disconnect devices shall be one of the following
manufacturers: Square D, General Electric or Westinghouse.
3. All equipment shop be provided with the proper size /rating
disconnect switch whether indicated on the drawings or not to
comply with NEC. Also, install and connect disconnect switches
furnished by other Trades.
16190 - SUPPORTS
A. Provide supports as follows:
1. Ali supports required to properly support cil equipment.
devices, raceways. etc. to be installed under this contract.
2. Provide supports as required by the NEC.
16195 - IDENTIFICATION
A. Equipment identiflociton
1. Provide engraved laminated phenolic nameplates to identify
panelboards disconnects and allmajor equipment.
2. Nameplates shall include the panel and circuit designation and
shcq be laminated, bakelite with I /4' high, recessed letters.
Nameplates shell bs securely attached to the equipment with
galvanized screws. Adhesives or cements shop not be used.
3. Nameplate for equipment on normal power shall be black In
color with white recessed letters.
4. Nameplates for devices on emergency power color shall be in
accordance with section 16130 with white recessed letters.
5. Furnishing and installing permanent Identification markers for
all electrical equipment and raceways installed under this
contract.
6. Nameplates shall include the following information:
a. Equipment Identification: Service voltage- phase -wire,
branch of power connected to.cnd source of
power the equipment is fed from.
T. All panelboards shall be provided with new written
directories. All directories shall Indicate loads served as well
as breaker ratings and pole space requirements for each load. This
requirement applies to all new or revised panelboards. Provide
copy of cq directories to engineer of record.
8. The contractors shall be responsible for tracing out
existing branch circuits and updating penal directories as required
to Insure proper directory listings.
B. Conduit Identification
1. Provide manufacturer's standard pre - printed, flexible or
semi - rigid, permanent, plastic -sheet conduit markers, extending 360
degrees around conduits; designed for attachment to conduit by
adhesive, adhesive lap joint of mcrker. matching adhesive plastic
tape at each end of morker,cr pretensloned snap -on. Except as
otherwise Indioated, provide lettering which indicates voltage of
conductors) in conduit. Provide minimum 8 Inch length for 2 inch
and smaller conduit.12 Inch length for larger conduit.
2. Paint conduits for emergency systems and low voltage systems
in accord with table I of this section. Spacing of paint markings
shell be 10' -O' on centers for entire length of conduit.
:a��rrrar,rr_>� rtrr
1. Colored tape shall be polyvinyl chloride. self - adhesive not
lose than 3 mile thick and 11/2 inch wide, sultable for use on
90 degree C conductors. ul Ilsted and shall be furnished in colors
as specified herein.
SECTION 16198 TESTING
A. Aq low voltage 600V equipment, cable, motors, dry type
transformers. etc. shall be field tested per NETA Standards.
! � II�?:Z•117 1r11,
A. A complete equipment grounding system shall be provided such
that all metallic structures, enclosures, raceways, junction boxes,
outlet boxes, cabinets, machine frames, metal fences, and c1l other
conductive Items operate continuously at ground potential cnd
provide a low impedance path to ground for possible fault currents.
B. A separate insulated green grounding conductor shall be
provided for each single and 3 -phase feeder and branch circuit•
Grounding conductor shall be run with the related phase and neutral
conductors. Panel feeders Installed In more than (1) raceway shall
have individual, full sized, green grounding conductor in each
raceway. The equipment grounding system shall not rely on the
metallic raceways for grounding continuity.
EF -2
(ON ROOF)
N OF THE - ROOF. AREA IS
# # "i i T •.•
PROTEC-ED F_ROM SYSTEMS
ION HIGHER ADJACENT wit
3P,3OA,WP
3*12,1 *12G. IN3 /4C.
1MCCE -7
r
PoA*
JA
MAI
MAIN CIRCUIT BREAKER
iDESCRIPTION
All
NATIONAL ELECTRIC CODE
�.
ABOVE COUNTER
OVER CURRENT
ABOVE FINISHED CEILING
OVER CURRENT PROTECTION
=11111;161111
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
SPECIAL MOUNTING HEIGHT
s
A0 444
CIRCUIT BREAKER
UNIT HEATER
0
UNDER GROUND ELECTRICAL
UNLESS OTHERWISE NOTED
r
CO
CENTER LINE
WATT(S), WIRE, WALL TELEPHONE OUTLET
CEILING MOUNTED DEVICE
WEATHERPROOF DEVICE, NEMA 3R
t�
nr�r-
�
�,
r
FIRE ALARM
EF -2
(ON ROOF)
N OF THE - ROOF. AREA IS
# # "i i T •.•
PROTEC-ED F_ROM SYSTEMS
ION HIGHER ADJACENT wit
3P,3OA,WP
3*12,1 *12G. IN3 /4C.
1MCCE -7
r
PoA*
JA
EXISTING MOTOR
HORSE POWER
CONTROL CENTER
1 MCCE�
................ .. - - - -- -
LEGEND
MOUNTING
_
DESCRIPTION
HEIGHT
q= NON- FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES)
FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES)
qED COMBINATION MOTOR STARTER
® FACTORY WIRED CONTROLLER OR EQUIPMENT
MOTOR CONNECTION
Q JUNCTION BOX
s PANELBOARD - FLUSH MOUNTED
® PANELBOARD - SURFACE MOUNTED
VFD VARIABLE FREQUENCY DRIVE
CONCEALED CONDUIT
CONDUIT CONCEALED IN FLOOR OR BELOW GRADE
HOMERUN TO PANELBOARD - NUMBER OF CIRCUITS IN MINIMUM 3/4 CONDUIT
UNLESS NOTED OTHERWISE
NOTES:
1. ONE NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR, ALTHOUGH NOT
INDICATED, SHALL BE INCLUDED IN EACH RACEWAY UNLESS OTHERWISE NOTED.
2. ONE INSULATED GREEN GROUNDING CONDUCTOR, ALTHOUGH NOT INDICATED, SHALL
BE INCLUDED IN EACH RACEWAY UNLESS OTHERWISE NOTED.
3. HOMERUNS TO PANELBOARDS SHALL HAVE A MAXIMUM OF THREE (3) PHASE
CONDUCTORS (ONE PER PHASE) PLUS THREE (3) NEUTRAL CONDUCTORS AND
ONE (1) GROUND CONDUCTOR IN EACH CONDUIT.
4. MULTI -WIRE BRANCH CIRCUITS THAT SHARE A COMMON NEUTRAL SHALL NOT BE
PERMITTED FOR INDIVIDUAL LiNE -TO- NEUTRAL LOADS.
5. EACH CIRCUIT (PHASE AND NEUTRAL CONDUCTORS) SHALL BE GROUPED TOGETHER
USING CABLE TIES AT THE PANELBOARD AND ALL JUNCTION BOXES, PULL BOXES &
ALL OTHER LOCATIONS WHERE TERMINATIONS, CONNECTIONS OR SPLICES ARE MADE.
6. ALL CONDUCTORS SHALL BE *12 AWG UNLESS OTHERWISE NOTED.
MAI
MAIN CIRCUIT BREAKER
iDESCRIPTION
MAIN LUGS ONLY
NATIONAL ELECTRIC CODE
�.
ABOVE COUNTER
OVER CURRENT
EXISTING MOTOR
HORSE POWER
CONTROL CENTER
1 MCCE�
................ .. - - - -- -
LEGEND
MOUNTING
_
DESCRIPTION
HEIGHT
q= NON- FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES)
FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES)
qED COMBINATION MOTOR STARTER
® FACTORY WIRED CONTROLLER OR EQUIPMENT
MOTOR CONNECTION
Q JUNCTION BOX
s PANELBOARD - FLUSH MOUNTED
® PANELBOARD - SURFACE MOUNTED
VFD VARIABLE FREQUENCY DRIVE
CONCEALED CONDUIT
CONDUIT CONCEALED IN FLOOR OR BELOW GRADE
HOMERUN TO PANELBOARD - NUMBER OF CIRCUITS IN MINIMUM 3/4 CONDUIT
UNLESS NOTED OTHERWISE
NOTES:
1. ONE NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR, ALTHOUGH NOT
INDICATED, SHALL BE INCLUDED IN EACH RACEWAY UNLESS OTHERWISE NOTED.
2. ONE INSULATED GREEN GROUNDING CONDUCTOR, ALTHOUGH NOT INDICATED, SHALL
BE INCLUDED IN EACH RACEWAY UNLESS OTHERWISE NOTED.
3. HOMERUNS TO PANELBOARDS SHALL HAVE A MAXIMUM OF THREE (3) PHASE
CONDUCTORS (ONE PER PHASE) PLUS THREE (3) NEUTRAL CONDUCTORS AND
ONE (1) GROUND CONDUCTOR IN EACH CONDUIT.
4. MULTI -WIRE BRANCH CIRCUITS THAT SHARE A COMMON NEUTRAL SHALL NOT BE
PERMITTED FOR INDIVIDUAL LiNE -TO- NEUTRAL LOADS.
5. EACH CIRCUIT (PHASE AND NEUTRAL CONDUCTORS) SHALL BE GROUPED TOGETHER
USING CABLE TIES AT THE PANELBOARD AND ALL JUNCTION BOXES, PULL BOXES &
ALL OTHER LOCATIONS WHERE TERMINATIONS, CONNECTIONS OR SPLICES ARE MADE.
6. ALL CONDUCTORS SHALL BE *12 AWG UNLESS OTHERWISE NOTED.
DRAWING INDEX
MAI
MAIN CIRCUIT BREAKER
iDESCRIPTION
MAIN LUGS ONLY
NATIONAL ELECTRIC CODE
ABOVE COUNTER
OVER CURRENT
ABOVE FINISHED CEILING
OVER CURRENT PROTECTION
=11111;161111
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
SPECIAL MOUNTING HEIGHT
TELEVISION
A0 444
CIRCUIT BREAKER
UNIT HEATER
0
UNDER GROUND ELECTRICAL
UNLESS OTHERWISE NOTED
r
CO
CENTER LINE
WATT(S), WIRE, WALL TELEPHONE OUTLET
CEILING MOUNTED DEVICE
WEATHERPROOF DEVICE, NEMA 3R
DISCONNEC
EXISTING
FIRE ALARM
FURNISHED BY OTHERS
s�
DRAWING INDEX
�M KEY PLAN
N.T.S.
�I -
•
600 West _Hills�_,=n, Suite 300
ri - r Be&ch, 71- 33441
9S4� 4:2-11-1260
FAX: (954) 421-1466
Firm Certification - r
: :::
John E. Moulder PE - FC
Michael A. Steward PE - 65701
SSR JOB # 1032079.0
MAI
MAIN CIRCUIT BREAKER
M!
MAIN LUGS ONLY
NATIONAL ELECTRIC CODE
OVER CURRENT
-w
OVER CURRENT PROTECTION
=11111;161111
SPECIAL MOUNTING HEIGHT
TELEVISION
A0 444
UNIT HEATER
UNDER GROUND ELECTRICAL
UNLESS OTHERWISE NOTED
r
CO
WATT(S), WIRE, WALL TELEPHONE OUTLET
WEATHERPROOF DEVICE, NEMA 3R
TRANSFORMER
�M KEY PLAN
N.T.S.
�I -
•
600 West _Hills�_,=n, Suite 300
ri - r Be&ch, 71- 33441
9S4� 4:2-11-1260
FAX: (954) 421-1466
Firm Certification - r
: :::
John E. Moulder PE - FC
Michael A. Steward PE - 65701
SSR JOB # 1032079.0
A�lx
-w
CL
A0 444
r
CO
r
•
A�lx