REGULATORY REQUIREMENTS
A. NFPA 101: Life Safety Code (2006).
B. NFPA 99: Standard for Health Care Facilities (2005).
C. ANSI Handicapped Code- A117.1.
D. Florida Fire Marshall's Rules 69A -3.012 F.A.C. - (2007).
E. Florida Building Code - 2007 with 2009 ammendments.
E. Guidelines for Design and Construction of Hospital and
Health Care Facilities - (2006).
5
i t
i
PLUMBING MATERIALS
PLUMBING SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH FLORIDA
BUILDING CODE - PLUMBING 2007 AND ADA REQUIREMENTS.
WASTE AND VENT: NO HUB SERVICE WEIGHT CAST IRON, BY CHARLOTTE OR TYLER,
ABOVE FLOOR WITH 'HUSKY' HEAVY DUTY #SD4000 COUPLINGS AND BELL AND SPIGOT WITH
NEOPRENE GASKETS BELOW SLAB FOR PIPING 2' AND LARGER AND COPPER TYPE !'.'M' HARD
DRAWN COPPER WITH WROUGHT FITTINGS, WITH 95/5 LEAD FREE SOLDER FOR PIPING UP
TO 1 -1/2.
WATER: DOMESTIC COLD AND HOT WATER PIPING SHALL BE TYPE 'L' HARD
DRAWN COPPER WITH WROUGHT FITTINGS, WITH 95/5 LEAD FREE SOLDERED
JOINTS PER FBC 2007. INSULATE HOT WATER AND HOT WATER RETURN PIPING USING 1' THICK
FIBERGLASS INSULATION HAVING A FLAME SPREAD RATING OF 25 OR LESS AND A SMOKE
DEVELOPMENT OF 50 OR LESS iN ACCORDANCE WITH ASTM E- 84,NPFA 225 AND UL 723.
ACCEPTABLE INSULATION MFGR'S: KNAUF, JOHNS - MANVILLE AND CERTAINTEED.
FOAMGLASS INSULATION SHALL BE USED WHERE PIPING
PENETRATES RATED WALLS. LABEL PIPING BY ADHESIVE LABELS (TO DENOTE
CONTENTS AND DIRECTION OF FLOW) ON PIPING AT NO MORE THAN 25 FOOT INTERVALS,
AT EACH VALVE, AND AT EACH CHANGE IN DIRECTION. PROVIDE ARROWS AT EACH
LOCATION WHERE LABELED INDICATING DIRECTION OF FLOW. LABELING TO BE MINIMUM OF
2' HIGH LETTERS.
COPPER PROPRESS FITTINGS BY VIEGA, CONFORMING TO MATERIAL AND SIZING
REQUIREMENT OF ASME 88.16 OR ASME B16.22. 0 -RINGS FOR COPPER PRESS FITTINGS
SHALL BE EPDM. TYPE 'L' FOR PIPING UP TO 4' IN SIZE. CONTRACTOR SHALL ONLY USE
TOOLS BY VIEGA AND RIDGE TOOL COMPANY.
TEST WATER AND WASTE PIPING AS PER LOCAL CODES.
PLUMBING FIXTURES: KOHLER, AMERICAN STANDARD, ZURN
PLUMBING TRIM: CHICAGO FAUCETS, ZURN
SHOCK ARRESTORS: SIOUX CHIEF OR PRECISION PLUMBING PRODUCTS.
FLOOR DRAINS : ZURN, WADE, J.R SMITH
MIXING VALVES: SYMMONS
FLUSH VALVES: SLOAN ROYAL, ZURN
FIXTURE CARRIER: ZURN, WADE, J.R SMITH
SUPPLY STOPS: MCGUIRE, ZURN HEAVY DUTY, WHEEL HANDLE
CONTRACTOR SHALL PROVIDE PLUMBING FIXTURE AND MATERIAL
SUBMITTALS TO THE ENGINEER FOR APPROVAL PRIOR
TO INSTALLATION AND PURCHASING.
PLUMBING FIXTURES
PROVIDE PLUMBING FIXTURES, TRIM AND RELATED ITEMS SUCH AS
HEAVY DUTY SUPPLIES, TRAPS, DRAINS, CLEANOUTS AND
FIXTURE SUPPORTS AND OTHER ACCESSORY ITEMS. COORDINATE
FIXTURE REQUIREMENTS BY REVIEWING ARCHITECTURAL AND EQUIPMENT
DRAWINGS. INSTALL FIXTURES IN ACCORDANCE WITH CONTRACT DRAWINGS
AND MANUFACTURER'S ROUGH -IN DRAWINGS. WALL HUNG LAVATORIES SHALL
BE PROVIDED WITH FLOOR MOUNTED CARRIERS.
MATERIALS
HANGERS - GRINNELL BY ANVIL, B -LINE, FEE AND MASON, PHD, VIKING AND RELIABLE.
1. GRINNELL FIGURE #260 MSS TYPE 1, CLEViS HANGER FOR: NON- INSULATED STEEL
AND GALVANIZED PIPING 2' THROUGH 241. NON - INSULATED CAST IRON PIPE - 3' AND
LARGER.
2. GRINNELL FIGURE #CT -69, MSS TYPE 10 WITH ADJUSTABLE WROUGHT TUBING RING
HANGER, COPPER PLATED FOR: NON - INSULATED COPPER TUBING WiTH NO LONGITUDINAL
MOVEMENT; NON- INSULATED CAST IRON PIPING 2' AND LESS.
EXPANSION ANCHORS: HILTI KWIK -BOLT, ZINC PLATED, METAL EXPANSION ANCHOR TO BE
USED ON EXISTING CONSTRUCTION. ANCHOR TO MEET U.L., ICBO -4627 AND FM LISTINGS.
POWDER INSERTS ARE NOT ACCEPTABLE
VALVES - NIBCO, KITZ OR MILWAUKEE
1. BALL VALVES (DOMESTIC WATER):
A. 2' AND LESS: NIBCO FIGURE T585 -70 OR S- 585 -70, 2- PIECE, FULL PORT,
600 PSI, WOG, TFE SEATS.
B. ALL VALVES SHALL BE NSF -61 RATED.
C. PROVIDE BALL VALVES WITH LOCKING HANDLES.
'�l dal[ �+ 1�IU7 ��►: i��li• hI���A�hl� :a�il:�h�•'�flAni��hL��I:i�II
2. LOCATE VALVES SO AS TO BE ACCESSIBLE BY MAINTENANCE PERSONNEL.
�t
MEDICAL GAS
MEDICAL GAS PIPING SYSTEM
1.9
FURNISH, INSTALL, AND TEST COMPLETE PIPING SYSTEM FOR OXYGEN, AIR AND VACUUM.
SYSTEM SHALL BE PRESSURE TESTED WITH OIL FREE NITROGEN (NF) AND ANALYZED IN
ACCORDANCE WITH NFPA 99. PROVIDE BRAZER PERFORMANCE QUALIFICATION TEST RECORDS
TO ENGINEER FOR EACH BRAZER USED ON INSTALLATION PRIOR TO INSTALLATION. GRAZERS
SHALL BE QUALIFIED PER PIPE, MGMC, OR AMGI WITH 37 MINIMUM HOURS TRAINING.
MEDICAL GAS PIPING: SEAMLESS TYPE 'L' HARD DRAWN COPPER WITH
WROUGHT COPPER FITTINGS FOR BRAZED CONNECTIONS. ALL PIPING PRECLEANED FOR OXYGEN
SERVICE (PRECLEANED FOR OXYGEN SERVICE iS NOT REQUIRED FOR VACUUM PIPING).
SILVER BRAZING MATERIAL: STAY- SILV -15, SILVALOY -15, AIRCOSIL #15, OR PROS- SILVER -15.
SILVER BRAZING ALLOY COMPOSITION: 15% SILVER, 80% COPPER AND 5% PHOSPHORUS,
NO CADMIUM.
FLUX: DO NOT USE FOR COPPER -TO- COPPER JOINTS. USE FLUX FOR JOINING COPPER TO
BRASS OR BRONZE. EXERCISE CARE IN APPLYING THE FLUX TO AVOID LEAVING ANY EXCESS
FLUX INSIDE THE COMPLETED JOINTS.
UTILIZE UNISTRUT SUPPORTS WITH PHD MANUFACTURING MODEL #2501 - 2514 UNISTRUT
CUSHIONED CLAMPS OR PHD MODEL #153 PVC COATED TEAR DROP HANGERS. TAPE IS NOT
ACCEPTABLE.
EXPANSION ANCHORS: HILTI KWIK -BOLT, ZINC PLATED, METAL EXPANSION ANCHOR TO BE
USED ON EXISTING CONSTRUCTION. ANCHOR TO MEET U.L., ICBO -4627 AND FM LISTINGS.
CONTRACTOR SHALL PROVIDE MEDICAL GAS CERTIFICATION REPORT TO OWNER & ENGINEER
PRIOR TO FINAL AHCA INSPECTION. CONTRACTOR SHALL CERTIFY EXISTING SYSTEM
PRIOR TO CUTTING INTO EXISTING SYSTEM AND SHALL SUBMIT MEDICAL GAS
CERTIFICATION TO ENGINEER FOR REVIEW PRIOR TO ANY NEW INSTALLATION.
CONTRACTOR SHALL ALSO PROVIDE COPY OF TESTS FOR ALL STEPS AS OUTLINED IN
NFPA 99 IN ADDITION TO MEDICAL GAS CERTIFICATION.
LABEL PIPING WITH ADHESIVE LABELS. COLOR CODED PER NFPA 99. LABEL PIPING AT
INTERVALS OF NOT MORE THAN 20 FEET, AT LEAST ONCE IN EACH ROOM, AT EACH STORY
TRAVERSED BY THE PIPING SYSTEM, AT EACH WALL AND FLOOR SLAB PENETRATION, AT
EACH VALVE AND AT EACH CHANGE IN DIRECTION. PROVIDE ARROWS AT EACH LOCATION
WHERE LABELED INDICATING DIRECTION OF FLOW. SYSTEM SHALL BE INSTALLED PER NFPA
99. ALL PIPING SHALL BE PRECLEANED AND PLUGGED PRIOR TO SHIPMENT TO THE JOB SITE.
JOINTS TO BE MADE WITH 1000 DEGREES F MELTING POINT MINIMUM WITH 15% SILVER
BRAZING ALLOY. SYSTEM SHALL BE PURGED CONTINUOUSLY WITH DRY NITROGEN (NF) WHILE
BEING ASSEMBLED AND BRAZED. USE OF FLUX IS NOT ALLOWED EXCEPT ON DISSIMILAR
METALS. USE SHALL BE KEPT TO A MINIMUM. PROVIDE HANGERS ON PIPING PER NFPA 99
AND IN EACH ROOM.
CROSS CONNECTION TESTING AND CERTIFICATION OF THE NEW AND EXISTING MEDICAL
GAS SYSTEM MUST BE PERFORMED BY FACTORY TRAINED TECHNICIANS FROM THE
MEDICAL GAS PIPELINE EQUIPMENT SUPPLIER. MEDICAL GAS VALVE BOXES,
VALVES, ALARMS AND OUTLETS SHALL BE BY ONE MANUFACTURER.
MEDICAL GAS OUTLETS SHALL BE BEACON MEDAES OHMEDA COMPATIBLE - DIAMOND 3,
QUICK CONNECT. CONTRACTOR SHALL VERIFY THAT OUTLETS MATCH EXISTING HOSPITAL
STANDARD PRIOR TO PURCHASING AND INSTALLATION.
MEDICAL GAS AREA ALARM PANEL SHALL BE BEACON MEDEAS MEDPLUS TOTALALERT
THREE MODULE ALARM PANEL #6819A3 WITH GAS SPECIFIC MODULES AS REQUIRED BY
MED GAS SCHEDULE. PROVIDE OPTIONAL NETWORK COMMUNICATIONS BOARD CAPABLE
OF INTERFACING WITH FACILITY'S ETHERNET AND CAT -5 ETHERNET CABLE.
MEDICAL GAS ZONE VALVE BOXIF SHALL BE BEACON MEDEES, AMICO OR OHIO MEDICAL.
VALVE BOXES SHALL INCLUDE 1 �' PRESSURE GAUGES READING 0 -100 PSIG FOR OXYGEN
& AIR,& 0-30' HG FOR VACUUM. GAUGES SHALL BE LOCATED DOWNSTREAM OF VALVES.
PROVIDE PERMENANTLY ENGRAVED LABELS ON ALL MEDICAL GAS ZONE VALVES AND ALARM
PANELS TO INDICATE AREA SERVED PER NFPA -99. COORDINATE WITH HOSPITAL STANDARDS.
PLUMBING CONTRACTOR SHALL PROVIDE AND COORDINATE ALL LOW VOLTAGE WIRING WITH
DIVISION 16 AND PROVIDE ALL REQUIRED CONDUITS AND WIRING. CONTRACTOR SHALL HOLD
A LOW VOLTAGE WIRING LICENSE.
PIPELINE PRODUCTS (INCLUDING ALARM PANEL, ZONE VALVE BOX AND OUTLETS) SHALL BE BY
BEACON MEDAES, AMICO OR OHIO MEDICAL. ALL PIPELINE PRODUCTS SHALL BE BY THE SAME
MANUFACTURER.
�r �r•��t a'r
CONTRACTOR SHALL PROVIDE AS BUILT DRAWINGS IN AUTOCAD FORMAT AT COMPLETION
OF PROJECT.
ALL MATERIAL SHALL BE MANUFACTURED WITHIN THE UNITED STATES.
i
I
s
- - Architecture Engineering Planning
Interior Gesign Landscape Architecture
2601
So Vvbayshore Drive 10th Floor
Miami, Florida 33133
(305) 859 -2050 Fax (305) 860 -3700
'CEP ENGINEER:
Smith
Seckman
Reid, inc.
600 West Hillsboro, Suite 300
Deerfield Beach, FL 33441
(954) 421 -1260
FAX: (954) 421 -1466
www.ssr- inc.com
Firm Certification - EB- 0000857
John E. Moulder PE - 33200
Michael A. Steward PE - 65701
SSR JOB # 1032062.0
��111111y�
M
•, N -
S
F
r bi q
D PHASE