10-732-027IIIIIIINI IIIIIIIIA!I 0� a A I 0 N 9 I I N R FIRE PROTECTION SPECIFICATIONS REGULATORY REQUIREMENTS A. NFPA 101: Life Safety Code (2006). B. NFPA 13: Standard for Sprinkler Systems (2002). C. Florida Fire Marshall's Rules 69A -3.012 F.A.C. - (2007). D. Florida Building Code - 2007 with 2008 ammendments. E. Guidelines for Design and Construction of Hospital and Health Care Facilities - (2006). ALL PRODUCTS ASSOCIATED WITH THE SPRINKLER SYSTEM SHALL BE UNDERWRITERS LABORATORIES (UL) LiSTED AND /OR FACTORY MUTUAL (FM) APPROVED. PiPE INTERIOR PIPE AND FITTINGS: 1. THREADABLE THIN WALL ALLIED DINA THREAD WITH CRR = 1.0 U.L. LISTED AND / OR U.L. LISTED ASTM A -795 TYPE E PROVIDE ABF COATING ON PiPING. GRADE A, ELECTRIC RESISTANCE WELDED BY WHEATLAND TUBING, ALLIED, OR BULL MOOSE FOR PIPING UP TO 21/2. 1. MECHANICAL COUPLINGS: ROLL GROOVE RIGID TYPE BY VICTAULIC OR GRINNELL. 2. CLASS 250 CAST IRON SPRINKLER FITTINGS - SCREWED, FLANGED, OR GROOVED -END. 3. ALL FITTINGS SHALL BE BY THE SAME MANUFACTURER. PROVIDE UL LISTED AND FM APPROVED HANGERS. ACCEPTABLE MANUFACTURERS: GRINNELL, BLINE, VIKING, FEE AND MASON. 1. GRINNELL ADJUSTABLE CLEVIS HANGER #260 MSS, TYPE 1 FOR PIPING 21/2 AND LARGER. 2. GRINNELL ADJUSTABLE SWIVEL RING HANGER #69 FOR PIPING 2' AND SMALLER. CLAMPS: 1. C- CLAMPS: GRINNELL #92 WITH RETAINER CLIP, MSS TYPE 23. 2. MALLABLE BEAM CLAMPS: GRINNELL FIGURE #218, MSS TYPE 30. EXPANSION ANCHORS: 1. HiLTI - HDT -KWIK -BOLT, ZINC PLATED, METAL EXPANSION ANCHOR. ANCHOR TO MEET U.L., ICBO -4627 AND FM LISTINGS. SPRINKLER HEADS: ACCEPTABLE MANUFACTURERS: VIKING, RELIABLE SPRINKLER COMPANY & VICTAULIC. SPRINKLER HEADS SHALL BE U.L. LISTED AND F.M. APPROVED. CONCEALED TYPE QUICK RESPONSE SPRINKLER HEAD MAY BE U.L. LISTED ONLY. CONCEALED: VIKING HORIZON MIRAGE MODEL VK404, BULB TYPE, 1/1 ORIFICE, WHITE COVER PLATE, QUICK RESPONSE, 5.6 K- FACTOR, 155 DEGREE UNLESS NOTED OTHERWISE. PIPE INSTALLATION PROVIDE HANGERS ON ALL ARM OUTS OF 12, OR MORE. SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS IN ACCORDANCE WITH UL FIRE RESISTANCE INDEX FOR THROUGH - PENETRATION FIRESTOP SYSTEMS. COORDINATE REQUIREMENTS WITH DIVISION 7. THE CONTRACTOR SHALL PROVIDE SPRINKLER SHOP DRAWINGS AND PRODUCT DATA SUBMITTALS TO ARCHITECT AND ENGINEER FOR APPROVAL PRIOR TO INSTALLATION AND SUBMITTAL TO THE BUILDING DEPARTMENT FOR REVIEW AND APPROVAL TO CONVEY THAT HE UNDERSTANDS THE INTENT OF CONTRACT DOCUMENTS AND TO FACILITATE COORDINATION OF SPRINKLER SYSTEM WITH OTHER TRADES. THE DRAWINGS SHALL INCORPORATE ALL OF THE REQUIREMENTS OF NFPA 13. CONTRACTOR SHALL PROVIDE AS -BUILT DRAWINGS IN AUTOCAD FORMAT AT COMPLETION OF PROJECT. ALL MATERIAL SHALL BE MANUFACTURED WITHIN THE UNITED STATES. N i Arct tecture_Engineering Planning Interior Design Lanci' caFle Architecture 260 ,_South Bad {shore Dnve 10th Floor Miami, Florida 33133 (305) 859 -2050 Fax (305) 860 -3700 EP ENGINEER: 2nSmith Seckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification - EB- 0000857 John E. Moulder PE - 33200 Michael A. Steward PE - 65701 SSR JOB # 1032062.0 71 *ANN REVISIONS: PROJECT NAME: SOUTH MIAMI HOSPITAL EAST TOWER FIBROID CENTER B PROJECT ADDRESS: 7400 S.W. 62nd Ave. South Miami, Florida 33143 KEY PLAN COMM. NO. 40062.100 SCALE: DATE: JUNE 30.2010 DRAWN: A CHECKED: CADD FILE: DRAWING TITLE: FIRE PROTECTION SPECIFICATIONS SHEET NO. 4 4