Loading...
10-732-026I M IIIIIIIIIIAII W W I 12 1. ALL FIRE PROTECTION SYSTEM SHALL BE IN COMPLIANCE WITH THE STATE AND LOCAL FIRE CODES AND ORDINANCES AND AS PER NFPA 13 - 2002 AND NFPA 14 - 2003 EDITION REQUIREMENTS. 2. MAKE ALL OFFSETS REQUIRED AS PER JOB CONDITIONS. 3. CONTRACTOR TO PROVIDE AND TURN OVER TO THE OWNER AT LEAST (6) SPARE SPRINKLERS OF SAME TYPE AND TEMPERATURE RATING BEING INSTALLED INSIDE OF SPARE SPRINKLER CABINETS. COORDINATE LOCATION WITH OWNER. 4. CONTRACTOR SHALL FIELD VERIFY AND COORDINATE SPRINKLER HEAD LOCATIONS WITH SOFFITS AND ANY CEILING OBSTRUCTIONS PER NFPA 13. 5. ALL SPRINKLER HEADS SHALL BE CENTERED AND PRESENT A NEAT AND BALANCED CEILING PATTERN UNLESS SHOWN OTHERWISE. 6. PROVIDE AND MAINTAIN A MINIMUM CLEARANCE OF 18' BETWEEN THE BOTTOM OF THE SPRINKLER DEFLECTOR AND THE TOP OF STORAGE, FILE, SHELVING, ETC. 7. CONTRACTOR SHALL FIELD VERIFY LOCATION AND QUANTITY OF ALL CEILING MOUNTED DEVICES INCLUDING SMOKE DETECTORS TO BE REMOVED DURING CONSTRUCTION TO INSTALL SPRINKLER PIPING. EXISTING EQUIPMENT AND FIXTURES SHALL BE REPAIRED TO ORIGINAL OPERATION OR REPLACED SHOULD THEY BE DAMAGED DURING CONSTRUCTION. 8. SCHEDULE 5 PIPING AND FLEXIBLE SPRINKLER HEAD DROPS ARE NOT APPROVED OR ACCEPTED PRODUCTS. 9. CONTRACTOR SHALL COORDINATE WITH STRUCTURE AND OTHER TRADES BEFORE INSTALLING SPRINKLER WORK. 10. SPRINKLER HEAD RATED c 155 DEGREES F.,' /¢ ORIFICE WITH 5.6 K- FACTOR, QUICK RESPONSE UNLESS OTHERWISE NOTED. 11. INSTALL PIPING TIGHT TO STRUCTURE WHERE POSSIBLE. 12. SPRINKLER SYSTEM SHALL BE INSTALLED BY A STATE CERTIFIED FIRE PROTECTION CONTRACTOR. 13. PIPES FOR FUTURE USE SHALL BE CAPPED ABOVE CEILING. 14. SPRINKLER PIPING SHALL BE UL LISTED THREADABLE THINWALL AND /OR ALLIED XL 1' THROUGH 3' AND SCHEDULE 10 BLACK STEEL ASTM /A.135, UL LISTED FOR PIPING 4' AND LARGER. 15. SYSTEM DESIGNED FOR LIGHT HAZARD OCCUPANCY. 16. CONTRACTOR SHALL REMOVE EXISTING SPRINKLER HEADS AS SHOWN AND ADJUST PIPING TO NEW CEILING PATERN. 17. CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINES INVOLVED SO AS TO AVOID ANY PIPE ROUTING PROBLEMS. 18. EXISTING SERVICES INDICATED ON THESE DRAWINGS WERE DERIVED FROM EXISTING DRAWINGS AND LIMITED FIELD OBSERVATIONS. THESE DRAWINGS MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES, LOCATION, TYPE AND SIZE PRIOR TO ANY CONSTRUCTION. ANY DEVIATIONS IMPACTING WORK SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT FOR COORDINATION PRIOR TO CONSTRUCTION. 19. CONTRACTOR IS RESPONSIBLE FOR RELOCATING ALL EXISTING FIRE MAINS AND SPRINKLER PIPING TO FACILITATE THE INSTALLATION OF NEW ELECTRICAL, MECHANICAL AND PLUMBING SYSTEMS. THIS INCLUDES ALL CEILING SPACES, SHAFTS, WALLS, ETC. 20. CONTRACTOR SHALL RAISE ALL EXISTING SPRINKLER PIPING WITHIN SCOPE TIGHT TO STRUCTURE AND PROVIDE NEW FITTINGS THROUGHOUT. 21. PRESSURE TEST PIPING AT 200 PSIG FOR A MINIMUM OF TWO HOURS. IF LEAKS ARE FOUND THEN CONTRACTOR SHALL FIX LEAKS AND TEST AGAIN. CONTRACTOR SHALL ALSO PROVIDE ALLOWANCE IN BID FOR PRESSURE TESTING OF EXISTING PIPING SHOWN TO REMAIN AT 200 PSIG FOR A MINIMUM OF 2 HOURS. ALLOWANCE SHALL INCLUDE FIXING LEAKS AND RETESTING. 22. FIRE PROTECTION CONTRACTOR SHALL PREPARE A SET OF INSTALLATION SHOP DRAWINGS BASED ON PIPE SIZES SHOWN COORDINATED WITH ALL THE ENGINEERING DISCIPLINES AND FIRE PROTECTION PIPING. THESE SHOP DRAWINGS SHALL BE SUBMITTED TO SSR ENGINEERS FOR APPROVAL PRIOR TO FABRICATION, INSTALLATION OR SUBMITTAL TO BUILDING DEPARTMENT. ALSO, MATERIAL SUBMITTALS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL PRIOR TO ANY INSTALLATION. 23. CONTRACTOR 8.14.16. SHALL PROVIDE FLUSH FLUSHING CONNECTIOSPRINKLER N SPRINKLER SHOP DRAWINGS. 24. SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS IN ACCORDANCE WITH U.L. FIRE RESISTANCE INDEX FOR THROUGH PENETRATION FIRE STOP SYSTEMS. COORDINATE REQUIREMENTS WITH ARCHITECTURAL PLANS AND SPECIFICATIONS. 25. ALL GROOVED AND SCREWED FITTING SHALL BE APPROVED BY AN ENGINEER WHO RESERVES THE RIGHT TO DISAPPROVE ANY FITTING. ALL FITTING TYPES SHALL BE FROM THE SAME MANUFACTURER. 26. VISIT THE SITE TO CHECK AND VERIFY ALL EXISTING CONDITIONS PRIOR TO BIDDING TO INSURE THE COORDINATION OF THE FIRE SERVICES WITH EXISTING CONDITIONS. 27. CUTTING OF STRUCTURAL AND /OR ARCHITECTURAL MEMBERS TO BE DONE ONLY WITH THE WRITTEN APPROVAL OF THE ARCHITECT AND STRUCTURAL ENGINEER. 28. SPRINKLER HEADS ARE TO BE COORDINATED WITH ALL CEILING DEVICES (LIGHTS, DIFFUSERS, ETC.) AND STRUCTURAL SYSTEM. 29. INDICATE CENTER TO CENTER DIMENSIONS AND /OR PIPE CUT LENGTHS AND NOMINAL PIPE DIAMETERS OF ALL PIPING ON SHOP DRAWINGS. 30. INDICATE PIPE TYPE, SCHEDULE OF WALL THICKNESS AND METHOD OF JOINING ON SHOP DRAWING. 31. PROVIDE A PERMANENTLY ATTACHED NAME TAG STATING THE REQUIRED DESIGN CRITERIA FOR EACH HYDRAULICALLY DESIGNED SYSTEM. 32. IMMEDIATELY NOTIFY THE ARCHITECT /ENGINEER OF ANY DISCREPANCIES FOUND BETWEEN THESE PLANS, OTHER ENGINEERING PLANS, THE ARCHITECTURAL PLANS AND /OR FIELD CONDITIONS PRIOR TO FINAL BID PRICE OR FINAL PERMITTING. 33. IN CASE OF DISPUTE OR DOUBT AS TO INTENT OF DRAWINGS OR SPECIFICATIONS, OBTAIN ARCHITECT /ENGINEER'S DECISION BEFORE PROCEEDING WITH WORK OR BID INVOLVED. FAILURE TO FOLLOW THIS INSTRUCTION SHALL CONSTITUTE LIABILITY FOR DAMAGE TO OTHER WORK AND FOR REMOVING AND REPAIRING DEFECTIVE OR MISLOCATED WORK IN PROPER MANNER. I 34. BEFORE SUBMITTING PROPOSAL OR BID, EXAMINE ALL DRAWINGS AND SPECIFICATIONS RELATING TO THIS PROJECT, THE AMOUNT OF SPACE AVAILABLE FOR PIPING, EQUIPMENT AND CONNECTING SERVICES, THE SITE OF THE WORK, THE REQUIREMENTS TO CORRELATE THE FIRE PROTECTION WORK WITH THAT OF OTHER TRADES AND THE TIME SCHEDULE NECESSARY TO PERFORM THAT WORK. 35. ALL SPRINKLER HEADS MOUNTED IN CEILING SHALL BE LOCATED A MINIMUM OF 4" AWAY FROM ANY WALLS, CEILING HEIGHT CHANGES OR ANY OTHER VERTICAL INTERSECTING STRUCTURAL SURFACE. 36. PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY, AND AFTER ASSEMBLY. THE ENTIRE PIPING SYSTEM SHALL BE FLUSHED CLEAN. 37. ALL PENETRATIONS OR OPENINGS FROM REMOVED PIPES THROUGH EXISTING BUILDING WALLS AND FLOORS SHALL BE SLEEVED AND /OR PATCHED TO MATCH ORIGINAL. SEE ARCHITECTURAL DRAWINGS FOR FINAL FINISHES. 38. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO EXISTING PIPING OR EQUIPMENT DUE TO NEW CONSTRUCTION AND HE SHALL RESTORE EXISTING WORK TO ITS ORIGINAL CONDITION AT NO COST TO THE OWNER. 39. PROVIDE HANGERS ON ALL ARMOVERS OF 12' OR MORE IN LENGTH AND PER NFPA 13. 40. WARRANTY /GUARANTEE A. THE CONTRACTOR SHALL WARRANTY /GUARANTEE AND MAINTAIN THE STABILITY OF WORK AND MATERIALS AND KEEP SAME IN PERFECT REPAIR AND CONDITION FOR THE PERIOD OF ONE YEAR. B. DEFECTS OF ANY KIND DUE TO FAULTY WORK OR MATERIALS, APPEARING DURING THE ABOVE MENTIONED PERIOD, MUST BE IMMEDIATELY REPAIRED BY THE CONTRACTOR AT HIS OWN EXPENSE TO THE ENTIRE SATISFACTION OF THE OWNER AND ENGINEER. SUCH RECONSTRUCTION AND REPAIRS SHALL INCLUDE DAMAGE TO THE FINISH OR FURNISHING OF THE BUILDING RESULTING FROM THE ORIGINAL DEFECT OR REPAIR THERETO. 41. PROVIDE HEAD GUARDS ON ALL SPRINKLERS IN MECHANICAL ROOMS, ELECTRICAL ROOMS AND ALL ROOMS WITH EXPOSED CEILINGS. 42. SPRINKLER HEADS SHALL BE A MINIMUM OF 12" FROM ANY DIFFUSER PER NFPA 13. 43. CONTRACTOR SHALL PROVIDE ALLOWANCE IN BID FOR AN ADDITIONAL 4 CONCEALED HEADS WITH 10 FOOT 1' ARMOVER, 1 TEE AND 2 ELBOWS TO EACH HEAD. PROVIDE LINE ITEM COST PER HEAD WITH ASSOCIATED ARMOVER, FITTINGS AND HANGERS. INSTALL HEADS WHERE REQUIRED BY TEMPORARY WALLS, LOCAL AHJ,UNFORSEEN CONDITIONS, ETC. 44. PROVIDE SPRINKLERS ABOVE AND BELOW DUCTWORK, CONDUIT, PIPING, ETC. 48' IN WIDTH AND LARGER. THIS INCLUDES SYSTEMS LOCATED ADJACENT TO EACH OTHER WHICH THEIR COMBINED WIDTH IS 48' OR LARGER. 45. PIPING SHALL NOT BE RUN OVER ANY ELECTRICAL AND PHONE PANELS OR EQUIPMENT. 46. THE FIRE PROTECTION CONTRACTOR SHALL KEEP A SET OF MARKED UP DRAWINGS AS THE JOB PROGRESSES. NO MAJOR CHANGE SHALL BE MADE TO FIRE PROTECTION DESIGN ENGINEERING UNLESS IT HAS BEEN COORDINATED, DRAWN AND SUBMITTED FOR APPROVAL. 47. FIRE PROTECTION SERVICES TO BE REMOVED SHALL BE CAPPED. 48. CONTINUITY OF SERVICE: INTERRUPTIONS OF EXISTING SERVICES OR FACILITIES SHALL BE KEPT TO A MINIMUM AND THE CONTRACTOR SHALL FURNISH ALL MATERIALS AND LABOR REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE NECESSARY TO MAINTAIN CONTINUITY OF SERVICE. INTERRUPTIONS OF THE EXISTING SERVICES, THE INSTALLATION OF TEMPORARY FACILITIES, AND THE WORK OF MAKING FINAL CONNECTIONS TO NEW WORK SHALL BE DONE ONLY AT SUCH TIMES AS PERMITTED AND SCHEDULED BY THE OWNER. ALL SUCH CONNECTIONS AND TIE -INS SHALL BE COORDINATED THROUGH THE OWNERS PROJECT MANAGER. 1. THE DURATION OF EACH SHUTDOWN SHALL BE LIMITED TO NIGHTS AND /OR WEEKENDS WITH THE TIME FRAME FOR SHUTDOWNS AS SPECIFIED BY THE OWNER. THE CONTRACTOR SHALL NOTIFY THE OWNER IN WRITING FORTY -EIGHT (48) HOURS IN ADVANCE OF EACH REQUIRED INTERRUPTION OF EXISTING SERVICE. ANY AREA AFFECTED BY SHUTDOWN SHALL REQUIRE A 24 HOUR /7 DAYS PER WEEK FIRE WATCH. 2. THE CONTRACTOR SHALL INCLUDE IN BID PRICE ALL PREMIUM TIME CHARGES FOR LABOR AND EQUIPMENT REQUIRED FOR ALL NIGHT AND WEEKEND OVERTIME WORK, AS NECESSARY, TO COMPLETE THE SCOPE OF THE CONTRACT. 49. SSR IS CONTRACTED BY THE HOSPITAL /OWNER TO BE THE ENGINEER OF RECORD FOR THIS PROJECT. CONTRACTOR SHALL PRODUCE SHOP DRAWINGS WHICH MATCH THESE DRAWINGS IN DESIGN INTENT (PIPE ROUTING, PIPE SIZING, SPRINKLER HEAD LAYOUT, ETC.). CONTRACTOR SHALL COORDINATE FIRE PROTECTION INSTALLATION WITH SITE CONDITIONS (STRUCTURE, CEILING, DUCTWORK, PIPING, CONDUIT, ETC.), AND PROVIDE OFFSETS TO PIPE ROUTING OR DEVIATIONS FROM DESIGN INTENT ONLY WHERE REQUIRED BY SITE CONDITIONS OR APPLICABLE CODES. 50. CONTRACTOR SHALL PROVIDE 24/7 FIRE WATCH FOR ALL AREAS OF THE HOSPITAL THAT HAVE THE FIRE PROTECTION SYSTEM SHUTDOWN FOR 4 HOURS OR MORE AS REQUIRED PER THE FLORIDA FIRE PREVENTION CODE 2007. COORDINATE REQUIREMENTS WITH OWNER. 51. CONTRACTOR SHALL PATCH WALLS, FLOORS, ROOFING AND CEILINGS TO MATCH EXISITNG FINISHES FOR DEMOLITION AND INSTALLATION OF FIRE PROTECTION SYSTEMS. COORDINATE WITH ARCHITECTURAL DRAWINGS. 52. ENGINEERING SERVICES TO BE REMOVED SHALL BE CAPPED AND PLUGGED. 53. CONTRACTOR SHALL PROVIDE ALLOWANCE IN BID FOR AN ADDITIONAL 10 CONCEALED HEADS WITH 10 FOOT V ARMOVER, 1 TEE AND 2 ELBOWS TO EACH HEAD. PROVIDE LINE ITEM COST PER HEAD WITH ASSOCIATED ARMOVER, FITTINGS AND HANGERS. 54. ALL EQUIPMENT AND PIPES IN MECHANICAL ROOMS SHALL BE LABELED. PIPE LABELS SHALL INCLUDE DIRECTION OF FLOW. 55. PROVIDE A MINIMUM OF 6 INCHES IN BETWEEN ALL PIPING AND FIRE RATED AND SMOKE TIGHT PARTITIONS FOR REQUIRED INSPECTIONS. ANY PIPING WITHIN THIS 6 INCHES SPACE SHALL BE REQUIRED TO BE MOVED AND REROUTED. ANY COST IMPACT TO OTHER TRADES WILL BE THE RESPONSIBILITY OF THE CONTRACTOR. 2 a Y I FIRE PROTECTION LEGEND SYMBOL DESCRIPTION SYMBOL DESCRIPTION F FIRE LINE OR MAIN 1111111111111111r FIRE DEPARTMENT VALVE CABINET A/S AUTOMATIC SPRINKLER MAIN FP -1, ETC FIXTURE INDENTIFICATION D DRAIN LINE 0 CONNECTION TO EXISTING ^ PIPE TURNED UP 9 FIRE EXTINGUISHER o PIPE TURNED DOWN I FLOW SWITCH j BALL VALVE F.D.V. CAP ON LINE CHECK VALVE --o- -' SPRINKLER HEAD BELOW DUCTWORK UNION IN PIPE PIPING TO BE REMOVED _ O.S. &Y. GATE OR BUTTERFLY VALVE W / TAMPER SWITCH. REMOVE EXISTING HEAD AND PLUG FITTING -- fi,,� -- CHECK VALVE REMOVE EXISTING HEAD & EXTEND 1' BRANCH LINE TO NEW HEAD LOCATION -;- CONTROL VALVE AND CHECK VALVE WITH FLOW AND TAMPER SWITCHES FIRE PROTECTION ABBREVIATIONS F.H.C. FIRE HOSE CABINET E.P. ELECTRICAL PANEL F.E. FIRE EXTINGUISHER F.E.0 FIRE EXTINGUISHER CABINET A/5 AUTOMATIC SPRINKLER F.D.V.C. FIRE DEPARTMENT VALVE CABINET F.SP. FIRE STANDPIPE O.S. & Y. OUTSIDE STEM AND YOKE RCV RISER CONTROL VALVE A.F.F. ABOVE FINISHED FLOOR T.S. TAMPER SWITCH F.S. FLOW SWITCH F.D.V. FIRE DEPARTMENT VALVE SPRINKLER HEAD LEGEND TYPE K -FACT TEMP LOCATION 1. CONCEALED - QRS (WHITE COVER PLATE) 5.6 1550 ALL SPACES UNLESS OTHERWISE NOTED FP2.1 PARTIAL FIRST FLOOR - NEW CONSTRUCTION - FIRE PROTECTION FP5.1 FIRE PROTECTION DETAILS SEE SPECIFICATIONS FOR MODEL NUMBERS. * PLUG ALL UNUSED OUTLETS. INFECTION CONTROL MEASURES 1. CONTRACTOR SHALL OBTAIN FROM THE OWNER A COPY OF THE INFECTION CONTROL RISK ASSESSMENT (ICRA) PREPARED FOR THIS PROJECT. CONTRACTOR SHALL REVIEW THE REQUIREMENTS IN THE REPORT AND PERFORM ALL WORK IN ACCORDANCE WITH THOSE REQUIREMENTS. CONTRACTOR SHALL STRICTLY ADHERE TO THE LIMITS OF THE CONSTRUCTION AREA, AND WHERE PHASING APPLIES SHALL ADHERE TO THE PHASING PLAN. ANY WORK OUTSIDE THE CONSTRUCTION AREA SHALL BE COORDINATED WITH THE OWNER AND PERFORMED IN ACCORDANCE WITH THE ICRA REPORT, UNDER THE SUPERVISION OF THE OWNER'S REPRESENTATIVE OR OTHER DESIGNATED ICRA COMMITTEE OFFICER. 2. TO THE EXTENT THAT IT IS REQUIRED BY THE ICRA, THE CONTRACTOR SHALL ENDEAVOR TO MAINTAIN EXISTING LEVELS OF INDOOR AIR QUALITY IN AREAS SURROUNDING AND ADJACENT TO THE CONSTRUCTION WORK ZONE, AND ELSEWHERE IN THE FACILITY. IT SHOULD BE ANTICIPATED THAT THE ICRA REPORT WILL REQUIRE MEASURES TO THIS EFFECT INCLUDING ERECTION OF CONSTRUCTION ZONE BARRIERS AND PROVISION OF NEGATIVE AIR PRESSURE IN THE CONSTRUCTION ZONE RELATIVE TO OTHER AREAS OF THE FACILITY. 3.IN ADDITION TO THE MEETING THE REQUIREMENTS OF THE ICRA REPORT, THE CONTRACTOR AT A MINIMUM SHALL PROVIDE EQUIPMENTAND COMPONENTS NECESSARY TO CREATE A NEGATIVE PRESSURE IN THE CONSTRUCTION WORK ZONE RELATIVE TO ADJACENT AREA. EXISTING HVAC SYSTEMS AND COMPONENTS SHALL NOT BE USED FOR THIS FUNCTION, UNLESS SPECIFICALLY APPROVED BY THE OWNER'S INFECTION CONTROL OFFICER. THE CONCEPT AND ALL ASPECTS OF THIS WORK SHALL BE DONE IN ACCORDANCE WITH THE ICRA REQUIREMENTS AND AT A MINIMUM AS FOLLOWS: VERIFY ALL EXISTING FIRE PROTECTION WHICH PASSES THROUGH THE CONSTRUCTION ZONE, AND IS TO REMAIN, IS SEALED AND PROTECTED DURING THE CONSTRUCTION DURATION. AIR REMOVED FROM THE CONSTUCTION ZONE SHALL BE FILTERED AND /OR DISCHARGED AS DIRECTED BY THE ICRA REPORT. PRESENT THE NEGATIVE AIR PRESSURE PLAN TO THE OWNER FOR APPROVAL BY THE INFECTION CONTROL COMMITTEE. PROVIDE MEANS TO MONITOR AND VERIFY NEGATIVE PRESSURE IS BEING MAINTAINED IN ACCORDANCE WITH THE ICRA REPORT, AND PROVIDE DOCUMENTATION TO THE OWNER AS REQUIRED. 4. COORDINATE IN ADVANCE ANY REQUIRED EQUIPMENT SHUTDOWN WITH THE OWNER, AND VERIFY BEFORE SHUTDOWN THAT EXISTING OR DESIRED AIR PRESSURE RELATIONSHIPS WILL NOT BE ADVERSELY AFFECTED. i DRAWING INDEX SHEET NUMBER SHEET TITLE FPO.O FIRE PROTECTION LEGENDS, SCHEDULES,AND DRAWING INDEX FPO.1 FIRE PROTECTION SPECIFICATIONS FP1.1 PARTIAL FIRST FLOOR - DEMOLITION - FIRE PROTECTION FP2.1 PARTIAL FIRST FLOOR - NEW CONSTRUCTION - FIRE PROTECTION FP5.1 FIRE PROTECTION DETAILS i M - A A w. 1 -Architecture Engineering Planning Interi6r Design Landscope Architecture 2-eO ,South Bcvsh6re_Drive 10th Floor Miami, Florida 33133 (305) 859 -2050 Fax (305) 860 -3700 ON MEP ENGINEER: Smith Seckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification - EB- 0000857 John E. Moulder PE - 33200 Michael A. Steward PE - 65701 SSR JOB # 1032062.0 11111111 u, E'NS` t . N. r PERMIT' SUBMITTAL CD PHASE REVISIONS: PROJECT NAME: SOUTH MIAMI HOSPITAL EAST TOWER FIBROID CENTER B PROJECT ADDRESS: 7400 S.W. 62nd Ave. South Miami, Florida 33143 I ON COMM. NO. 40062.100 SCALE: DATE: JUNE 30.2010 DRAWN: A CHECKED: CADD FILE: DRAWING TITLE: FIRE PROTECTION LEGENDS, SCHEDULES & DRAWING INDEX SHEET NO. ?a �f a`