10-640-004ELECTRICAL SPECIFICATIONS 16010 - BASIC ELECTRICAL REQUIREMENTS A. THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND INSTALLATION OF THE NECESSARY MATERIAL AND LABOR TO ACCOMPLISH THE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. ALL WORK BY CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL, STATE AND LOCAL BUILDING CODES AND STANDARDS INCLUDING BUT NOT LIMITED TO: 1. STATE OF FLORIDA 2. CITY OF SOUTH MIAMI 3. LIFE SAFETY CODE - NFPA 101 (2006) 4. UNDERWRITERS LABORATORIES, INC. PUBLICATIONS (UL) 5. NATIONAL FIRE PROTECTION ASSOCIATION. (NFPA) 6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 7. NATIONAL ELECTRICAL CODE - NFPA 70 (2008) 8. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE) 9. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) 10. INTERNATIONAL POWER CABLE ENGINEER'S ASSOCIATION (IPCEA) 11. NATIONAL ELECTRICAL SAFETY CODE (NBS Handbook 81) 11 REQUIREMENTS OF LOCAL UTILITY COMPANY 13. FLORIDA ADMINISTRATIVE CODE 59A -3, (March 2003) 14. NATIONAL FIRE PROTECTION ASSOCIATION 72 (2005) 15. NATIONAL FIRE PROTECTION ASSOCIATION 99 (2005) 16. THE STATE FIRE PREVENTION CODE, 4A60 (2001) 17. BUILDING CODE: FLORIDA BUILDING CODE (2007) WITH 2008 AND 2009 REVISIONS 18. AIA GUIDELINES (2006) 19. NFPA 110 (2005) 20. FIRE MARSHALL'S RULE 4A3.012 F.A.C. adopted January 1, 2001 B. CODES AND STANDARDS REFERRED TO ARE MINIMUM. WHERE THE REQUIREMENTS OF THE DRAWINGS OR SPECIFICATIONS EXCEED THOSE OF THE CODES AND REGULATIONS, THE DRAWINGS AND SPECIFICATIONS GOVERN. C. THE CONTRACTOR SHALL OBTAIN AND PAY FOR PERMITS, PLAN CHECKS, INSPECTIONS, AND APPROVALS APPLICABLE TO THE WORK AS REQUIRED BY THE REGULATORY AUTHORITIES, FEES AND COSTS OF ANY NATURE WHATSOEVER INCIDENTAL TO THESE PERMITS, INSPECTIONS AND APPROVALS SHALL BE ASSUMED AND PAID BY THE CONTRACTOR. THE PRO -RATA COSTS, IF ANY, FOR UTILITIES SERVING THIS PROPERTY WILL BE PAID FOR BY THE OWNER AND SHALL NOT BE INCLUDED AS PART OF THIS CONTRACT. D. SPACE ALLOCATIONS FOR MATERIALS, EQUIPMENT AND DEVICES HAVE BEEN MADE ON THE BASIS OF PRESENT AND KNOWN FUTURE REQUIREMENTS AND THE DIMENSIONS OF ITEMS OF EQUIPMENT OR DEVICES OF A PARTICULAR MANUFACTURER WHETHER INDICATED OR NOT. THE CONTRACTOR SHALL VERIFY THAT ALL MATERIALS, EQUIPMENT AND DEVICES PROPOSED FOR USE ON THIS PROJECT ARE WITHIN THE CONSTRAINTS OF THE ALLOCATED SPACE E ALL EXISTING SYSTEMS, EQUIPMENT OR MATERIAL. CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING THE EXISTING CONDITIONS AT THE JOB SITE BEFORE SUBMITTING PROPOSALS. SUBMISSION OF PROPOSALS SHALL BE TAKEN AS EVIDENCE THAT SUCH INSPECTION HAS TAKEN PLACE THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE COMPLETE SET OF CONSTRUCTION DOCUMENTS, AND THE LACK OF SPECIFIC INFORMATION ON THE DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR OF ANY RESPONSIBILITY. F. EQUIPMENT SHALL BE NEW AND SHALL BEAR THE U.L LABEL WHERE APPLICABLE, UNLESS NOTED OTHERWISE ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR AFTER COMPLETION AND ACCEPTANCE BY THE OWNER. G. CONTRACTOR SHALL INSTALL ELECTRICAL SYSTEMS WITHOUT INTERFERENCE AND IN STRICT COORDINATION WITH OTHER TRADES. H. MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE CONTRACT DOCUMENTS AND APPLICABLE CODES AND STANDARDS IN CASE OF DIFFERENCE BETWEEN APPLICABLE CODES AND STANDARDS AND THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL PROMPTLY NOTIFY THE ARCHITECT/ENGINEER IN WRITING OF SUCH DIFFERENCE SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE REQUIREMENTS OF APPLICABLE CODES AND STANDARDS, HE /SHE SHALL BEAR ALL COSTS ARISING IN CORRECTING SUCH DEFECTS. APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL ORDINANCES, UTILITY COMPANY REGULATIONS, AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. SHOULD THE CONTRACTOR SUPPLY EQUIPMENT DIFFERING FROM THE SPECIFIED ITEMS IN THE CONTRACT DOCUMENTS WITHOUT NOTIFICATION TO THE ENGINEER, HE SHALL BEAR ALL COSTS TO UPGRADE DEFICIENCIES ARISING FROM SUCH. I. WHERE ONLY ONE MANUFACTURER'S NAME IS LISTED IN THE EQUIPMENT SPECIFICATION, OTHER MANUFACTURERS OF SIMILAR CHARACTERISTICS AND OF EQUAL OR BETTER PERFORMANCE CAPACITIES MAY BE CONSIDERED FOR "OR EQUAL" ACCEPTANCE BY THE ENGINEER. SUBSTITUTION REQUESTS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL WHERE MORE THAN ONE MANUFACTURER IS LISTED IN THE NOTES AND EQUIPMENT SPECIFICATIONS, ONLY THOSE NAMED MANUFACTURERS WILL BE CONSIDERED FOR ACCEPTANCE SHOULD A SUBSTITUTION BE ACCEPTED, AND SHOULD THE SUBSTITUTE MATERIAL PROVE DEFECTIVE, OR OTHERWISE UNSATISFACTORY FOR THE SERVICE INTENDED WITHIN THE GUARANTEE PERIOD, THIS MATERIAL OR EQUIPMENT SHALL BE REPLACED WITH THE MATERIAL OR EQUIPMENT SPECIFIED AT NO COST TO THE OWNER. J. PROVIDE ACCESS, INCLUDING NECESSARY ACCESS DOORS, FOR NEW AND EXISTING EQUIPMENT REQUIRING OPERATION AND /OR MAINTENANCE RELOCATE EXISTING AND LOCATE ALL NEW EQUIPMENT SUCH THAT OPERATION OR MAINTENANCE IS NOT RESTRICTED. K. INSTALL EQUIPMENT WITH WORKING CLEARANCES COMPLYING WITH NEC 110-26 AND 110 -34. L SHOP DRAWING SUBMITTALS 1. CONTRACTOR SHALL PREPARE AND SUBMIT SEVEN COPIES OF ALL SUBMITTALS FOR ALL PERTINENT ELECTRICAL EQUIPMENT AND DEVICES INDICATED IN THE SCOPE OF WORK. 2. COMPLETE UST OF MATERIALS TO BE FURNISHED UNDER EACH SPECIFIC SECTION. 3. MANUFACTURERS' SPECIFICATIONS AND OTHER DATA REQUIRED TO ASSURE SPECIFICATION COMPLIANCE 4. CATALOG SHEETS, CLEARLY MARKED FOR IDENTIFICATION OF ITEMS TO BE PROVIDED, INCLUDING DISCONNECT SWITCHES, BREAKERS, FUSES, STARTERS, LIGHTING FIXTURES, TRANSFORMERS, OR OTHER MATERIAL NOT REQUIRING SPECIALLY PREPARED SHOP DRAWINGS 5. ALL SHOP DRAWING CUT SHEETS SHALL CLEARLY IDENTIFY THE SPECIFIC PRODUCT TO BE REVIEWED AND APPROVED, INCLUDING MANUFACTURER. GENERIC CUT SHEETS, INCOMPLETE CUT SHEETS AND CUT SHEETS SUBMITTED WITHOUT IDENTIFYING THE SPECIFIC PRODUCT PROVIDED, WILL BE AUTOMATICALLY REJECTED. 6. AS PART OF EQUIPMENT SHOP DRAWINGS, PROVIDE DETAILED DIMENSIONED LAYOUT DRAWINGS FOR ALL LARGE ELECTRICAL EQUIPMENT AND ELECTRICAL ROOMS WHERE NEW EQUIPMENT IS BEING INSTALLED. M. CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED FOR ALL FLOOR MOUNTED EQUIPMENT, UNLESS NOTED OR REQUIRED OTHERWISE ALL PADS SHALL BE NOT LESS THAN 3-1/2" HIGH AND EXTEND A MAXIMUM 3' BEYOND THE ACTUAL EQUIPMENT SIZE COORDINATE THE PROPER SIZE OF THE PAD WITH HE EQUIPMENT FURNISHED. PADS SHALL BE POURED IN FORMS BUILT OF NEW DRESSED LUMBER WITH CORNERS CHAMFERED USING SHEET METAL OR TRIANGULAR WOOD STRIPS NAILED TO THE FORM. USE 6X6 No. 3 MESH FOR REINFORCING. INSTALL HEAVY DUTY ADJUSTABLE ANCHOR BOLTS, SET IN THE FORM AND POSITIONED USING TEMPLATES, PRIOR TO POURING CONCRETE AFTER THE EQUIPMENT IS SET ON THE PAD, THE EQUIPMENT SHALL BE ALIGNED, LEVELED AND FULLY GROUTED TO THE PAD AND ALL VOID SPACES SHALL BE FILLED WITH A NON- SHRINKING GROUT. PERFORM ALL CONCRETE WORK SPECIFIED TO BE PROVIDED UNDER THIS DIVISION IN STRICT ACCORDANCE WITH THE APPLICABLE PROVISIONS OF DIVISION 3, CONCRETE 0. CONTRACTOR SHALL KEEP A CLEAN SET OF DRAWINGS AT THE SITE, NOTING DAILY ALL CHANGES MADE IN THESE DRAWINGS IN CONNECTION WITH THE FINAL INSTALLATION INCLUDING EXACT DIMENSIONED LOCATIONS OF ALL NEW AND UNCOVERED EXISTING UTILITIES TURN OVER A CLEAN, NEATLY MARKED SET OF REPRODUCIBLE MYLARS SHOWING "AS INSTALLED' WORK TO THE ARCHITECT FOR SUBSEQUENT REVIEW AND TRANSMITTAL TO THE OWNER. CONTRACTOR SHALL NOTE ALL CONSTRUCTION CHANGES, DATE EACH SHEET AND LABEL " AS- BUILTS' IN THE REVISION BLOCK ON THE DRAWINGS. CONTRACTOR SHALL ALSO FURNISH ONE (1) SET OF "AS- BUILT' BLUELINE PRINTS. P. IN ADDITION TO THE ABOVE, CONTRACTOR SHALL ACCUMULATE DURING THE JOB'S PROGRESS, THE FOLLOWING DATA, IN TRIPLICATE, PREPARED IN A NEAT BROCHURE OR PACKET FOLDER AND TURNED OVER TO THE ARCHITECT FOR REVIEW AND SUBSEQUENT DELIVERY TO THE OWNER. 1. ALL WARRANTIES AND GUARANTEES AND MANUFACTURER'S DIRECTIONS ON EQUIPMENT AND MATERIAL COVERED BY THE CONTRACT INCLUDING THE NAMES, ADDRESSES AND TELEPHONE NUMBERS OF THE MANUFACTURER'S REPRESENTATIVE. Z APPROVED FIXTURE BROCHURES, WIRING DIAGRAMS AND CONTROL DIAGRAMS (ORIGINAL DATA, NO COPIES). 3. COPIES OF APPROVED SHOP DRAWINGS. 4. OPERATING INSTRUCTIONS FOR ALL ELECTRICAL SYSTEM EQUIPMENT. OPERATING INSTRUCTIONS SHALL ALSO INCLUDE RECOMMENDED MAINTENANCE PROCEDURES 5. TEST REPORTS REQUIRED BY THESE SPECIFICATIONS. 6. ANY AND ALL OTHER DATA AND /OR DRAWINGS REQUIRED DURING CONSTRUCTION. 7. REPAIR PARTS LISTS OF ALL MAJOR ITEMS OF EQUIPMENT INCLUDING NAME, ADDRESS AND TELEPHONE NUMBERS OF LOCAL SUPPLIER OR AGENT. Q. ALL OF THE ABOVE DATA SHALL BE SUBMITTED TO THE ENGINEER FOR HIS REVIEW AT SUCH TIME AS THE CONTRACTOR SUBMITS HIS LAST ESTIMATE PRIOR TO HIS FINAL PAYMENT, BUT IN NO CASE, LESS THAN TWO WEEKS BEFORE FINAL INSPECTION. 16020 - ELECTRICAL WORK IN EXISTING FACILITIES A. THE CONTRACT DOCUMENTS DO NOT PROPOSE TO SHOW ALL EXISTING SYSTEMS MATERIAL OR EQUIPMENT. OBTAIN INFORMATION RELATED TO EXISTING FACILITIES FROM EXISTING DOCUMENTS, MEASUREMENTS, NOTATIONS, PHOTOGRAPHS, SURVEYS, AND OTHER OBSERVATIONS AT THE SITE B. SINCE THE BUILDING WILL CONTINUE IN USE THROUGHOUT THE CONSTRUCTION PERIOD, CARRY OUT THE WORK UNDER THIS DIVISION IN SUCH A MANNER AS TO MINIMIZE DISTURBANCE TO THE OCCUPANTS. C. REMOVE EXISTING WIRE, CONDUIT, EQUIPMENT, FIXTURES AND OTHER ITEMS TO PROVIDE ACCESS FOR WORK IN EXISTING FACILITIES. REINSTALL AND REFINISH ITEMS REMOVED, OR OTHERWISE DAMAGED, TO MATCH EXISTING ADJACENT SURFACED UPON COMPLETION OF THE WORK. D. WHERE EXISTING FUNCTIONS TO REMAIN IN USE ARE DISRUPTED, THEY SHALL BE FULLY RESTORED AFTER DISRUPTION, IN FULL COMPLIANCE WITH THIS DIVISION OF THE SPECIFICATIONS FOR NEW WORK. E MODIFY, REMOVE OR RELOCATE MATERIALS AND ITEMS INDICATED ON THE DRAWINGS OR REQUIRED BY THE INSTALLATION OF NEW WORK. F. MAKE MINOR RELOCATIONS NECESSITATED BY THE CONDITIONS AT THE SITE OR AS DIRECTED BY THE ARCHITECT, WITHOUT ADDITIONAL COST TO THE OWNER. REPAIR AND RESTORE TO GOOD FUNCTIONAL CONDITION, EQUIPMENT, MATERIALS AND ITEMS SCHEDULED FOR RELOCATION, WHICH ARE DAMAGED DURING DISMANTLING OR REASSEMBLY OPERATIONS. NEW MATERIALS AND ITEMS OF SIMILAR DESIGN AND QUALITY MAY BE SUBSTITUTED FOR MATERIALS AND ITEMS INDICATED TO BE RELOCATED UPON APPROVAL OF SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. REMOVE CAREFULLY, IN REVERSE ORDER TO ORIGINAL ASSEMBLY OR PLACEMENT, ITEMS WHICH ARE TO BE RELOCATED. PROTECT ITEMS UN11L RELOCATION IS COMPLETE CLEAN AND REPAIR ITEMS TO BE RELOCATED, AND PROVIDE NEW MATERIALS, FITTINGS AND APPURTENANCES REQUIRED TO COMPLETE THE RELOCATIONS AND TO RESTORE TO GOOD OPERATING. ORDER. PERFORM THE RELOCATION WORK IN ACCORDANCE WITH APPLICABLE: PORTIONS OF THESE SPEgFlCATIONS, UTILI ZING SKILLED WORKERS. 16110 - SYSTEMS OF RACEWAYS A. CONDUIT 1. RIGID STEEL CONDUIT (GRC - GALYANIZED RIGID CONDUIT): CONSTRUCTED OF MILD STEEL PIPING, GALVANIZED INSIDE AND OUTSIDE, CONFORMING WITH FED. SPEC. WW- -581E, ANSI C80.1 AND UL 6, 2. INTERMEDIATE METAL CONDUIT (IMC): CONSTRUCTED OF ZINC COATED STEEL TUBING MANUFACTURED IN ACCORDANCE WITH FED. SPEC. WW-C- 581 -E, UL -1242 AND MEE- NG THE REQUIREMENTS OF THE NEC. 3. ELECTRIC METALLIC TUBING (EMT): CONSTRUCTED OF HIGH GRADE STEEL MANUFACTURED SPECIFICALLY TO STANDARDS ASSURING MAXIMUM WIRING CHARACTERISTICS AND DUCTILITY, AND SHALL CONFORM TO FED. SPEC. WW- C- 563-A, ANSI CEID-3, AND UL 797. 4. LIQUIDTIGHT FLEXIBLE CONDUIT- FLEXIBLE METAL CONDUIT AS SPECIFIED HEREIN WITH A COPPER GROUNDING STRAND AND FACTORY - APPLIED NEOPRENE JACKET. LIQUID TIGHT FLEXIBLE CONDUIT SHALL BE UL LISTED, EQUIVALENT TO ANACONDA "SEALTITE", TYPE UA. 6. INSTALLATION OF CONDUIT a. ALL INTERIOR RACEWAYS SHALL BE EMT. RACEWAYS IN DAMP OR WET LOCATIONS, OR IN HAZARDOUS LOCATIONS, SHALL BE GRC OR IMC. b. CONDUITS SHALL BE OF SUCH SIZE AND SO INSTALLED THAT THE CONDUCTORS MAY BE DRAWN THROUGH WITHOUT INJURY OR EXCESSIVE STRAIN, SHALL BE SECURED AT CABINETS AND BOXES WITH GALVANIZED LOCKNUTS, BOTH INSIDE AND OUTSIDE, AND SHALL HAVE APPROPRIATE BUSHINGS INSIDE BUSHINGS SHALL BE INSULATING TYPE WITH BOND GROUND CAMPS. a USE LENGTHS OF FLEXIBLE METAL CONDUIT NOT LESS THAN 12 INCHES LONG AT FINAL CONNECTIONS TO ALL MOTORS, TRANSFORMERS AND SIMILAR DEVICES SUBJECT TO MOVEMENT BECAUSE OF VIBRATION OR MECHANICAL ADJUSTMENT. USE FLEXIBLE METAL CONDUITS TO EFFECT FINAL CONNECTIONS TO RECESSED LIGHTING FIXTURES (6FT MAX). USE LIQUID TIGHT FLEXIBLE METAL CONDUIT, WITH APPROPRIATE CONNECTIONS, IN DAMP OR WET LOCATIONS, AT MOTOR OR EQUIPMENT LOCATIONS IN MECHANICAL EQUIPMENT ROOMS, AT OR NEAR PUMPS, AND WHEN INSTALLED OUTDOORS d. GROUND METALLIC CONDUITS AS REQUIRED BY NEC. 7. INSTALLATION OF UNDERGROUND CONDUIT a. INSTALL UNDERGROUND FEEDER CONDUCTORS IN RIGID NONMETALLIC CONDUIT (PVC), U.N.O. INSTALL AT LEAST 30 INCHES BELOW FINISHED GRADE U.N.O. ON A BED OF SAND BEFORE CONTINUING BACKFlLL b. WHERE CONDUIT ENTERS INTO PULL OR JUNCTION BOXES AND AT ALL BENDS, CHANGE FROM PVC TO RIGID GALVANIZED STEEL CONDUIT BELOW GRADE a PROVIDE A PULL BOX OF APPROPRIATE SIZE EVERY 500 FEET OF STRAIGHT RUN AND AT EVERY 90 DEGREE BEND. B. COUPLINGS AND TERMINATORS 1. FOR RIGID STEEL OR INTERMEDIATE METAL CONDUIT: FACTORY- MADE THREADED COUPLINGS OF SAME MATERIAL AS THE CONDUIT. 2. FOR ELECTRICAL METALLIC TUBING, USE STEEL COMPRESSION COUPLINGS AND NYLON INSULATED GROUNDING BUSHINGS. 3. FOR FLEXIBLE METAL CONDUIT: COUPLI NGS AT CONNECTIONS BETWEEN FLEXIBLE CONDUIT AND EMT, AND NYLON INSULATED THROAT STEEL CONNECTORS AT BOX OR CABINET TERMINATIONS. 4. SCREW COUPLINGS; STEEL SET SCREW BOX CONNECTORS WITH NYLON INSULATED THROAT AND LOCKNUTS AT ALL BOXES AND CABINET TERMINATIONS OR NON - INSULATED BOX CONNECTOR, LOCKNUT AND NYLON - INSULATED GROUNDING BUSHING ON ALL TUBING WHERE GROUNDING BUSHINGS ARE REQUIRED. C. JUNCTION AND PULL BOXES 1. SIZE BOXES IN ACCORDANCE WITH THE REQUIREMENTS OF THE NEC. BOXES SHALL BE UL LISTED AND NO SMALLER THAN 4 INCHES SQUARE BY 1 -1/2 INCHES DEEP WITH COVERS ACCESSIBLE AT ALL TIMES SET BOXES ON CONCEALED CONDUITS WITH COVERS FLUSH WITH THE FINISHED WALL OR CEILING LINE PROVIDE JUNCTION AND PULL BOXES OF APPROPRIATE DIMENSIONS FOR CONDUITS AND CONDUCTORS NOTED, WHERE SHOWN AND WHERE NECESSARY FOR THE INSTALLATION AND PULLING OF CABLES AND WIRES INSTALL COVERS ON JUNCTION BOXES AND CONDULETS AFTER WIRING AND CONNECTIONS ARE COMPLETED. 2. ALL JUNCTION AND PULL BOXES FOR EMERGENCY SYSTEMS AND LOW VOLTAGE SYSTEMS SHALL HAVE COVER PLATES PAINTED. COLORS FOR COVERS SHALL BE YELLOW (LIFE SAFETY BRANCH), ORANGE (CRITICAL BRANCH), GREEN (EQUIPMENT SYSTEM), RED (FIRE ALARM), AND BROWN (DATA/TELEPHONE). 3. INSTALLATION OF PULL AND JUNCTION BOXES a. FASTEN ALL BOXES SECURELY TO THE BUILDING CONSTRUCTION, INDEPENDENT OF CONDUIT SYSTEMS b. ON CONCEALED CONDUIT SYSTEMS WHERE BOXES ARE NOT OTHERWISE ACCESSIBLE, SET BOXES FLUSH WITH FINISHED SURFACES FOR ACCESS, AND PROVIDE OVERLAPPING COVERS. C. ALL WIRING DEVICES FACEPLATES SHALL BE ENGRAVED WITH THE PANELBOARD DESIGNATION AND CIRCUIT NUMBER SERVING THE OUTLET. LABEL TAPE WILL NOT BE ACCEPTABLE D. PULL CORDS 1. PROVIDE A NYLON POLYETHYLENE CORD, WITH A TENSILE STRENGTH OF NOT LESS THAN 200 POUNDS, IN EACH EMPTY CONDUIT TO FACILITATE THE FUTURE INSTALLATION OF CONDUCTORS INCORPORATE PLASTIC TAGS FOR IDENTIFICATION. 16120 - SYSTEM OF CONDUCTORS A. CONDUCTORS SHALL BE 98% CONDUCTIVITY SOFT DRAWN ANNEALED COPPER, 600 VOLT, THHN/THWN INSULATION, #10 AND SMALLER - SOLID, #8 AND LARGER - STRANDED. B. NO CONDUCTORS SHALL BE SMALLER THAN NO. 12, EXCEPT FOR SIGNAL OR CONTROL CIRCUITS AND FOR INDIVIDUAL LIGHTING FIXTURE TAPS AS PERMITTED BY NEC. C. FOR HOME RUNS ON 120 -VOLT, 20- AMPERE BRANCH CIRCUITS, WHERE LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 100 LINEAR FEET, USE NO. 10 CONDUCTORS. WHERE LENGTH OF RUN IS 100 LINEAR FEET OR LESS, USE NO. 12 CONDUCTORS D. FOR HOME RUNS ON 277 -VOLT, 20- AMPERE BRANCH CIRCUITS, WHERE LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 200 LINEAR FEET, USE NO. 10 CONDUCTORS. WHERE LENGTH OF RUN IS 100 LINEAR FEET OR LESS, USE NO. 12 CONDUCTORS. E. NO MORE THAN FIVE CONDUCTORS (3 PHASE, 1 NEUTRAL, AND 1 GROUND) SHALL BE INSTALLED IN A COMMON BRANCH CIRCUIT CONDUIT. F. PROVIDE COLOR CODED CABLE SYSTEM APPROVED BY OWNER. IF NONE IS REQUIRED BY OWNER, PROVIDE THE FOLLOWING COLOR CODING: a. 48OV/277 b. 208V/120 A PHASE - BROWN A PHASE - BLACK B PHASE - ORANGE B PHASE - RED C PHASE - YELLOW C PHASE - BLUE NEUTRAL - GREY NEUTRAL - WHITE GROUND - GREEN GROUND - GREEN COLOR CODING SHALL BE CONTINUOUS ON INSULATION FOR #6 AWG OR SMALLER AND CONTINUOUS OR MARKED WITH COLOR TAPE AT ALL CONNECTIONS FOR CONDUCTORS LARGER THAN /6 AWG. G. INSTALLATION OF CONDUCTORS 1. PULL NO CONDUCTORS INTO CONDUITS UNTIL ALL WORK OF A NATURE WHICH MAY CAUSE INJURY TO CONDUCTORS IS COMPLETED. 2. RUN FEEDERS IN CONTINUOUS LENGTHS, WITHOUT JOINTS OR SPLICES, INSOFAR AS PRACTICABLE 16190 - SUPPORTING DEVICES A. ACCEPTABLE MANUFACTURERS: UNISTRUT CORP., B -LINE SYSTEMS, INC., AND MIDLAND ROSS- KINDORF. B. FURNISH AND INSTALL ALL HANGERS AND SUPPORTS REQUIRED BY RACEWAY SYSTEMS. C. HANGERS SHALL BE SUPPORTED BY MEANS OF UNCOATED SOLID STEEL RODS WHICH ARE THREADED TO ALLOW VERTICAL ADJUSTMENTS. LOCK NUTS SHALL BE PROVIDED IN SUFFICIENT NUMBER AND LOCATION TO LOCK ALL ROD ADJUSTMENTS PERMANENTLY AT THE ADJUSTED HEIGHT. TWO LOCK NUTS SHALL BE USED UNLESS THE NUT TIGHTENS AGAINST A THREADED SOCKET. MINIMUM ROD DIAMETERS SHALL BE AS FOLLOWS: NOMINAL CONDUIT SIZE ROD DIAMETER 1/2- THROUGH 2" 1/4- 2 -1/2" THROUGH 3" 3/8" 4" AND 5' 1/2" D. HANGER SPACING SHALL BE AS REQUIRED FOR PROPER SUPPORT OF RACEWAY, BUT IN NO CASE SHALL BE LESS THAN ONE HANGER PER 8' -0' OF RACEWAY LENGTH EXCEPT THAT CONDUIT LESS THAN 1' DIAMETER SHALL BE SUPPORTED AT LEAST EVERY 6' -0'. E WHERE NUMEROUS CONDUITS ARE RUN PARALLEL TO ONE ANOTHER, THEY MAY BE SUPPORTED FROM A TRAPEZE TYPE HANGER ARRANGEMENT WITH STRUT BOTTOM. F. SUPPORT OF HANGERS SHALL BE BY MEANS OF SUFFICIENT QUANTITIES OF INDIVIDUAL AFTER SET STEEL EXPANSION SHIELDS, OR BEAM CLAMPS ATTACHED TO STRUCTURAL STEEL G. STIFF -LEGS SHALL BE FURNISHED AND INSTALLED IN CASES WHERE SUPPORT FROM OVERHEAD STRUCTURE IS NOT POSSIBLE H. FURNISH AND INSTALL COMPLETE ANY ADDITIONAL STRUCTURAL SUPPORT STEEL, BRACKETS, FASTENERS, ETC. AS REQUIRED TO ADEQUATELY SUPPORT ALL RACEWAY AND EQUIPMENT. I. SUPPORT OF HANGERS FROM CONCRETE SLABS SHALL BE BY MEANS OF SUFFICIENT QUANTITY OF "U" BRACKETS ATTACHED WITH AFTER SET EXPANSION SHIELDS AND BOLTS. 16195 - E.ECTIEICAL IDENTIFICATION ELECTRICAL ABBREVIATIONS A. PROVIDE ELECTRICAL IDENTIFICATION FOR THE FOLLOWING: K. INSTALLATION OF TRANSFORMERS BFC 1. SWITCHGEARS, SWITCHBOARDS, MOTOR CONTROL CENTERS, PANELBOARDS, 1. TRANSFORMERS 15KVA OR LESS SHALL BE WALL OR FLOOR MOUNTED AFG MOTOR STARTERS, CONTACTORS, DISCONNECT SWITCHES, CIRCUIT OR SUSPENDED AS INDICATED. 30KVA AND 45KVA TRANSFORMERS SHALL C BREAKERS, AND OTHER ELECTRICAL EQUIPMENT WITH NAMEPLATE BE FLOOR MOUNTED OR SUSPENDED AS INDICATED. TRANSFORMERS CB IDENTIFYING THE ITEM OF EQUIPMENT SERVING THE SAME GREATER THAN 45 KVA SHALL BE FLOOR MOUNTED. CCT 2 RACEWAYS, JUNCTION BOXES, AND PULL BOXES 2. FLOOR MOUNTED TRANSFORMERS SHALL BE SET ON A CONCRETE CCTV 3. WIRING DEVICES, WIRING, AND THREE PHASE MOTOR ROTATION. HOUSEKEEPING PAD WITH A NEOPRENE VIBRATION ISOLATING PAD. B. PROVIDE THE FOLLOWING COLOR CODING FOR ALL EQUIPMENT NAMEPLATES: 3. WALL MOUNTED AND SUSPENDED TRANSFORMERS SHALL UTILIZE EC NORMAL SYSTEM - BLACK W/ WHITE LETTERS APPROPRIATE HARDWARE BASED ON THE WEIGHT OF THE UNIT AND C. ALL NAMEPLATES SHALL INCLUDE VOLTAGE, PHASE, WIRE, BRANCH INSTALLATION LOCATION. WALL MOUNTED UNITS SHALL HAVE NEOPRENE EX OF POWER CONNECTED TO, AND SOURCE OF POWER EQUIPMENT IS VIBRATION ISOLATORS BETWEEN THE WALL AND TRANSFORMER. F FED FROM. NAMEPLATES SHALL BE LAMINATED, WHITE CORE, PLASTIC WITH 3. WALL MOUNTED AND SUSPENDED TRANSFORMERS SHALL UTILIZE F/A BEVELED EDGES, MINIMUM 1/16" THICK. LETTERING SHALL BE MACHINE APPROPRIATE HARDWARE BASED ON THE WEIGHT OF THE UNIT AND FPB ENGRAVED, NOT LESS THAN 1/4" HIGH, CUT THROUGH THE SURFACE TO INSTALLATION LOCATION. WALL MOUNTED UNITS SHALL HAVE NEOPRENE FTP THE WHITE CORE NAMEPLATES SHALL BE SECURELY ATTACHED VIBRATION ISOLATORS BETWEEN THE WALL AND TRANSFORMER. TO THE EQUIPMENT USING GALVANIZED SCREWS ADHESIVES SHALL 4. WIRING CONNECTIONS TO TRANSFORMER ENCLOSURE SHALL BE MADE G -GRD NOT BE USED. USING FLEXIBLE METAL CONDUIT WITH MINIMUM 12" LENGTH. D. IDENTIFICATION OF JUNCTION AND PULL. BOXES SHALL BE WITH A BLACK 5. PROVIDE TRANSFORMER GROUNDING IN ACCORDANCE WITH SECTION 16450. IC PERMANENT MARKING PEN ON THE TOP OF THE e X 4' JUNCTION BOX 16470 - PANELBOARDS IG COVER OR ON THE BACK OF THE OUTLET BOX COVER PLATE IDENTIFYING A. ACCEPTABLE MANUFACTURERS: CUTLER HAMMER, GENERAL ELECTRIC, OR MATV THE BRANCH CIRCUITS AND SYSTEMS WITHIN THE CONDUIT. PULL BOXES SQUARE D. MID SHALL BE PROVIDED WITH A NAMEPLATE STATING VOLTAGE AND SYSTEM B. PROVIDE TIME / CURRNET CHARACTERISTIC TRIP CURVES FOR EACH TYPE OF E RARCEWAY IDENTIFICATION SHALL BE PROVIDED AT A MINIMUM OF EVERY OVERCURRENT PROTECTIVE DEVICE 50', AT EACH END IF LESS THAN 50', AND A MINIMUM OF ONCE PER C. LIGHTING AND APPLIANCE PANELBOARDS ROOM OR SPACE THROUGH WHICH IT PASSES. 1. PANELBOARDS SHALL BE RATED 240V OR 480/277V AS INDICATED ON F. CONDUIT, RACEWAYS AND BOXES SHALL BE SPOT PAINTED. CONDUIT SHALL THE DRAWINGS CONTINUOUS MAIN CURRENT RATINGS SHALL BE AS BE IDENTIFIED WITHIN 6 INCHES OF THE BOX OR ENCLOSURE THE ENTIRE INDICATED ON THE DRAWINGS MINIMUM SHORT CIRCUIT RATINGS SHALL BOX AND COVERPLATE SHALL BE PAINTED. USE THE FOLLOWING COLOR BE AS INDICATED ON THE DRAWINGS. CODING SCHEME: 2. PROVIDE ONE (1) CONTINUOUS BUS BAR PER PHASE EACH BUS BAR NORMAL SYSTEM - WHITE SHALL HAVE SEQUENTIALLY PHASED BRANCH CIRCUIT CONNECTORS SUITABLE FOR PLUG -ON OR BOLT -ON BRANCH CIRCUIT BREAKERS. THE IN EVENT THAT THERE IS A DISCREPANCY BETWEEN THESE COLORS AND BUSSING SHALL BE FULLY RATED. PANELBOARD BUS CURRENT RATINGS THE FACILITY STANDARD. CONTRACTOR SHALL SUBMIT AN RFl REQUESTING SHALL BE DETERMINED BY HEAT -RISE TESTS CONDUCTED IN ACCORDANCE CLARIFICATION. WITH UL 67. BUSSING RATED 100 -400A SHALL BE COPPER. BUSSING RATED FOR 600A SHALL BE COPPER AS STANDARD CONSTRUCTION. 16450 - GROUNDING PANELBOARDS SHALL BE SUITABLE FOR USE AS SERVICE EQUIPMENT A. EXPOSED METALLIC PARTS OF THE ELECTRICAL SYSTEM WHICH ARE NOT WHEN APPLICATION REQUIREMENTS COMPLY WITH UL 67 AND NEC INTENDED TO CARRY CURRENT, INCLUDING SYSTEM COMPONENTS SUCH AS ARTICLES 230 -F AND G. BUSDUCTS, SWITCHBOARDS, PANELBOARDS AND RACEWAY SYSTEMS, AND 3, ALL CURRENT CARRYING PARTS SHALL BE INSULATED FROM GROUND AND INCLUDING GROUNDING AND NEUTRAL CONDUCTORS OF THE VARIOUS PHASE -TO -PHASE BY NORYL HIGH DIELECTRIC STRENGTH THERMOPLASTIC WIRING SYSTEMS, SHALL BE GROUNDED IN ACCORDANCE WITH NEC OR EQUIVALENT. REQUIREMENTS., 4, SPLIT SOUD NEUTRAL SHALL BE PLATED AND LOCATED IN THE MAINS B. PROVIDE COPPER CLAD STEEL GROUND RODS 3/4 INCH DIAMETER 10 FEET COMPARTMENT UP TO 225A SO ALL INCOMING NEUTRAL CABLE MAY BE LONG DESIGNED FOR DRIVEN INSTALLATION. OF THE SAME LENGTH. C. PROVIDE EXOTHERMIC TYPE CHEMICAL WELDED TYPE CONNECTORS FOR 5. INTERIOR TRIM SHALL BE OF DEAD -FRONT CONSTRUCTION TO SHIELD JOINING OF GROUNDING ELECTRODE CONDUCTORS TO GROUND RODS, USER FROM ENERGIZED PARTS. DEAD -FRONT TRIM SHALL HAVE GROUNDING PLATES AND SPLICING OF CONDUCTORS PROVIDE COMPRESSION PRE - FORMED TWISTOUTS COVERING UNUSED MOUNTING SPACE AND BOLTED TYPE CONNECTORS FOR JOINING OF GROUNDING ELECTRODE 6. METAL NAMEPLATES SHALL BE SECURED TO DEAD -FRONT WITH RIVETS CONDUCTORS TO GROUND BARS. OR SCREWS, STICKER OR FOIL NAMEPLATES ARE NOT PERMITTED. D. PROVIDE MECHANICAL TYPE CONNECTORS FOR JOINING OF ALL EQUIPMENT INTERIOR WIRING DIAGRAM, NEUTRAL WIRING DIAGRAM, UL USTED LABEL AND ISOLATED GROUND CONDUCTORS AND SHORT CIRCUIT CURRENT RATING SHALL BE DISPLAYED ON THE E SIZE GROUNDING CONDUCTORS IN ACCORDANCE WITH TABLES 250-66 AND INTERIOR 250 -122 OF THE NEC. 7, INTERIORS SHALL BE FIELD CONVERTIBLE FOR TOP OR BOTTOM INCOMING F. PROVIDE GROUNDING BUSHINGS ON ALL RACEWAYS TERMINATING WITHIN ALL FEED. MAIN AND SUB -FEED CIRCUIT BREAKERS SHALL BE VERTICALLY ELECTRICAL ENCLOSURES CONSTRUCTED OF SEPARATE ENCLOSURE PANELS MOUNTED. MAIN LUG INTERIORS UP TO 400A SHALL BE FIELD WHICH ARE NOT INTEGRALLY WELDED TOGETHER. PROVIDE GROUNDING CONVERTIBLE TO MAIN BREAKER. INTERIOR LEVELING PROVISIONS SHALL CONDUCTORS FROM SUCH BUSHINGS TO THE FRAME OF THE ENCLOSURE, BE PROVIDED FOR FLUSH MOUNTED APPLICATIONS. GROUND BUS AND EQUIPMENT GROUNDING STRAP WHERE ONE OCCURS. G. PROVIDE A SEPARATE GREEN - INSULATED EQUIPMENT GROUNDING CONDUCTOR, 8, MAIN BREAKERS: SHALL BE MOLDED CASE TYPE, WITH A PUSH -TO -TRIP WITH INSULATION OF THE SAME RATING AS THE PHASE CONDUCTORS, FOR BUTTON FOR MAINTENANCE AND TESTING PURPOSES. BREAKER HANDLE ALL FEEDERS AND BRANCH CIRCUITS. INSTALL THE GROUNDING CONDUCTORS AND AND FACEPLATE SHALL INDICATE RATED AMPACITY. LUGS SHALL BE IN THE RACEWAY WITH RELATED PHASE AND NEUTRAL CONDUCTORS WHERE UL LISTED TO ACCEPT SOLID OR STRANDED COPPER CONDUCTORS ONLY. PARALLEL CONDUCTORS IN SEPARATE RACEWAYS OCCUR, PROVIDE A LUGS SHALL BE SUITABLE FOR 75'C RATED WIRE GROUNDING CONDUCTOR IN EACH RACEWAY. CONNECT ALL GROUNDING 9. NEMA 1 BOXES: BOXES SHALL BE GALVANIZED STEEL CONSTRUCTED IN CONDUCTORS TO GROUND TERMINALS AT EACH END OF THE RUN, TO THE ACCORDANCE WITH UL 50. BOXES SHALL HAVE REMOVABLE ENDWALLS END THAT THERE WILL BE NO UNINTERRUPTED GROUNDING CIRCUIT FROM THE WITH KNOCKOUTS LOCATED ON ONE END. BOXES SHALL HAVE WELDED POINT OF GROUND FAULT BACK TO A POINT OF CONNECTION OF THE INTERIOR MOUNTING STUDS INTERIOR MOUNTING BRACKETS ARE NOT EQUIPMENT GROUND AND SYSTEM NEUTRAL. REQUIRED. H. CONNECT THE SECONDARY NEUTRAL POINT AND THE ENCLOSURE IN EACH 10. ENCLOSURE FINISH FOR OUTDOOR UNITS: FACTORY - APPLIED FINISH IN DRY TYPE TRANSFORMER TOGETHER AND RUN A GROUNDING ELECTRODE MANUFACTURER'S STANDARD ANSI GRAY ENAMEL OVER CONDUCTOR FROM THEIR COMMON POINT OF CONNECTION TO THE BUILDING CORROSION- RESISTANT TREATMENT OR RUST - INHIBITING PRIMER COAT, GROUNDING ELECTRODE SYSTEM. UNDERSURFACES TREATED WITH CORROSION- RESISTANT UNDERCOATING. I. PERFORM THE FOLLOWING TESTS: 11. COORDINATE THE PANELBOARD BUS RATINGS AND CIRCUIT BREAKER COORDINATION RATINGS WITH THE AVAILABLE FAULT CURRENT. 1. TEST THE CONTINUITY OF, AND THE PROPER CONNECTION OF, EACH GROUND CONDUCTOR AND SYSTEM, TO ASSURE THAT THE GROUNDING 16475 - OVERCURRENT PROTECTIVE DEVICES SYSTEM IS COMPLETE AND UNINTERRUPTED. TESTING SHALL BE A. PROVIDE DATA SHEETS SHOWING ELECTRICAL CHARACTERISTICS INCLUDING PERFORMED USING LABORATORY -- ACCURACY TEST INSTRUMENTS OF TIME- CURRENT CURVES AS PART OF THE SHOP DRAWING SUBMITTAL SUITABLE DESIGN FOR THE TESTS TO BE PERFORMED. TEST INSTRUMENTS B. FAULT CURRENT VALUES INDICATED ON THE DRAWINGS ARE BASED ON SHALL BE PROVIDED UNDER DIVKAON 16. ACTUAL AVAILABLE FAULT VALUES AT EACH SWITCHBOARD, PANELBOARD 2. TEST GROUNDING CONDUCTORS, PHASE CONDUCTORS AND NEUTRAL AND ANY OTHER SIMILAR EQUIPMENT. EQUIPMENT MANUFACTURERS SHALL CONDUCTORS FOR CONTINUITY AND FOR POSSIBLE DAMAGE TO PROVIDE EQUIPMENT AND PROTECTIVE DEVICES SUITABLY RATED FOR THE INSULATION. EACH CONDUCTOR SHALL BE TESTED FOR INSULATION FROM CONFIGURATIONS INDICATED RATE) FOR THE AVAILABLE FAULT CURRENT GROUND AND FR09 nTHER CONDUCTORS. INDICATED. SERIES RATING OF DEVICES IS NOT ACCEPTABLE 3. ANY PORTIONS OF EFHE INSTALLAT1GrNS WHICH FAIL TO PASS THESE C. CIRCUIT BREAKERS TESTS SHALL BE REPLACED, REPAIRED OR OTHERWISE CORRECTED TO 1. CIRCUIT BREAKER MANUFACTURER SHALL BE THE SAME AS THE THE SATISFACTION OF THE OWNER'S REPRESENTATIVE, AND COMPLETELY SWITCHBOARD/PANELBOARD/MOTOR CONTROL CENTER MANUFACTURER. RETESTED TO SHOW PROPER CONFORMITY. D. SELF - CONTAINED CIRCUIT BREAKER ENCLOSURES SHALL BE PADLOCKABLE 16460 - TRANSFORMERS NEMA 1, EXCEPT FOR UNITS IN DAMP OR WET AREAS WHICH SHALL BE A A. ACCEPTABLE MANUFACTURERS: CUTLER HAMMER, GENERAL ELECTRIC, OR NEMA 3R ENCLOSURE WITH CONDUIT HUBS. SQUARE D. B. TRANSFORMERS SHALL BE UL LISTED AND LABELED, AND CONSTRUCTED IN ACCORDANCE WITH NEMA STANDARDS. C. TRANSFORMER COILS SHALL BE OF CONTINUOS WOUND CONSTRUCTION AND SHALL BE IMPREGNATED WITH NONHYGROSCOPIC, THERMOSETTING VARNISH. D. TRANSFORMERS 15KVA AND LARGER SHALL BE 15O'C RISE ABOVE 40'C AMBIENT. TRANSFORMERS 25KVA AND LARGER SHALL HAVE A MINIMUM OF 4-2 1/2% FULL CAPACITY PRIMARY TRAPS. E ALL INSULATING MATERIALS SHALL BE IN ACCORDANCE WITH NEMA ST20 STANDARDS FOR 22W G UL COMPONENT RECOGNIZED INSULATION SYSTEM. TRANSFORMERS SHALL BE MANUFACTURED AND TESTED IN ACCORDANCE WITH ANSI STANDARDS C57.12.01 AND C57.12.91. F. CONSTRUCT ALL CORES OF HIGH GRADE, NON -AGING SILICON MEANS OF RUBBER, VIBRATION- ABSORBING MOUNTS. THERE STEEL WITH HIGH MAGNETIC FLUX DENSITIES WELL BELOW THE SATURATION POINT. CLAMP THE CORE LAMINATIONS TOGETHER WITH STEEL ANGLES BOLT THE COMPLETED CORE AND COIL TO THE BASE OF THE ENCLOSURE BUT ISOLATED THEREFROM BY SHALL BE NO METAL -TO -METAL CONTACT BETWEEN THE CORE AND COIL AND THE ENCLOSURE SOUND ISOLATION SYSTEMS REQUIRING THE COMPLETE REMOVAL OF ALL FASTENING DEVICES WILL NOT BE ACCEPTABLE G. VISIBLY GROUND THE CORE OF THE TRANSFORMER TO THE ENCLOSURE BY MEANS OF A FLEXIBLE GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH APPLICABLE UL AND NEC STANDARDS. H. THE TRANSFORMER ENCLOSURES SHALL BE VENTILATED AND BE FABRICATED OF HEAVY GAUGE, SHEET STEEL CONSTRUCTION. THE ENTIRE ENCLOSURE SHALL BE FINISHED UTIU2ING A CONTINUOUS PROCESS CONSISTING OF DEGREASING, CLEANING AND PHOSPHATIZING, FOLLOWED BY ELECTROSTATIC DEPOSITION OF A POLYMER POLYESTER POWER COATING AND BAKING CYCLE TO PROVIDE UNIFORM COATING OF ALL EDGES AND SURFACES THE COATING SHALL BE ANSI 49 GRAY, BAKED ENAMEL I. THE MAXIMUM TEMPERATURE OF THE TOP OF THE ENCLOSURE SHALL NOT EXCEED 50'C RISE ABOVE A 40'C AMBIENT. J. SOUND LEVELS SHALL BE WARRANTED BY THE MANUFACTURER NOT TO EXCEED THE FOLLOWING: NOTE: IT IS THE RESPONSIBILITY OF CONTRACTOR TO VISIT THE SITE AND EXAMINE IN DETAIL THE SCOPE OF WORK OF THIS PROJECT PRIOR TO BID AND SHALL NOTIFY THE ARCHITECT AND /OR ENGINEER IF A CONDITION EXISTS WHICH PREVENTS HIM/HER FROM ACCOMPLISHING THE WORK INDICATED AND INTENDED BY THESE DRAWINGS, SO NO ADDITIONAL COST IS INCURRED BY THE OWNER. AFTER CONTRACT IS AWARDED IT WILL BE ASSUMED THAT THE SITE WAS VISITED AND EXAMINED AND ALL PARTIES ARE IN AGREEMENT WITH THE SCOPE OF THE WORK. GENERAL NOTES: FLOOR PLANS A. CONTRACTOR TO COORDINATE WITH FPL FOR CONNECTION TO EXISTING TRANSFORMER. B. CONTRACTOR SHALL TRENCH SITE FOR CONDUIT INSTALLATION. CONTRACTOR SHALL COVER TRENCH WITH CLEAN FILL, COMPACT AND LEVEL FOR A COMPLETE AND OPERATIONAL INSTALLATION. C. CONTRACTOR SHALL PROVIDE TEMPORARY POWER, LIGHTING, COMM., ETC., WHERE REQUIRED DURING CONSTRUCTION SCOPE OF WORK. D. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR AND SHALL BE COORDINATED WITH OTHER TRADES E. CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY FOR THE DURATION OF THE WORK. F. CONTRACTOR SHALL PAY FOR THE PERMITS, FEES do INSPECTIONS. G. CONTRACTOR SHALL NOT DISRUPT SERVICE TO ELECTRICAL APPURTENANCES TO REMAIN. H. THE CONTRACT DOCUMENTS DO NOT PROPOSE TO SHOW ALL EXISTING SYSTEMS, MATERIAL OR EQUIPMENT. IT IS 'THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO OBTAIN DATA RELATED TO EXISTING CONDITIONS FROM EXISTING DOCUMENTS, NOTATIONS, PHOTOGRAPHS, SURVEYS AND OTHER OBSERVATIONS AT THE SITE 1. REMOVE EXISTING WIRE, CONDUIT, EQUIPMENT AND OTHER ITEMS TO PROVIDE ACCESS FOR WORK IN EXISTING FACIUTIES REINSTALL AND REFINISH ITEMS REMOVED, OR OTHERWISE DAMAGED, TO MATCH EXISTING AT NO ADDITIONAL COST TO OWNER. J. WHERE EXISTING FUNCTIONS TO REMAIN IN USE ARE DISRUPTED, THEY SHALL BE FULLY RESTORED AFTER DISRUPTION, IN FULL COMPLIANCE WITH APPLICABLE CODES AND STANDARDS. K. MAKE RELOCATION NECESSITATED BY THE CONDITIONS AT THE SITE, WITHOUT ADDITIONAL COST TO THE OWNER. REPAIR, REPLACE AND /OR RESTORE TO GOOD FUNCTIONAL CONDITION, EQUIPMENT, MATERIAL AND ITEMS SCHEDULE FOR RELOCATION, WHICH ARE DAMAGED DURING DISMANTLING OR REASSEMBLE OPERATIONS PROVIDE NEW MATERIALS, FITTINGS AND APPURTENANCES REQUIRED TO COMPLETE THE RELOCATION AND TO RESTORE TO GOOD OPERATING ORDER. PERFORM THE RELOCATION WORK IN ACCORDANCE TO APPLICABLE CODES ASO STANDARDS, USING SKILLED WORKERS, L CONTRACTOR SHALL KEEP A CLEAN SET OF DRAWINGS ON THE JOB, NOTING DAILY, ALL CHANGES MADE IN THESE DRAWINGS IN CONNECTION WITH THE DEMOLITION PHASE, INCLUDING EXACT DIMENSIONED LOCATIONS OF ALL UNCOVERED EXISTING UTILITIES AND SHALL, WITH THIS, REQUEST FOR FINAL PAYMENT. TURN OVER A CLEAN, NEATLY MARKED SET OF REPRODUCIBLE MYLARS SHOWING "EXISTING CONDITTI,IS" WORK TO THE ARCHITECT FOR SUBSEQUENT REVIEW AND TRANSMITTAL TO THE OWNER. CONTRACTOR SHALL NOTE ALL CONSTRUCTION CHANGES, DATE EACH AND LABEL " AS- BUILTS" IN THE REVISION BLOCK ON THE DRAWINGS. CONTRACTOR SHALL ALSO FURNISH ONE SET OF "AS- BUILTS" BLUEPRINTS. NONFUSED NOT IN CONTRACT NIGHT LIGHT NORMALLY OPEN RECEPTACLE(S) PAGING PANEL SPACE ONLY SPARE SPEAKER SECURITY SUPPORT CABINET SHUNT TRIP SWITCH SWITCHBOARD SWITCHGEAR UNDERFLOOR UNDERGROUND UNLESS NOTED OTHERWISE VARIABLE AIR VOLUME WIRE GUARD WEATHERPROOF TRANSFORMER ARCHITECT. BERMELLO AJAMIL & PARTNERS, INC. H,,chitPL;'u,re Engillaering Planning Interior Design Landscape Architecture 2601 Gout:l Baysho. e D. ive 10th Floor Miami, Florida 33133 (305) 859 -2050 Fax (305) 860 -3700 PLANNING ARCHITECT: 11TAN NIZIN WILMOT SANZ A R C H I T E C T U R E P L A N N I N G 10;s1 � V� 0010 301- aY0 -ZY00 3014 -40 -0150 STRUCTURAL ENGINEER: Q� RAMON R. DONNELLL P ❑PEDRO J. DUQUESNE P.EE. 000222n7�64 ❑AIDA M. ALBAISA PE. 8(45190 493 S.W. 74th CT. MIAMI, LOR A 33155 1306 666 -0711 FAX 666 -6259 STATE OF FLORIDA - AUTHORIZATION No. 1230 MEP ENGINEER: 2121 Po � nce de Leon Blvd., Suite 350 Coral Gables, FL 33134 Professional Consulting Engineers phone: 305.569.1692 fax: 305.569,1 693 Dallas • Houston • Nashville • Miami . Richmond Austin • Denver • Phoenix • Washington D.C. ccrd project number: 410336.000 EB00007658 IT CONSULTANT: VGENE BURTON & ASSOCIATES General George Patton Drive 5840 West 1 -20, Suite 150 lin,'Perrnesse, 37067 Arlington,'1exas 76017 : 615.376.3100 Phune :817.563.2486 615.776.3114 T :817.563.2757 te: www.gbaino.com Medical Equipment and Communications Planners \ l%l l l l l I 1/`!111!/`` ",-,, `'\ ly , , ,",N 1 N 57 2 � = -0 UJ F OFD r �� ��/zNI -1 0 IN AL �� 2010 DOUG CALHOUN PE #57882 PERMIT SET REVISIONS: PROJECT NAME: SOUTH MIAMI HOSPITAL SITE PREPARATION PACKAGE PROJECT ADDRESS: 7400 S.W. 62nd Ave. South Miami, Florida 33143 KEY PLAN ELECTRICAL ABBREVIATIONS AFF ABOVE FINISHED FLOOR NF BFC BELOW FINISHED CEILING NIC AFG ABON E FINISHED GRADE NL C CONDUIT NO (N.O.) CB CIRCUIT BREAKER RCPT(S) CCT CIRCUIT PA CCTV CLOSED CIRCUIT TELEVISON PNL CPT CONTROL POWER TRANSFORMER SO (S.O.) EC EMPTY CONDUIT SP EP EXPLOSION PROOF SPKR EX EXISTING SSC F FUSE ST (S.T.) F/A FIRE ALARM SW FPB FAN POWERED BOX SWBRD FTP FIRE ALARM TERMINAL/ SWGR TRANSPONDER CABINET OF G -GRD GROUND (EQUIPMENT) UG GFI (GFCI) GROUND FAULT INTERRUPTER UNO(U.N.O.) IC INTERRUPTING CAPACITY VAV IG ISOLATED GROUND WG MATV MASTER ANTENA TELEVISION WP MID MOUNT OR MOUNTED XFMR NC (N.C.) NORMALLY CLOSED NONFUSED NOT IN CONTRACT NIGHT LIGHT NORMALLY OPEN RECEPTACLE(S) PAGING PANEL SPACE ONLY SPARE SPEAKER SECURITY SUPPORT CABINET SHUNT TRIP SWITCH SWITCHBOARD SWITCHGEAR UNDERFLOOR UNDERGROUND UNLESS NOTED OTHERWISE VARIABLE AIR VOLUME WIRE GUARD WEATHERPROOF TRANSFORMER ARCHITECT. BERMELLO AJAMIL & PARTNERS, INC. H,,chitPL;'u,re Engillaering Planning Interior Design Landscape Architecture 2601 Gout:l Baysho. e D. ive 10th Floor Miami, Florida 33133 (305) 859 -2050 Fax (305) 860 -3700 PLANNING ARCHITECT: 11TAN NIZIN WILMOT SANZ A R C H I T E C T U R E P L A N N I N G 10;s1 � V� 0010 301- aY0 -ZY00 3014 -40 -0150 STRUCTURAL ENGINEER: Q� RAMON R. DONNELLL P ❑PEDRO J. DUQUESNE P.EE. 000222n7�64 ❑AIDA M. ALBAISA PE. 8(45190 493 S.W. 74th CT. MIAMI, LOR A 33155 1306 666 -0711 FAX 666 -6259 STATE OF FLORIDA - AUTHORIZATION No. 1230 MEP ENGINEER: 2121 Po � nce de Leon Blvd., Suite 350 Coral Gables, FL 33134 Professional Consulting Engineers phone: 305.569.1692 fax: 305.569,1 693 Dallas • Houston • Nashville • Miami . Richmond Austin • Denver • Phoenix • Washington D.C. ccrd project number: 410336.000 EB00007658 IT CONSULTANT: VGENE BURTON & ASSOCIATES General George Patton Drive 5840 West 1 -20, Suite 150 lin,'Perrnesse, 37067 Arlington,'1exas 76017 : 615.376.3100 Phune :817.563.2486 615.776.3114 T :817.563.2757 te: www.gbaino.com Medical Equipment and Communications Planners \ l%l l l l l I 1/`!111!/`` ",-,, `'\ ly , , ,",N 1 N 57 2 � = -0 UJ F OFD r �� ��/zNI -1 0 IN AL �� 2010 DOUG CALHOUN PE #57882 PERMIT SET REVISIONS: PROJECT NAME: SOUTH MIAMI HOSPITAL SITE PREPARATION PACKAGE PROJECT ADDRESS: 7400 S.W. 62nd Ave. South Miami, Florida 33143 KEY PLAN SHEET NO. E0.00 0 COMM. NO. 40057.100 SCALE: AS NOTED GITY OF: 80!yt, -�1 mli,,�Iii DATE: 6.24.10 l'(, ;I(,. (,)jt4G OE.tYT, DRAWN: CHECKED: ER ,arrw � rJ,�l' AL. SFCTI,01" CADD FILE: HANSTITUTIONAL I DRAWING TITLE: t y7'I�1d, V%L iY: _ . . Ir ,,)/ CONSTRUCTION * . TRAILER PLAN SHEET NO. E0.00 0