10-559-007• • LAYOUT `` \� • Ee Eo FLOOR PLAN —POWER LAYOUT SCALE. 1/4!'= 1'-0" Ee Eo ELECTRICAL NOTES FART I - GENERAL 1.1 GENERAL: THE GENERAL AND SPECIAL CONDITIONS AND REQUIREMENTS OF THE CONTRACT AND SPECIFICATIONS AS WELL AS PLANS AND SPECIFICATIONS OF OTHER DISCIPLINES AND TRADES SHALL APPLY AND BE PART OF THE WORK HEREBY SPECIFIED. THESE SPECIFICATIONS AND THE ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE COMPLETE FURNISHING AND INSTALLATION OF THE ELECTRICAL SYSTEMS. 'PROVIDE' MEANS 'FURNISH AND INSTALL'. 12 COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH NEC 2008, WPA -101 2006, NFPA -99 2005, ADA GUIDELINES 2006, FBC 2001 WITH 2009 SUPLEMENT, NFPA -12 2002 AND THE LATEST ADOPTED EDITIONS OF OSHA, HRS, HEALTH AGENCIES, AHCA, SOUTH MIAMI HOSPITAL DESIGN GUIDELINES AND OTHER APPLICABLE NATIONAL, STATE, AND LOCAL CODES AND PERTAINING REGULATIONS ESTABLISHED BY RULING AUTHORITIES HAYING JURISDICTION. CONTRACTOR SHALL ALSO MEET OTHER RECOGNIZED STANDARDS AND REQUIREMENTS WHERE SUCH ARE MORE $TRIt -sENT THAN THOSE CITED ABOVE. 13 WORKMANSHIP: ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN 'THEIR RESPECTIVE DISCIPLINES. WORK SHALL BE DONE IN A FIRST CLASS MANNER FULLY OPERATIVE, AND TO THE ACCEPTANCE OF THE ARCHITECT/ENGINEER CONTRACTOR SHALL PROVIDE FOR ALL NECESSARY LABOR AND MATERIALS REQUIRED FOR COMPLETION OF THE WORK INCLUDING BUT NOT LIMITED TO CONNECTIONS TO RELATED WORK SUCH AS CONNECTION TO EXISTING SYSTEMS, EXCAVATIONS AND BACKFILLNG. 1.4 MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS OF AMERICAN MANUFACTURE, BEARING THE UNOERlJRITER'S LABORATORY (UL) LABEL AS APPLICABLE. MATERIALS SHALL BE ACCEPTABLE AND ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR ON PLANS. SUPPLEMENTAL MATERIALS, PRODUCTS AND COMPONENTS NECESSARY TO COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS AND /OR SPECIFICATIONS, BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, SHALL BE PROVIDED BY CONTRACTOR AS REQUIRED FOR COMPLETION OF THE WORK AT NO ADDITIONAL COST TO THE OWNER CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISIONS AND COORDINATION OF DELIVERY OF MATERIALS. EQUIPMENT MARRED OURIWs SHIPMENT OR INSTALLATION SHALL BE TOUCHED UP AND REFINISHED TO FACTORY FINISH, REPLACED WHERE NOT ACCEPTABLE. 15 MFe 11T$ 4 INSURANCE: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF COMPLETE ELECTRICAL SYSTEMS AS OUTLINED HEREIN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK 16 EXISTING CONDITIONS: BEFORE BIDDING CONTRACTOR SHALL VISIT tHE JOB SITE AND ASCERTAIN ALL EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIAL OR LABOR ANY EXISTING CONDITION FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. UTILITY COMPANIES: BEFORE SUBMITTING BID CONTRACTOR SHALL CHECK WITH WATER SEWER GAS, ELECTRICAL, TELEPHONE, CABLE TV AND OTHER UTILITY COMPANIES SUPPLYING SERVICE TO THIS INSTALLATION TO DETERMINE INSTALLATION STANDARDS AND EQUIPMENT REQUIREMENTS AND COSTS TO BE INCLUDED IN THE BID. EXCEPT WHERE UTILITY REQUIREMENTS CHANCsE AFTER SUBMITTAL, NO EXTRA PAYMENT WILL BE MADE TO THE CONTRACTOR FOR SUCH ITEMS. PROVIDE TEMPORARY ELECTRICAL SERVICES FOR ALL TRADES AS REQUIRED. 18 PLANS- DRAWINGS ARE GENERALLY DIAGRAMMATIC, INTENDED TO SHOW APPROXIMATE EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL. PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS. L9 INTERFERENCE: CONTRACTOR SHALL C00RONATE HIS WORK WITH THE WORK OF OTHER TRADES SO THAT INTERFERENCES WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL, STRUCTURAL MEMBERS WILL BE AVOIDED. 1,10 SHOP DRAWINGS= PRIOR TO PLACING AN ORDER AND BEFORE INSTALLATION, SUBMIT FOR REVIEW PROPERLY IDENTIFIED AND BOUND SHOP DRAWINGS AND MANUFACTURER'S LITERATURE GIVING SPECIFICATIONS, DETAILS, COMPLIANCE, UL APPROVAL, MATERIALS, FINISHES, ACCESSORIES AND INSTALLATION DIRECTIONS WHERE REQUIRED OF THE EQUIPMENT SPECIFIED. FACTORY CERTIFIED PRINTS SHALL BE FURNISHED FOR ALL MAJOR ITEMS OF EQUIPMENT AND SPECIFIED. SUBMISSION OF EQUIPMENT FOR APPROVAL SHALL BE MADE COMPLETE AND ALL AT THE SAME TIME. 1,11 SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME AND /OR CATALOG NUMBERS ESTABLISH A STANDARD OF QUALITY, APPEARANCE, PERFORMANCE AND DIMENSION. CONTRACTOR SHALL BASE HIS PROPOSAL ON THOSE ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF BIDDING REQUESTS FOR SUBSTITUTIONS SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT/ENGINEER DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND BASIC DESIGN, CONSTRUCTION STANDARDS AND WARRANTIES, DIMENSIONS TO FIT WITHOUT CHANGE, AND DOES NOT CAUSE EXTRA WORK FOR OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVING EQUALITY OF SUBSTITUTIONSt ARCHITECT/ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE SUCH ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM. ARCHITECT/ENGINEER EXPENSES INCURRED DUE TO CONTRACTOR'S REQUESTED REVISIONS OR SUBSTITUTIONS SHALL BE PAID BY CONTRACTOR UI2 GUARANTEES: AFTER THE SYSTEM IS INSTALLED, THE CONTRACTOR SHALL CONDUCT AN OPERATIVE TEST FOR APPROVAL AND ACCEPTANCE BY THE ARCHITECT /OWNER ENTIRE ELECTRICAL WORK, INCLUDING PARTS AND LABOR SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL WRITTEN ACCEPTANCE THEREOF AGAINST DEFECTIVE MATERIALS, CONSTRUCTION AND WORKMANSHIP. WHERE APPLICABLE, LONGER GUARANTEES FOR CERTAIN COMPONENTS SHALL APPLY AS REQUIRED AND NOT BE REDUCED IN ANY WAY. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE TO THE OWNER AND SHALL INCLUDE REPLACEMENTS AND /OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. L13 RECORD DRAWINGS: MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL CHANGES. USE COLORED PENS TO MARK CHANGES AT THE TIME OF EXECUTION AND DELIVER THE SET TO ARCHITECT/ENGINEER UPON COMPLETION. CONTRACTOR SHALL _ STAMP 'AS BUILT' ON PRINTS AND PLANS, DATE AND SIGN IN INK FART 2 - PRODUCTS 2J SHOP DRAWINGS: SUBMIT SHOP DRAWINGS OF THE FOLLOWING PRODUCTS: A. PANELBOARDS, OVERCURRENT PROTECTION DEVICES, CIRCUIT BREAKERS, SWITCHES, FUSES. B. WIRING, CABLING, CONDUITS, RACEWAYS, FLOOR AND OUTLET BOXES. C. WIRING DEVICES: RECEPTACLES, OUTLETS, LIGHT SWITCHES, DIMMERS, PLATES, PLUGMOLDS. D. LIGHTING FIXTURES, LAMPS, POLES AND RELATED HARDWARE, E. TIMECLOCKS, PHOTOCELLS AND CONTACTORS. 2.2 LIGHTING FIXTURES SHALL BE COMPLETE WITH ALL NECESSARY LAMPS, BALLASTS, WIRING, LAMP HOLDERS REFLECTORS, GLASSWARE, POLES, BASES AND MOUNTINGS ACCESSORIES AS REQUIRED TO PROVIDE FOR A COMPLETE INSTALLATION. LIGHTING FIXTURES SHALL BE SELECTED BY ARCHITECT /OWNER PROVIDED BY CONTRACTOR REFER TO ARCHITECTURAL DRAWINGS FOR COLOR FINISH AND EXACT MOUNTINGS DETAILS. 20A, 120V, DUPLEX RECEPTACLE - q PHONE 4 DATA OWLET - Ln LIGHT SWITCH .�_ 21X4I FLUCINWENT LAMP O CONNECTED TO NORMAL CIRCUIT 2'X4' FLUONSICENT LAMP CONNECTED TO EMER3ENCY CIRCUIT 23-a:'-ICES SHALL BE MADE WITH UL LISTED MECHANICAL PRESSURE SOLDERLESS CONNECTORS, BURNDY SERVITS TYPE OR APPROVED EQUAL. FEEDER SPLICES AND r n_- e d w a r d I e W i s TERMINATIONS SHALL BE MADE MECHANICALLY USIWs COMPRESSION TYPE SLEEVES OR LUGS AND CONNECTION TO PANELS AND SWITCHES AS MANUFACTURED BY BURNDY OR a r c h i t e c t s THOMAS 4 BETTS. 2.4 RACEWAYS: A, R3S AND IMC: HOT- DIPPED GALVANIZED INCLUDING THE THREADS. PROVIDE FOR EXTERIOR LOCATIONS, WHERE EXPOSED TO PHYSICAL DAMAGE AND FOR ELBOWS, ELLS AND RISERS INTO GROUND AND SLAB_ INSTALL ELLS AND RISERS STUBBED UP 6 INCHES FROM CONCEALED SLAB RUNS, 48' ABOVE GROUND WHERE EXPOSED ON WALL. PAINT RACEWAYS BELOW SLAB OR FINISHED EXTERIOR GRADE WITH TWO (2) COATS OF BITUMASTIC PAINT UP TO A POINT 2' ABOVE SLAB. B. EMT: MAY BE USED FOR INTERIOR SPACES IN DRY LOCATIONS, WHEN NOT EXPOSED TO PHYSICAL DAMAGE. FITTINGS SHALL BE STEEL. C. PVC SCHEDULE 40: MAY BE USED WHERE CONDUIT IS RUN IN CONCRETE SLABS WITH 4' COVER 12' BELOW SLAB, WHERE BURIED 24' BELOW FINISHED GRADE AND 30' UNDER VEHICULAR TRAFFIC AREAS. D. FLEXIBLE METALLIC CONDUIT: LIGHTING FIXTURES, MOTORS, TRANSFORMERS AND VIBRATING EQUIPMENT CONNECTIONS IN LENGTHS NOT TO EXCEED IS'. PVC JACKETED FLEXIBLE METAL CONDUIT FOR LOCATIONS OUTSIDE AND /OR EXPOSED TO MOISTURE. GREENFIELD OR APPROVED EQUAL. E. RUNS BELOW SLAB SHALL BE PROVIDED WITH A YELLOW RIBBON TAPED ALONG TRENCH 6' BELOW GRADE FOR RACEWAY IDENTIFICATION. 2.5 CONDUCTORS: SOFT -DRAWN SS CONDUCTIVITY COPPER INSTALLED IN CONDUIT. MINIMUM SIZE SHALL BE 012 FOR POWER WIRING AND 016 FOR CONTROL CIRCUITS, 014 FOR 15A CIRCUIT BREAKERS WHERE INDICATED. PROVIDE 010 WIRES FOR 120V POWER CIRCUIT HOMERUNS LONGER THAN 100 FEET. INSULATION SHALL BE 600V THI- N/THWN FOR GENERAL USE, THW IN SIZES 06 AND ABOVE, COLOR CODED THROUGHOUT PER NEC AND TRADE STANDARDS. WIRING IN DUCTS, PLENUMS AND OTHER AIR HANDLING SPACES SHALL COMPLY WITH NEC 300 -22. WHERE PREVIOUSLY APPROVED BY OWNER ENGINEER AND RULINGS AUTHORITIES, NONMETALLIC SHEATHED CABLE MAY BE USED FOR BRANCH CIRCUITS PER NEC 336. 2b WIRING DEVICES SHALL BE HOSPITAL OR COMMERCIAL SPECIFICATION GRADE AS REQUIRED, FLUSH MOUNTED, MANUFACTURED BY HUBBELL, SLATER OR LUTRON. A. SWITCHES: TOGGLE TYPE, 20A 120nllV, SINGLE POLE, THREE -WAY WHEN NOTED. SWITCHES SHALL BE HEAVY DUTY FULL SIZE. B. DIMMERS: LINEAR ON/OFF TYPE, RATED 20A 600W MINIMUM FOR GENERAL AREA, 1000W FOR OTHER AREAS NOTED. C. RECEPTACLES: 20A 120V GROUNDNG TYPE DUPLEX, HOSPITAL GRADE. SPECIAL OUTLETS RATED TO MATCH CIRCUIT BREAKERS AS NOTED ON PLANS. QUADRUPLEX OUTLETS AND SWITCH /OUTLET COMBINATIONS SHALL HAVE THE SAME FACE PLATE. ISOLATED GROUND TYPE SHALL BE PROVIDED WITH SEPARATE ISOLATED GROUND WIRE. D. ELEPHONE AND DATA OUTLETS: TELEPHONE/DATA JACKS AND WIRING AS SELECTED BY OWNER UNLESS OTHERWISE NOTEDt OTHERWISE, PULL WIRE WITH 12' SLACK AT EACH END, RUN N 3/4' EMPTY CONDUIT. E. MOUNTING HEIGHTS: WHERE NOT ESTABLISHED ON PLANS OR LEGEND BY ARCHITECT OR EQUIPMENT MANUFACTURERS, MOUNTING HEIGHT SHALL BE AS FOLLOWS: MH - IWAFF - GENERAL AREA RECEPTACLES AND TELEPHONE OUTLETS. MH - 42'AFF - COUNTER RECEPTACLES AND TELEPHONE OUTLETS. MH - 3WAFF - OTHER EQUIPMENT OUTLETS. MH a 48'AFF - SWITCHES AND DIMMERS. MH - 52'AFF - WALL MOUNTED PHONES F. ALL DEVICE PLATES SHALL BE PERMANENTLY ENGRAVED WITH PANEL AND CIRCUIT NUMBER SUPPLYING THE DEVICE. G. RECEPTACLES AND LIGHTS ON EMERGENCY POWER SHALL HAVE RED FACEPLATE$. FART 3 - EXECUTION - 3.1 TESTS: PROVIDE ALL NECESSARY INSTRUMENTS AND SPECIAL APPARATUS TO CONDUCT ANY TESTS THAT MAY BE REQUIRED TO INSURE SYSTEM IS FREE OF ALL IMPROPER GROUNDS AND SHORT CIRCUITS AND THAT ALL FEEDERS ARE PROPERLY BALANCED. SYSTEM SHALL BE CHECKED FOR QUALITY, CAPACITY AND COMPLETENESS TO CONFORM WITH THE FULL REQUIREMENTS AND INTENT OF THE DRAWINGS AND SPECIFICATIONS. 32 CONDUIT RUNS, RACEWAYS AND PIPING SHALL BE CONCEALED IN WALLS, CEILINGS, SLABS AND PARTITIONSt NO RACEWAY SHALL BE EXPOSED WITHIN INTERIOR SPACES, ALL OUTLETS AND WIRING DEVICES SHALL BE FLUSH MOUNTED. 33 GROUNDING AND BONDING SHALL COMPLY WITH NEC 250. ALL METALLIC RACEWAYS SHALL BE GROUNDED AND BONDED PER NEC 250. NON - METALLIC RACEWAYS SHALL BE PROVIDED WITH A GROUNDING CONDUCTOR SIZED PER NEC 250-95. 3.4 ELECTRICAL EQUIPMENT SPACE AND INSTALLATION SHALL BE IN ACCORDANCE WITH NEC 110 -16A AND 384 -2. WIRING IN DUCTS, PLENUMS AND OTHER AIR HANDLING SPACES SHALL COMPLY WITH NEC 300 -22. 35 PANELBOARDS, SWITCHES, CONTROLLERS, CONTROL PANELS, TIMECLOCKS, AND OTHER ELECTRICAL COMPONENTS SHALL BE CLEARLY AND PERMANENTLY IDENTIFIED. INDICATE PANELBOARDS CIRCUITS ON UPDATED TYPED DIRECTORY CARD HOLDERS WITH GLASS COVER AND METAL FRAME INSTALLED ON INSIDE OF PANELBOARD DOOR MARK CONDUCTORS WITH PREPRINTED ADHESIVE MARKERS AS MANUFACTURED BY W.H. BRADY CO. OR THOMAS 4 BETTS. 3b CONTRACTOR SHALL MAKE ALL NECESSARY EXCAVATIONS, CUTTINGS AND REPATCHING AS REQUIRED FOR THE PROPER EXECUTION OF THIS WORK 3.1 CONTRACTOR SHALL FIELD SPOT LOCATION OF WIRING DEVICES TO VERIFY AND GET APPROVAL FROM ARCHITECT /OWNER BEFORE INSTALLATION. 3.8 ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND PROVIDED BY THIS CONTRACTOR EQUIPMENT TO BE REMOVED NOT CLAIMED BY THE OWNER SHALL BE REMOVED FROM THE JOB SITE AS DIRECTED. FIELD VERIFY WITH OWNER BEFORE REMOVAL. FART 4 - NURSE CALL /CODE BLUE SYSTEM MODIFICATIONS PROVIDE ALL NECESARY EQUIPMENT, HARDWARE, SOFTWARE, CABLING ETC. AS REQUIRED TO MODIFY THE EXISTING NURSE CALL SYSTEM AS DESCRIBE ON THE DRAWINGS. MANUFACTURER SHALL HAVE REPRESENTAVIVES AVAILABLE ON A 24 -HOUR BASIS WITHIN 150 MILES FROM THIS PROJECT. ALL WORK SHALL BE Mf;�FORMED UNDER THE DIRECT SUPERVISION OF THE MANUFACTURE'S REPRESENTATIVE. 'oht}'L ELECTRICAL LEGEND w($ @-°.,,iaaLL C 9024 SW 152 STREET VILLAGE OF PALMETTO BAY, FL 3315 305.234.0576 FAX 786.472.4193 EDWARD LEWIS ARCHITECTS, INC. AAC001678 C. EDWARD LEWIS AR 0009567 FJ[4k] im _ c; _ c c-• - - MIAMI, FLORIDA M!P0000 W ip8041 H.V. 14TH STREET DMAL, FLORIDA, 33126 (305) 436 -9292 FA% (305) 436 -9272 E-MIU JGPMAHIQDELLSGUTK ET JOSE G PUIG FLORIDA P.E. 0 47817 JOSE G PUIG JR. FL[RIDA P.E. t 49148 HECTOR K MASCO FLa2IDA P.E. 0 56115 ftebi 10-410 Dab MAYl 2010 owd Tft FLOOR PLAN 4 ELECTRICAL LAYOU` cu oCD 'fib E 1.0 v 0 co i • • uj i � < i co r Lu i i • i • C Q 10-410 Dab MAYl 2010 owd Tft FLOOR PLAN 4 ELECTRICAL LAYOU` cu oCD 'fib E 1.0 v 0