FLOOR PLAN —POWER LAYOUT
SCALE. 1/4!'= 1'-0"
Ee
Eo
ELECTRICAL NOTES
FART I - GENERAL
1.1 GENERAL: THE GENERAL AND SPECIAL CONDITIONS AND REQUIREMENTS OF THE
CONTRACT AND SPECIFICATIONS AS WELL AS PLANS AND SPECIFICATIONS OF OTHER
DISCIPLINES AND TRADES SHALL APPLY AND BE PART OF THE WORK HEREBY
SPECIFIED. THESE SPECIFICATIONS AND THE ACCOMPANYING PLANS ARE INTENDED
TO PROVIDE FOR THE COMPLETE FURNISHING AND INSTALLATION OF THE ELECTRICAL
SYSTEMS. 'PROVIDE' MEANS 'FURNISH AND INSTALL'.
12 COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT
ACCORDANCE WITH NEC 2008, WPA -101 2006, NFPA -99 2005, ADA GUIDELINES 2006,
FBC 2001 WITH 2009 SUPLEMENT, NFPA -12 2002 AND THE LATEST ADOPTED EDITIONS
OF OSHA, HRS, HEALTH AGENCIES, AHCA, SOUTH MIAMI HOSPITAL DESIGN GUIDELINES
AND OTHER APPLICABLE NATIONAL, STATE, AND LOCAL CODES AND PERTAINING
REGULATIONS ESTABLISHED BY RULING AUTHORITIES HAYING JURISDICTION.
CONTRACTOR SHALL ALSO MEET OTHER RECOGNIZED STANDARDS AND REQUIREMENTS
WHERE SUCH ARE MORE $TRIt -sENT THAN THOSE CITED ABOVE.
13 WORKMANSHIP: ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN 'THEIR
RESPECTIVE DISCIPLINES. WORK SHALL BE DONE IN A FIRST CLASS MANNER FULLY
OPERATIVE, AND TO THE ACCEPTANCE OF THE ARCHITECT/ENGINEER CONTRACTOR
SHALL PROVIDE FOR ALL NECESSARY LABOR AND MATERIALS REQUIRED FOR
COMPLETION OF THE WORK INCLUDING BUT NOT LIMITED TO CONNECTIONS TO RELATED
WORK SUCH AS CONNECTION TO EXISTING SYSTEMS, EXCAVATIONS AND BACKFILLNG.
1.4 MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS OF AMERICAN
MANUFACTURE, BEARING THE UNOERlJRITER'S LABORATORY (UL) LABEL AS APPLICABLE.
MATERIALS SHALL BE ACCEPTABLE AND ABOVE STANDARD QUALITY NORMALLY USED
FOR THE PURPOSE AS CALLED FOR ON PLANS. SUPPLEMENTAL MATERIALS, PRODUCTS
AND COMPONENTS NECESSARY TO COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS
AND /OR SPECIFICATIONS, BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, SHALL BE
PROVIDED BY CONTRACTOR AS REQUIRED FOR COMPLETION OF THE WORK AT NO
ADDITIONAL COST TO THE OWNER CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVISIONS AND COORDINATION OF DELIVERY OF MATERIALS. EQUIPMENT MARRED
OURIWs SHIPMENT OR INSTALLATION SHALL BE TOUCHED UP AND REFINISHED TO
FACTORY FINISH, REPLACED WHERE NOT ACCEPTABLE.
15 MFe 11T$ 4 INSURANCE: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS,
FEES, TAXES, INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE
INSTALLATION OF COMPLETE ELECTRICAL SYSTEMS AS OUTLINED HEREIN AND SHOWN
ON PLANS. PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC
LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK
16 EXISTING CONDITIONS: BEFORE BIDDING CONTRACTOR SHALL VISIT tHE JOB
SITE AND ASCERTAIN ALL EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK
FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING
EXTRA PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIAL OR
LABOR ANY EXISTING CONDITION FOUND BY THE CONTRACTOR WHICH WILL
ADVERSELY AFFECT THE WORK SHALL IMMEDIATELY BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT/ENGINEER CORRECTION OF ANY DEFECTS SHALL
BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE
REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH
MAY HAVE BEEN DAMAGED THEREBY.
UTILITY COMPANIES: BEFORE SUBMITTING BID CONTRACTOR SHALL CHECK
WITH WATER SEWER GAS, ELECTRICAL, TELEPHONE, CABLE TV AND OTHER
UTILITY COMPANIES SUPPLYING SERVICE TO THIS INSTALLATION TO DETERMINE
INSTALLATION STANDARDS AND EQUIPMENT REQUIREMENTS AND COSTS TO BE
INCLUDED IN THE BID. EXCEPT WHERE UTILITY REQUIREMENTS CHANCsE AFTER
SUBMITTAL, NO EXTRA PAYMENT WILL BE MADE TO THE CONTRACTOR FOR
SUCH ITEMS. PROVIDE TEMPORARY ELECTRICAL SERVICES FOR ALL TRADES
AS REQUIRED.
18 PLANS- DRAWINGS ARE GENERALLY DIAGRAMMATIC, INTENDED TO SHOW
APPROXIMATE EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW
EVERY MINOR DETAIL. PLANS SHALL NOT BE SCALED TO DETERMINE EXACT
LOCATION AND DIMENSIONS.
L9 INTERFERENCE: CONTRACTOR SHALL C00RONATE HIS WORK WITH THE WORK
OF OTHER TRADES SO THAT INTERFERENCES WITH EXISTING CONDITIONS,
CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL, STRUCTURAL MEMBERS WILL
BE AVOIDED.
1,10 SHOP DRAWINGS= PRIOR TO PLACING AN ORDER AND BEFORE INSTALLATION,
SUBMIT FOR REVIEW PROPERLY IDENTIFIED AND BOUND SHOP DRAWINGS AND
MANUFACTURER'S LITERATURE GIVING SPECIFICATIONS, DETAILS, COMPLIANCE, UL
APPROVAL, MATERIALS, FINISHES, ACCESSORIES AND INSTALLATION DIRECTIONS
WHERE REQUIRED OF THE EQUIPMENT SPECIFIED. FACTORY CERTIFIED PRINTS
SHALL BE FURNISHED FOR ALL MAJOR ITEMS OF EQUIPMENT AND SPECIFIED.
SUBMISSION OF EQUIPMENT FOR APPROVAL SHALL BE MADE COMPLETE AND
ALL AT THE SAME TIME.
1,11 SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME AND /OR
CATALOG NUMBERS ESTABLISH A STANDARD OF QUALITY, APPEARANCE,
PERFORMANCE AND DIMENSION. CONTRACTOR SHALL BASE HIS PROPOSAL ON
THOSE ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF BIDDING
REQUESTS FOR SUBSTITUTIONS SHALL BE SUBMITTED IN WRITING TO THE
ARCHITECT/ENGINEER DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND
BASIC DESIGN, CONSTRUCTION STANDARDS AND WARRANTIES, DIMENSIONS TO FIT
WITHOUT CHANGE, AND DOES NOT CAUSE EXTRA WORK FOR OTHER TRADES.
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVING EQUALITY OF SUBSTITUTIONSt
ARCHITECT/ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE
SUCH ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM.
ARCHITECT/ENGINEER EXPENSES INCURRED DUE TO CONTRACTOR'S REQUESTED
REVISIONS OR SUBSTITUTIONS SHALL BE PAID BY CONTRACTOR
UI2 GUARANTEES: AFTER THE SYSTEM IS INSTALLED, THE CONTRACTOR SHALL CONDUCT
AN OPERATIVE TEST FOR APPROVAL AND ACCEPTANCE BY THE ARCHITECT /OWNER
ENTIRE ELECTRICAL WORK, INCLUDING PARTS AND LABOR SHALL BE GUARANTEED
FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL WRITTEN ACCEPTANCE
THEREOF AGAINST DEFECTIVE MATERIALS, CONSTRUCTION AND WORKMANSHIP.
WHERE APPLICABLE, LONGER GUARANTEES FOR CERTAIN COMPONENTS SHALL
APPLY AS REQUIRED AND NOT BE REDUCED IN ANY WAY. CORRECTION OF ANY
DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE TO THE OWNER AND
SHALL INCLUDE REPLACEMENTS AND /OR REPAIR OF ANY OTHER PHASE OF THE
INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY.
L13 RECORD DRAWINGS: MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL
CHANGES. USE COLORED PENS TO MARK CHANGES AT THE TIME OF EXECUTION AND
DELIVER THE SET TO ARCHITECT/ENGINEER UPON COMPLETION. CONTRACTOR SHALL _
STAMP 'AS BUILT' ON PRINTS AND PLANS, DATE AND SIGN IN INK
FART 2 - PRODUCTS
2J SHOP DRAWINGS: SUBMIT SHOP DRAWINGS OF THE FOLLOWING PRODUCTS:
A. PANELBOARDS, OVERCURRENT PROTECTION DEVICES, CIRCUIT BREAKERS,
SWITCHES, FUSES.
B. WIRING, CABLING, CONDUITS, RACEWAYS, FLOOR AND OUTLET BOXES.
C. WIRING DEVICES: RECEPTACLES, OUTLETS, LIGHT SWITCHES, DIMMERS,
PLATES, PLUGMOLDS.
D. LIGHTING FIXTURES, LAMPS, POLES AND RELATED HARDWARE,
E. TIMECLOCKS, PHOTOCELLS AND CONTACTORS.
2.2 LIGHTING FIXTURES SHALL BE COMPLETE WITH ALL NECESSARY LAMPS, BALLASTS, WIRING,
LAMP HOLDERS REFLECTORS, GLASSWARE, POLES, BASES AND MOUNTINGS ACCESSORIES
AS REQUIRED TO PROVIDE FOR A COMPLETE INSTALLATION. LIGHTING FIXTURES SHALL
BE SELECTED BY ARCHITECT /OWNER PROVIDED BY CONTRACTOR REFER TO
ARCHITECTURAL DRAWINGS FOR COLOR FINISH AND EXACT MOUNTINGS DETAILS.
20A, 120V, DUPLEX RECEPTACLE
- q PHONE 4 DATA OWLET
- Ln LIGHT SWITCH
.�_ 21X4I FLUCINWENT LAMP
O CONNECTED TO NORMAL CIRCUIT
2'X4' FLUONSICENT LAMP
CONNECTED TO EMER3ENCY CIRCUIT
23-a:'-ICES SHALL BE MADE WITH UL LISTED MECHANICAL PRESSURE SOLDERLESS
CONNECTORS, BURNDY SERVITS TYPE OR APPROVED EQUAL. FEEDER SPLICES AND r n_- e d w a r d I e W i s
TERMINATIONS SHALL BE MADE MECHANICALLY USIWs COMPRESSION TYPE SLEEVES OR
LUGS AND CONNECTION TO PANELS AND SWITCHES AS MANUFACTURED BY BURNDY OR a r c h i t e c t s
THOMAS 4 BETTS.
2.4 RACEWAYS:
A, R3S AND IMC: HOT- DIPPED GALVANIZED INCLUDING THE THREADS. PROVIDE
FOR EXTERIOR LOCATIONS, WHERE EXPOSED TO PHYSICAL DAMAGE AND FOR
ELBOWS, ELLS AND RISERS INTO GROUND AND SLAB_ INSTALL ELLS AND
RISERS STUBBED UP 6 INCHES FROM CONCEALED SLAB RUNS, 48' ABOVE
GROUND WHERE EXPOSED ON WALL. PAINT RACEWAYS BELOW SLAB OR
FINISHED EXTERIOR GRADE WITH TWO (2) COATS OF BITUMASTIC PAINT UP TO A
POINT 2' ABOVE SLAB.
B. EMT: MAY BE USED FOR INTERIOR SPACES IN DRY LOCATIONS, WHEN NOT
EXPOSED TO PHYSICAL DAMAGE. FITTINGS SHALL BE STEEL.
C. PVC SCHEDULE 40: MAY BE USED WHERE CONDUIT IS RUN IN CONCRETE
SLABS WITH 4' COVER 12' BELOW SLAB, WHERE BURIED 24' BELOW FINISHED
GRADE AND 30' UNDER VEHICULAR TRAFFIC AREAS.
D. FLEXIBLE METALLIC CONDUIT: LIGHTING FIXTURES, MOTORS, TRANSFORMERS
AND VIBRATING EQUIPMENT CONNECTIONS IN LENGTHS NOT TO EXCEED IS'.
PVC JACKETED FLEXIBLE METAL CONDUIT FOR LOCATIONS OUTSIDE AND /OR
EXPOSED TO MOISTURE. GREENFIELD OR APPROVED EQUAL.
E. RUNS BELOW SLAB SHALL BE PROVIDED WITH A YELLOW RIBBON TAPED ALONG
TRENCH 6' BELOW GRADE FOR RACEWAY IDENTIFICATION.
2.5 CONDUCTORS: SOFT -DRAWN SS CONDUCTIVITY COPPER INSTALLED IN CONDUIT. MINIMUM
SIZE SHALL BE 012 FOR POWER WIRING AND 016 FOR CONTROL CIRCUITS, 014 FOR 15A CIRCUIT
BREAKERS WHERE INDICATED. PROVIDE 010 WIRES FOR 120V POWER CIRCUIT HOMERUNS
LONGER THAN 100 FEET. INSULATION SHALL BE 600V THI- N/THWN FOR GENERAL USE, THW
IN SIZES 06 AND ABOVE, COLOR CODED THROUGHOUT PER NEC AND TRADE STANDARDS.
WIRING IN DUCTS, PLENUMS AND OTHER AIR HANDLING SPACES SHALL COMPLY WITH NEC
300 -22. WHERE PREVIOUSLY APPROVED BY OWNER ENGINEER AND RULINGS AUTHORITIES,
NONMETALLIC SHEATHED CABLE MAY BE USED FOR BRANCH CIRCUITS PER NEC 336.
2b WIRING DEVICES SHALL BE HOSPITAL OR COMMERCIAL SPECIFICATION GRADE
AS REQUIRED, FLUSH MOUNTED, MANUFACTURED BY HUBBELL, SLATER OR
LUTRON.
A. SWITCHES: TOGGLE TYPE, 20A 120nllV, SINGLE POLE, THREE -WAY WHEN NOTED.
SWITCHES SHALL BE HEAVY DUTY FULL SIZE.
B. DIMMERS: LINEAR ON/OFF TYPE, RATED 20A 600W MINIMUM FOR GENERAL
AREA, 1000W FOR OTHER AREAS NOTED.
C. RECEPTACLES: 20A 120V GROUNDNG TYPE DUPLEX, HOSPITAL GRADE. SPECIAL
OUTLETS RATED TO MATCH CIRCUIT BREAKERS AS NOTED ON PLANS.
QUADRUPLEX OUTLETS AND SWITCH /OUTLET COMBINATIONS SHALL HAVE THE SAME
FACE PLATE. ISOLATED GROUND TYPE SHALL BE PROVIDED WITH SEPARATE
ISOLATED GROUND WIRE.
D. ELEPHONE AND DATA OUTLETS: TELEPHONE/DATA JACKS AND WIRING AS
SELECTED BY OWNER UNLESS OTHERWISE NOTEDt OTHERWISE, PULL WIRE WITH 12'
SLACK AT EACH END, RUN N 3/4' EMPTY CONDUIT.
E. MOUNTING HEIGHTS: WHERE NOT ESTABLISHED ON PLANS OR LEGEND
BY ARCHITECT OR EQUIPMENT MANUFACTURERS, MOUNTING HEIGHT SHALL
BE AS FOLLOWS:
MH - IWAFF - GENERAL AREA RECEPTACLES AND TELEPHONE OUTLETS.
MH - 42'AFF - COUNTER RECEPTACLES AND TELEPHONE OUTLETS.
MH - 3WAFF - OTHER EQUIPMENT OUTLETS.
MH a 48'AFF - SWITCHES AND DIMMERS.
MH - 52'AFF - WALL MOUNTED PHONES
F. ALL DEVICE PLATES SHALL BE PERMANENTLY ENGRAVED WITH PANEL
AND CIRCUIT NUMBER SUPPLYING THE DEVICE.
G. RECEPTACLES AND LIGHTS ON EMERGENCY POWER SHALL HAVE RED
FACEPLATE$.
FART 3 - EXECUTION -
3.1 TESTS: PROVIDE ALL NECESSARY INSTRUMENTS AND SPECIAL APPARATUS TO CONDUCT
ANY TESTS THAT MAY BE REQUIRED TO INSURE SYSTEM IS FREE OF ALL IMPROPER
GROUNDS AND SHORT CIRCUITS AND THAT ALL FEEDERS ARE PROPERLY BALANCED.
SYSTEM SHALL BE CHECKED FOR QUALITY, CAPACITY AND COMPLETENESS TO CONFORM
WITH THE FULL REQUIREMENTS AND INTENT OF THE DRAWINGS AND SPECIFICATIONS.
32 CONDUIT RUNS, RACEWAYS AND PIPING SHALL BE CONCEALED IN WALLS, CEILINGS,
SLABS AND PARTITIONSt NO RACEWAY SHALL BE EXPOSED WITHIN INTERIOR SPACES,
ALL OUTLETS AND WIRING DEVICES SHALL BE FLUSH MOUNTED.
33 GROUNDING AND BONDING SHALL COMPLY WITH NEC 250. ALL METALLIC RACEWAYS
SHALL BE GROUNDED AND BONDED PER NEC 250. NON - METALLIC RACEWAYS SHALL BE
PROVIDED WITH A GROUNDING CONDUCTOR SIZED PER NEC 250-95.
3.4 ELECTRICAL EQUIPMENT SPACE AND INSTALLATION SHALL BE IN ACCORDANCE
WITH NEC 110 -16A AND 384 -2. WIRING IN DUCTS, PLENUMS AND OTHER AIR HANDLING
SPACES SHALL COMPLY WITH NEC 300 -22.
35 PANELBOARDS, SWITCHES, CONTROLLERS, CONTROL PANELS, TIMECLOCKS, AND OTHER
ELECTRICAL COMPONENTS SHALL BE CLEARLY AND PERMANENTLY IDENTIFIED. INDICATE
PANELBOARDS CIRCUITS ON UPDATED TYPED DIRECTORY CARD HOLDERS WITH GLASS
COVER AND METAL FRAME INSTALLED ON INSIDE OF PANELBOARD DOOR MARK
CONDUCTORS WITH PREPRINTED ADHESIVE MARKERS AS MANUFACTURED BY W.H. BRADY
CO. OR THOMAS 4 BETTS.
3b CONTRACTOR SHALL MAKE ALL NECESSARY EXCAVATIONS, CUTTINGS AND REPATCHING
AS REQUIRED FOR THE PROPER EXECUTION OF THIS WORK
3.1 CONTRACTOR SHALL FIELD SPOT LOCATION OF WIRING DEVICES TO VERIFY AND GET
APPROVAL FROM ARCHITECT /OWNER BEFORE INSTALLATION.
3.8 ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND PROVIDED BY THIS CONTRACTOR
EQUIPMENT TO BE REMOVED NOT CLAIMED BY THE OWNER SHALL BE REMOVED FROM THE
JOB SITE AS DIRECTED. FIELD VERIFY WITH OWNER BEFORE REMOVAL.
FART 4 - NURSE CALL /CODE BLUE SYSTEM MODIFICATIONS
PROVIDE ALL NECESARY EQUIPMENT, HARDWARE, SOFTWARE, CABLING ETC. AS REQUIRED
TO MODIFY THE EXISTING NURSE CALL SYSTEM AS DESCRIBE ON THE DRAWINGS.
MANUFACTURER SHALL HAVE REPRESENTAVIVES AVAILABLE ON A 24 -HOUR BASIS WITHIN
150 MILES FROM THIS PROJECT.
ALL WORK SHALL BE Mf;�FORMED UNDER THE DIRECT SUPERVISION OF THE
MANUFACTURE'S REPRESENTATIVE.
'oht}'L ELECTRICAL LEGEND
w($ @-°.,,iaaLL C
9024 SW 152 STREET
VILLAGE OF PALMETTO BAY, FL 3315
305.234.0576 FAX 786.472.4193
EDWARD LEWIS ARCHITECTS, INC.
AAC001678
C. EDWARD LEWIS AR 0009567
FJ[4k] im _ c; _ c c-• - -
MIAMI, FLORIDA M!P0000 W
ip8041 H.V. 14TH STREET
DMAL, FLORIDA, 33126
(305) 436 -9292 FA% (305) 436 -9272
E-MIU JGPMAHIQDELLSGUTK ET
JOSE G PUIG FLORIDA P.E. 0 47817
JOSE G PUIG JR. FL[RIDA P.E. t 49148
HECTOR K MASCO FLa2IDA P.E. 0 56115
ftebi
10-410
Dab
MAYl 2010
owd Tft
FLOOR PLAN
4
ELECTRICAL LAYOU`
cu
oCD
'fib
E 1.0
v
0
co
i
•
•
uj
i
�
<
i
co
r
Lu
i
i
•
i
•
C
Q
10-410
Dab
MAYl 2010
owd Tft
FLOOR PLAN
4
ELECTRICAL LAYOU`
cu
oCD
'fib
E 1.0
v
0