10-327-037Calculation Summary
Label
IcalcType
I Units
I Avg
I Max I
Min
I Avg/Min
I Max /Min
Construction Pa
Illuminance
JFc
13.75
16.5
11.4
12.68
14.64
WUP WUP
— — ow
.�, WUP
CONSTRUCTION TRAILER
0 2SCALE: 1/16" = T-0" I
PHOTOMETRICS
MIAMI HO~
WUP
W
WUP
SUP
A
SUP FITTER, POLE --
GROUND BROUGHT OUT
THRU TENON, BOND TO
FIXTURE INTERNALLY
NOTE:
PROVIDE MANUFACTURER'S
CERTIFICATION THAT ENTIRE
ASSEMBLY IS RATED TO
WITHSTAND A SUSTAINED
WIND VELOCITY OF NOT
LESS THAN 110 MPH.
WITH A GUST FACTOR
OF 1.2
R
0
I
Q
N
GRADE
6
I
0
LIGHTING FIXTURE
PRECAST TAPERED
CONCRETE POLE
HAND HOLE WITH ALUMINUM
COVER PLATE
CONCRETE PULL BOX
BROOKS SERIES 36
WITH COVER PLATE.
2 Cu. FT. 3/4"
CRUSHED STONE
— COPPER CLAD GROUND
ROD 5/8' X 10' -0"
03POLE MOUNTING DETAIL
SCALE: N,s
6
1
Z'
I
1
I
I
I
I
I
1YryIINIn
Il
O
O
t ,
U
PANEL: LC FED FROM: FPL NORMAL
LOCATION: TRAILER SITE WIRES: 3W + G NEUTRAL BUS: No
MAIN BUS: 225A ENCLOSURE NEMA 3R GROUND BUS: Yes
MCB: 200A BUS TYPE: Copper ISOLATED GROUND BUS. No
VOLTAGE 208/120 MOUNTING: Surface 200% NEUTRAL: No
NC: 10,000A PANEL LUGS: Main Circuit Breaker FEED THROUGH LUGS: Yes
CKT
NO.
DESCRIPTION
TOTAL
LOAD
VA
CIRCUIT
BREA10
PHASE
CIRCUIT
BREAKER
TOTAL
LOAD
VA
DESCRIPTION
CKT
NO
AMPS
POLES
AMPS
POLES
1
EXISTING PANEL "A" NOTE 1
8000
100
2
A
100
2
8000
EXISTING PANEL "B" NOTE 1
2
3
-
8000
-
-
B
-
-
8000
-
4
5
SPACE
-
A
25
1
1800
GATE NOTE 2
6
7
PARKING LOT LIGHTING WEST NOTE 3
1800
20
1
B
20
1
-
PARKING LOT LIGHTING EAST NOTE 3
8
9
-
A
-
10
11
-
B
-
12
13
-
A
-
14
15
-
B
-
16
17
-
A
-
18
NOTES:
NOTE 1: PROVIDE A 2P -100A CB WITH 39, 1#8G IN 1 1/4 "C.
NOTE 2: PROVIDE A 1P -20A CB WITH 2110, 11106 IN 3/4 "C. TO BE CONTROLLED VIA NEW N&A 313 TIMECLOCK.
NOTE 3: PROVIDE A 1P -25A CB WITH 2110, 111OG IN 3/4 "C.
'LC' LOAD SUMMARY
LTS
RCPTS
MISC
TOTAL
(KVA)
TOTAL
(AMPS)
TOTAL CONNECTED LOAD
1.8
0.0
33.8
35.8
171.2
DEMAND FACTOR
SEE DEMAND FACTOR TABLE
TOTAL DEMAND LOAD
1.8
0.0 1
33.8 1
35.8
1 171.2
CONTINUOUS (DESIGN) FACTOR
1.25
1.00 1
1.00
TOTAL DESIGN LOAD
2.2
0.0 1
33.8 1
36.0
1 173.3
D
0CONSTRUCTION TRAILER ELECTRICAL
1 �a� 1/16" . ,-�
KEYED NOTES:
Oj RUN CONDUIT UNDERGROUND TO CORRESPONDING PANELS INSIbE TRAILER.
20
OPROVIDE 2#12, 1112G IN 3/4 "C AND NEW 2P -20A CIRCUIT BREAKER.
BERMELLO AJAMIL & PARTNERS, INC.
Architecture Engineering Planning
Interior Design Landscape Architecture
2601 South Bayshore Drive 10th Floor
Miami, Florida 33133
(305) 859 -2050 Fax (305) 860 -3700
PLANNING ARCHITECT:
W I LMOT SANZ
A R C H I T E C T U R E
P L A N N II N G
is s o 2w
-tea -� ao+-e0"50
STRUCTURAL ENGINEER:
❑P®RO a Du0W8W %,JqM
DADA M. ALBAI8A
�m.14"A
MEP ENGINEER:
2121 Ponce de Leon Blvd., Suite 350
Coral Gables, FL 33134
Professional Consulting Engineers phone: 305.569.1692
fox: 305.569.1693
Dallas . Houston . Nashville Miami . Richmond
Austin . Denver . Phoenix . Washington D.C.
ccrd project number: 409337
EB00007658
IT CONSULTANT:
GENE BURTON & ASSOCIATES
1893 General George Patton Drive 5840 West (-20, Suite 150
Franklin, Tennessee 37067 Arlington, Texas 76017
Phone: 615.376.3100 Phone: 817.563.2486
Fax: 615.376.3114 Fax: 817.563.2753
Website.- www.gbain ,.con
Medical Equipment and Communications Planners
11111/11
PERMIT SET
EVISIONS:
2 03.19.2010 MEP COORDINATION
15 11.11.2010 CLIENT REQUEST
20 02.11.2010 CLIENT REQUEST
PROJECT NAME:
SMH- CLINICAL EXPANSION
SITE PACKAGE
PROJECT ADDRESS:
7400 S.W. 62nd Ave.
South Miami, Florida 33143
KEY PLAN
COMM. NO.
SCALE: -
DATE: 04 -08 -2010
DRAWN: CCRD
CHECKED: CCP,11)
CADD FILE:
DRAWING TITLE:
CONSTRUCTION
TRAILER -
ELECTRICAL
SHEET NO.
ET1,01 l'
0