10-327-019SUB -BASE OF RESTORATION
SUB -BASE OF RESTORATION OR NEW SURFACE
RED POLYETHYLENE WARNING TAPES r— NEW SURFACE FINISHED GRADE
-..1'- UR A rwnr — .ice
-GREEN MARKER / TAPE
SEE SPECIFICATIONS
2 1/2-OXYGEN LINE IN
PROTECTIVE CONDUIT
SEE SPECIFICATION
SECTION 226313
REINFORCED CONDUIT DETAIL
ZZ NO SCALE
SUB -BASE OF RESTORATION
SUB -BASE OF RESTORATION OR NEW SURFACE
RED POLYETHYLENE WARNING TAPES F—OR NEW SURFACE
_,--FINISHED GRADE
wwnwun TALC .
FM =4" FORCE MAIN 2" � � I I I 1 PSPARE S= I L— PLANS CONDUIT AND IN SPECSD ON I UNDISTURBED EARTH
0 -lu klwv ,
oriNizInQr.FD [:()NDUIT DETAIL
NO 5GALt
SPLIT SYSTEM A/C
UNIT SCHEDULE
AHU DESIGNATION
AC -1
SERVES
TEMPORARY CORRIDOR
OUTSIDE AIR CFM
75
°
<
SUPPLY CFM
1600
EXT. S.P. ( "WG)
0.5
FAN MOTOR HP /FLA
0.75/2.9
MCA /MOCP
53.8/60
VOLTS /PH
208/1/60
o a
0 °
MAX FACE VEL. (FPM)
500
NOMINAL TONNAGE
4.0
TOTAL HEAT (MBTUH)'
45.4
SENS. HEAT (MBTUH)
32.5
I J—
-
0
z 0
HEATING COIL VOLTAGE
208V
HEATING CAPACITY
5 KW
CONDENSING UNIT DESIGNATION
CU -1
a
0
v
VOLTS /PH
208/1/60
MCA
26.2
MOCP
40
FLA
21.3
MANUFACTURER
CARRIER
W°o
AIR HANDLING UNIT
FY4ANFO48TO5
CONDENSING UNIT
24ABB348AO03
HUBBELL
UNV
REMARKS /NOTES
ALL
NOTES:
1. CAPACITY AT 95Y O.A.T., 80' DB /67' WB E.A.T.
2. PROVIDE REFRIGERANT LINES PER UNIT MANUFACTURERS RECOMMENDATIONS
3. PROVIDE UNIT MOUNTED COMBINATION STARTER/FUSED DISCONNECT, HOA
SELECTOR SWITCH & GREEN/RED RUNNING STOP UGHTS.
4. PROVIDE AUX DRAIN PAN UNDER UNIT WITH HIGH WATER CUT -OFF SWITCH.
AIR DEVICE SCHEDULE
DESIG.
SERVICE
FINISH
NECK SIZE
MANUFACTURER /MODEL NO.
REMARKS /NOTES
(LAMPS
REMARKS
COORD WITH ARCH
SEE PLAN
TITUS /TDCAA
SUPPLY DIFFUSER
24x24 LAY -IN FRAME
S1
SUPPLY
2'x4', 2 -LAMP, FLUORESCENT
COLUMBIA STR22- 240TTG- MPO- ETTU -M841-
COORD WITH ARCH
SEE PLAN
TITUS /350 R
LOUVERED RETURN GRILLE
24x24 LAY -IN FRAME
R1
RETURN
C388
I J—
-
-
B
ER
EXISTING
RETURN
EXISTING EXHAUST FAN
DESIG.
SERVICE
EXISTING CFM
NEW BALANCE
VOLT.
(LAMPS
REMARKS
EF -1 /2
EMER. DPT.
42108
42183
A
LIGHTING FIXTU RE SC H
EDULE
MACATALOG NUFACTURNO. AND
VOLT.
(LAMPS
REMARKS
TYPE
DESCRIPTION
A
2'x4', 2 -LAMP, FLUORESCENT
COLUMBIA STR22- 240TTG- MPO- ETTU -M841-
UNV
(2)
F40TT
UNIVERSAL VOLT BALLAST
C388
B
NOT USED
UNIVERSAL VOLT BALLAST AND
C
WALLPACK
HUBBELL
PGM3- 150S- 18- BZ -L -QSS
UNV
15OHPS
QUARTZ RESTRIKE
WALL PACK
HUBBELL
UNV
(2)24PL
PROVIDE WITH BATTERY BACKUP
PVL3- 242F- 18- BZ- L -2BOC
F
1X4 FLU ORESCNET
COLUMBIA
LUN- 8- 2- 32- E -U -GLR
UNV
( 2 ) F32T8
G
2X4 FLUORESCNET
COLUMBIA
ST8- 24- 3- 32- G- FA- Al2 -3E -U
UNV
3 F32T8
( )
'
H
OUTDOOR RATED SURFACE
HUBBELL
HVSO- 42F9- 1- 42CFL- UNV -LP
UNV
(1) 2W CFL
)
MOUNTED LUMINAIRE
84
CONSTRUCTION
TRAILER LIGHT POLE
WIDELITE
AL3P- 250- 4F -QV- SPTA -SK SHIELD
UNV
(1) 250W MH
SINGLE HEAD POLE
A
CONSTRUCTION
WIDELITE
AL3P- 250- 4F -QV- SPTA -SK SHIELD
UNV
(2) 25OW MH
DOUBLE HEAD POLE
TRAILER LIGHT POLE
DUALLITE
UNV
LED
®
EXIT SIGN
LES. RED LETTERS /CROME FINISH
ARROWS AS SHOWN ON DRAWINGS
TA
WALLPACK
W.F. WP RHB- PLT32 -HPF -277 -WL
UNV
(1) 32 PLT
WET LOCATION
TB
INDUSTRIAL FLOURESCENT
COLUMBIA LIGHTING
LUN4- 232- EU -GLR
UNV
(2) 32W T8
TC
EXIT SIGN
DUAL -LITE
UNV
LED
LXURWE
ARG"011 to 1:
BERMELLC AJAMIL 6 RARTNERS, INC.
Architecture Engineering Planning
Interior Design LandscaNF- Architecture
2601 South Eayshore Oriw- 10th Floor
Mlam;, FIorda -3133
(305) 859 -2050 Fax (305) 860 -3700
PLANNING ARCHITECT:
ITIN
■�1
WILMOT SANZ
A R C H I T E C T U R E
P L A N N I N G
10!10 wirdw- 3 M -2 4 0 " W
3M-�21 50
STRUCTURAL ENGINEER:
fkq@=
❑SRO J. DUQUESM?.4
❑ADA K All 1A
to or. �
"..2 or twm�o�aA,roM M.
MEP ENGINEER:
ow
!*%164 ,
2121 Ponce de Leon Blvd., Suite 350
Coral Gables, FL 33134
phone: 305.569.1692
Profesiona[ConsulfingEnginem fax: 305.569.1693
Dallas • Houston • Nashville • Miami. Richmond
Austin . Denver . Phoenix . Washington D.C.
ccrd project number: 409337
EB00007658
IT CONSULTANT:
GENE BURTON & ASSOCIATES
1893 General George Patton Drive 5840 West I -20, Suite 150
Franklin, Tennessee 37067 Arlington, Texas 76017
Yhane: 615376.3100 Phone: 817.563.2486
F-:615.376.3114 Fux: 817.563.2753
Web,Fite: www.gbainc.com
Medical Equipment and Communications Planners
PERMIT SET
EVISIONS:
06.29.2010 CLIENT REQUEST
1 09.10.2010 OWNER'S CHANGES
,d 10.19.2010 OWNER'S CHANGES
PROJECT NAME:
SMiI- CLINICAL EXPANSION
SITE PACKAGE
PROJECT ADDRESS:
7400 S.W. 62nd Ave.
South Miami, Florida 33143
KEY PLAN
IN
COMM. NO.
SCALE: -
DATE: 04 -08 -2010
DRAWN: CC RD
CHECKED: Mw
CADD FILE:
DRAWING TITLE:
MEP
SCHEDULES
SHEET EP3.000