10-264-013ELECTRICAL REMODELING AND DEMOLITION NOTES:
I. ALL WORK AND MATERIALS SHALL BE NEW AND PROVIDED 13Y THIS CONTRACTOR UNLESS OTHERWISE
NOTED AS EXISTING TO REMAIN OR 13E RELOCATED. WORK SHALL ALSO INCLUDE THE REMOVAL AND
DISPOSAL OF MATERIALS FROM THE SITE AND THOROUGH CLEANING OF THE PREMISES UPON
COMPLETION OF THE WORK AS DIRECTED BY ARCHITECT/TENANT AND LANDLORD,
2. WORK SHALL INCLUDE PROVISIONS OF ALL MATERIALS, CUTTING, EXTENSIONS, CONNECTIONS, PATCHING,
PAINTING, REPAIRING, ADAPTING AND OTHER WORK INCIDENTAL THERETO, TOGETHER WITH SUCH
TEMPORARY CONNECTIONS AS MAY BE REQUIRED.
3. ANY WORK NOT SHOWN OR SPECIFICALLY MENTIONED ON PLANS AND /OR SPECIFICATIONS BUT
CONSIDERED NECESSARY FOR COMPLETION OF THE WORK IN THE PROPER MANNER SHALL BE PROVIDED
BY THIS CONTRACTOR WITHOUT ADDITIONAL CHARGE.
4. WHERE PRESENT WORK IS DAMAGED IN THE EXECUTION OF THIS CONTRACT, OR WHERE OPENINGS ARE
LEFT DUE TO THE REMOVAL OF PIPES, EQUIPMENT OR APPARATUS, THE SAME SHALL BE REPAIRED OR
CLOSED UP TO CORRESPOND IN MATERIAL, QUALITY, SHAPE AND FINISH WITH THAT OF SIMILAR AND
ADJOINING WORK, UNLESS OTHERWISE CALLED FOR WHEN DAMAGE IS UNREPAIRABLE, NEW ITEMS
OR EQUIPMENT SHALL BE PROVIDED. PROVIDE ALL NECESSARY WATERPROOFING, FIRE STOPPING AND
SEALING OF PENETRATIONS LEFT FROM REMOVED EQUIPMENT OR PRODUCED BY THIS WORK
3. INTERRUPTION OF EXISTING SERVICES AND /OR OPERATION OF FACILITIES SHALL BE KEPT TO A MINIMUM.
CONTRACTOR SHALL FURNISH ALL MATERIALS REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE
NECESSARY TO MAINTAIN CONTINUITY OF SERVICE. INTERRUPTION OF EXISTING SERVICES, THE
INSTALLATION OF TEMPORARY FACILITIES, AND THE WORK OF MAKING FINAL CONNECTIONS TO THE NEW
WORK SHALL BE DONE ONLY AT SUCH TIMES PERMITTED AND SCHEDULED IN ADVANCE BY THE
ARCHITECT/TENANT AND LANDLORD WITHOUT ADDITIONAL COST. CARE MUST BE USED IN REMOVING
SERVICES TO AREAS BEING DEMOLISHED SO THAT SERVICES TO OTHER AREAS WHICH MIGHT BE SERVED
THROUGH THESE AREAS WILL NOT BE INTERRUPTED.
6. WHERE DEMOLITION WORK REQUIRES TEMPORARY INTERRUPTION OF ELECTRICAL, TELEPHONE, TV,
ALARM OR COMMUNICATION SERVICES, RESPECTIVE UTILITIES AND /OR COMPANY REPRESENTATIVES
SHALL BE NOTIFIED AS NECESSARY AND ALL WORK DONE UNDER THEIR SUPERVISION AND ESTABLISHED
STANDARDS.
1. ALL LIG14TING FIXTURES, RECEPTACLES, SWITCHES, WIRING DEVICES, SPECIAL OUTLETS, TELEPHONE
CABLES, TV CABLES, MISCELLANEOUS SYSTEM WIRING, POWER CONDUCTORS, CONDUITS, ELECTRICAL
BOXES, RACEWAYS AND ANY OTHER ELECTRICAL SYSTEM COMPONENTS LOCATED IN THE AREAS SHOWN
AS BEING DEMOLISHED OR NOT USED AFTER WORK IS COMPLETED SHALL BE REMOVED UNLESS
OTHERWISE NOTED AS EXISTING TO REMAIN OR EsE RELOCATED. RELOCATED LIGHTING FIXTURES SHALL
BE RELAMPED/REBALLASTED, WITH DIFFUSERS REPLACED/REFURBISHED AS REQUIRED. CONDUITS RUN
IN SLAB IN FINISHED AREAS SHALL BE CUT FLUSH, PLUGGED AND ABANDONED AFTER CONDUCTORS ARE
REMOVED* WHERE PREVIOUSLY APPROVED BY ARCHITECT/TENANT AND LANDLORD, CUT 6 INCHES
FROM SLAB AND CAP ACf.ORDINGLY WHERE TERMINATED IN OTHER AREAS. NO WIRING SHALL BE LEFT
ABANDONED AFTER WORK IS COMPLETED.
S. EXISTING AREAS WHERE NO ELECTRICAL WORK IS TO BE DONE SHALL REMAIN CONNECTED TO EXISTING
PANEL($) OR BE RECONNECTED TO CIRCUITS AS NOTED ON PLANS. DISCONNECTS, PROTECTION AND
WIRING SHALL MATCH EXISTING WIRING CONNECTION.
% EXISTING EQUIPMENT TO BE RELOCATED OR TO REMAIN SHALL BE RECONNECTED TO CIRCUIT BREAKERS
ORIGINALLY FEEDING SUCH EQUIPMENT UNLESS OTHERWISE NOTED.
10. CIRCUIT BREAKERS INSTALLED IN EXISTING PANELS SHALL BE FULLY COMPATIBLE AND OF THE SAME
TYPE, RATING, MODEL AND MANUFACTURER AS PANEL.
11_ EXISTING NON - GROUNDING: TYPE RECEPTACLES SHALL BE REPLACED WITH GROUNDING TYPE
RECEPTACLES. OUTLETS AND RECEPTACLES WITHIN 6 FEET FROM SINKS AS WELL AS WET AND /OR
OUTDOOR LOCATIONS SHALL BE PROVIDED WITH GFI RECEPTACLES OR CIRCUITS.
12. WHERE PREVIOUSLY APPROVED BY THE ARCHITECT/ENGINEER, CONTRACTOR MAY REUSE EXISTING
RACEWAYS DEEMED IN ACCEPTABLE CONDITION IN ORDER TO MINIMIZE CUTTING OF SLABS, PLASTER
PARTITIONS, CEILINGS AND FLOORS, ANY CUTTING OF EXISTING SURFACES SHALL BE LIMITED TO THE
NARROWEST CUT OR TRENCH THAT WOULD ACCOMMODATE BRANCH CIRCUITING AND OUTLET BOXES.
13. AFTER THE WORK IS COMPLETED ALL CONDUCTORS SHALL BE COPPER RUN IN RACEWAYS_ ALUMINUM
WIRING AND ROMEX TYPE NON - METALLIC GABLE ARE NOT ACCEPTABLE* ANY WIRING FOUND DURING
REMODELING SHALL BE REPLACED WITH COPPER CONDUCTORS OF EQUAL OR GREATER AMPACITY
RUN IN CONDUIT.
SCALE; 1/4" = T -0"
- LABOR AND DELIVERY
ELECTRICAL LEGEND (DEMO PLAN ONLY) ,z
20A, 120V, DUPLEX RECEPTACLE
(D: 20A, 120V, GFCI DUPLEX RECEPTACLE
Y 20A, 120V, ABOVE COUNTER GFCI DUPLEX RECEPTACLE
PHONE i DATA OULET
Q DATA OULET
® TV OULET
E EXISTING DEVICE TO REMAIN
ER EXISTING DEVICE TO BE RELOCATED, SEE PROPOSSED
PLAN FOR NEW LOCATION.
D DEVICE TO BE DEMOLISHED
Ln LIC -44T SWITCH
T 3 -WAY LIGHT SWITCH
O RECESSED MOUNTED CEILING LIGHT FIXTURE
2'X4' FLUORESCENT LAMP
- DEMOLITION PLAN
n
c
C
A
n
s
C
z
a
CL
EIRJA
DE]
edward lewis
architects
Imawllnxf eT
YUMM OF PMMKff 1 SAY. R =W
�1111 Ll ARCID119 M NL
AACNIM
&m AND �A NWW
J 0 P ElNG14HERNO GROUP PA
MIAMI, FLORIDA EW 000071863
fp8041 N.W. 14TH STREET
DORAL, FLORIDA, 33126
(305) 436 -9292 FAX (305) 436 -9272
E -MAIL- JGPMIAMI@BELLSOUTH.NET
JOSE G. PUIG FLORIDA P.9, # 47817
JOSE G. PUIG JR. FLORIDA P.E. # 49148
HECTOR M. BLgSCO FLORIDA P.E. # 56113
Y • '
RNrNlO�
PION WAOM-
00 -058
Dd
February, 2010
ftm Tft
ELECTRICAL
DEMOLITION PLAN
I
I ?
Dry by KL
CUSM bar Munn
I �t NN■16�
E -02
Uj
aIm
J
o
cc
=c000
m
°-O
=
o
�
o
ol
W
woo
0
0
,j
Y • '
RNrNlO�
PION WAOM-
00 -058
Dd
February, 2010
ftm Tft
ELECTRICAL
DEMOLITION PLAN
I
I ?
Dry by KL
CUSM bar Munn
I �t NN■16�
E -02