10-1098-0012000 NFPA101 HANDICAPPED ACCESSIBILITY: ADA ,/ ANSI A117.1 / FACBC
GENERAL NOTES: 2001 FBC
1. HANDICAP ACCESS TO BUILDING IS DESIGNED AND FIELD BUILT BY OTHERS AND
SUBJECT TO LOCAL JURISDICTION,
2. ALL DOORS SHALL BE OPENABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A
KEY, TOOL, SPECIAL KNOWLEDGE OR EFFORT. MANUALLY OPERATED FLUSH BOLTS
OR SURFACE BOLTS SHALL NOT BE USED,
3. ALL GLAZING WITHIN A 24 INCH ARC OF DOORS, WHOSE BOTTOM EDGE IS LESS THAN
60 INCHES ABOVE THE FLOOR, AND ALL GLAZING IN DOORS SHALL BE SAFETY,
TEMPERED OR ACRYLIC PLASTIC SHEET,
4. FLOOR DESIGN LIVE LOAD -100 PSF CORRIDORS, LOBBY, 50 PSF ELSEWHERE
5. MAXIMUM WIND SPEED - 146 MPH
6. SEISMIC PERFORMANCE CATEGORY-A
7. OCCUPANCY IS BUSINESS
8, OCCUPANT LOAD IS BASED ON 1 PERSON PER 100 SQUARE FEET OF FLOOR AREA FOR EGRESS
9, ALL STEEL STRAPS REFERENCED ON FLOOR PLAN SHALL BE 1,5 INCH x 30 GA. WITH
(7)- 16 GA. x 7/16 INCH CROWN x 1 INCH PENETRATION STAPLES EACH END OF STRAP
(OR EQUIVALENT) FROM RIDGE BEAM TO COLUMN AND COLUMN TO FLOOR.
10. PORTABLE FIRE EXTINGUISHER(S) PER N.F.P.A. -10 INSTALLED BY OTHERS ON
SITk`, AND S')SJECT TO LOCAL JURISDICTION.
11. _MINIMUM -CORR?DOR WIDTH IS 44 INCHES.
12_,MINIMUM _00RR�DOR FINISH IS CLASS A (GYPSUM),
ELECTRICAL NOTES: 1999 NEC
1. . At.l CIRCU TS ;ND EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH THE
APPROPRIATE PRTICLES OF THE NATIONAL ELECTRIC CODE (N.E.C.).
BOXES IN RATED PARTITIONS SHALL BE METAL BOXES.
2, -' i 1 EN LIGHT FIXTURES ARE INSTALLED IN CLOSETS, THEY SHALL BE SURFACE
MOUNTED OR.RECESSED, INCANDESCENT FIXTURES SHALL HAVE COMPLETELY
,.ENCLOSE6 LAMrS. SURFACE MOUNTED INCANDESCENT FIXTURES SHALL HAVE
A MINIMUM, 01,FARANCE OF 12 INCHES AND ALL OTHER FIXTURES SHALL HAVE
A MINIMUM CLEARANCE OF 6 INCHES FROM "STORAGE AREA" AS DEFINED BY
N.E,C. 410 -8(a).
3. WHEN WATER HEATERS ARE INSTALLED THEY SHALL BE PROVIDED WITH READILY
ACCESSIBLE DISCONNECTS ADJACENT TO THE WATER HEATER(S) SERVED, THE
BRANCH CIRCUIT SWITCH OR CIRCUIT BREAKER SHALL BE PERMITTED TO SERVE
AS THE DISCONNECTING MEANS ONLY WHERE THE SWITCH OR CIRCUIT BREAKER
IS WITHIN SIGHT FROM THE WATER HEATER OR IS CAPABLE OF BEING LOCKED
IN THE OPEN POSITION,
4. HVAC EQUIPMENT SHALL BE PROVIDED WITH READILY ACCESSIBLE DISCONNECTS
ADJACENT TO THE EQUIPMENT SERVED, A UNIT SWITCH WITH A MARKED "OFF"
POSITION THAT IS A PART OF THE HVAC EQUIPMENT AND DISCONNECTS ALL
UNGROUNDED CONDUCTORS SHALL BE PERMITTED AS THE DISCONNECTING
MEANS WHERE OTHER DISCONNECTING MEANS ARE ALSO PROVIDED BY A
READILY ACCESSIBLE CIRCUIT BREAKER.
5. PRIOR TO ENERGIZING THE ELECTRICAL SYSTEM THE INTERRUPTING RATING
OF THE MAIN BREAKER MUST BE DESIGNED AND VERIFIED AS BEING IN COMPLIANCE
WITH SECTION 110 -9 OF THE N.E.C. BY LOCAL ELECTRICAL CONSULTANT,
6, THE MAIN ELECTRICAL PANEL AND FEEDERS ARE DESIGNED BY OTHERS, SITE
INSTALLED AND SUBJECT TO LOCAL JURISDICTION APPROVAL,
7, ALL CIRCUITS CROSSING OVER MODULE MATING LINE(S) SHALL BE SITE
CONNECTED WITH APPROVED ACCESSIBLE JUNCTION BOXES OR CABLE CONNECTORS.
8. RECESSED PORTIONS OF LIGHTING FIXTURE ENCLQSURES.OTHER THAN AT THE POINTS
OF SUPPORT, SHALL BE SPACED AT LEAST 112" FROM CUM BUSTIBLE MATERIALS.
9• THERMAL INSULATION SHALL NOT BE INSTALLED WITHIN 3" OF THE RECESSED
FIXTURE ENCLOSURE, WIRING COMPARTMENT, OR BALLAST, AND SHALL NOT BE
INSTALLED ABOVE THE FIXTURE SO AS TO TRAP HEAT AND PREVENT THE FREE
CIRCULATION OF AIR,
MECHANICAL NOTES: 2001 FMC
1. ALL SUPPLY AIR REGISTERS SHALL BE INCHES BY INCHES ADJUSTABLE
WITH 8 INCHES BY 16 INCHES (INSIDE) x 5/8 INCH OVERHEAD FIBERGLASS
DUCT, UNLESS OTHERWISE SPECIFIED. DUCTS LOCATED IN VENTILATED ATTIC
SHALL HAVE AN INSULATION VALUE OF R -6. DUCTS LOCATED IN UNCONDITIONED
INTERIOR SPACES SHALL HAVE AN INSULATION VALUE OF R 4.2.
2. INTERIOR DOORS SHALL BE UNDERCUT 1.5 INCHES ABOVE FINISHED FLOOR
FOR AIR RETURN, ANY ON -SITE ADJUSTMENTS OF DOORS AFTER SET -UP
ARE NOT THE RESPONSIBILITY OF THE BUILDING MANUFACTURER,
3. VENT FANS SHALL BE DUCTED TO THE EXTERIOR AND TERMINATE AT AN
APPROVED VENT CAP,
4. HVAC EQUIPMENT SHALL BE EQUIPPED WITH OUTSIDE FRESH AIR INTAKE
PROVIDING 20 CFM FOR EACH OCCUPANT, OR 50 CFM FOR EACH
WATER CLOSET OR URINAL, WHICHEVER IS GREATER,
5. IN PRIVATE RESTROOMS CONTAINING ONE TOILET AND ONE LAVATORY,
RESTROOM VENT FANS SHALL PROVIDE ONE CFM PER SQUARE FOOT OF FLOOR AREA,
IN OTHER RESTROOMS FANS SHALL PROVIDE A MINIMUM OF TWO CFM
PER SQUARE FOOT OF RESTROOM SQUARE FOOT.
6. IN ANY BATHROOM THAT DOES NOT CONTAIN BATHTUBS, AND /OR SHOWERS,
MECHANICAL EXHAUST MAY BE OMITTED WHEN NATURAL VENTILATION OR
AN APPROVED RECIRCULATING AIR TREATMENT SYSTEM IS PROVIDED,
7. IF UNIT IS EQUIPPED WITH MECHANICAL ATTIC VENTILATION,
VENTILATOR SHALL BE CONTROLLED BY A HUMIDASTAT CALIBRATED TO ACTIVATE WHEN
RELITAVE HUMIDITY EXCEEDS 60%
PLUMBING NOTES:
1. CUSTOMER ASSUMES ALL RESPONSIBILITY FOR DRINKING WATER FACILITIES
DRINKING FOUNTAINS SHALL BE INSTALLED IN ACCORDANCE WITH SECTION
407 SPC 2001 EDITION, AND SECTION 415 OF THE FLORIDA ACCESSIBILITY CODE
2, ALL PLUMBING FIXTURES SHALL HAVE SEPARATE SHUT -OFF VALVES,
3. STORAGE TYPE W/H SHALL HAVE A SHUT- OFFVALVE WITHIN 3 FEET ON COLD WATER SUPPLY LINE,
4, WATER SUPPLY LINES SHALL BE POLYBUTYLENE, CPVC, OR COPPER; WHEN POLYBUTYLENE
SUPPLY LINES ARE INSTALLED, THE MAXIMUM WATER HEATER TEMPERATURE IS 180 DEGREES F.
THE POLYBUTYLENE PIPE INSTALLER SHALL VERIFY THAT IT'S USE WILL BE RESTRICTED
TO THE PRODUCT MANUFACTURER'S CONDITITIONS AND LIMITATIONS INCLUDING CHLORINE
CONCENTRATION LEVELS.
5. WATER CLOSETS ARE TANK TYPE AND URINALS ARE FLUSH VALVE TYPE UNLESS
OTHERWISE SPECIFIED,
6. DWV SYSTEM SHALL BE EITHER ABS OR PVC -DWV,
7. BUILDING DRAIN AND CLEANOUTS ARE DESIGNED AND SITE- INSTALLED BY OTHERS,
SUBJECT TO LOCAL JURISDICTION APPROVAL.
8, TOILETS SHALL BE ELONGATED TYPE WITH NON- ABSORBENT OPEN FRONT SEATS,
9. RESTROOM WALLS SHALL BE COVERED WITH NON - ABSORBENT MATERIAL TO A
MINIMUM HEIGHT OF 48" A.F.F.
10. HOT WATER SUPPLY TO A FIXTURE REQUIRING HOT WATER SHALL BE INSTALLED ON LEFT SIDE
OF FIXTURE.
11. WATER SERVICE PIPING SHALL BE NOT LESS THAN ONE INCH INSIDE DIAMETER FOR GALVANIZED
FERROUS PIPING, OR 3/4" INSIDE NOMINAL DIAMETER FOR COPPER, OR APPROVED NON
CORROSIVE PIPE OR TUBE.
12, SHOWERS(WHEN PROVIDED) SHALL BE CONTROLLED BY AN APPROVED MIXING VALVE WITH A
MAXIMUM WATER OUTLET TEMPERATURE OF 120 DEG. F.
13. LAVATORIES OF PUBLIC RESTROOMS SHALL BE EQUIPPED WITH OUTLET DEVICES WHICH LIMIT
THE FLOW OF HOT WATER TO A MAXIMUM OF 0.5 GPM., OR BE EQUIPPED W17H SELF - CLOSING
VALVES (NON HANDI - CAPPED APPLICATIONS ONLY), MAXIMUM WATER TEMPERATURE IS 110 DEG,
1, THE INTERNATIONAL SYMBOL OF ACCESSIBILITY SIGN SHALL BE DISPLAYED AT ALL
ACCESSIBLE RESTROOM FACILITIES AND AT ACCESSIBLE BUILDING ENTRANCES UNLESS
ALL ENTRANCES ARE ACCESSIBLE. INACCESSIBLE ENTRANCES SHALL HAVE
DIRECTIONAL SIGNS INDICATING THE ROUTE TO THE NEAREST ACCESSIBLE ENTRANCE,
2. ACCESSIBLE DRINKING FOUNTAINS SHALL HAVE A SPOUT HEIGHT NO HIGHER THAN
36 INCHES ABOVE THE FLOOR AND EDGE OF THE BASIN NO HIGHER THAN 34 INCHES
ABOVE THE FLOOR FOR INDIVIDUALS IN WHEELCHAIRS, ADDITIONALLY, DRiNKiNG WATER
PROVISIONS SHALL BE MADE FOR INDIVIDUALS WHO HAVE DIFFICULTY IN BENDING.
3. WHERE STORAGE FACILITIES SUCH AS CABINETS, SHELVES, CLOSETS AND DRAWERS
ARE PROVIDED, AT LEAST ONE OF EACH TYPE PROVIDED SHALL CONTAIN STORAGE
SPACE COMPLYING WITH THE FOLLOWING: DOORS, ETC. TO SUCH SPACES SHALL BE
ACCESSIBLE (ie. TOUCH LATCHES, U- SHAPED PULLS); SPACES SHALL BE WITHIN 15
INCHES MINIMUM AND 48 INCHES MAXIMUM OF THE FLOOR FOR FORWARD REACH OR 9
INCHES MINIMUM AND 54 INCHES MAXIMUM, OF THE FLOOR FOR SIDE REACH; CLOTHES
RODS SHALL BE A MAXIMUM OF 54 INCHES ABOVE THE FLOOR (48 INCHES MAXIMUM
WHEN DISTANCE FROM WHEELCHAIR TO ROD EXCEEDS 10 INCHES)
A. 'CONTROLS, DISPENSERS, RECEPTACLES, AND OTHER OPERABLE EQUIPMENT SHALL BE NO
HIGHER THAN 45 INCHES ABOVE THE FLOOR FOR FRONT APPROACH OR 54 INCHES
ABOVE THE FLOOR FOR SIDE APPROACH, RECEPTACLES ON WALLS SHALL BE MOUNTED
NO LESS THAN 15 INCHES ABOVE THE FLOOR, EXCEPTION: HEIGHT LIMITATIONS DO
:NOT APPLY WHERE THE USE OF SPECIAL EQUIPMENT DICTATES OTHERWISE OR WHERE
ELECTRICAL RECEPTACLES ARE NOT NORMALLY INTENDED FOR USE BY BUILDING
OCCUPANTS
5, WHERE EMERGENCY WARNING SYSTEMS ARE PROVIDED, THEY SHALL INCLUDE BOTH
AUDIBLE AND VISUAL ALARMS. THE VISUAL ALARMS SHALL BE LOCATED THROUGHOUT,
INCLUDING RESTROOMS, AND PLACED 80 INCHES ABOVE THE FLOOR OR 6 INCHES
BELOW CEILING, WHICHEVER IS LOWER,
6. DOORS TO ALL ACCESSIBLE SPACES SHALL HAVE ACCESSIBLE HARDWARE (ie, LEVER -
OPERATED, PUSH -TYPE, U- SHAPED) MOUNTED NO HIGHER THAN 48 INCHES ABOVE
THE FLOOR.
7. FLOOR SURFACES SHALL BE STABLE, FIRM, AND SLIP - RESISTANT. CHANGES IN
LEVEL BETWEEN 0.25 INCH AND 0.5 INCH SHALL BE BEVELED WITH A SLOPE NO
GREATER THAN 1 :2, CHANGES IN LEVEL GREATER THAN 0.5 INCH REQUIRE RAMPS.
CARPET PILE THICKNESS SHALL BE 0,5 INCH MAXIMUM, GRATINGS IN FLOOR SHALL HAVE
SPACES NO GREATER THAN 0.5 INCH WIDE IN ONE DIRECTION, DOORWAY THRESHOLDS
SHALL NOT EXCEED 0,5 INCH IN HEIGHT,
8, ALL DOORS SHALL BE OPENABLE BY A SINGLE EFFORT, THE MAXIMUM FORCE
REQUIRED TO OPEN A DOOR SHALL NOT EXCEED 8.5 LBS, FOR EXTERIOR SWINGING
DOORS AND 5 LBS, FOR ALL SLIDING, FOLDING, AND INTERIOR SWINGING DOORS.
9, ACCESSIBLE WATER CLOSETS SHALL BE 19 INCHES FROM THE FLOOR TO
THE TOP OF THE SEAT, GRAB BARS SHALL BE 36 INCHES LONG MINIMUM WHEN
LOCATED BEHIND WATER CLOSET AND 42 INCHES LONG MINIMUM WHEN LOCATED ALONG
SIDE OF WATER CLOSET, AND SHALL BE MOUNTED AT 33 INCHES FROM THE FLOOR TO THE
TOP OF THE RAIL WITH 0.5 INCH MAXIMUM VARIATION,
10, ACCESSIBLE URINALS SHALL BE STALL -TYPE OR WALL -HUNG WITH ELONGATED RIMS AT
A MAXIMUM OF 17 INCHES ABOVE THE FLOOR.
11. ACCESSIBLE LAVATORIES SHALL BE MOUNTED WITH THE RIM NO HIGHER THAN 34 INCHES
ABOVE THE FLOOR AND A CLEARANCE OF AT LEAST 29 INCHES ABOVE THE FLOOR TO
THE BOTTOM OF THE APRON,
12, ACCESSIBLE SINKS SHALL BE MOUNTED WITH THE RIM NO HIGHER THAN 34 INCHES
ABOVE THE FLOOR AND A CLEARANCE OF AT LEAST 27 INCHES HIGH, 30 INCHES WIDE,
AND 19 INCHES DEEP UNDERNEATH SINK, THE SINK DEPTH SHALL BE 6.5 INCHES
MAXIMUM.
13, HOT WATER AND DRAIN PIPES UNDER ACCESSIBLE LAVATORIES AND SINKS SHALL BE
INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST CONTACT, THERE SHALL
BE NO SHARP OR ABRASIVE SURFACES UNDER ACCESSIBLE LAVATORIES AND SINKS.
�i4. ACCESSIBLE LAVATORIES AND SINKS SHALL HAVE ACCESSIBLE FAUCETS OPERABLE WITH
ONE HAND AND REQUIRING LESS THAN 5 LBS, OF FORCE TO ACTIVATE (ie LEVER - OPERATED,
PUSH -TYPE, ELECTRONICALLY CONTROLLED). SEPARATE LAVATORIES FOR
PHISICALLY HANDI- CAPPED PERSONS SHALL NOT BE EQUIPPED WITH SELF CLOSING VALVES,
15' WHERE MIRRORS ARE PROVIDED IN RESTROOMS, AT LEAST ONE SHALL BE PROVIDED
WITH ITS BOTTOM EDGE NO HIGHER THAN 40 INCHES ABOVE THE FLOOR.
16; 'WHERE MEDICINE CABINETS ARE PROVIDED, AT LEAST ONE SHALL BE LOCATED WITH
A USABLE SHELF NO HIGHER THAN 44 INCHES ABOVE THE FLOOR.
17, GRAB BARS REQUIRED FOR ACCESSIBILITY SHALL BE 1,5 INCHES IN DIAMETER WITH
1,5 INCHES OF CLEAR SPACE BETWEEN THE BAR AND THE WALL.
1; TOILET STALL DOORS SHALL BE THE SELF - CLOSING TYPL.
19: ,jk TOWEL DISPENSER SHALL BE LOCATED ADJACENT TO ALL ACCESSIBLE LAVATORIES.
SITE- INSTALLED ITEMS:
NOTE THAT THIS LIST DOES NOT NECESSARILY LIMIT THE
ITEMS OF WORK AND MATERIALS THAT MAY BE REQUIRED
FOR A COMPLETE INSTALLATION, ALL SITE RELATED ITEMS
ARE SUBJECT TO LOCAL JURISDICTION APPROVAL,
1. THE COMPLETE FOUNDATION SUPPORT AND TIE DOWN SYSTEM,
2, RAMPS, STAIRS, AND GENERAL ACCESS TO THE BUILDING,
3, PORTABLE FIRE EXTINGUISHER(S),
4, DRINKING WATER APPARATUS (WHEN NOT SHOWN ON PLAN),
BUILDING DRAINS, CLEANOUTS, AND CONNECTION TO THE
PLUMBING SYSTEM,
5, ELECTRICAL SERVICE CONNECTION (INCLUDING FEEDERS) TO
THE BUILDING,
6. THE MAIN ELECTRICAL PANEL AND SUB - FEEDERS (MULTI -UNITS ONLY),
7, CONNECTION OF ELECTRICAL CIRCUITS CROSSING OVER MODULE
MATING LINE(S) (MULTI -UNITS ONLY).
8, STRUCTURAL AND AESTHETIC INTERCONNECTIONS BETWEEN
MODULES (MULTI -UNITS ONLY),
9. REQUIRED PLUMBING FACILITIES NOT PROVIDED IN THE MODULAR
3UILDING ARE TO BE LOCATED IN ADJACENT BUILDING(S), SEE
ATTATCHED LETTER,
10. DRAINAGE PIPING BELOW FLOOR JOIST LEVEL
11. FIRE ALARM SYSTEM (IF APPLICABLE)
12, SPRINKLER SYSTEM (INSTALLED BY A LICENCED INSTALLER)
13. EMERGENCY LIGHTING IF REQUIRED PER LOCAL GOVERNMENT SHALL BE PROVIDED AND INSTALLED
INSTALLED BY OWNER /LEASE - HOLDER.
_
STRI TURAL LOAD
14, GUTTERS AND DOWNSPOUTS WHEN REQUIRED AND NOT ON BUILDING ARE TO BE SITE
11IITATIONS
INSTALLED BY OWNER /LEASE - HOLDER.
15, FIRE SAFETY INSPECTION COMPLYING WITH CHAPTER 663
ROOF LIVE
LOAD 30PSF
16. STORM SHUTTERS WHEN NOT INSTALLED WILL BE SUPPLIED AND SITE INSTALLED BY OWNER /LEASEE
WIND LOAD
.�.
A. 146
MPH ........ HIG VELOCITY HURRICANE ZONE
INTERIOR FINISH 2001 FBC CHAPTER 8
I
B. ..
1.0,,......IMPRTANCE FACTOR
C. .....
C.
............. W!Ni EXPOSURE CATEGORY
D. GCpi
= 0.18_ .... VIb1D EXPOSURE CATEGORY
E. Pw
= 65,6 PSF._ WALL COMPONENT AND CLADDING LOAD
F. Pr =
123.7 PSF,,.,,.ROOF COMPONENT CLADDING LOAD
ALL CORRIDORS AND CEILING FINISH ARE CLASS "A" GYPSUM
G. THIS
BUILDING KNOT DESIGNED TO BE LOCATED ON A HILL
A M V P 0 4 0
OR ESCARP MEN -EXCEEDING 15 FEET IN HEIGHT
min FLAME SPREAD 0 -25, NDS OKE DE ELO ED - 5
ALI. INTERIOR WALL FINISH IS CLASS "A" GYPSUM
WITH FLAME SPREAD 0-25, ANDSMOKE DEVELOPED 0 -450
CARPEL` HAS A CRITICAL RADIENT FLUX OF 0,22 WATTS /SO. CM
AS TESTED IN ACCORDANCE WITH NFiPA 253
LISTING AGENCY
APPROVAL
THESE PRINTS COMPLY WITH TIME
FLORIDA MANUFACTURED BUILDING
ACT OF 1979 CONSTRUCTION CODES
AND ADHERE TO THE FOLLOWING
CRITERIA:
CONST, TYPE VI
OCCUPANCY B
ALLOWABLE #
OF FLOORS 1
WIND VELOCITY 146
FIRE RATING OF
EXTERIOR WALLS 0
PLAN NO. MDS003627
ALLOWABLE
FLOOR LOAD 50/900
APPROVAL DATE 01/31/2004
MANUFACTURER PER DCA LETTER
APPROVED FOR HIGH VELOCITY
WIND ZONE YES
DATE_ - -- 01/31/2004 _ - -- PLAN NO -------- MDS003627 - - --
APPROVED BY SAM ACOSTA
MODULAR BUILDING PLANS EXAMINER
FLORIDA CERTIFICATE NUMBER SMP- OQ0003
FIRESAFETY INSPECTOR
CERTIFICATE NUMBER 113873
DESIGN SPACE INC.
P.O. BOX 2008, DOUGLAS, GA, 31533
JOHN A. BODZIAK
ARCHITECT
11^J,
�r
.CH�cK�rrp'.
' SN T•: �3'•'•'
3637 4TH STREET NORTH
SAINT PETERSBURG, FLORIDA 33704
LICENSE #AR- 0005065
AMC-low sr Ana W, 2730 12TH STREET SOUTH
SAINT PETERSBURG, FLORIDA 33705
LISTING AGENCY PHONE #727- I19-c004
DATE SCALE QUOTE SER. NO.
01/31/2004 1 -NTS- MDS003627
SIZE CODE TYPE USE I cl-n rr
PER PRINT 2001 FBC VI 8 MDS
. MCS003627
REV, APPRO A 1y PAGE
... 27 1 OF 4