10-1035 (2)-001FIRE PROTECTION LIFE SAFETY CRITERIA A. CODES: APPLICABLE CODES INCLUDE BUT ARE NOT LIMITED TO THE FOLLOWING REFERENCES: 1. FLORIDA BUILDING CODE 2007 EDITION. 2.NFPA 101 LIFE SAFETY CODE 2006 EDITION 3.NFPA 10 PORTABLE FIRE EXTINGUISHERS 4.AIA GUIDELINES FOR DESIGN AND CONSTRUCTION FOR HEALTHCARE FACILITIES - 2006 EDITION. B. BUILDING GROUP: (CLASSIFIED BY OCCUPANCY) FBC SEC. 3, NFPA101 CHP. 6.15 1. PRIMARY OCCUPANCY: FBC SECTION 310- INSTITUTIONAL (1 -2) / NEW HEALTHCARE NFPA 101 -CH. 18 C. BUILDING CLASSIFICATION OF HAZARD CONTENTS: 1. CLASSIFICATION: LOW HAZARD (NFPA 101 6.2.2) D. BUILDING TYPE: (CLASSIFIED BY TYPE OF CONSTRUCTION) FBC SEC. 5 CRITERIA OUTLINED BELOW IS TYPICAL FOR ALL OCCUPANCIES AND BASED UPON CRITERIA OF A FULLY SPRINKLERED BUILDING. 1. TYPE OF CONSTRUCTION: (TYPE I -A) FULLY SPRINKLERED IN ACCORDANCE WITH 903.3.1 AND 903.2.5 2.STRUCTURE OF EXISTING (ASSUMED I -A) = FBC EXISTING BUILDINGS: CHAPTER 4 (405 AND 407) ADDITION AND ALTERATION LEVEL 2. EXISTING BUILDING 7- STORIES 27,420 SF. PER STORY. PRIMARY BUILDING W/O ADDITIONS: 3.ALLOWABLE HEIGHT = UNLIMITED (FBC TABLE 503) 4.MAX NO. OF STORIES = UNLIMITED (FBC TABLE 503) 5.ALLOWABLE BUILDING AREA = UNLIMITED (TABLE 503) E. FIRE RESISTANT RATED CONSTRUCTION FBC SEC. 6 &7 CRITERIA OUTLINED BELOW IS TYPICAL BASED UPON A FULLY SPRINKLERED BUILDING. APPLICABLE OCCUPANCY GROUP AND BUILDING TYPE OF CONSTRUCTION BASED ON A TYPE I -A BUILDING. 1. STRUCTURAL ELEMENTS FIRE RATING REQUIREMENTS (FBC TABLE 601): a.STRUCTURAL FRAME: 3 HR. b.EXTERIOR BEARING WALLS: 4 HR. c.INTERIOR BEARING WALLS: 4 HR. d.FL00R CONSTRUCTION (INCLUDING SUPPORTING BEAMS AND JOISTS): 3 HR. e.R00F CONSTRUCTION (INCLUDING SUPPORTING BEAMS AND JOISTS): 1-1/2 HR. C EXTERIOR NON- BEARING WALLS (FBC TABLE 602) X <5' = 3 HR. 5' S X < 10' = 2 HR 10'5 X S 20' = 2 HR 20'5 X < 30' = 1 HR 30' <X =NR g.ALLOWABLE AREA OF OPENING (FBC 704.8) X <3' = NP 3'<X <5'= NP 5' S X < 10' _ 10% 10' <X <15'= 15% 15' <X <20'= 25% 20' <X <25'= 45% 25' <X <30' =70% 30' <X= NR 2.FIRE WALLS: 3 HR. / PARTY WALLS 4HR. 3.INTERIOR NON- BEARING WALLS: OCCUPANCY SEPARATION REQUIRED (FBC TABLE 302.3.2) a.INSTITUTIONAL 1 -2: 0 HR. 4.FIRE PARTITIONS (FBC 708): a.FIRE RATINGS FOR ACCESS /EXIT CORRIDORS (TABLE 1017.1): INSTITUTIONAL 1 -2 = 0 5.FIRE RATINGS FOR SHAFTS /OPENING PROTECTIVE (FBC 707.4): a.2 HR. (CONNECTING 4 OR MORE STORIES) b.1 HR. (CONNECTING 3 STORIES OR LESS) 6.FIRE BARRIERS (FBC 706) a.MIN FIRE RESISTANCE RATING = 2 HR. (TABLE 706.3.9.) F. OCCUPANCY LOAD: FBC SEC. 10 (TABLE 1004.1.2) /NFPA TABLE 7.3.1.2 1. PRIMARY OCCUPANCY (INSTITUTIONAL - INPATIENT TREATMENT): 240 SF GROSS 2.ACCESSORY OCCUPANCY (INSTITUTIONAL - OUTPATIENT AREAS): 100 SF GROSS 3.ACCESSORY OCCUPANCY (BUSINESS) 100 SF GROSS 4.ACCESSORY OCCUPANCY (ASSEMBLY - 2) 15 SF /P G. TRAVEL DISTANCES / EXIT WIDTHS REQUIREMENTS: (FBC SEC. 10) THE REQUIREMENTS OUTLINED BELOW ARE BASED ON A FULLY SPRINKLERED BUILDING AND APPLICABLE OCCUPANT TYPES. 1. ALLOWABLE TRAVEL DISTANCES BY OCCUPANCY(FBC 1016.1): INSTITUTIONAL (1 -2) a.MAX. TRAVEL DISTANCE TO EXIT: 200 FT (FBC TABLE 1016.1)./200 NFPA 18.2.6.3.1 b. MAX TRAVEL DISTANCE TO EXIT FROM RM DOOR. 150 FT. (NFPA 101) c.MAX DEAD END CORRIDOR : 20 FT. (FBC 1016.30/20 NFPA 18.2.5.2 d.MAX COMMON PATH OF TRAVEL: 50 FT. /50 NFPA 101 2.EGRESS WIDTHS: a.LEVEL EXIT: 0.2 IN. PER PERSON (FBC TABLE 1005.1) b.STAIRS: 0.3 IN. PER PERSON (FBC TABLE 1005.1) c.MIN. CORRIDOR WIDTH: 44 IN. (FBC 1016.2) d.CLEAR OPENING DOOR EXIT: 32 IN. (FBC 1008.1.1) e.MIN. STAIR WIDTH 44 IN. (FBC 1009.1) 3.VERTICAL EXIT ENCLOSURES a.1 HR. CONNECTING 3 STORIES OR LESS / 2 HR. CONNECTING 4 OR MORE STORIES. (FBC 1020.1) 4.EXIT PASSAGEWAYS a.WIDTH = 44 -IN. MIN. (FBC 1021.2) b.CONSTRUCTION = 1 HR. MIN BUT NOT LESS THAN THAT REQUIRED FOR ANY CONNECTING EXIT ENCLOSURES (FBC 1021.3) c.OPENINGS AND PENETRATIONS = ONLY FROM EXIT ACCESS FROM NORMALLY OCCUPIED SPACES. (1021.4) AS REQ. BY FBC 715.4. d.PENETRATIONS = NP EXCEPT WHEN SERVING EXIT PASSAGEWAY _ 5.HORIZONTAL EXIT (FIRE COMPARTMENTS) a. 2/3 OF THE REQUIRED EXIST FROM ANY FLOOR AREA (FBC 1022.1 EXEP.1) b.2 HR. FIRE SEPARATION (FBC 1022.2) 1 FIRST FLOOR LIFE SAFETY PLAN LS 1.1 SCALE:1 " = 30' H. INTERIOR FINISHES: (FBC SEC. 8) THE REQUIREMENTS OUTLINED BELOW ARE BASED UPON A FULLY SPRINKLERED BUILDING AND APPLICABLE OCCUPANT TYPES. CLASS A - FLAME SPREAD - 00 -25 / SMOKE DEVELOPMENT - 0 -450 CLASS B - FLAME SPREAD - 26 -75 / SMOKE DEVELOPMENT - 0 -450 CLASS C - FLAME SPREAD - 76 -200 / SMOKE DEVELOPMENT - 0 -450 1. EXIT ENCLOSURES AND EXIT PASSAGEWAYS a.INSTITUTIONAL 1 -2: CLASS B 2.CORRIDORS a.INSTITUTIONAL 1 -2: CLASS B 3.ROOMS AND ENCLOSED SPACES a.INSTITUTIONAL 1 -2: CLASS B *CLASS C ON ADMINISTRATIVE SPACES *CLASS C ON ROOMS WITH CAPACITY FOR FOUR PERSONS OR LESS. I. OTHER APPLICABLE DATA 1. SMOKE BARRIERS: (FBC 407.4) a.SMOKE COMPARTMENTS AREA NO MORE THAN 22,500 SQR. FT. b. MAX DISTANCE TO A SMOKE BARRIER DOOR = 200 FT. I - - -- - -- 8 Iti j E.Da WALK- w 1 IN ENTRY PAST TRACK m� I me n..,a ® 19,25 S k �_____________ ____ _J 1 , I ' I SUITE 8 2 2 S.F. I 1 PD. AMBBURiJWCE 1 YY J 1 , I- 1 HR FIREi SMOKE PARTITION` _ ,-" r�-1 j l ___ ` 1 � - I��L I N W ^^ 0 N CLINICAL a.�a � ,J I , m I EXPA NSIO � J 1 l •� ILI 13,641 S.F. °' I t0E' - KkrloH aKCau gl •- � � n5-- L_ _s 1 HR FIRE/ SItOKE PARTITI - - --r -------- - - - - -- I I NEW ��-� EXISTING a ADDITION 1 e I I I b I I I I -► e-► - - W- W- _- _- _- W-W__ -_W WW NEW `, ADDITIDN �. RADIATION ONCOLOGY CTaD I tl�srtoua txKl.a I runs alrouo aeumu I I Ca1MCM A OB.'t 1.Q nm nuat m a-a:ll1[ �aac ^I M" A rAlr 1a1 aaa i own cu arm SArun un s veam tom nl- W A a7YCIU[ Knt tltaat was tawo mans „ I 2HR FIRE/ SMOKE PARTITION -ta _'Cr > i A"► ik�4 •° 2HR FIRE/ SMOKE PARTITION CENTRAL I 2HR FIRE/ SMOKE PARTITION 1 HR FIRE/ MRMROOM SMOKE WALL 2HR FIRE/ SMOKE PARTITION NORTH TOWER 2HR FIRE/ 2HR FIRE/ SMOKE SMOKE PARTITION PARTITION OPEN MAIN BUILDING LL COMPLY SHA U TIES► POR-110N5 OF �� IEpIST1;dG ENT10N �dpE- ;T1NG PR0v1S10 �LORIOA FIRE PREY SET FORTH IN T1AE ,RTITION 1 ��R1OVLO IficY -'T"O � I 01 ESE NDOAO A4 4HR FIRE/ SMOKE PARTITION AP.C!-IITECT:- - - _A - SYMBOL LEGEND ONE HOUR FIRE RATED PARTITION ONE HOUR FIRE RATED/ SMOKE PARTITION "'' ... w > >- - - - - _ _ _ - - BERMFLLO- AJAMIL & PARTNERS, INC. TWO HOUR FIRE RATED PARTITION - - - - - Architecture Engineering Planning I I TWO HOUR FIRE RATED/ SMOKE PARTITION = Interior Dcsig; Landscape Architecture e� e ■ e THREE HOUR FIRE RATED/ SMOKE PARTITION 2601 South Bayshore Drive 10th Floor FOUR HOUR RATED/ SMOKE PARTITION Miami, Florida 33133 (305) 859 -2050 Fax (305) 860 -3700 EXIT LIGHT (CENTER ON DOOR(S)) PLANNING ARCHITECT: NOTE: SHADED AREA INDICATES LIGHTED FACE I Al 0 EXIT LIGHT: DIRECTIONAL (CENTER ON DOOR(S) ■ AS REQUIRED) NOTE: SHADED AREA INDICATES LIGHTED FACE WILMOT SANZ FE FIRE EXTINGUISHER: SEE DETAIL A R C H I T E C T U RE 6/A6.42 P L A N N I N G FIRE JACK 18310 Monlgommy Village Avenue F GaWwsburg Maryland 20879 301 - 590.2900 0! > 301- 590 -8150 STRUCTURAL ENGINEER: q FHC FIRE HOSE CABINET A '. RA�is�iiL. NRINEEN�Ei,N�EEfis ❑RAMON R. DONNELL aHt/srR cRRO ❑PEDRO J. DUQUESNE aP gWI64 FD MANUAL FIRE ALARM BOX (PULL STATION) ' ; ((❑gA14Djtj. ALBAIS MIAMI. rpPF��o� d Lg90 Yr iTASiE OFFBFLOPoOA - UTHORIZATION No. 11306 Ell FIRE ALARM COMBINATION AUDIBLE / VISIBLE 'V1 0612 2006 NOTIFICATION APPLIANCE MEP ENGINEER: Od FIRE ALARM VISIBLE NOTIFICATION APPLIANCE FIRE ALARM AUDIBLE NOTIFICATION APPLIANCE P2121 Ponce de Leon Blvd., Suite 350 Coral Gables, FL 33134 Prole:nondCorm,ItxpUleneen phone: 305.569.1692 fax 305.569.1693 OD SMOKE DETECTOR (CEILING MOUNTED) Dallas . Houston . Nashville . Miami - Richmond Austin - Denver - Phoenix - Washington D.C. ccrd project number. 405112.038 E800007658 OS FIRE ALARM SPEAKER (CEILING MOUNTED) IT CONSULTANT: FAAP FIRE ALARM ANNUNCIATOR PANEL VFronkhn,Tcmes=37067 ENE BURTON &ASSOCIATES Crnerol George Patton Drive 5640 West I -20, Suite 150 Arlington, Texas 76017 e: 613.376.3100 Phone: 817363.2486 615376.3114 Fax: 817.5632753 MGAP MEDICAL GAS ALARM PANEL u`: `"rrr`'.gbalacxom Medical Equipment and Communications Planners IRRIGATION CONSULTANT: Kenneth DiDonoto, Inc. 2212 Hollywood Blvd. F-D-H-1 SMOKE DOOR MECHANICAL HOLD OPEN Hollywood. FL 33020 954-923 -2555 SIGNAGE CONSULTANT: tgadesign [361 180 EXIT CAPACITY: 4649 Ponce de Leon Blvd. INCHES / NUMBER OF OCCUPANT CAP. 305-669°25550 FL 33'a6 ACOUSTICS CONSULTANT: Kinsella -Marsh Group, Inc. 4045 Sheridan Ave. OHEAT DETECTOR Miami Beach. FL 33140 FL FIRE LIGHT FIRE INDICATOR LIGHT CEILING MOUNTED ■ m m m m m m m m■ I NEW ADDITION DEMARCATION 214819 -1400 HOBO/, 657A' t. CONSTRUCTION DOCUMENTS REVISIONS: 10 _ 06/2412011 OWNER REQUESTED CHANGES 21 5125/2012 FIELD COORDINATION 24 08 -27 -12 FIELD CHANGES 31 _ 05122/13 OWNER CHANGES 34 01117/14 OWNER CHANGES 1. SEE SHEET LS1.1 FOR COMPARTMENT AND EXIT LOADS TABLES 2. NON- SLEEPING SUITE: PROJECT NAME: • 18.2.5.7.3.3. NON- SLEEPING SUITE MAXIMUM SIZE, SMH- CLINICAL EXPANSION NON- SLEEPING SUITE SHALL NOT EXCEED 10,000 SQ. FT. • 18.2.5.7.1.4. SUITE SUBDIVISION, THE SUBDIVISION OF SUITES SHALL BE BY MEANS OF NONCOMBUSTIBLE OR LIMITED - COMBUSTIBLE PARTITIONS OR PARTITIONS PROJECT ADDRESS: CONSTRUCTED WITH FIRE - RETARDANT - TREATED WOOD ENCLOSED WITH NONCOMBUSTIBLE OR LIMITED - CUMBUSTIBLE 7400 S.W. 62nd Ave. MATERIALS, AND SUCH PARTITIONS SHALL NOT RE REQUIRED South Miami, Florida 33143 TO BE FIRE RATED. LIFE SAFETY CALCULATIONS FIRST FLOOR EXIT CALCULATIONS COMFY COMPARTMENT AREA (SF) OCCCUPAN TLOAD (PERSONS) EXIT CAPACITY PROVIDED (INCHES) TOTAL EXIT OCCPT. PROVIDED /REQ' D(PERSONS) SLEEPIN G (120 SF /P) NON- SLEEPING (240 SF /P) ASSEMBL Y 15 SF /P) OFFICE 100 SF/P) MERCNT (30 SF /P) STAIR (.30 ) LEVEL (.20 ) 1A 13,525 56 - 721360 360156 113 - 20,234 - 84 - 34811740 1740184 1C 11,707 827 3,574 760 165 - 304/1520 1520/165 ID 549 11,590 118 - 46/230 230/118 1E - 8,977 3,560 275 - 1081540 540/275 1F 12,439 - 52 - 1441720 720/52 1G 1H - 8,003 5,864 - - 33 24 - - 1381690 1141570 690/33 570124 11 6,841 - 29 - 126/630 630/29 0 11K 8,338 35 - 421210 210135 1J 6,239 - 26 - 841420 420/26 1M 13,641 - - 57 - 841420 420157 1 N 1 19,254 - 80 - 841420 420180 D ' NEW CONS COMM. NO. 40051.100 SCALE: AS SHOWN DATE: 10 -22 -2010 DRAWN: JEC CHECKED: sH CADD FILE: H:INSTI=ONAL DRAWING TITLE: FIRST FLOOR LIFE SAFETY PLAN SHEET NO. LS1 A