PRODUCT INFORMATION
FEATURES:
• UL LISTED
• FM APPROVED
• CALIFORNIA STATE FIRE MARSHAL LISTING NUMBERS:
2098 -9163 CONTROL ZAM: 7300 - 0026:182
• ZONE ADAPTER MODULES (ZAOa PROVIDE
ADDRESSABILTTY TO CONVENTIONAL CIRCUITS
• FOR USE WITH SIMPLEX MAPNET II COMMUNICATIONS
• NFPA STYLE 4 OR 6 COMMUNICATIONS
• STYLE 4 WIRING MAY BE EITHER 'T' TAPPED OR IN /OUT
• DIP SWITCH ADDRESS SELECTION, 8 SWITCHES
• MOUNTING: SURFACE
SPECIFICATIONS:
• DEVICE OTY: 127 MAPNET II DEVICES ON A SINGLE PAIR OF WIRES
• OPERATING TEMPERATURE RANGE 32' F TO 120' F
• HUMIDITY RANGE 85% NON - CDNDENSING O B6' F
• CONTROL ZAM RELAY CONTACTS ARE RATED Ar- .5A O 120
VA OR 2A O 28 VDC, RESISTIVE
• SUPERVISORY DC CURRENT: 10 mAl LOAD PEB ZAM
• ALARM DC CURRENT: 40 mA ff
DESCRIPTION:
CONTROL ZAMS ARE USED TO PROVIDE ADDRESSABLE
CONTROL FUNCTIONS SUCH AS ELEVATOR CAPTURE, WAG
CONTROL, PRESSURIZATION FAN CONTROL, DAMPER CONTROL
WIRING:
1. ALL WIRING TO COMPLY WITH LOCAL. CODE.
2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS.
3. MAPNEr II LINES ARE TO BE 118 AWG TWISTED
SHIELDED PAIR (CONSULT STR SALES ENGINEERING
FOR EXCEPTIONS).
4. MAXIMUM ALLOWABLE LINE RUN FROM
4020 OR 4100 OR 4120 TO FARTHEST
DEVICE NOT TO EXCEED 2500 FEET.
5. FOR MAXIMUM VOLTAGE PROP ,ETC.REFER TO
STIR SALES ENGINEERING S 4020 bR 4100
OR 4120 FIELD WIRING GUIDE.
6. MINIMUM NO. 14 AWG WIRE FOR 28 VDC WIRING,
OR TO LOCAL CODE.
7. CONTRACTOR WIRING TO RELAY CONTACTS IS
MAPNET II ADDRESSABLE CONTROL ZAM 2190 -9163
(RACO NO. 191) 4 11 /16- SQUARE
2 1/8- DEEP BOX
SUPPLIED BY CONTRACTOR
(RACO NO. 203) EXTENSION
SUPPLIED BY CONTRACTOR n
UNSUPERVISED. USE NO. 14 AWG, OR TO SEE WIRING N01
LOCAL CODE. 7, 8, 9
B. RELAY CONTACTS RATED 2A, 28 VDC. FOR DC
LOADS. POWER MUST BE PROVIDED FROM FA
CONTROL 4020 OR 4100 OR POWER SUPPLY LISTED
FOR FIRE PROTECTIVE SIGNOALING USE. DERATE
CU RENT RATTING BY 50% FOR INDUCTIVE LOADING. LOADNNG.. LISTED
9. REFER TO INSTALLATION INSTRUCTIONS 575 -279 OR
575 -592.
10. REFER TO FIELD WIRING DIAGRAMS 841 -804 OR
841 -996.
MAPNET II ADDRESS DIP SWITCHES
SEE INSTALLATI N INSTR TIONS
PER -21 -021 575 -279 FOR SETTINGS
2 MTG SCREW 8 -32 FHMS
2 SCREWS SIMPLEX P/N 412 -779
SIMPLEX SURFACE COVER - J
SURFACE MOUNTING
'" "^TONAL MAPNET II
OR RETURN TO
FOR STYLE 6
APPLICATION
28VCC _ _ 3. 4. 5�..�
FROM PREVIOUS DEVICES B) SEE WIRING NOTES
OR FIRE ALARM CONTROL +(C) 5, 6 SEE WIRING NOTES
PANEL
MAPNET
SHIELD SEE WIRING . NOTES
TrueAlert�`NON- ADDRESSABLE MULTI - CANDELA VISIBLE NOTIFICATION APPLIANCE
TO NEXT DC
POWERED DEVICE
PRODUCT INFORMATION
WHEN SURFACE MOUNTING USE 4' SQUARE x 1 -1/2' DEEP BOX
(WALL MOUNT) RED SKIRT NO.4905 -9937 OR
FEATURES: WHITE SKIRT NO. 4905 -9940
• UL LISTED TO STANDARD 1971 4905 -9931 ADAPTER PLATE o 2975 -9145 BOX /\
• ADA COMPATIBLE
RATING
RMS CURRENT 0
1/2W
79 dBA
SYNCHRONIZATION FLASH RATE MODE FOR USE WITH:
2W
85 dBA
ANECHOIC CHAMBER
*i+:al
•SEPARATE STROBE SYNCHRONIZATION MODULES THAT ARE AVAILABLE
p
96 dBA
SURFACE MOUNTING
FOR CLASS B OR CLASS A OPERATION
_Cia\f»
>_
cl)�
2099 -9819 (BLACK) OR
75cd
186 rtJA
•SEPARATE SMARTSYNC CONTROL MODULES (SCMs) THAT PROVIDE
124 mA
1 0
52 mA
168
CLASS B OR CLASS A OUTPUT FROM CONVENTIONAL NAC INPUTS
15cd
60 mA
E[.J; ►:\
O
tttttO1A1:1:�EbTCP:��:,r���r�
SPECIFICATIONS:
94 mA
•
0
63 mA
75c
186
• HOUSING DIMENSIONS: 5 -1/8' H X 5' W X 2 -3/4' D (130mm X 127mm X 70mm)
124 rnA
11 Dcd
252 mA
224 mA
168 mA
• TEMPERATURE RANGE: 3ZF TO 12TF (0 TO 50'C)
�NOTE: BOX MUST BE RECESSED
2 L0
0
INTO WALL 1' TO 1 1/8'.
• HUMIDITY RANGE: 10x TO 93% NON - CONDENSING AT 100'F (3L1'C)
CUTOUT MUST BE A MINIMUM
FLUSH
MOUNTING 6' HIGH BY 5' WIDE
.�
•TERMINAL BLACKS FOR 1BAWG TO 12AWG; TWO WIRES PER
O
CC 2
CL
w
:)
v
=
TERMINAL FOR IN /OUT WIRING.
p
U)
WIRING:
1. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL STANDARD
ELECTRICAL. BOX MOUNTING
2. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP V
SQUARE BOX, 1 -1/2' DEEP
WIRES UNDER TERMINALS.
3. ALL NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER - LIMITED.
ZW
4. SEE INSTALLATION INSTRUCTIONS (579 -548) FOR ADDITIONAL INFORMATION.
STROBE: SURFACE
MOUNTING
• RATED VOLTAGE RANGE UL USTED: 16 VDC TO 33 VDC PER UL 1971
0_
U)
ULC LISTED: 20 VDC TO 30 VDC PER ULC 5526 -M878
• FLASH RATE 1Hz
• MODE
SURF MOU ADAPTER SKIRT
1 5/8 (41mm) DEEP.
SYNCHRONIZED NA LOADIIv,;: MAXIMUM OF 35 SYNCHRONIZED STROBES PER NAG CIRCUIT.
CONNDUIT CUTOUTS ARE PROVIDED
*CURRENT DRAWS REFLECT STROBE FLASHING
ON ALL FOUR SIDES.
I " Mm
RATING
RMS CURRENT 0
1/2W
79 dBA
1W
82 dBA
2W
85 dBA
ANECHOIC CHAMBER
*i+:al
90 dBA
-+�+';
96 dBA
SURFACE MOUNTING
BY CONTRACTOR
_Cia\f»
>_
cl)�
2099 -9819 (BLACK) OR
75cd
186 rtJA
122ffkA
124 mA
1 0
52 mA
168
iIDIMmwasmswki
15cd
60 mA
E[.J; ►:\
ISTI�I- '- DT<��;7;ILL_
tttttO1A1:1:�EbTCP:��:,r���r�
30ed
94 mA
•
0
63 mA
75c
186
INSTITUTIONAL
124 rnA
11 Dcd
252 mA
224 mA
168 mA
IMPORTANT!
WALL MOUNT INSTALLATION
HEIGHT REFERENCE
ELECTRICAL BOTTOM OF LENS
BOX OURJNE IS EEFER EVEN WITH
OR SUGHRY ABOVE
BOTTOM of
COMPATIBLE BOXES
NFPA 72 REQUIRES THAT
�. THE ENTIRE LENS BE NOT
MIN. LESS THW 80' AND NOT
GREATER TRW 96' ABOVE
THE FINISM FLOOR.
FROM A COMPATIBLE SIMPLEX
SMARTSYNC NAC OR FROM
SMARTSYNC CONTROL
MODULE (SCM) 4905 -9938
OR SIMPLEX 4905 -9914
OR 9922 SYNC CUBE
WIRE
FOR
N BE
1NTING
TrueAlert'MNON- ADDRESSABLE MULTI -CANDE i' 51' 1I R %�1I IY L;Et'.,N(
PRODUCT INFORMATION
FEATURES: (WALL MOUNT)
• UL LISTED TO STANDARD 1971 & 1480 -
• ADA COMPATIBLE
[FICA
0
0
0
ALTERNATE BACK BOXES
1. 2 GANG 1 -1/2' DEEP BOX
2. SINGLE GANG 1 -1/2' DEEP BOX
TO ADDITIONAL NOTIFICATION
APPLIANCE DEVICE OR RETURN
TO FACP FOR STYLE Z APPLICATION
IF LAST DEVICE ON CIRCUIT IN A
STYLE Y APPLICATION PLACE A
1OK 1/2W END -OF LINE RESISTOR
STROBE INTENSITY
VIEWING SLOT
APPLIANCE
STANDARD ELECTRICAL BOX MOUNTING I . I { 4' SQUARE BOX, 1J1/2' DEEP,
• OPTIONS FOR WALL MOUNT SPEAKER VISUALS: 4' SQUARE BOX, 1 -1/2' DEEP, f -- -- -- 1i k• 4*'SQUARE'BOX EXTENSION,
- SKIRTS FOR SURFACE MOUNT ELECTRICAL BOXES WITH A 4' SQUARE BOX EXTENSION, __ -- -�w.._ C1 -1 /r DEEP, SUPPLIED BY OTHERS �� QC
RED 4905 -9946, WHITE 4905 -9947 1 -1/2' DEEP, SUPPLIED BY OTHERS F F )
- 4905 -9998 WIRE GUARD TRANSPARENT HOUSING QQQp' __..� _ - _{ _ SURF/ACF*'�AOUtADAPTER SKIRT;
SYNCHRONIZATION FLASH RATE MODE FOR USE WITH: AND LENS ASSEMBLY QO 0 { CO DUR UfOm AREPROVIDED
• SEPARATE STROBE SYNCHRONIZATION MODULES THAT ARE AVAILABLE e Q Q ! ON ALL FOUR SIDES.
FOR CLASS B OR CLASS A OPERATION •Q ._ _.._�. .. 1._- «._ L_ -- -- -- -- p
REMOVABLE COVER
(TOOL REQUIRED)
SPECIFICATIONS:
• HOUSING DIMENSIONS: 7 -1/4' H X 5' W X 2 -5/8' D (184mm X 127mm X 67mm)
• TEMPERATURE RANGE 37F TO 127F (0 TO 50'C)
• HUMIDITY RANGE: 10% TO 93% NON- CONDENSING AT 1WF (NC)
•TERMINAL BLOCKS FOR 18AWG TO 12AWG; TWO WIRES PER
TERMINAL FOR IN /OUT WIRING.
WIRING NOTES:
1. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL
2. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP
WIRES UNDER TERMINALS.
3. ALL NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER- UMITED.
4. SEE INSTALLATION INSTRUCTIONS (579 -548) FOR ADDITIONAL INFORMATION.
STROBE:
• RATED VOLTAGE RANGE: UL LISTED: 16 VDC TO 33 VDC PER UL 1971
• FLASH RATE: 1Hz ULC LISTED: 20 VDC TO 30 VDC PER ULC 5526 -MB78
• SYNCHRONIZED MODE NA LOADING: MAXIMUM OF 35 SYNCHRONIZED STROBES PER NAG CIRCUIT.
*riIRRrM nDAWC PMrrT -=Mr rIACIeuD
HOUSING LCOLORO
MODEL NUMBER
RATING
RMS CURRENT 0
1/2W
79 dBA
1W
82 dBA
2W
85 dBA
ANECHOIC CHAMBER
87 dBA
90 dBA
93 dBA
96 dBA
SURFACE MOUNTING
BY CONTRACTOR
SEE INSTALLATION INSTRUCTIONS (574 -332 FOR SETTINGS
>_
cl)�
2099 -9819 (BLACK) OR
75cd
186 rtJA
122ffkA
124 mA
1 0
52 mA
168
4906-9153 WHIT RED
15cd
60 mA
40 mA
COVER FORWARD
30ed
94 mA
•
0
63 mA
75c
186
INSTITUTIONAL
124 rnA
11 Dcd
252 mA
224 mA
168 mA
SPEAKER:
FREQUENCY RESPONSE: FIRE ALARM: 400 TO 4000Hz
GENERAL SIGNALING: 125 TO 12kHz
SPEAKER OUTPUT RATINGS O 10 FT. (3m)
REVERBERATE CHAMBER
UL 464 TEST
1 /4W
76 dBA
1/2W
79 dBA
1W
82 dBA
2W
85 dBA
ANECHOIC CHAMBER
87 dBA
90 dBA
93 dBA
96 dBA
\ \SCMIAMIt \DRAFTING \00 - 2003 \SOUTH MIAMI HOSPITAL (MAS'TER SITE) \SMH CLINICAL EXPANSION- REV01- 952933613\ SMB) A647N�A' FJ® ANBFDN •I:f�[.f1- E64933613.DWGDATE PL077'ID: January 21, 2011 DATE 3AVSD: January 21, 2011
e 191RIN6 INPUT 1EiC INALS eD,, J : A A: I. ^+ o
e . S .F • . SPEAKER TAP SELECTION ARE •__ _ r , _
k° ACCESSIBLE FROM REAR-. 1
SPEAKER ASSEMBLY
OBE ASSEMBLY J s
INTENSITY SELECTION
INTENSITY SELECTION PLUG, ACCESSIBLE ONLY
PLUG; ACCESSIBLE ONLY FROM REAR OF HOUSING;
STROBE INTENSITY FROM' REAR OF HOUSING; _ ... FACTORY SETTING IS 15cd
VIEWING SLOT •"'FACTORY SETTING IS 15cd : F
I STROBE INTENSITY
! VIEWING SLOT
SEMI - FLUSH - MOUNT -' -' I"' F
IMPRTANT! SURFACE MOUNT OPTION
WALL MOUNNTT INSTALLATION
w,_ --,- •-- -•� HEIGHT REFERENCE'
s•,.«+Yfnw.w. y1 '297'n°- 145' "4'SOC BUJ('bllfUFE' • • ...
ia{ Sox. OUIUNE;: 4' A 5
"•.� �a�.'X +.".� :a +, .• - '_78.1/2'. ,NF?A72 REQ08tES•7�JAT .:S:ni uF+t...9a..: .
MIN. THE ENTIRE LENS BE NOT
LESS THAN 80' AND NOT
MIN. GREATER TWW 96' ABOVE
THE FINISHED FLOOR.
FROM -AUDIO NA CHANNEL
(41DU /4Dt)3)'(SEE WIRING NOTES)
FROM STANDARD NAG OR
COMPATIBLE SIMPLEX SMARTSYNC
NA OR FROM SMARTSYNC CONTROL
MODULE (SEE WIRING NOTES)
SPKR - Sm -
TYPICALS
D- OF -UNE
SISTOR (VALUE
PENDANT ON FAP)
PRODUCT INFORMATION
4- SQUARE x
4099 -9001 SINGLE ACTION IDNET ADDRESSABLE STATION y 1/8• DEEP BOX
FEATURES:
SINGLE GANG EXTENSION RING
(RACO NO. 773)
3/4' (RACO, NO. 231 OR 232)
RA
0R (EGO NO. 5DO)
• UL LISTED
• SINGLE ACTION, IDNET ADDRESSABLE
• PULL LEVEL PROTRUDES WHEN ALARMED
• TAMPER RESISTANT RESET KEY LOCK
MOUNTING INSTRUCTIONS: KNOCKOUTS FOR 3/4* CONDUIT
1. COVER & BACKPLATE COME ASSEMBLED. TOP AND BOTTOM BOX
2. UNLOCK STATION DROP COVER FORWARD
TO EXPOSE MOUWNG SCREWS.
SUPPLIED BY CONTRACTOR
MOUNTING INSTRUCTIONS:
1. COVER & BACKPLATE COME ASSEMBLED.-
2. UNLOCK STATION, DROP COVER FORWARD
TO EXPOSE MOUNTING SCREWS. c
SINGLE GANG SWITCH BOX
2 1 Y DEEP
O UP UED BY CONTRACTOR
O
^ D
• MOUNTING: SEMI - FLUSH, SURFACE 4
• OPERATING TEMPERATURE RANGE: 32 - 120' F r
• OPERATING HUMIDITY RANGE: 0 - 93x RH 2099 -9828
• ADAPTER PLATES 2099 -9813 OR 2099 -9814 CAN BE INSTITUTIONAL
USE FOR RETROFIT APPLICATIONS. COVER KIT
• 5' HIGH X 3 3/4' WIDE X 1' DEEP (IF REQ'D)
• SCREW TERMINALS FOR 18 TO 14 AWG WIRE
• ADDRESSED BY MEANS OF AN 8 POSITION DIP SWITCH
• COMPATIBLE WITH IDNet/MAPNET
OPERATION:
ACTIVATION:
4099 -9001 SINGLE ACTION STATION REQUIRES A FIRM DOWNWARD
PULL TO ACTIVATE THE ALARM SWITCH. COMPLETING THIS ACTION
BREAKS AN INTERNAL PLASTIC BREAK -ROD THAT IS VISIBLE BELOW THE
PULL LEVER (USE OF PLASTIC ROD IS OPTIONAL). THE PULL LEVEL LATCHES
'470 THE ALARM POSITION AND REMAINS EXTENDED OUT OF THE
HOUSING TO PROVIDE A VISIBLE INDICATION.
RESETTING
4099 -9001 SINGLE ACTION STATION REQUIRES A KEY TO RESET
THE ACTIVATION LEVER AND DEACTIVATE THE ALARM SWITCH.
(IF OPTIONAL PLASTIC BREAK ROD WAS USED IT MUST BE REPLACED)
CONSTRUCTION:
STATION HOUSING AND PULL LEVER ARE CONSTRUCTED OF CHIP
RESISTANT AND DIRT RESISTANT, HIGH IMPACT LEKAN.
HOUSING IS RED WITH RAISED WHITE LETTERING AND PULL LEVER IS
WHITE WITH RED RAISED LETTERING.
• LEXAN IS A REGISTERED TRADEMARK OF THE GENERAL ELECTRIC CO.
APPLICATION:
PULL STATIONS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72
AND ADA GUIDE LINES.
INTRODUCTION:
THE 4099 -9001 ADDRESSABLE PULL STATIO)N PROVIDES TWO -STATE
MARRMCONTROL PANELN(FACP VIA THE RIDNET CHANNEL THE IDNET
LE FIRE
2099 -9828
INSTITUTIONAL
COVER KIT
(IF REQ'D)
`\�
OR
2975 -9022 BOXES
?9
ROM SIMPLEX
FROM SIMPLEX OR
w
w
WIREMOLD BOX
57C0 4NTRACTORU�
ADDRESS DIP SWITCHES UNDER RE- SEALABLE LABEL
SURFACE MOUNTING
BY CONTRACTOR
SEE INSTALLATION INSTRUCTIONS (574 -332 FOR SETTINGS
>_
cl)�
2099 -9819 (BLACK) OR
4 11/16' SQUARE x 2 1/B' DEEP BOX SEMI -FLUSH MOUNTING
2099 -9820 (BEIGE)
SUPPLIED BY CONTRACTOR
Q Q
FLUSH ADAPTOR AVAILABLE
FROM SIMPLEX
MOUNTING
OOO
COVER & BACKPLATE COME ASSEMBLED.
2. UNLOCK STATION, DROP
COVER FORWARD
TO EXPOSE MOUNTING SCREWS.
•
0
2099 -9828
•O
INSTITUTIONAL
,
COVER KIT
I
0
(IF REQ'D)
�NOTE: BOX MUST BE RECESSED
2 L0
0
INTO WALL 1' TO 1 1/8'.
�,
CUTOUT MUST BE A MINIMUM
FLUSH
MOUNTING 6' HIGH BY 5' WIDE
f,HANtrEI PROVIDES THE COM UNCATION LINK BETWEEN PULL STATION IDNET
AND THE FAP AND POWERS THE ENTIRE CIRCUITRY.
WIRING: FROM FIRE ALARM CONTROL PANEL OR
1. ALL WIRING TO COMPLY WITH LOCAL CODE. OTHER IDNET DEVICES ON CIRCUIT
m
2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS.
3. MAINTAIN CORRECT POLARITY
4. IDNET LINES ARE TO BE 18 AWG TWISTED SHIELDED PAIR
5. MAXIMUM LINE RUN FROM PANEL TO FARTHEST DEVICE NOT
TO EXCEED 2500 FEET.
6. MAXIMUM TOTAL WIRE (INCLUDING ALL T -TAPS) FROM PANEL NOT TO
EXCEED 10,000 FEET.
7. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT: 250
8. TERMINALS 1 AND 2 FOR FIELD WIRING. TERMINALS 3 AND
4 ARE FACTORY WIRING.
9. WIRE NUT, SPLICE, OR SOLDER THE SHIELD WIRES.
10. IF SHIELD IS PRESENT R SHOULD BE CONNECTED TO THE
OUTGOING IDNET SHIEIb TO PROVIDE A CONTINUOUS SHIELD OVER
THE LENGTH OF THE IDNET CHANNEL SHIELD SHOULD BE
INSULATED FROM THE ELECTRICAL BOX.
11. SEE INSTALLATION INSTRUCTIONS 574 -332
PRODUCT INFORMATION 4098 -9792 STANDARD SENSOR BASE
FEATURES:
• UL LISTED, FM APPROVED
• TRUEALARM ANALOG SENSING PROVIDES DIGITAL TRANSMISSION OF ANALOG
SENSOR VALUES VIA MAPNETII, OR IDNet TWO WIRE COMMUNICATIONS
• FIRE ALARM CONTROL PANEL PROVIDES:
-INDIVIDUAL SENSITIVITY SELECTION FOR EACH SENSOR
-PEAK VALUE LOGGING ALLOWING ACCURATE ANALYSIS FOR SENSITIVITY SELECTION
- AUTOMATIC ENVIRONMENTAL COMPENSATION
- DISPLAY OF SENSITIVITY IN PERCENT PER FOOT
- MULTISTAGE ALARM OPERATION
- ABILITY TO DISPLAY AND PRINT DETAILED SENSOR INFORMATION IN PLAIN ENGLISH LANGUAGE
• PHOTOELECTRIC SMOKE SENSOR 4098 -9714:
SEVEN LEVELS OF SENSITIVITY FROM 0.2x TO 3.7%
• IONIZATION SMOKE SENSOR 4098 -9717:
FOUR LEVELS OF SENSITIVITY FROM 0.5% TO 1.7%.
• HEAT SENSOR 4098 -9733:
- RATE -OF -RISE TEMPERATURE DETECTION IS SELECTABLE AT THE CONTROL PANEL FOR EITHER 16F
OR 20'F PER MINUTE
-FIXED TEMPERATURE SENSING IS INDEPENDENT OF RATE -OF -RISE AND PROGRAMMABLE TO OPERATE
AT 135'F OR 155F
-TRUEALARM HEAT SENSORS CAN BE PROGRAMMED AS A UTILITY DEVICE TO MONITOR
FOR TEMPERATURE EXTREMES IN THE RANGE FROM 37 F TO 120' F.
• UL STANDARD SPACING:
-60 FT SPACING FOR 135' F
-40 FT SPACING FOR 155 F
• INTEGRAL RED LED FOR POWER -ON (PULSING), OR ALARM OR TROUBLE (STEADY ON)
• BASE MOUNTED ADDRESS SELECTION:
- ACCESSIBLE FROM FRONT (DIP SWITCH UNDER SENSOR)
- ADDRESS REMAINS WITH ITS PROGRAMMED LOCATION
• FOR USE WITH SIMPLEX 4010, 4100, 4020, AND 4120 SERIES CONTROL PANELS.
• MAXIMUM QUANTITY OF DEVICES:
-127 FOR 4020, 4100 4120
-250 FOR 4010, 4100U
• MOUNTING: CEILING OR WALL
• COLOR : FROST WHITE
• BASE DIMENSIONS: 15/16' X 4-7/8'
SPECIFICATIONS:
• UL LISTED TEMPERATURE RANGE: 3TF TO 1OD'F
• OPERATING TEMPERATURE RANGE 3TF TO 120'F
• HUMIDITY RANGE: 10% TO 95% RH
• PHOTOELECTRIC SENSOR AIR VELOCITY RANGE 0 -2000 FT /MIN
• IONIZATION SENSOR AIR VELOCITY RANGE 0 -300 FT /MIN
• WIRING CONNECTIONS: SCREW TERMINALS FOR IN /OUT WIRING, #18 TO 114 AWG
•
COMMUNICATIONS (CATIOONS DN�I /ID et- 1 ADDRESS PER BASE
CURRENT.400uA ICAL
DESCRIPTION:
TRUEALARM SENSOR BASES CONTAIN INTEGRAL ADDRESSABLE ELECTRONICS
THAT CONSTANTLY MONITOR THE STATUS OF THE DETACHABLE PHOTOELECTRIC,
IONIZATION, OR HEAT SENSORS. EACH SENSOR'S OUTPUT IS DIGITIZED AND
TRANSMITTED TO THE SYSTEM FIRE ALARM CONTROL PANEL EVERY FOUR SECONDS.
SINCE TRUEALARM SENSORS USE THE SAME BASE, DIFFERENT SENSOR TYPES
CAN BE EASILY INTERCHANGED TO MEET SPECIFIC LOCATION REQUIREMENTS. THIS
FEATURE ALLOWS INTENTIONAL SENSOR SUBSTITUTION DURING BUILDING CONSTRUCTION.
WHEN CONDITIONS ARE TEMPORARILY DUSTY, INSTEAD OF COVERING THE SMOKE SENSORS.
HEAT SENSORS MAY BE INSTALLED WITHOUT REPROGRAMMING THE CONTROL PANEL,
ALTHOUGH THE CONTROL PANEL WILL INDICATE AN INCORRECT SENSOR TYPE, THE HEAT
SENSOR WILL OPERATE AS A DEFAULT SENSITIVITY PROVIDING HEAT DETECTION FOR
BUILDING PROTECTION AT THAT LOCATION.
WIRING:
1. ALL WIRING TO COMPLY WITH LOCAL CODE. FROM PR OUS
2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS,
3. MAINTAIN CORRECT POLARITY MAPNETII IDNet
4. MAPNETII /IDNet WIRING TO BE /18 AWG TWISTED SHIELDED PAIR OR FIRE ALARM
5. IF SHIELD IS USED, TWIST SHIELD WIRES TOGETHER AND CAP WITH CONTROL PANEL
WIRE NUT. SHIELD SHOULD BE INSULATED FROM ELECTRICAL BOX.
6. REFER TO INSTALLATION INSTRUCTIONS (574 -707)
7. REFER TO APPLICATION MANUAL (574 -709)
TO ADDITIONAL IDNet DEVICES OR RETURN
TO FIRE ALARM CONTROL PANEL FOR STYLE 6
APPLICATION.
I T•]
4' X 1 1/2' DEEP OCTAGONAL
4' SQUARE X01 1/2' DEEP, WHICH REQUIRES
A 4098 -9832 ADAPTER PLATE (6 -3/8' X 1/41
BOX SUPPLIED BY CONTRACTOR
MAPNETII IDNet ADDRESS DIP SWITCHES C
SEE I INSTALLATION INSTRUCTIONS
574 -709 FOR SETTINGS Y�I
4098 -9714 PHOTOELECTRIC SMOKE SENSOR
4098 -9717 IONIZATION SMOKE SENSOR
4098 -9733 HEAT SENSOR
FLUSH MOUNTING
(BOX TO BE FLUSH OR RECESSED 1/4' MAXIMUM)
TO ADDITIONAL MAPNETII /IDNet DEVICES
OR RETURN TO FIRE ALARM CONTROL
PANEL FOR A SUE 6 APPLICATION
NIIAMI -DADE COUNTY
FIRE DEPARTMENT
L. TRIANA & ASSOCIATES, INC.
CONSULTING ENGINEERS
CERTIFICATE' OFD � lhijR �tI N: 266,44
5151 S.W. 98� �AV .E'RI3 s
MIAMI, FLORI , -33��� N S
n '
LESTER �' [ANA, P.E.
Florida Registration No. PE65707
s
a%
ti
a.
M•.•,t
1
.e
ti
3
'gym!
x'47
r
-;:
w
w
>_
cl)�
Q Q
J W
col LL
Y
aLn
CL' 04
N
wC00
F- LU?
Z N
I
o
WMIhCD
EL
w c0
LL M
2 L0
0
LLoiy
�,
°'°'
.�
oz>
L n Q
c
O
CC 2
CL
w
:)
v
=
W
J
U)
(L
m
J
ww
ZW
O
�U)
w
0_
U)
a.
� CO
O J
oQ
U
O
LU
1-
j
ZOZ
OZ
F_
Q
U
cc
WOU
Z
O
Z
ZO
U.
w
U)
LU
W
IL
o
w
N
Z
.-
a
et'•-
ar .
Ws
W
H
U)
LLl
1.4
W
�
��
w
lil:
0
w
O
cq
14
~ 0
z
O
W
Z
r,IiE
g
a O'
In
Z
rt 0_
coo
Z
C.
Q
J
O
E-+
Z
p
U.
•�`•tZl
U
of
T"
ur
U
pq
t.. Lal
w
w
QF-
W p.%
iU
_
-, LL
W.
d5
ww<
d
O V)
Q
(n
O�
Q
LU
HOU
F-
O
H
Z
z
z0OU
w
H 0
J
U�
w D_
z
o
�4
Z W O
aw
�F-
J
W
O
z
Q
¢ Uwi
D =)
O W
0
x
W
� 0
W
OL
z
F'--F
Q it
U) LL
W
Z
3
p
0
Z�0
zo
�z
0 co
0. U� Z` In
�oa
o Q
Op
DRAWN BY:
DATE:
KS
09/29/10
DESIGNED BY:
DATE:
KS
APPROVED BY:
DATE:
KS
09/29/10
PROJECT NUMBER:
409382/952933613
SHEET NUMBER:•
;
TYP2
SIZE: D 1 4•X36.)
s
a%
ti
a.
M•.•,t
1
.e
ti
3
'gym!
x'47
r
-;: