10-1021R-0114100 -8201 Fire Alarm Control Panel -Node 2 -South Miami Hospital -1 St Floor Fire Command Room Standby Total Alarm Total Module Qty Description Current Standby Current Alarm Panel Equipment 4120.8602 1 NETWORK VOICE COMMAND CENTER 0.000000 0.000000 0.000000 0.000000 4120.7501 1 MASTER CONTROLLER 0.177000 0.177000 0.177000 0.177000 4120.6051 1 NON -POWER LIMITED OPTION 0.000000 0.000000 0.000000 0.000000 4120 -6014 1 MODULAR 4120 NETWORK IFC CARD 0.035000 0.035000 0.035000 0.035000 41204321 9 16 CIRCUIT CLASS B STYLE Y 0.025000 0.225000 0.070000 0.630000 4120.3003 1 IS RELAYS, 3 AMP WIFEEDBACK 0.025000 0.025000 0.280000 0.280000 4120 -2003 1 6 UNIT WIGLASS DR & RETAINER 0.000000 0.000000 0.000000 0.000000 4120.0210 1 SINGLE CHANNEL AUDIO CONTROLLE 0.185000 0.185000 0.185000 0.185000 4120 -0203 1 25V 100W AMP W1120 VAC SUPPLY 0.068000 0.068000 8.750000 8.750000 4120 -0201 1 25V 25W AMP WITHOUT POWER SUPP 0.036000 0.036000 2.200000 2.200000 4120.0142 2 RS485 COMMUNICATION MEDIA MOD. 0.040000 0.080000 0.040000 0.080000 4120 -0110 2 MAPNET II ADORESSABLEITRUEALAR 0.270000 0.540000 0.290000 0.580000 4120 -0108 1 EXPANSION 120V 8A REG POWERS U 0.000002--- 0.000000 0.000000 0.000000 0 Total Panel Stb 1.371000 Total Panel Alarm 12.917000 Peripheral Devices 4099.9001 15 IDNET SINGLE ACTION PULL STATION 0.000000 0.000000 0.000000 0.000000 4098 -9733 0 TRUEALARM HEAT SENSOR 0.000000 0.000000 0.000000 0.000000 4098 -9714 101 TRUEALARM PHOTO SMOKE SENSOR 0.000000 0.000000 0.000000 0.000000 4098 -9792 101 TRUEALARM SENSOR BASE - 0.000000 0.000000 0.000000 0.000000 4098 -9756 13 TRUEALARM DUCT SMOKE SENSOR WI RELAY OUTPUT "2 0.002400 0.031200 0.015000 0.195000 2098 -9797 13 SAMPLING TUBE 49" 0.000000 0.000000 0.000000 0.000000 2098 -9806 13 REMOTE TEST STATION W1 LED AND KEY SWITCH 0.000000 0. 000000 0.000000 0.000000 4098.9843 13 ENCAPSULATED RELAY PAM -SD 0.002400 0.031200 0.015000 0.195000 4090 -9001 23 IDNET SUPERVISED IAM " 0.000000 0.000000 0.000000 0.000000 2190 -9161 4 MAPNET CLASS B SIGNAL ZAM 0.015000 0.060000 0.040000 0.160000 2190 -9163 0 MAPNET UNSUPERVISED CONTROL ZAM 0.010000 0,000000 0.040000 0.000000 4902 -9721 0 SPEAKER 25V/70VRMS WHITE CEILING 0.000000 0.000000 0.000000 0.000000 4903 -9150 54 15CD SPEAKERIVISIBLE RED HORIZONTAL MOUNT 25 OR 70VRM 0.000000 0.000000 0.090000 4.860000 ET- 1010 -R 1 WHEELOCK SPEAKER ONLY 0.000000 0.000000 0.000000 0.000000 4906.9151 8 SPEAKERISTROBE ONLY, MC, RED, 75CD, WALL. 0.000000 0.000000 0.186000 1.488000 49049176 28 15CO VISIBLE ONLY FIS RED VERTICAL MOUNT 0.000000 0.000000 0.090000 2.520000 4906.9105 1 JWP STROBE ONLY 75CD 0.000000 0.000000 0.205000 0.205000 4906 -9101 ET70WP- 2475W -FR 3 0 IWHEELOCK IsTRaBE ONLY, Me, RED, 75CD, WALL. WALL MOUNT SPEAKER STROBE 75CD WP 0.000000 0.000000 0.000000 0.000000 0.186000 0.102000 0.558000 0.000000 4905 -9938 13 TRUEALERT SYNC CONTROL MODULE 0.000000 0,000000 0.030000 0.390000 EXISTING 1 EXISTING LOADS 0.000000 0.000000 0.699000 0.699000 4903.9357 1 TRUEALERT 75CD SPEAKERMSIBLE 25V /70VRMS RED 0.000000 0.000000 0.177000 0.177000 4904.9332 6 TRUEALERT 75CD VISIBLE ONLY RED SYNC 1 0.000000 0.000000 0.177000 1.062000 20849001 1 15 IREMOTEPHONEJACK 1 0.000000 0.000000 0.000000 0.000000 0 Total Perlph Stby 0.122 Total Perlph Alarm 12.509 Total Standby Amps 1.493 Total Alarm Amps 25.426 * Current Draw Included With Device Addresses Used (See additional current draws) Quantity Of Back -up Amplifiers 0 1 2 -wlre detector alarm current Is Included In the alarm current of the Initiating Device CirculL 2- 50% of these devices In alarm, are used In the calculations below GENERATOR BACK -UP Standby Alarm Battery Set # 1 (CabinetfCharger #1) Qty Current Current Control Panel Power (Master Power Supply) 0.763 1.387 MapneUIDNet Card Current Draw 2 0.540 0.580 Current Draw For 90 Watt Or 100 Watt Amplifiers 1 0.068 8.750 Current Draw For Dual 25 Watt Amplifiers 0 0.000 0.000 Power For External Peripheral Devices 0.12240 12.43700 1.493 ; - -Sub Totals -4 23.154 Additional Current Draws MAPNETIIONet Device Addresses ordered 1 used 156 156.0 0.128 0.159 Spare addressable point capacity included for battery calc 20% 31 0.026 0.032 1.647 - -Grand Totals - 23.345 Additional Battery Capacity Required 20% 0.329 4.669 Standby Time = 4 Hrs 7.908 StandbyAh Alarm Time = 15 Mins. 7.003 Alarm Ah Minimum Battery Supplied 2081 -9296 50AH 34.467 Total Ah 1004MI Fire Alarm Control Parel - Node 2 - South Miami ital - 1st Floor Fire Command Room t I I I i i I , i , i i VAC SCHEDULE 1 VOLTAGE DROP CALCULATION SPEAKER CIRCUIT LOAD CALCULATION MAXIMUM -3dB DROP PER CIRCUIT 2:SIGA _ - 2:SIG-6 2:SIG•6 2:SiG-7 WIRE CIRCUIT _ 1ST FL RADIATION THERAPY AREA 2:SiG 27 APPLIANCES QUANTITIES I TAP VALUES 2:SIG 29 2:SiG30 2:SiG31 TOTAL ESTIMATED i MAXIMUM TOTAL 2:SIG -34 STROBE SYNC CIRCUIT SIG34 PANEL GAUGE VOLTAGE 40028721 vmbl50 ET -1010R 49064151 ET70WP- 2479N- 4903 -0357 2084-9001 CIRCUIT CIRCUIT ACTUAL ALLOWABLE CIRCUIT AmpllBer PiiONEISPEAKER CIRCUIT DESCRIPTION CIRCUIT (10, 16, 14 RS OR TAPPED AT TAPPED AT TAPPED AT TAPPED AT TAPPED AT TAPPED AT PHONE JACK LOAD LENGTH WIiE1LOSS CH T. LENGTH RESISTANCE Power 0 NUMBER 1 70VRM 425 Watt s 0.5 Watts 2 Watts M5 Watts 1 Watts 0.5 Watts 0 Watts ATTS EE B E OHMS supply 1FL PAVILION STAIR #1 2Sig3 10 awU 25 vrms 0 0 0 0 0 0 1 0.00 Watts 2DU ft 400 d6 0 ft Z6 Ohms I NIA 1FL PAVILION EMERGENCY ROOM 2S -4 18 awn 25 Vans 0 0 0 0 0 0 1 O.UO Wags 2D0It 0.00 dB O ft Z6 Ohms NIA SEE STROBE SCHEDULE 2Sig5 1 5.56% 25 arms 0 0 0 0 0 0 0 0.UU Wags 200 It. 400 dB Oft Z6 Ohms NIA SEE STROBE SCHEDULE 2S -6 RVISUAL 25 vans 0 0 0 0 0 D 0 MOD Wags 200 ft 400 dB 0 IL Z6 Ohm NIA SEE STROBE SCHEDULE ZS' •7 Alarm Time =r 15 Mins. 25 vans 0 0 0 0 0 0 0 0.00 wags 200 ft [LOU dB 0 ft 26 Ohms NIA SEE STRODE SCHEDULE 25 0 17.0% 29 vans 0 0 0 0 0 0 0 0.00 Waga 20011. 0.00 d8 0 ft Z6 Ohms NIA 1FL PAVILION WEST 2Sig -9 0.00 25 vrms 0 9 0 0 0 0 0 4.50 Wags 200 IL 418 dB 4,497 1L Z6 Ohms AMP01 AVILION STAIR #1 FLOORS 1 THRU 7 ZSI 10 25 vans 0 3 0 0 0 0 0 1.50 Wags 20011. -0.05 dI3 13,490 1L 26 Ohms AMr01 APEL AREA SPEAKERS ZSIg -11 lama 25 Vents 0 5 0 0 0 0 0 2.50 Wass 2001L -Q09 tl8 8,441 1t. Z6 Ohms A P01 1ST FLOORRADIATION THERAPY SPEAKER ZSig•12 18 awg 25 vrms 0 4 0 1 0 0 0 2.50 Wass 2DO IL 409 dB 8,094 U. Zo Ohms AMP01 1ST FLOOR PAVFLION SIG 13 2SI -13 13 awg 25 mis 0 4 1 0 0 0 0 4.00 Wags 200 ft -0.14 d8 5 059 g. Z6 Ohms AMP01 1ST FLOORPAVLUON SIG U 2SIg•14 18 awg 25 vents 0 1 0 0 0 0 0 0.50 Wass 2DO ft .402 dB 40,471 s. ZG Ohms AMP01 L PAVILION WEST STAIR #1 2SI 15 10 awg I NIA vrms 0 0 0 0 0 0 1 0.00 Wass 2DO ft (LOU d8 011. 28 Ohms NIA L PAVILION WEST STAIR #1 2Si 16 10 a NIA vans 0 0 0 0 0 0 1 0.00 Wass 200 ft 400 d8 0 IL Z6 Ohms NIA L PAVILION WEST STAIR #1 2Si 17 10 a NIA vrma 0 0 0 0 0 0 1 0.00 Wass 200 ft 400 dB 0 ft 26 Ohms NIA L PAVILION WEST STAIR #1 251g.18 18 awn NIA Vents 0 0 0 0 0 0 1 MOD Wass 200 ft 400 dB 0 ft Z6 Ohms NIA L PAVILION WEST STAIR #1 251 19 18 awU NIA vans 0 0 0 0 0 0 1 0.00 Wags 200 g. I (LOU d6 011. 7-6 Ohms NIA L PAVILION WEST STAIR #1 2SI 20 18 awg NIA vrms 0 0 0 0 0 0 1 0.00 Wass 2DO g. (LOU d8 Oil. Z6 Ohms NIA 1ST FLOOR SIG21 2SI 21 13 awU NIA vrms 0 0 0 0 a 0 1 0.00 Wass 200 ft 0.00 dB 0 ft Z6 Ohms NIA 1ST FLOOR STAIR #11 S1622 2Si 22 18 awn NIA vrms 0 0 0 6 0 0 1 CAM Wass 200 R 1100 dB 0 ft Z6 Ohms NIA 1ST FLOORSTAIR #9 SIG23 2Sig -23 18 awg NA vrms 0 0 0 0 0 0 1 0.00 Wass 2DU ft U. DO dB 0 ft Z6 Ohms NIA 1ST FLOOR SIG24 2SI 24 18 awg MIA vents 0 0 0 0 0 0 1 0.00 Wass 2901L 0. 00 dB 0 g. Z6 Ohms NIA 1ST FLOOR SIG25 2SI 25 10 awp NIA vrm 0 0 0 0 0 0 1 0.00 Wags 2DO ft 0. 00 dB 0 ft 26 Ohms NIA D FLOOR STAIR #11 SIG26 251 26 18 swu NIA vans 0 0 0 0 0 0 1 0.00 Wass 2M 1L 0.00 d6 0 tt. Z6 Ohms NIA 1ST FLOOR SIG39 2Si 39 18 awg 25 vrms 0 5 0 3 0 0 0 4.W Wass 2DU ft -0.14 dB 5,U59 ft ZB Ohms AMPO7 1ST FLOOR SIG40 2SI 40 18 a 25 Vrns 0 5 0 5 0 1 0 5.50 Wass 2DO ft -0.19 tlB ft Z6 Ohms AMP01 1ST FLOOR SIG41 ZSig -41 18 awg 25 vans 0 1 0 0 0 0 0 0.50 Wass 2DO IL .402 dB -3,67D 40,471 IL ZB Ohms AMP01 1ST FLOOR SIG42 2S10-42 10 own 25 vents 0 5 0 0 0 0 0 2.50 Wass 200 ft -0.09 dB 8,n94 ft Z6 Ohms AMPO7 D FLOOR S1643 2Si 43 10 awn 25 vrms 0 0 0 0 0 0 0 4.001 Wats 2001L •414 dD 5 O59 ft Z6 Ohms A#P01 D FLOOR SIG44 2SI 44 g3 awg 25 Vrma 0 0 1 0 0 0 0 0 4.00 Wags 2DO ft -0.14 d6 500 R. ZB Ohms AMP01 STAIR #111 SIG 45 ZSig•45 g3 awg 25 vrms 0 1 0 0 0 0 0 0.50 Wats 2DO ft •Q02 dB 40,471 IL Z6 Ohms AMP01 1ST FLOOR SIG46 2SI 46 10 awn 25 vrms 0 2 0 0 0 0 0 1.00 Wass 200 ft -0.04 d8 20 23511. Z6 Ohms AMPO1 ARE 2SIg•47 18 awg 25 vents 0 0 0 0 0 0 0 0.00 Wass O ft 400 dB D 1L QO Ohms AMP01 ARE 2SI 48 In awg 25 vrms 0 O O 0 0 0 0 0.00 Wags 0 ft 0.00 dB 0 g. 0.0 Ohms AMP01 SEE STROBE SCHEDULE 2Si 49 1 13 awn NM vrms 0 0 0 0 0 0 0 O.W Wass O ft (LOU dB 0 ft QO Ohms NIA SEE STROBE SCHEDULE 2Si 50 10 awU MIA vrms 0 0 0 0 0 0 0 0.00 Wags O IL (LOU d8 U IL QO Ohms MIA D FLOOR 2Sig 51 18 awg MIA vrtns 0 0 g 0 0 0 1 0.00 Wags 200 g. (LOU dB 0 g- ZB Ohms NIA ARE 2SI 52 21 awU NIA vans 0 0 0 0 0 0 0 0.00 Wats oil. (LOU dB 0 g. 0.0 Ohms NIA ARE 2SI 53 18 awq NIA vans 0 0 0 0 0 0 0 0.00 Wags O ft 0.0D dB 0 s. QO Ohms NIA ARE 2SI 54 10 awg NIA vrms 0 0 0 i 0 9 0 0 0.00 Wags O ft 0.00 d8 0 1L 0.O Ohms NIA ARE 2Si 55 18 a vrms ms 0 0 0 6 9 0 0 MUD Wass O ft (100 dB a ft 0.0 Ohms I NIA ARE 2Sig -56 10 awg NIA vans 0 0 0 1 0 D 1 0 1 0 0.00 Wags 01L 400 d8 0 1L QO Ohms I NIA I rtes Summa Total Pita Load (Watts) d (Wass) Per Amp 81 1 0 1 15 37.50 10400 O - - - i Max LLaa ars I d (Watts) Per CM 4500 NOTE:. �_ L- P SUM METHOD WAS USED TO CALCULATE MAXIMUM ALLOWABLE CIRCUIT LENGTH. THIS METHOD ALLOWS FORA SMALL GIN OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS tSHOWN ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT I GTH CONTACT YOU LOCAL SIMPLEX BRANCH. I I I i I i f l 1 1100 -8201 Fire Alarm Control Panel -Node 2 - South M VAC SCHEDULE 1 VOLTAGE DROP CALCULATION 17 %MAXIMUM VOLTAGE DROP ' IRCUIT OUTPUT VOLTAGE= 20.4 (FOR CALCULATIOI CIRCUIT 2:SIG3 DESCRIPTION SEE PHONE SCHEDULE 2:SIGA SEE PHONE SCHEDULE 2:SIG-6 2:SIG•6 2:SiG-7 1FL PAVILION WEST PAVILION STAIR #1 FLOORS 1 THRU 7 CHAPEL AREA STROBES 2:SiG3 1ST FL RADIATION THERAPY AREA 2:SiG 27 1ST FLOOR SIG27 2:SIG -28 1ST FLOOR SIG28 2:SIG 29 2:SiG30 2:SiG31 1ST FLOOR SIG29 1ST FLOOR SIG30 1ST FLOOR SIG31 2:SiG32 1ST FLOOR SIG32 2:SiG33 15T FLOOR SIG33 2:SIG -34 STROBE SYNC CIRCUIT SIG34 2:SIG36 2ND FLOOR SIG35 2:SIG36 2:SiG37 2ND FLOOR SIG36 STAIR *ll SIG37 2:5iG38 2:SIGA5 STROBE SYNC CIRCUIT SIG38 SEE SPEAKER SCHEDULE 2:SIG47 SEE SPEAKER SCHEDULE 2:SiG -48 SEE SPEAKER SCHEDULE 2:SiG -49 1ST FL PAVILLION EMERGENCY RM AREA 2:SIG -60 SPARE MIAMI -DADE FIRE RESCUE APP OV D FOR SCOPE OF WO ONLY COMPLETE AS -BUILT RRE ALARM SYSTEM INSTALLATION DRAWINGS, INCLUDING A COMPLETE SYSTEM RISER, OPERATION AND MAINTENANCE MANUALS, AND A WRITTE;4 SEQUENCE OF OPERATION AS REQUIRED BY NFPA 72 (2002 E[VTfON) 10,6.1.1 & 10.6.13 AND FLORIDA ADMINISTRATIVE CODE 69A- 48.007 SHALL 13E PROVIDED UPON REQUEST, ANY DOCUMENT DEFICIENCY, OR DEFICIENCY fNVOLVrNG rHE FUNCTIONALITY OF THE SYSTEM THAT IS OUTSIDE OF THE SCOPE )F 1'VORK IN TENANT SPACE & THROUGIIOUT REMAINDER OF BUILDING ;HALL BE COMMUNICATED IN WRITING TO THE BUILDING OWNER'S MPRESENTATIVE, AND REFERRED TO THE M.D.F.R. CODE COMPLIANCE 1UREAU FOR ENFORCEMENT. SUCH DEFICIENCY SHALL NOT AFFECT THE )UTCOME OF THE SCOPE OF WORK FOR THE TENANT SPACE FIRE ALARM ERMIZ AS LONG AS, THE DEFICIENCY DOES NOTAFFECT THE UNCTIONALITY OF THE FIRE ALARM WITHIN THE TENANT SPACE. I -lit Floor Fire Command Room 225 ft. VOLTAGE DROP TOTALS CIRCUIT TYPE PHONE ESTIMATED CIRCUIT LENGTH 0 ft. 490343150 15cd Spkr /Strb 0.090 0 ET4010 -11 WP SPEAKER 0.000 0 490649161 110cd SpkrlStrb 0.186 0 49048176 16cd Strobe 0.090 0 490649106 WP 75cd Strobe 0.205 0 4906.8101 75cd Strobe 0.186 0 E770WP- 2476W -FR 75cd WP SpkHStrb 0.102 0 490649938 Sync Module 0.030000 0 EXISTING LOADS 1.000 0.000 TOTAL CKT. LOAD (AMPS) 0.000 WIRE GAUGE (18, 16, 14, 12) 12 ACTUAL VOLTAGE DROP % 0.00% ACTUAL VOLTAGE DROP (VOLTS) 0.000 PHONE 0 ft. 0 0 0 0 0 0 0 0 0.000 0.000 12 0.00% 0.000 RVISUAL 225 ft. 8 0 0 11 0 0 0 1 0.000 1.740 12 7.41% 1.611 RVISUAL 225 ft. 3 0 0 0 0 0 0 1 0.000 0.300 12 1.28% 0.261 RVISUAL 225 ft. 5 0 0 1 0 0 0 1 0.000 0.570 12 2.43% 0.495 RVISUAL 225 ft. 4 0 1 0 0 0 0 1 0.000 0.576 12 2.45% 0.500 RVISUAL 225 ft. 5 0 0 1 1 0 0 1 0.000 1 1.306 1 12 1 5.56% 1 1.134 RVISUAL 226 ft. 1 Ej 0 0 4 0 0 0 1 1 0.000 1 0.480 1 12 1 2.04% 1 0.417 RVISUAL 226 ft. 2 0 3 2 0 1 0 0 1 0.000 1 1AD4 1 12 1 4.70% 1 0.969 RVISUAL 225 ft. 0 0 6 0 0 RVISUAL 225 ft. 1 0 0 3 0 RVISUAL 225 ft. 6 0 0 0 0 RVISUAL 225 ft. 0 0 0 4 0 RVISUAL 225 ft. 0 0 0 0 0 RVISUAL 225 ft. 8 0 0 0 0 RVISUAL 225 ft. e 0 0 0 0 RVISUAL RVISUAL SPEAKER 225 ft. 20 ft. 0 ft. 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SPEAKER 0 ft. 0 0 0 0 0 SPEAKER 0 ft. 0 1 0 0 0 0 SPEAKER 0 ft. 0 0 0 0 0 RVISUAL 225 ft. 2 0 0 2 0 RVISUAL 225 ft. 0 0 0 0 0 % Appliance Summ 64 0 9 1 28 1 1 METHOD USED TO CALCULATE PERCENT OF VOLTAGE DROP: [(CIRCUIT LENGTH IN FEET X 2) (AMPS X OHMSIFOOT)l X 100 20.4 VOLTS Wire Resistance At 76 Degrees Celsius Ohm/1000 ft 12GA = 1.93 14GA = 3.07 16GA = 4.89 18GA = 7.77 NlRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE (UNCOATED SOLID COPPER WIRE) VOTE: -UMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD ALLOWS FOR A SMALL MARGIN 7F SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN 7N THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT - ENGTH, CONTACT YOUR LOCAL SIMPLEX BRANCH. '4009 Notification Appliance 0 Extender Panel Battery Calculation - NAC #1 0.699 1.806 12 0 0 1 0.000 Standby Total Alarm Total Module Qty Description Current Standby Current Alarm Panel Equipment 1 0.000 0.930 12 0 0 4009 -9201 1 1 12 14009 IDNET NAC EXTEN DER, 120 VAC 0.085000 0.085000 0.185000 0.185000 12 0 0 Total Total Panel Stby 0.085000 Total Panel Alarm 0.185000 Peripheral Devices 0 0 0 1 0 0 0.000 0.000 0.000 0.120 0.000 0.000 12 12 12 0 0 11 0.000 TRUEALERT MULTI - CANDELA STROBE RED, WALL @ 75 CANDELA 0.000000 0.000000 0.186000 2.046000 4906 - 9151 *75 12 6 0 TRUEALERT MULTI - CANDELA SPEAKER /STROBE RED, WALL @ 75 CANDELA 0.000000 0.000000 0.186000 1.116000 4906 - 9128 *75 1 1 0.576 TRUEALERT MULTI- CANDELA HORN /STROBE RED, CEILING @ 75 CANDELA 0.000000 0.000000 0.250000 0.250000 0.000 12 FT Total Periph Stby 0.000 Total Periph Alarm 3.412 AMPS AMPS Total Standby Amps 0.085 Total Alarm Amps 3.597 OHMS VOLTS % Standby 2a Alarm N1 -1 ED DEPARTMENT STROBES V/0 Battery Calculations Current 250 Current 6 1 0 Control Panel Card Power 0.085 1.0 0.185 6.2% 19.1 2.7 Power For External Peripheral Devices 0.00000 16.9 3.41200 2.000 N1 -2 ED DEPARTMENT STROBES 0.085 <- Totals -? 3.597 250 761 O w Additional Battery Capacity Required 20°% 0.017 1.180 0.719 1.14 5.6% 19.3 Standby Time = 4 Hrs 0.408 Standby Ah 16.9 " 2.000 LL. Alarm Time =r 15 Mins. 1.079 Alarm Ah 14 0.00307 250 607 =23) 1.487 Total Ah 0.930 1.5 1.43 7.0% Battery Required 2081 -9272 6.2 4.099 Ah 17.0% 16.9 \ \SUMWAt \DRAFTING \00 - 2003 \SOUTH MWA HOSPITAL (MASTER SrrEASMH CUNICAL EXPANSION- REV02- 952933813\ SMBAMNM7 ?A7r.M4S6mWAVYM,gWgMe13.DWGDAIE PrVr=: February 21, 2011 DATE SAVED: February 21, 2011 0 0 0 0.699 1.806 12 0 0 1 0.000 0.567 12 0 0 1 0.000 0.570 12 1 0 1 0.000 0.930 12 0 0 0 0.000 0.000 12 0 0 1 0.000 0.750 12 0 0 1 0.000 0.760 12 0 0 0 0 0 0 1 0 0 0.000 0.000 0.000 0.120 0.000 0.000 12 12 12 0 0 0 0.000 0.000 12 0 0 0 0.000 0.000 12 0 0 0 0.000 0.000 12 1 1 0 1 0.000 0.576 12 0 1 0 0 1 0.000 0.000 12 FT Total Load (AMPS) 12.146 3 1 0 1 13 1 1 FIRE ALARM SYSTEM TO BE )NSTALLED IN ACCORDANCE WrM NFPA 72; 7(1; 101 - AS ff)1RO % [0= [0 NO' MIAMI -DADE COUNTY FI DEPAkTME'V f N- BLDG. PERMIT �.,_..�.. FIRESUPPRESSION� M EXT.- -•-r• OATE:eP2 iz4- It BY; I& 0.808 0.00% 3.19% 3.19% 0.51% 0.00% 0.104 0.000 0.00% 0.000 0.00% 0.000 0.00% 0.000 0.00% 0.000 2.45% 0.500 0.00% 0.000 Max Load (AMPS) 24.000 TOTAL CIRCUIT RESISTANCE 0.0 Ohms MAXIMUM ALLOWABLE CKT. LENGTH 0 M 0.0 Ohms 0 K- 0.9 Ohms 621 ft 0.9 Ohms 3,022 ft 0.9 Ohms 0.9 Ohms 1,591 ft 1,674 fL 0.9 Ohms 694 ft 0.9 Ohms 1,889 fL 0.9 Ohms 821 IL 0.9 Ohms 602 fL 0.9 Ohms 1,699 ft 0.9 Ohms 1,691 ft 0.9 Ohms 975 fL 0.0 Ohms 0 M 0.9 Ohms 1,209 ft 0.9 Ohms 1,209 ft 0.9 Ohms 0.0 Ohms 7,556 M 0 M 0.0 Ohms 0 fL 0.0 Ohms 0 M 0.0 Ohms 0 M 0.0 Ohms 0 ft 0.9 Ohms 0.0 Ohms 1,574 M 0 ft Max Load (AMPS) Per Circuit 2.000 Note: Each Power Supply Is 8 Amps divided Into two 4 Amp taps. PSMA System Power Amps PSM-B 2.040 Amps PS01A 2.932 Amps PS01 -8 4.047 Amps P802A 2.660 Amps PS02 -B 0.000 Amps BATTERY CALL 1P POWER SUPPLY PSM43 PSM43 FSM-B P502 -A P502 -A P SM-B P 4uuu Notincatlon Appliance txtenaer Panel Battery Calculation - NAC ##1 p(D'S S / CURRENT DRAW I VOLTAGE DROP TOTALS NAC SCHEDULE /VOLTAGE DROP ION W AS DESIGNED MAMUM STROBE SPKR/STRB HORN /STRB AS DESIGNED ATMAXALLOW. CIRC. LENGTH Q 17% MAXIMUM VOLTAGE DROP CIRCUIT WIRE WIRE ESTIMATED ALLOWABLE TOTAL MAX It 4906 - 9101 *75 4906 - 9151175 4906 - 9128`75 TOTAL ACTUAL LAST TOTAL MAXIMUM LAST CIRCUIT OUTPUT VOLTAGE FOR CALCULATIONS )= 20.4 TYPE GAUGE RESIST CIRCUIT CIRCUIT CIRCUIT gRCUIT CIRCUIT VOLTAGE DEVICE CIRCUIT VOLTAGE DEVICE 75CD 75CD 75CD CIRCUIT DESCRIPTION CDC) O 1100 LENGTH LENGTH LOAD CAP. RES. DROP VOLT RES. DROP VOLT ,v LZ 0.1860 0.1860 0.2500 g0 If M- �I ' AWG OHM /FT FT FT _z zvi O AMPS AMPS OHMS VOLT % VOLTS OHMS VOLTS % VOLTS 2a N1 -1 ED DEPARTMENT STROBES V/0 12 0,00193 250 690 6 1 0 1.302 2.000 1.0 1.26 6.2% 19.1 2.7 3.5 17.0°A 16.9 2.000 N1 -2 ED DEPARTMENT STROBES V/O 12 0,00193 250 761 O w 1 1.180 1.0 1.14 5.6% 19.3 2.9 3.5 17.0% 16.9 " 2.000 LL. N1 -3 CLINICAL EXPANSION CORR V/0 14 0.00307 250 607 =23) 0 0.930 1.5 1.43 7.0% 19.0 ' 3.7 3.5 17.0% 16.9 2.000 N1-4 SPARE V/0 12 0.00193 250 N/A 0 0.000 1.0 0.00 0.0% 20.4 N/A N/A NIA N/A I j I 3.412 METHOD USED TO CALCULATE VOLTAGE DROP: y 11 6 1 Total NAC Load: 3.41 A 43% N [(CIRCUIT LENGTH IN FEET X 2) (AMPS) (OHMS ! FT)] Largest Single Circuit Load: 1.30 A 65 °r6 I 1 f ! Lowest Voltage at any Device: 16.9 V 106% >- Ld Wire Resistance At WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL__ CODE (UNCOATED SOLID COPPER WIRE) 75;Degrees Celsius NOTE: I i i I I I Total NAC Capacity: BA zd Ohms/ftl LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD ALLOWS FOR A SMALL MARGIN Single Circuit Capacity: 2.0 A 101GA = ;0.001210 OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN Minimum Device Voltage: 116V g 12;GA = '0.001930 ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXMUM ALLOWABLE CIRCUIT 14 GA = 10.003070 LENGTH, CONTACT YOUR LOCAL SMPLEXGRINNELL DISTRICT OFFICE. i j Note: < z 16' GA = i0.004890 I "Regulated 24 VDC" refers to the voltage range of 16 to 33 VDC 18 GA = 10 007770 ! I I ( � per UL standard 1971. This voltage is the absolute operating range. U LL Please note that 16VDC is the lowest operating voltage that is allowed at the last appliance on the NAC under worst case conditions. W O The maximum RMS current listed is the nameplate rating. Strobe designs are constant wattage and the maximum RMS current N I I rating occurs at the lowest allowable operatingwftage. BATTERY CALL 1P POWER SUPPLY PSM43 PSM43 FSM-B P502 -A P502 -A P SM-B P W N 1� Z Q 0 W It COI Lt- a I,- In F- t N 0MC)tn IY C0 ti (D Q m O. 000 yw CD 'V)V) CD U p CDC) O 1100 O w a. o 'zz _ 0- Tn V V = zZ J V) ,v LZ m g0 w0 _z zvi O Cc w �U) U) 2a V) =1 �a U 0 w z �i U O w LU 0 0 ? L� v z0 " zW LL. 0 I a U) T) < W a C O z .- N Iv-I N >- Ld zd W g � W < z U LL W O GV Q N C� " 0 z Cr m ? 0 CO) a o c� m IX < a. Ixw <� LL 3 0 0W a5 Lu 0 CIit a 0 Z O Z0 0 Be Q a 0 0 ^ Z m� W U � W 0 Z 0' z 0 C\2 �co 0 21 W IL z 12 0 a. - It Z) T��:: Vin (3 0 z0 W Q 610 O z > Za W Z CX co a N 03 �aa 300 DRAWN BY: DATE: KS 0929110 DESIGNED BY: DATE: KSi" 0929110 APPROVED BY: DATE: -KS 0929110 PROJECT NUMBER: 4093821952933613 SHEET NUMBER: BATT 1 - e�. o {trxtcl