10-1021R-002it \ \SGMWMtt \DRA L SYMBOL LEGEND DEVICES Nom Pipe Tube or Conduit Diam In. (mm) SYMBOL SIMPLEX MODEL # DESCRIPTION TSW TSW TRUE SITE WORKSTATION 1/2 -12 (13 -305) NODE2 4120 -8602 NETWORK FIRE ALARM PANEL 2-1/2(64) NAC 4009 -9201 NAC EXTENDER, 120VAC. iDNET. I 2 SD -1000L- 4098 -9792 4098 -9714 SSD SENSOR BASE SSD PHOTO SENSOR 8 2 4099 -9001 2099 -9814 MANUAL STATION SURFACE TRIM MANUAL STATION 1 Z5 2190 -9163 CONTROL ZAM 1 ® 2088 -9032 MR -801/T RELAY 1 1/2 -20 (13 -508) ® 75CD 4906 -9101 MULTI - CANDELA STOBE 75CD 3 EN 75CD 4906 -9151 MULTi- CANDELA SPEAKER STROBE 2 DH 2088-9608 DOOR HOLDERS 2 5-1/2(140) 1/2-6 (13 -152) END OF LINE RESISTOR 1 (25) (b) 4 2 m CONNECTION TO AN APPROVED, DEDICATED EARTHGROUND, NFPA 70. COMPLY WITH NEC. NOTES: 1. FIRE ALARM SYSTEM SHALL BE POWER LIMITED. 2. WIRING SHALL BE #14 THHN OR 18/2 TWISTED SHIELDED PAIR FPL TYPE CABLE. 3. INSTALLATION SHALL COMPLY WITH NFPA 1, 2006, APPLICABLE CHAPTERS. 4. INSTALLATION SHALL COMPLY WiTH NFPA 72, 2002, APPLICABLE CHAPTERS. 5. INSTALLATION SHALL COMPLY WITH NFPA 101, 2006, APPLICABLE CHAPTERS. 6. INSTALLATION SHALL COMPLY WITH NEC 2005. 7. CONDUIT, AS APPLICABLE SHALL BE 1/2" MINIMUM WITH A MAXIMUM FILL OF 40 %. COMPLY WITH NEC. 8. SYSTEM SHALL BE GROUNDED PER MANUFACTURERS SPECIFICATIONS. 9. ALL DEVICES SHALL BE COMPATIBLE & SHALL BE UL LISTED FOR FIRE SERVICE USE. 10. ALL SPACES SHALL MEET THE AUDIBLE CHARACTRISTICS OF NFPA 72 AND NFPA 101. 11. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN X OF A/C DIFFUSERS, KITCHEN OR BATHROOM DOORS. 12. CEILING MOUNTED DEVICES SHALL BE LOCATED AT A HEIGHT OF 10'+/- ON SMOOTH FLAT CEILINGS UNLESS OTHERWISE NOTED. 13. SIGNALLING LiNE CIRCUITS SHALL HAVE A MAXIMUM OF 127 POINTS PER CHANNEL. SEE FLOOR PLANS FOR QUANTITIES & TYPES OF DEVICES. 14. FIRE ALARM PANEL & ANY ASSOCIATED FIRE ALARM TRANSPONDERS SHALL BE FED BY A 120VAC, SINGLE PHASE, 20 AMP, DEDICATED BREAKER. 15. ALL INTERCONNECTED FIRE ALARM PANELS SHALL BE ARRANGED TO FUNCTION AS A SINGLE SYSTEM AND SHALL BE MONITORED FOR INTEGRITY PER NFPA 72. 16, RACKS, SHELVES AND EQUIPMENT ARE ALL LOWER THAN 80" ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED. 17. THE DESIGN INSTALLATION COMPLIES WITH F.B.C. 11- 4.287.3 18. THE SYSTEM IS AN EXISTING REMOTE SUPERVISING STATION FIRE ALARM SIGNALING SYSTEM. 19. BUILDING HAS BACK UP GENERATOR 20. ROOM CONTAINING FACP AND /OR BOOSTER POWER SUPPLY PANEL(S) IS MECHANICALLY VENTILATED. SCOPE OF WORK: 1. PROVIDE & INSTALL NEW DEVICES AS SHOWN ON DRAWINGS. TIE INTO EXISTING SYSTEM. 2. SIGNALING LINE CIRCUIT WIRING SHALL BE STYLE 4. 3. NOTIFICATION APPLIANCE CIRCUIT WIRING SHALL BE STYLE Y. 4. THiS SYSTEM SHALL BE AN EXISTING REMOTE SUPERVISING STATION FIRE ALARM SIGNALING SYSTEM PER NFPA - 72.8.2 FIRE ALARM SYSTEM SEQUENCE OF OPERATION_ (EXISTINGI UPON ACTIVATION OF A MANUAL PULL STATION, ANY AUTOMATIC INITIATION DEVICE (i.e. Smoke or Heat detector). OR A FIRE SPRINKLER FLOW SWITCH THE FOLLOWING SEQUENCE OF EVENTS SHALL OCCUR: ALL AUDIO /VISUAL APPLIANCES, SPEAKERS AND STROBES WITHIN THE FLOOR WHERE THE ALARM INITIATED SHALL BE ACTIVATED. IN ADDITION, ALL AUDIO/ViSUAL APPLIANCES, SPEAKERS AND STROBES LOCATED ON THE FLOOR IMMEDIATELY ABOVE AND ON THE FLOOR IMMEDIATELY BELOW, SHALL ALSO BE ACTIVATED. ALL STROBES ACTIVATED UPON ALARM, WITHIN EACH SMOKE COMPARTMENT, SHALL BE SYNCHRONIZED. ALL MAGNETIC DOOR HOLDERS ASSOCIATED WITH THE DOORS LEADING INTO AND OUT OF THE SMOKE COMPARTMENT iN ALARM SHALL BE ACTIVATED TO RELEASE DOORS TO ISOLATE THE SMOKE COMPARTMENT WHERE THE ALARM INITIATED FROM. ALL AIR HANDLING UNITS AND FANS SERVING THE SMOKE COMPARTMENT, FROM WHICH THE ALARM ORIGINATED FROM, SHALL BE SHUT DOWN PER NFPA 90 -A. ALL SMOKE DAMPERS ASSOCIATED WITH THE AIR CONDITIONING DUCTS PENETRATING THE RATED PARTITIONS ASSOCIATED WITH THE SMOKE COMPARTMENT WHERE THE ALARM IS ORIGINATED FROM, SHALL BE CLOSED. UPON ACTIVATION OF THE ELEVATOR LOBBY SMOKE DETECTORS (WITH THE EXCEPTION OF THE ELEVATOR LOBBY DETECTOR AT THE PRIMARY LEVEL OF EGRESS), THE FOLLOWING SHALL OCCUR IN ADDITION TO ABOVE: 1. ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL OF EGRESS. 2. WARNING SiGN SHALL ILLUMINATE. UPON ACTIVATION OF THE ELEVATOR LOBBY SMOKE DETECTOR AT THE PRIMARY LEVEL OF EGRESS, THE FOLLOWING SHALL OCCUR, IN ADDITION TO ABOVE: 1. ELEVATORS SHALL RECALL TO THE ALTERNATE LEVEL OF EGRESS. 2. WARNING SIGN SHALL ILLUMINATE. UPON ACTIVATION OF THE ELEVATOR MACHINE ROOM SMOKE DETECTOR, THE FOLLOWING SHALL OCCUR, IN ADDITION TO ABOVE: 1. ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL OF EGRESS. 2. WARNING SIGN SHALL BLINK. UPON ACTIVATION OF THE ELEVATOR TOP OF SHAFT SMOKE DETECTOR, THE FOLLOWING SHALL OCCUR: 1. ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL OF EGRESS. 2. WARNING SIGN SHALL BLINK. UPON ACTIVATION OF A TAMPER SWITCH, THE FOLLOWING SHALL OCCUR. 1. A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT. UPON ACTIVATION OF A DUCT SMOKE DETECTOR, THE FOLLOWING SHALL OCCUR. 1. A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT. 3. THE AIR HANDLER UNIT ASSOCIATED WITH THAT DUCT DETECTOR SHALL SHUT DOWN. UPON ACTIVATION OF A ELEVATOR HEAT DETECTOR LOCATED IN THE SHAFT OR MACHINE ROOM THE FOLLOWING SHALL OCCUR. 1. A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT. 3. THE SIGNAL WILL BE SENT TO THE SHUNT SWITCH FOR POWER SHUTDOWN. .Y r i -SCOPE OF WORK TiMC \Or °RAL (A44STER SfiE) \sw CLINICAL EXPANSION- REV03- 952933613 \SMBAaMNMEATRBMRI MhRE6pIV962933613.DWGDATS PIDWED: March 16, 2011 DATE SAVED: March 16, 2011 ��p,SSPF /�� OUL US FILL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS LABORATORIES, ING.(9 FOR USE IN THROUGH•PENETRAnON FiRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FIRE RESISTANCE DIRECTORY 501-61 90G9 6" BELOW CEILING CEILING MOUNTED SMOKE /HEAT DETECTOR 24" MIN HANDICAP BEDROOM STROBE f SYNCHRONIZE MORE THAN TWO APPLIANCES IN ANY FIELD OF VIEW, MUST BE SYNCHRONIZED NFPA 72 2002 EDITION (SECTION 7.5.4.1.2) 80 "A. F. F OR 6 BELOW BELOW CEILING, WHICHEVER IS LESS FLA BLD CODE 11- 4.28.3(6) 91114611-11121, System No. C -A3 -1044 June 15, 2005 F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr L Rating At Ambient - 2 CFM /sq ft L Rating At 400 F - less than 1 CFM /sq I't W Rating - Class I (See Item 4) SECTION A -A 1. Floor or Wan Assembly - Lightweight or normal weight (100-150 pd or 1600 -2400 kg1m3) concrete. Except as noted in table under Item 4, min thickness of solid concrete floor or wall assembly is 4-12 in. (114 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UL Classed hollow core Precast Concrete Units' . When floor is constructed of hollow core precast concrete units, packing material (Item 3) and caulk fill material (Item 4) to be installed symmetrically on both sides of floor, flush with floor surface. Waft assembly may also be constructed of any UL Classified Concrete Blocks` . Max diam of opening is in solid lightweight or normal weight concrete. Floor is 32 in. (813 mm). Max dam of opening in floor constructed of hollow -core {recast concrete units is 7 In. (178 mm). See Concrete 6lodks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 1A. Steel Sleeve (Optional, not shown) - Max 15 in. (381 mm) ID (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wail assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wall. Max 16 In. (406 mm) ID (or smaller) min 0.028 (0.71 mm) wall thickness (or heavier) galvanized steel sleeve cast or grouted into floor or wail assembly. Sleeve may extend a max of 12 in. (13 mm) beyond either surface of floor or wall. 2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the frestop system. Max annular space between pipe, conduit or tubing and edge of through opening or sleeve is dependent on the parameters shown in hem 4. Nlin annular space between pipe or conduit and edge of through opening is 0 in. (0 mm) (point contact). Pipe conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A' Steel Pipe - Nom 301n, (762 mm) dam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 30 in. (762 mm) dam (or smaller) cast or ductile ion pipe. C. Conduit - Nom 6 In. (152 mm) diam (or smaller) rigid steel conduit D. Conduit - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. E. Copper - Tubing Nan Sin. (152 mm) dam (or smaller) Type L (or heavier) copper tube. F. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. 3. Packing Material - Polyethylene backer rod or nom 1 in. (25 mm) thickness of tightly- packed mineral wool ball or glass fiber insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of waft as required to accommodate the required thickness of caulk fig material (Item 4). 4. FiII,Vold or Cavity Materiar - Caulk or Sealant - Applied to fill the annular space flush with top surface of floor. In wag assemblies, required caulk thidmess to be installed symmetrically on both sides of wall, flush with wag surface. At point contact location between penetrant and sleeve or between penetrant and concrete, a min 1/4 in. (6 mm) dam bead of caulk shag be applied at top surface of floor and at both surfaces of wall. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown in the following table: Min Floor or wall Thkns In. (mm) Nom Pipe Tube or Conduit Diam In. (mm) Max Annular Space in. (mm) Min Caulk Thkns in. (mm) F Rating Hr 2-1/2(64) 1/2 -12 (13 -305) 1-3/8(35) 1/2(13) 2 2-1/2(64) 1/2 -12 (13 -305) 3-1/4(83) 1(25) 2 4- 1/2(114) 1/2 -6 (13 -152) 1-3/8(35) 1/4 (6) (a) 2 4-1/2(114) 1/2- 12(13 -305) 1-1/4(32) 1/2(13) 3 4-1/2(114) 1 1/2 -20 (13 -508) 2 (51) 1(25) 3 4-1/2(114) 1/2 -20 (13 -508) 2(51) 1 (25) 3 4-1/2(114) 1/2- 12(13 -305) 3 -1/4 (B3) 1 (25) 3 4- 1/2(114) 22 -30 (558 -762) 2 (51) 2(51) 3 5-1/2(140) 1/2-6 (13 -152) 1-3/8(35) 1 (25) (b) 4 (a)Min 2 In, (51 mm) thickness of mineral wool ball insulation required in annular space. (b)Min 1 kn. (25 mm) thickness of mineral wool batt insulation required in annular mace on both sides of floor or wall assembly. Min 1 in. (25 mm) thickness of caulk to be installed flush with each surface of floor or wall assembly. 3M COMPANY - CP 25WB+ caulk or FB3000 Wr sealanL (Note: W Rating applies only when FB -3000 Wr sealant is used.) *Bearing the UL Classification Marking * NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. DEVICE MOUNTING HEIGHTS A/C SUPPLY DIFFUSER 3` (MIN) vx AUDIO /VISUAL & VISUAL -ONLY DEVICES ACCEPTED HER IMPORTANT NOTE VERIFY EXACT MOUNTING REQUIREMENTS WITH MANUFACTURERS DATA SHEETS MANUAL PULL STATION FIRE PHONE_ (� JACK 48" MAX (ADA 42" MIN /54" MAX (NFPA NFPA 72 2002 EDITION (SECTION 5.12.4) MAGNETIC DOOR HOLDER U LESS 3" __T IR� r r � ROUG FIRESTOP SEECUR RESISTAM r NEVER HERE WALL MOUNTED SMOKE /HEAT DETECTOR I FINISHED WALL NOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST OF THE DETECTOR. SIDE WALL 12' (MAX) System No.W -L -3001 September 07, 2004 (Formerly System No. 149) F Ratings - 1 and 2 Hr (See Item l) T Ratings - 3/4, 1, 1 -1/2 and 2 Hr (See Item 2) L Rating At Ambient 15 CFM /sq ft (See Item 3) L Rating At 400 F - less than 1 CFM /sq ft (See Item 3) SECTION A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed L. TRIANA &ASSOCIATES INC. CONSULTING ENGINEERS a s , CERTIFICATE �gF AyJ;HOR1ZATION: 26 5151 S.W.,,,98lh AYE' ' ®• MIAMI, LE94 -: -T� NA, .E`. Florida Regtsirvgtlwbl PE65707 i of the materials and in the manner described in the individual 0300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wail framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 In. lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross u, braces. Steel studs to be min 3 -5/8 in. wide by 1 -3/8 in, deep channels spaced max 24 in OC. B. Gypsum Board* - Nom 1/2 or 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers and sheet orientation shall be as specified in the individual Wall or Partition Design. Diam of circular through opening to be 3/8 in. to 5/8 in. larger than outside diam of cable or cable bundle. C. Fasteners - When wood stud framing is employed gypsum wallboard layers attached to studs W with cement coated nails as specified in the individual Wall or Partition Design. When steel channel stud framing is employed, gypsum wallboard attached to studs with Type S self - drilling, self- tapping bugle -head steel screws as specified in the individual Wall or Partition Design. of The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Cables - Individual cable or max 1 in. diam cable bundle installed In through opening with an annular space of min 0 in. (point contact) to max 3/4 in. Cable to be rigidly supported on both sides of wall assembly. The following types and sizes of cables may be used: A. Max 150 pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride (PVC insulation (V and jacket materials. When max 25 pair telephone cable is used, 4u) • Rating is 2 hr.When 50 to 150 pair telephone cable is used in 1 hr fire rated wall, • Rating is 3/4 hr.When 50 to 150 pair telephone cable is used in 2 hr fire rated wail, T P4 Rating is 1 hr. B. Max No. 10 AWG Type "Romex" A" If% multiple copper conductor NM ( ) nonmetallic sheathed cable with PVC insulation and jacket materials. When Type NM cable is used, max T Rating is 1 -1/2 hr. 2 m C. Multiple fiber optical communication cable jacketed with PVC and having a max outside diam of "Ll W 5/8 in. When fiber optic cable is used, max T Rating is 2 hr. 00 Q Z Z D. Max 12 AWG multi conductor (max seven conductors) power /control cable with cross - linked 1-h -DALE COUNTY FIRE DEPARTME polyethylene (XLPE) insulation and XLPE or PVC jacket materials. !BLDG. PERMIT PW ALARM When multi conductor power /control cable is used, max T Rating is 2 hr. FIRE SUPP EESSSIIO WA R N E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER cables with polyvinyl °mall_ m chloride Insulation and jacket materials. DA ' tv +''' t Lu J 3. Fill,Void or Cavity Materials* - Caulk, Sealant or Putty - Caulk or putty fill material installed to Z completely fill annular space between cable and gypsum wallboard on both sides of wall and with a min F SYSTEM BE 1/4 in. diam bead of caulk or putty applied to perimeter of cable(s) at its egress from each side of the INSTALLED IN ACWRDANCEWMI wail A.��'%0• ZQI 3M COMPANY - MP+ Stix u pity, CP 25W6+ caulk, FB -3000 WT sealant or Cable Wrap putty wW (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant is used.) *Bearing the UL Classification Mark L. TRIANA &ASSOCIATES INC. CONSULTING ENGINEERS a s , CERTIFICATE �gF AyJ;HOR1ZATION: 26 5151 S.W.,,,98lh AYE' ' ®• MIAMI, LE94 -: -T� NA, .E`. Florida Regtsirvgtlwbl PE65707 i u, x � Z W of C01 ti (V 4u) F- L9 Z Wag Q W�IL cv m �(0 W cg 2 m 00 Q Z Z to 1`-) �G) o .� � Lf) W 0- p� °mall_ m Ob = Lu J "\ V Z fn a m J wW Zw O �w t- WU) 20 r__J of �a U o w Z U 13 0 = FF- a rn U to Z w co ° Z o W O Z5 W U_ O cn ° W It W W W J 5 j cc ° S2 a a a a a m to W N r ° O O ci Z .- N ko U U rE--i `./ ►-� a Z w W co to M W `1 III C _ O LL cli -.1 O Z w � F- X W E m z 0- ° _ � U) H Q J J U O U P Z U W U m LL Ix °- W= a ILL U OW n. w� a. O U M :3 a U Cr XA a !_- U OTT Z a °Q Z l-1 U Z d Z W J J O dt W z - O in i II��t 2 F- w 90 Z LC ��tQ o� J x0x J C0 to 1--f �= ° N f- N O a 0�I: Z° S W Z ?O t- D O O � Z XZ co &5 0 ¢ ¢ 3 ® DRAWN BY: DATE: KS 09/29/10 DESIGNED BY: DATE: KS 09/29/10 APPROVED BY: DATE: KS 09/29110 PROJECT NUMBER: 409382/952933613 SHEET NUMBER: NOTES SIZE D (N�