09-98-006BATTERY CALCULATIONS FOR THE FIRE ALARM CONTROL PANEL THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS - THE EXISTING FIRE ALARM CONTROL PANEL STANDBY CONDITION CURRENT VALUE IS 120mA AND THE ALARM CONDITION CURRENT VALUE IS 700mA THE NEW POWER EXPANDER CONTROL PANEL STANDBY CURRENT VALUE IS Oma AND THE ALARM TRIGGER CURRENT IS 15mA ( USING ONE INPUT) THE EXISTING REMOTE ANNUNCIATOR STANDBY CONDITION CURRENT VALUE IS SOMA AND THE ALARM CONDITION CURRENT VALUE IS 120 mA THE EXISTING PULL STATION STANDBY CONDITION CURRENT VALUE IS OmA AND THE ALARM CONDITION CURRENT IS OmA THE EXISTING SMOKE DETECTOR (4 -WIRE) STANDBY CONDITION CURRENT VALUE IS 0,000050 mA AND THE ALARM CONDITION CURRENT IS 35mA THE NEW SMOKE DETECTOR (4 -WIRE) STANDBY CONDITION CURRENT VALUE IS 0.000050 mA AND THE ALARM CONDITION CURRENT IS 35mA THE END -OF -THE -LINE RELAY STANDBY CONDITION CURRENT VALUE IS 20m k AND THE ALARM CONDITION CURRENT IS 2OmA THE EXISTING HEAT DETECTOR STANDBY CONDITION CURRENT VALUE IS OmA AND THE ALARM CONDITION CURRENT IS OmA THE EXISTING HORN / STROBE "TYPE 1" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 35 mA THE EXISTING HORN /STROBE "TYPE 2" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 47 mA THE EXISTING HORN /STROBE "TYPE 3" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 74 mA THE EXISTING HORN /STROBE "TYPE 4" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 217 mA THE EXISTING HORN /STROBE "TYPE 5" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 263 mA THE EXISTING HORN /STROISE "TYPE 6" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 137 mA Description Of Device Quantity y Time ;.R Standby Current per unit (Amps Total Standby Current per Item Quantity Am s Alarm Time Alarm Current per unit (Amps Alarm Capacity Total Alarm Current Am s Existin Fire Alarm Control Panel 1 ac 0.200000 0.200000 1 x 0.295000 - 0.285000 Existing Remote Annunciator 1 rc 0.060000 _ 0,060000 1 x x 0.120000 0.015000 - 0.120000 0.015000 New Power Expander Control Panel 1 x 0.000000 0.000000 1 Existing Pull Stations 20 Ic 0.000000 0.000000 20 x x x 0.000000 0.035000 0.035000 - - - 0.000000 _ 0.105000 0.035000 Existing Smoke Detectors 4 -wire 3 x 0.000050 0.000150 3 New Smoke Detectors 4 -wire 1 X 0.000050 - 0.000050 1 Existing End -of -the Line Relay 2 X 0.020000 - 0.040000 2 x 0.020000 - 0.010000 Existin Heat Detectors 1 x 0.000000 - 0.000000 1 x 0.000000 - 0.000000 Existing Horn /Strobes 2cd "Tye 1" 1 X 0.000000 - 0.000000 1 x 0.035000 - 0.035000 Existing Horn /Strobes 15cd "Type 2" 1 x 0.000000 - 0.000000 1 x 0.047000 - 0.047000 Existing Horn/Strobes 2cd "Type 3" 6 ft 0.000000 - 0.000000 6 x x 0.074000 0.217000 - 0.444000 1.085000 Existin Horn /Strobes 75cd "T e 4" 5 x 0.000000 0.000000 5 Existing Horn /Strobesl IOcd "T e 5" 3 x 0.000000 _ - 0000000 3 x 0.268000 - 0.804000 0.411000 3.426000 as Existin Horn /Strobes 15�d Tie 6" 3 x 0.000000 - 0.000000 x 0.137000 = Total System Standby Current (Amps) 0.300200 Total System Alarm Current (Amps) Required Operating Time of Secondary Power Source from N.F.P.A. 72 1- 19.2.5 Standby Condition : 24 hours Alarm Condition : i Minutes x 1 /60 = 0.0333 irod Total System Required Required Total System Required y Time ;.R Standby Current Standby Capacity Alarm Time Alarm Current Alarm Capacity urs ) ( Amps ) ( Amps - Hours) ( Hours) ( Amps) ( Amps -Hours 4 x 0 300200 - 7.204800 0.(1933 x 3.426000 L=1 0.2995396 equired Required Total Required Optional Factor ReluireU Stby Capacity ;7.204800 Alarm Caparit", Capacity Of safety ■attory Capacity ( ps - Hours) (Amps - hours) rwwMraps- Ho.,r:.. (Amps-Hours ) (Amps -Hours ) 1- 0.2.85.336 7.�901i6 x 1.2 8.589223 NOTE 1) THE FIRE ALARM CONTROL. PANEL NEEDS TWO 12 VOLTS WITH 12 AMPS /HOURS BACKUP BATTERIES 2) THE BACKUP BATTERIES CAN BE INSTALLED INSIDE THE; FIR!F A AR" CONTROL PANEL BATTERY CALCULATIONS FOR THE POWER EXPANDER CONTROL PANEL THE DIP SWITCHES FOR THE WALL MOUNT HORN /STROBES WILL BE SELECTED ON "HIGH ", TEMPORAL" AND "ELECTROMECHANICAL" THE CANDELA SELECTABLE SWITCH FOR THE WALL MOUNT HORN /STROBES WILL BE SET AT "l10cd" THE DIP SWITCHES FOR THE CEILING MOUNT HORN /STROBES WILL BE SELECTED ON "HIGH ", TEMPORAL" AND "ELECTROMECHANICAL" THE CANDELA SELECTABLE SWITCH FOR THE CEILING MOUNT HORN /STROBES WILL BE SET AT "76c11" OR"l10cd" THE CANDELA SELECTABLE SWITCH FOR THE CEILING MOUNT STROBE LIGHTS WILL BE SET AT "75cd" = 0.0833 Required Required Total Required Optional Factor Required StaEA Current Total Standby Alarm Current Total Alarm Description Of Device Quantity nit Current per Item Quantity per unit Current 0.15 - s ( Am . s Am s _ Aln s Horn /Strobes wall mount 11Ocd 1 x 00 0.000 1 x 0.212 - 0.212 Horn /Strobes ceilin mount 11Ocd 3 x 00 = 0.000 3 x 0.212 = 0.636 Strobe Li htseillng mount 75cd 6 x 00 = 0.000 6 x 0.151 = 0.549 Description Of Device Total System standby Current 0.00 Total System Alarm Current 1.80__ (Amps ) ( Amps ) 1 1 ` 0.120 ( Amps) 1 = 0.0833 Required Required Total Required Optional Factor Required Standby Capacity Alarm Capacity Capacity Of Safety ■attery Capacity ( Amps -Hours Is ( Amps - Hours) (Ampc-Hours) ( Amps -Hours ) 0 + .00 0.15 - 015 x 1.2 11 - 0.16 NOTE 1) THE POWER EXPANDER CONTROL PANEL NEEDS TWO 12 VOLTS WITH 7 AMPS /HOURS BACKUP BATTERIES 2) THE TWO BACKUP BATTERIES CAN BE STORED INSIDE THE POWER EXPANDER CONTROL PANEL A7f'blt�l CRYS7ALENE rrr 74 r,L S7nIkO A.Rp FARM EiIGIIVEER'.'S INFC1r-ZRl�IiAT�'O119: STATE LICENSE: EF0000228 COMPANY GPM ENGINEERING, INC:. QUALIFIER'S INFORMATION: NAME: 5HANTJLAL C. PATEL ADDRESS: 5502 S UV. 114 AVENUE - NAME BRUCE HOTCHKISS COOPER CITY, FLORID�i 33330 �L ° ADDRESS: 5650 SERIDAN STREET KIND Or ENGINEER: MECHANICAUELECTRICA! Eh)C21 1�IEeR ' HOLLYWOOD, FLORIDA 33021 .� LICENSE NUMBER: P.E. # _.LICENSE NUMBER: )- 0000228 CURRENT LOAD CALCULATIONS VOLTAGE DROP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR PER NOTIFICATION APPLIANCE CIRCUITS IN THE FIRE ALARM CONTROL PANEL THE FIRE ALARM CONTRC)L PANED. THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS THE POWER EXPANDER CONTROL PANEL USES A TRIGGER CURRENT OF 2.0 mA THE DC OPERATING CURRENT VALUE HAS BEEN USED BECAUSE THE FIRE ALARM CONTROL PANEL HAS A FILTERED AND REGULATED 24VDC POWER FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS THE EXISTING HORN /STROBE "TYPE 1" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 35 mA THE EXISTING HORN /STROBE "TYPE 2" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 47 mA THE EXISTING HORN/STROBE "TYPE 3" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 74 mA THE EXISTING HORN /STROBE "TYPE 4" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 217 mA THE EXISTING HORN /STROBE "TYPE i" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 269 mA THE EXISTING HORN /STROBE "TYPE S" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 212 mA THE NON - RESETABLE POWER INCLUDES THE FOLLOWING: THE ONE REMOTE ANNUNCIATOR THE ALARM CONDITION CURRENT IS 1206 THE RESETABLE POWER INCLUDES THE FOLLOWING: THE THREE EXISTING 4 -WIRE SMOKE DETECTOR THE ALARM CONDITION CURRENT IS 36mA THE ONE NEW 4 -WIRE SMOKE DETECTOR THE ALARM CONDITION CURRENT IS 35mA THE TWO EXISTING END -OF- THE -LINE RELAY THE ALARM CONDITION CURRENT IS 20MA CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 1 I`"' Alarm Current Total Alarm w Description Of Device I Quantity per unit Current Horn/Strobe N /Ace wall mount 1 TYPE ' 1" t � 1 0.035 0035 - - - -- - Horn/Strobe N /Acd LLvall mount) TYPE 1 0.047 0.047 Horn /Strobe NIAcd ( wall mount ) TYPE '3" 6 0.074 0,444 Horn /Strobe NiAcd mount T� 5 0.217 1,095 _wall Horn /Strobe 110cd wall mount ) TYPE "5" w :a 3 0.268 0.11104 Horn /Strobe 110cd wall mount TYPE "6" 3 0.212 Description Of Device Quantity per unit Total System Alarm Current 0.636 ( Amps) "', I ( Amps ) ( Amps ) 0 0.212 `cr 0 0.212 0 0.158 CALCULATIONS FOR THE AUXILARY POWER OUTPUT Horn/Strobes ceiling mount ) 11Ocd "..._ Alarm Current Total Alarm >r �{. 0.00 Description Of Device Quantity I per unit Current CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT X 4 .�^ (Amps) (Amps ) Nonresettable AuxilaryPower 1 1 ` 0.120 0.120 Resettable Auxila Power 1 0.130 ��w i 0.180 w� _ esxw.�w_,w.uw.reMr Total System Alarm Current p.30 -000 ( Ampa 1 __0 0 0 212 TOTAL CURRENT PER CIRCUIT 0 0.212 kK 0 0.158 Total System Alarm Current NOTIFICATION APPLIANCE CIRCUIT# 1.58 (Amps) 0.00 NOTIFICATION APPLIANCE CIRCUIT 7t 1 0.64 AUXILARY OUTPUT CIRCUI'.5 0.30 ( Amps ) TOTAL ALARM CURRENT Is 0.94 000�� (Am s NOTIFICATION APPLIANCE CIRCUIT # 3 NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 2.5 AMPS. 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION' APPLIANCE CIRCUITS AND OTHER DC POWER 011'8 U7!; CAN NOT EXCEED 2.5 Amps CURRENT LOAD CALC*UZ_ATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN THE POI.A.ItERM EXPANDER CONTROL PANEL THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS - THE DC OPERATING CURRENT VALUE HAS BEEN USED BECAUSE THE POWER EXPANDERCONTROL PANEL HAS A FILTERED AND REGULATED 24VDC POWER FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS - THE DIP SWITCHES FOR THE WALL MOUNT HORN /STROBES WILL BE SELECTED ON "HIGH ", TEMPORAL" AND "ELECTROMECHANICAL" - THE CANDELA SELECTABLE SWITCH FOR THE WALL MOUNT HORN /STROBES WILL BE SET AT "110ci" - THE DIP SWITCHES FOR THE CEILING MOUNT HORN /STROBES WILL BE SELECTED ON "HIGH ", TEMPORAL" AND "ELECTROMECHANICAL" - THE CANDELA SELECTABLE SWITCH FOR THE CEILING MOUNT HORN /STROBES WILL BESET AT "75cd " OR "110cd" - THE CANDELA SELECTABLE SWITCH FOR THE CEILING MOUNT STROBE LIGHTS WILL BE SET AT "75cd" CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 1 Alarm Current Total Alarm Description Of Device Quantity per unit Current ( Amps) (Amps) Horn /Strobes (Wall mount) 110cd 1 0.212 0.212 Horn /Strobes (ceiling mount 110cd2 T 0.212 0424 Strobe Li hts ceilin mount 75cd 1 6 0.158 0.948 Total System Alarm Current L_ ( Amps) 1.69 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 2 Aiarm Current Total Alarm Descrintion Of Device Quantity per unit hx Cument i Horn /Strobes (Ceiling mount) 110cd Strobe Li.hts ceiling mount 75cd 0 0.212 kK 0 0.158 Total System Alarm Current 0.000 0,000 1.58 NOTIFICATIONAPPL.IANGEGIRCUIT#2 _ 0.00 0.00 0.00 ( Amps ) t - At J XI LARY POWER OUI I I'l 3T 000�� CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 3 Alarm Current Total Alarm Description Of Device Quantity per unit Current ( Amps) "', I ( Amps ) Horn /Strobes (wall mount) 11OCd 0 0.212 `cr 0 0.212 0 0.158 0.000 0.000 0.000 Horn/Strobes ceiling mount ) 11Ocd Strobe Li hts ceilin mount 75Cd Total System Alamo Current 0.00 ( I Amps ) (Ohm) ( CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT X 4 (volts) Alamo Curent 'Total Alarm Description Of Device Quantity per unit Current I (Amps ( Amps ) Horn /Strobes ( wall mount ) 1 )0cd 0_ 0.212 - -000 Horn /Strobes ceiling mount 11 Ocd __0 0 0 212 0.000 Strobe Li hts ceiling mount 75cd 0� 0.153 0.000 Total System Alarm Current L (( Am�........ps) CALCULATIONS FOR THE AUXILARY POWER OUTPUT Alan Current Total Alarm Description Of DnvicF Quant +ty per unit Current 5' ( Amps) ( Amps ) Nonresettable AuxilaryPower LL 0 _ 0000 0.000 Resettable AUXII@rV Power 0 0.000 0.000 System Alarm Gurenk ( Amps) ..rrr..rr. 0.00 NOTIFICATION APPLIANCE CIRCUIT A TOTAL CURRENT PER CIRCUIT ( Amps ) NOTIF ICA I'ION APPI.IANCF CIRCUII A 1 1.58 NOTIFICATIONAPPL.IANGEGIRCUIT#2 _ 0.00 NOTIFICATIONAPPLIAN(',f3CIRCUIT83 0.00 NOTIFICATION APPLIANCE CIRCIA 1 $4 - 000 -- - At J XI LARY POWER OUI I I'l 3T 000�� TOTAL ALARM CUE i" (Amps 1.59 NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS. 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps - THE TOTAL WIRE RUN VALUE IS OBTAIN 13Y MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.001307 OHMS PER FOCiT THE CURRENT LOAD VALUE ALUE IS OBTAIA FROM THE CORRESPONDING "TOTAL 7TAL ALARM CURRENT" U RI.NT" FROM THE ONE I NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION 1 PPLIANCE CIRCUIT FOR THE FIRE ALARM CONTROL PANEL CHART THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT tt 1 Beginning Voltage Total voltage drop voltage I farthe for the for the I Indicating Indicating Indicating Appliance Appliance Appliance Circuit Circuit Circuit ( volts ) ( volts) (volts) 20.40 4.37 = 16.03 NOTES: 1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN BE IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR. THE NOTIFICATION APPLIAlail i:�3 BETWEEN 16 TO 33 VOLTS Total ire Total Total Veitat}e wiring run gauge line current drop for the. resistance resistance lead for the Notification for the for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit circuit Circuit (feet) EXISTING NOTIFICATION APPLIANCES .._ DESCRIPTION MANUFACTURER � MODEL DISCONTINUE"D Horn /Strobe wall Mount TYPE "1' � WHEELOCK 24T -34� YES Horn /Strobe wall Mount TYPE "2" _� SIMPLEX 49113 -8219 YES Morn /Strobe wall Mount TYPE "3" FARADAY 60:'.0/5511 YES Horn/Strobe _(wall Mount) TYPE "4" SENSOR SYSTEM P22475 _YES Horrt /5irnbe wall Mount T) YF,i'°5> SENSOR SYSTEM -_ P1 224110 YES Horn /Strobe wall Mount) TYI't "6" SENSOR SYSTEM �F'2R � NO VOLTAGE DROP CALCULATION415 PER NOTIFICATION APPLIANCE CIRC UITS IN THE POWER EXPANDER CONTROL_ PANEL THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN Ih'i THE FLOOR PLAN - TIME WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - 1'kE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURREf IT" FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT:! FOR THE ADDRESSABLE FIRE ALARM CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1 Total Wire Total Total Voltage Beginning Voltage Total wrong run gauge line current drop vritag9 drop voltage for the resistance resistance bad farthe forth.: forthc for the I Notification far the for the for the Indicating Indicathlg Indicating Indicating i Appliance 14 gauge Notification NotiiTicatian Appliance Appliance Appliance Appliance � M Circuifi wire Circuit Circuit Circuit Circui�.: Circuit Circuit (feet) (Ohmsffeet ) (Ohm) (amps) (volts) (volts) (volts) 2 =0 .003 07 - 0.4912 x 1.59 = �� 0.776 L2O;') - 0.79 i� �LCULATION5 FOR THE NOTIFICATION APPLIANCE CIRCUIT *_2 Total Wire Total Total Voltage Beginning Voltage Total � wooing run gauge line current dap wltaee dap voltage for the resistance resistance lead for the for the for the for the 1 i Notification for the for the for the Indicating Indicatimg Indicating Indicating I i Appliance 14 gauge Notification Notification Appliance Appliance Appliance Appliance I Circuit wire Circuit Circuit Circuit Circuit Circuit Circuit ( feet) '. (Ohms /feet) (Ohm) (amps) (units) (volt-) (volts) (volts) 2',00 x 0 x 0.00307 El 0 x 0.00 = 0 -000 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT it 3 _ 11 Total Wire Total Total VaBta,e NeyinrjnceApp;iance Voltage h )'Dial wlnng run gauge line current drop valta dap voltage for the, resistance resistance bad farthe for tl for cite for the i Notification far the for the for the Indicating Indic -Be ndicating indicating ia./i,Ppliance 14 gauge Notification Notification Appliance Applia Appliance Circuit wire Circuit Circuit Circuit Circu Circuit Circuit f feet) (Ohmsffeet) (Ohm) (amps) (volts , !, ) (volts) (wits ) o x 0.00307 0.000 0.00 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 8 4 Total Wire Total Total Voltage icginning Voltage Total t wiring run gauge line current dray voltage drop , voltage ' farthe resistance resistance lead farthe for the ter the I farthe eta Notification far the for the for the Indicating Indicating Indicating Indicating " Appliance 14 gauge Notification Notification Appliance Appli;.mce Appliance Appliance Circuit wire Circuit Circuit Circuit Girc At Circuit Circuit (feet) (Ohmsffeet) (Ohm) (amps) (volts) (volts) (volts volts 1 ) Z.00 x 0 x 0.00307 = 0 x 0.00 = � 0.000 20.70 20.40 NOTES: 1) THE LOWEST VOLTAGE OM EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIAfJ 'E CIRCUIT II 3) THE OPERATING VOLTAGE RANGE FOR THE - NOTIFICATION APPLIANCES IS BETV'VEEN 16 TO 33 VOLTS I'�OTE'.) cannot exceed 6.0 amps BURGLAR ,ALARM SERVICES 560 SHERIDAN STREET HOLLYWOOD,, FLORIDA 33021 -320 PHONE: (945) 983 -3358 FAX: (13"1554) 981 -4302 �- SOUTH MlAn�l Ha�PIirAL _��ITN�S � ��r� 6200 S�.W.73 STREET IREEfi SOUTH MIAMI, i=LOt' °9;10,0 313 143 Approved by: _ti Drawn Icy °,,..._ „�..,.._. J.13. 12/19/(38 SHANTJAKL C. F'�IATEL F2evised:� "`".. °". BURGLAR ALARM SIERVICEES 5650 SkiERIpAN STREET, HOLLY'1JYOOD, FLGRIDAA ::13021 ....'A DRhWiNG NUMESEF;- i.1A rJ E, IN Il.S,A Required Operating Time of Secondary Power source from N.F.P.A, 72 1.5.2.5 Standby Condition :24 flours Alarm Condition : 5 Minutes x 1 /60 1) All conduit to be 1/2" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3} All wires for the Initiating Circuit will be THWN wire, 14" gauge 4 All Ices for the Notification Circuit rt will THW;J 14" g,.t.ga 5) All work to he done in accordance with the Nati ^rz' electrical Core and shall comply with ill the local rules and ordinances G) The Fire Alarm /Communicator Control Panel is i'b6d by a .;ol,duit n:fl, (3)11Z Ta'NN ..ondl ctors (one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch branch circuit breaker at 120vac with i breaker lock 7 The w- e rr Expander Control Panel i s feed by a 1/2 EMT conduit with (3) X12 cu THWN conductors i one phase conductor, one neutral T conductor ciao and one grounding conductor) supplied by a 20 amp single pole dedicated branch circuit breaker at 120vac with a breaker lock i) All equipment instilled are " U.L. Listed" for the Fire Alarm Services and shall be compatible between them 9} All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association 4 72 1 n} The Fire Alarm Control Panel is Power Limited 11) The Power Expander Control Panel is Power Limited 12) The Bzckup 15atttry Charger is inside the Fire Alarm Control Panel (batteries must be UL Listed Batteries not to exceed 17 AH ) 13} The Qackup Battery Charger is inside the Power Expander Control Panel (Batteries must be UL t.istr3d Batteries not to exceed 13 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall) activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 41111" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor 18) Pull Stations to be instilled at least one per floor and within 200' of any point in the premises 19) Smoke Detectors and Heat Detectors to be installed at 6" away from the wall or 6" below the ceiling 20) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 21) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 22) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 23) Smoke Detectorsind Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 7.4} The Wall Mount Horn /Strobes, Ceiling Mount Horn /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 25) The Wall Mount Horn/Strobes to be installed at 80" A.F.F. or 6" below the ceiling (which ever is Iowls:, ) 26) The Ceiling Mount Hom /Strobes to be installed at 95" A.F.F. or above 27 All Wall } Mount Horn /Strobes and Ceiling Mount Flom /Strobes will provide 15dbA above ambient or 5 bA above peak levels 211111) All Strobe Lights are adequate for the area that are covering 29) All Corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends olf the corridor 30) The ceiling heights inside the Data /Phone /Fire Alarm Area and Electrical Panel Area is between T Bold i' from the floor 31) The Acoustic ceiling heights inside the Gym Area are between T and 10' from the floor 32) The Acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room are between 6.G' and 7.1' from the floor 33) All ranks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 34) Na Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 35) All the devices will be instilled at normal conditions as per the N.F.P.A. 72 36) The Devices and Appliances that are in areas which the voltage, temperature and humidity variation;; exceed the normal conditions have a W.P. label next to it 37) The Fire Alarm Control Panel and the Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 3E) The Remote Annunciator will be located inside an occupied area and will be protected by a Smoke Detector 39) The Fire Alarm will be connected to z Proprietary Supervising Station 40) The method of communication of the F=irel Alarm Control Panel with the Proprietary Supervising Station is by the Fire Alarm Control Panel Alarm Dry Contacts and the Trouble Dry Contacts 40) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the Fire Alarm Control Panel 41) The Fire Alarm System a Fire Alarm System will be provided with i 24 hours Secondary Power 42) The Fire Alarm Control Panel has nine Initiating Circuits 43) The Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "81" or meet Style "A" or Style "D" (Class "A") 44) The maximum smoke Detectors in each Initaitiny Zones can not exceed a draw of 3mA per Initaitng !'_one 45) The Fire Alarm Control Panel his, is Manufacturer Specification, a Capacity of 2.5 amps for the one Notification Circuit 46) The Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2.5 amps 47) The Notification Appliance Circuits for the Fire Alarm Control Panel meet the NFPA Style "Y" (Class "13 ")and Style 7" ( Class "A") 50) The Power Expander Control Panel has four Notification Appliance Circuits 51) The Notification Appliance Circuits for the Power Expander Control Panel meet the NFPA Style "Y" (loose "B ")and Style "z" ( Class "A") 52) The Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the Notification Circuits 53} The Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Circuits and the DC Power Output ( (Ohmsffeet) ( (Ohm) ( (amps) ( (volts) 2_UU x x 1120 x 0 0.00307 = 6 6.i7Gi x x 0.636 4 I APPLIANCES .._ DESCRIPTION MANUFACTURER � MODEL DISCONTINUE"D Horn /Strobe wall Mount TYPE "1' � WHEELOCK 24T -34� YES Horn /Strobe wall Mount TYPE "2" _� SIMPLEX 49113 -8219 YES Morn /Strobe wall Mount TYPE "3" FARADAY 60:'.0/5511 YES Horn/Strobe _(wall Mount) TYPE "4" SENSOR SYSTEM P22475 _YES Horrt /5irnbe wall Mount T) YF,i'°5> SENSOR SYSTEM -_ P1 224110 YES Horn /Strobe wall Mount) TYI't "6" SENSOR SYSTEM �F'2R � NO VOLTAGE DROP CALCULATION415 PER NOTIFICATION APPLIANCE CIRC UITS IN THE POWER EXPANDER CONTROL_ PANEL THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN Ih'i THE FLOOR PLAN - TIME WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - 1'kE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURREf IT" FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT:! FOR THE ADDRESSABLE FIRE ALARM CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1 Total Wire Total Total Voltage Beginning Voltage Total wrong run gauge line current drop vritag9 drop voltage for the resistance resistance bad farthe forth.: forthc for the I Notification far the for the for the Indicating Indicathlg Indicating Indicating i Appliance 14 gauge Notification NotiiTicatian Appliance Appliance Appliance Appliance � M Circuifi wire Circuit Circuit Circuit Circui�.: Circuit Circuit (feet) (Ohmsffeet ) (Ohm) (amps) (volts) (volts) (volts) 2 =0 .003 07 - 0.4912 x 1.59 = �� 0.776 L2O;') - 0.79 i� �LCULATION5 FOR THE NOTIFICATION APPLIANCE CIRCUIT *_2 Total Wire Total Total Voltage Beginning Voltage Total � wooing run gauge line current dap wltaee dap voltage for the resistance resistance lead for the for the for the for the 1 i Notification for the for the for the Indicating Indicatimg Indicating Indicating I i Appliance 14 gauge Notification Notification Appliance Appliance Appliance Appliance I Circuit wire Circuit Circuit Circuit Circuit Circuit Circuit ( feet) '. (Ohms /feet) (Ohm) (amps) (units) (volt-) (volts) (volts) 2',00 x 0 x 0.00307 El 0 x 0.00 = 0 -000 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT it 3 _ 11 Total Wire Total Total VaBta,e NeyinrjnceApp;iance Voltage h )'Dial wlnng run gauge line current drop valta dap voltage for the, resistance resistance bad farthe for tl for cite for the i Notification far the for the for the Indicating Indic -Be ndicating indicating ia./i,Ppliance 14 gauge Notification Notification Appliance Applia Appliance Circuit wire Circuit Circuit Circuit Circu Circuit Circuit f feet) (Ohmsffeet) (Ohm) (amps) (volts , !, ) (volts) (wits ) o x 0.00307 0.000 0.00 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 8 4 Total Wire Total Total Voltage icginning Voltage Total t wiring run gauge line current dray voltage drop , voltage ' farthe resistance resistance lead farthe for the ter the I farthe eta Notification far the for the for the Indicating Indicating Indicating Indicating " Appliance 14 gauge Notification Notification Appliance Appli;.mce Appliance Appliance Circuit wire Circuit Circuit Circuit Girc At Circuit Circuit (feet) (Ohmsffeet) (Ohm) (amps) (volts) (volts) (volts volts 1 ) Z.00 x 0 x 0.00307 = 0 x 0.00 = � 0.000 20.70 20.40 NOTES: 1) THE LOWEST VOLTAGE OM EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIAfJ 'E CIRCUIT II 3) THE OPERATING VOLTAGE RANGE FOR THE - NOTIFICATION APPLIANCES IS BETV'VEEN 16 TO 33 VOLTS I'�OTE'.) cannot exceed 6.0 amps BURGLAR ,ALARM SERVICES 560 SHERIDAN STREET HOLLYWOOD,, FLORIDA 33021 -320 PHONE: (945) 983 -3358 FAX: (13"1554) 981 -4302 �- SOUTH MlAn�l Ha�PIirAL _��ITN�S � ��r� 6200 S�.W.73 STREET IREEfi SOUTH MIAMI, i=LOt' °9;10,0 313 143 Approved by: _ti Drawn Icy °,,..._ „�..,.._. J.13. 12/19/(38 SHANTJAKL C. F'�IATEL F2evised:� "`".. °". BURGLAR ALARM SIERVICEES 5650 SkiERIpAN STREET, HOLLY'1JYOOD, FLGRIDAA ::13021 ....'A DRhWiNG NUMESEF;- i.1A rJ E, IN Il.S,A Required Operating Time of Secondary Power source from N.F.P.A, 72 1.5.2.5 Standby Condition :24 flours Alarm Condition : 5 Minutes x 1 /60 1) All conduit to be 1/2" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3} All wires for the Initiating Circuit will be THWN wire, 14" gauge 4 All Ices for the Notification Circuit rt will THW;J 14" g,.t.ga 5) All work to he done in accordance with the Nati ^rz' electrical Core and shall comply with ill the local rules and ordinances G) The Fire Alarm /Communicator Control Panel is i'b6d by a .;ol,duit n:fl, (3)11Z Ta'NN ..ondl ctors (one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch branch circuit breaker at 120vac with i breaker lock 7 The w- e rr Expander Control Panel i s feed by a 1/2 EMT conduit with (3) X12 cu THWN conductors i one phase conductor, one neutral T conductor ciao and one grounding conductor) supplied by a 20 amp single pole dedicated branch circuit breaker at 120vac with a breaker lock i) All equipment instilled are " U.L. Listed" for the Fire Alarm Services and shall be compatible between them 9} All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association 4 72 1 n} The Fire Alarm Control Panel is Power Limited 11) The Power Expander Control Panel is Power Limited 12) The Bzckup 15atttry Charger is inside the Fire Alarm Control Panel (batteries must be UL Listed Batteries not to exceed 17 AH ) 13} The Qackup Battery Charger is inside the Power Expander Control Panel (Batteries must be UL t.istr3d Batteries not to exceed 13 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall) activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 41111" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor 18) Pull Stations to be instilled at least one per floor and within 200' of any point in the premises 19) Smoke Detectors and Heat Detectors to be installed at 6" away from the wall or 6" below the ceiling 20) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 21) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 22) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 23) Smoke Detectorsind Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 7.4} The Wall Mount Horn /Strobes, Ceiling Mount Horn /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 25) The Wall Mount Horn/Strobes to be installed at 80" A.F.F. or 6" below the ceiling (which ever is Iowls:, ) 26) The Ceiling Mount Hom /Strobes to be installed at 95" A.F.F. or above 27 All Wall } Mount Horn /Strobes and Ceiling Mount Flom /Strobes will provide 15dbA above ambient or 5 bA above peak levels 211111) All Strobe Lights are adequate for the area that are covering 29) All Corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends olf the corridor 30) The ceiling heights inside the Data /Phone /Fire Alarm Area and Electrical Panel Area is between T Bold i' from the floor 31) The Acoustic ceiling heights inside the Gym Area are between T and 10' from the floor 32) The Acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room are between 6.G' and 7.1' from the floor 33) All ranks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 34) Na Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 35) All the devices will be instilled at normal conditions as per the N.F.P.A. 72 36) The Devices and Appliances that are in areas which the voltage, temperature and humidity variation;; exceed the normal conditions have a W.P. label next to it 37) The Fire Alarm Control Panel and the Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 3E) The Remote Annunciator will be located inside an occupied area and will be protected by a Smoke Detector 39) The Fire Alarm will be connected to z Proprietary Supervising Station 40) The method of communication of the F=irel Alarm Control Panel with the Proprietary Supervising Station is by the Fire Alarm Control Panel Alarm Dry Contacts and the Trouble Dry Contacts 40) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the Fire Alarm Control Panel 41) The Fire Alarm System a Fire Alarm System will be provided with i 24 hours Secondary Power 42) The Fire Alarm Control Panel has nine Initiating Circuits 43) The Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "81" or meet Style "A" or Style "D" (Class "A") 44) The maximum smoke Detectors in each Initaitiny Zones can not exceed a draw of 3mA per Initaitng !'_one 45) The Fire Alarm Control Panel his, is Manufacturer Specification, a Capacity of 2.5 amps for the one Notification Circuit 46) The Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2.5 amps 47) The Notification Appliance Circuits for the Fire Alarm Control Panel meet the NFPA Style "Y" (Class "13 ")and Style 7" ( Class "A") 50) The Power Expander Control Panel has four Notification Appliance Circuits 51) The Notification Appliance Circuits for the Power Expander Control Panel meet the NFPA Style "Y" (loose "B ")and Style "z" ( Class "A") 52) The Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the Notification Circuits 53} The Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Circuits and the DC Power Output UITS IN THE POWER EXPANDER CONTROL_ PANEL THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN Ih'i THE FLOOR PLAN - TIME WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - 1'kE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURREf IT" FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT:! FOR THE ADDRESSABLE FIRE ALARM CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1 Total Wire Total Total Voltage Beginning Voltage Total wrong run gauge line current drop vritag9 drop voltage for the resistance resistance bad farthe forth.: forthc for the I Notification far the for the for the Indicating Indicathlg Indicating Indicating i Appliance 14 gauge Notification NotiiTicatian Appliance Appliance Appliance Appliance � M Circuifi wire Circuit Circuit Circuit Circui�.: Circuit Circuit (feet) (Ohmsffeet ) (Ohm) (amps) (volts) (volts) (volts) 2 =0 .003 07 - 0.4912 x 1.59 = �� 0.776 L2O;') - 0.79 i� �LCULATION5 FOR THE NOTIFICATION APPLIANCE CIRCUIT *_2 Total Wire Total Total Voltage Beginning Voltage Total � wooing run gauge line current dap wltaee dap voltage for the resistance resistance lead for the for the for the for the 1 i Notification for the for the for the Indicating Indicatimg Indicating Indicating I i Appliance 14 gauge Notification Notification Appliance Appliance Appliance Appliance I Circuit wire Circuit Circuit Circuit Circuit Circuit Circuit ( feet) '. (Ohms /feet) (Ohm) (amps) (units) (volt-) (volts) (volts) 2',00 x 0 x 0.00307 El 0 x 0.00 = 0 -000 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT it 3 _ 11 Total Wire Total Total VaBta,e NeyinrjnceApp;iance Voltage h )'Dial wlnng run gauge line current drop valta dap voltage for the, resistance resistance bad farthe for tl for cite for the i Notification far the for the for the Indicating Indic -Be ndicating indicating ia./i,Ppliance 14 gauge Notification Notification Appliance Applia Appliance Circuit wire Circuit Circuit Circuit Circu Circuit Circuit f feet) (Ohmsffeet) (Ohm) (amps) (volts , !, ) (volts) (wits ) o x 0.00307 0.000 0.00 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 8 4 Total Wire Total Total Voltage icginning Voltage Total t wiring run gauge line current dray voltage drop , voltage ' farthe resistance resistance lead farthe for the ter the I farthe eta Notification far the for the for the Indicating Indicating Indicating Indicating " Appliance 14 gauge Notification Notification Appliance Appli;.mce Appliance Appliance Circuit wire Circuit Circuit Circuit Girc At Circuit Circuit (feet) (Ohmsffeet) (Ohm) (amps) (volts) (volts) (volts volts 1 ) Z.00 x 0 x 0.00307 = 0 x 0.00 = � 0.000 20.70 20.40 NOTES: 1) THE LOWEST VOLTAGE OM EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIAfJ 'E CIRCUIT II 3) THE OPERATING VOLTAGE RANGE FOR THE - NOTIFICATION APPLIANCES IS BETV'VEEN 16 TO 33 VOLTS I'�OTE'.) cannot exceed 6.0 amps BURGLAR ,ALARM SERVICES 560 SHERIDAN STREET HOLLYWOOD,, FLORIDA 33021 -320 PHONE: (945) 983 -3358 FAX: (13"1554) 981 -4302 �- SOUTH MlAn�l Ha�PIirAL _��ITN�S � ��r� 6200 S�.W.73 STREET IREEfi SOUTH MIAMI, i=LOt' °9;10,0 313 143 Approved by: _ti Drawn Icy °,,..._ „�..,.._. J.13. 12/19/(38 SHANTJAKL C. F'�IATEL F2evised:� "`".. °". BURGLAR ALARM SIERVICEES 5650 SkiERIpAN STREET, HOLLY'1JYOOD, FLGRIDAA ::13021 ....'A DRhWiNG NUMESEF;- i.1A rJ E, IN Il.S,A Required Operating Time of Secondary Power source from N.F.P.A, 72 1.5.2.5 Standby Condition :24 flours Alarm Condition : 5 Minutes x 1 /60 1) All conduit to be 1/2" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3} All wires for the Initiating Circuit will be THWN wire, 14" gauge 4 All Ices for the Notification Circuit rt will THW;J 14" g,.t.ga 5) All work to he done in accordance with the Nati ^rz' electrical Core and shall comply with ill the local rules and ordinances G) The Fire Alarm /Communicator Control Panel is i'b6d by a .;ol,duit n:fl, (3)11Z Ta'NN ..ondl ctors (one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch branch circuit breaker at 120vac with i breaker lock 7 The w- e rr Expander Control Panel i s feed by a 1/2 EMT conduit with (3) X12 cu THWN conductors i one phase conductor, one neutral T conductor ciao and one grounding conductor) supplied by a 20 amp single pole dedicated branch circuit breaker at 120vac with a breaker lock i) All equipment instilled are " U.L. Listed" for the Fire Alarm Services and shall be compatible between them 9} All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association 4 72 1 n} The Fire Alarm Control Panel is Power Limited 11) The Power Expander Control Panel is Power Limited 12) The Bzckup 15atttry Charger is inside the Fire Alarm Control Panel (batteries must be UL Listed Batteries not to exceed 17 AH ) 13} The Qackup Battery Charger is inside the Power Expander Control Panel (Batteries must be UL t.istr3d Batteries not to exceed 13 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall) activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 41111" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor 18) Pull Stations to be instilled at least one per floor and within 200' of any point in the premises 19) Smoke Detectors and Heat Detectors to be installed at 6" away from the wall or 6" below the ceiling 20) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 21) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 22) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 23) Smoke Detectorsind Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 7.4} The Wall Mount Horn /Strobes, Ceiling Mount Horn /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 25) The Wall Mount Horn/Strobes to be installed at 80" A.F.F. or 6" below the ceiling (which ever is Iowls:, ) 26) The Ceiling Mount Hom /Strobes to be installed at 95" A.F.F. or above 27 All Wall } Mount Horn /Strobes and Ceiling Mount Flom /Strobes will provide 15dbA above ambient or 5 bA above peak levels 211111) All Strobe Lights are adequate for the area that are covering 29) All Corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends olf the corridor 30) The ceiling heights inside the Data /Phone /Fire Alarm Area and Electrical Panel Area is between T Bold i' from the floor 31) The Acoustic ceiling heights inside the Gym Area are between T and 10' from the floor 32) The Acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room are between 6.G' and 7.1' from the floor 33) All ranks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 34) Na Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 35) All the devices will be instilled at normal conditions as per the N.F.P.A. 72 36) The Devices and Appliances that are in areas which the voltage, temperature and humidity variation;; exceed the normal conditions have a W.P. label next to it 37) The Fire Alarm Control Panel and the Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 3E) The Remote Annunciator will be located inside an occupied area and will be protected by a Smoke Detector 39) The Fire Alarm will be connected to z Proprietary Supervising Station 40) The method of communication of the F=irel Alarm Control Panel with the Proprietary Supervising Station is by the Fire Alarm Control Panel Alarm Dry Contacts and the Trouble Dry Contacts 40) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the Fire Alarm Control Panel 41) The Fire Alarm System a Fire Alarm System will be provided with i 24 hours Secondary Power 42) The Fire Alarm Control Panel has nine Initiating Circuits 43) The Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "81" or meet Style "A" or Style "D" (Class "A") 44) The maximum smoke Detectors in each Initaitiny Zones can not exceed a draw of 3mA per Initaitng !'_one 45) The Fire Alarm Control Panel his, is Manufacturer Specification, a Capacity of 2.5 amps for the one Notification Circuit 46) The Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2.5 amps 47) The Notification Appliance Circuits for the Fire Alarm Control Panel meet the NFPA Style "Y" (Class "13 ")and Style 7" ( Class "A") 50) The Power Expander Control Panel has four Notification Appliance Circuits 51) The Notification Appliance Circuits for the Power Expander Control Panel meet the NFPA Style "Y" (loose "B ")and Style "z" ( Class "A") 52) The Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the Notification Circuits 53} The Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Circuits and the DC Power Output cannot exceed 6.0 amps BURGLAR ,ALARM SERVICES 560 SHERIDAN STREET HOLLYWOOD,, FLORIDA 33021 -320 PHONE: (945) 983 -3358 FAX: (13"1554) 981 -4302 �- SOUTH MlAn�l Ha�PIirAL _��ITN�S � ��r� 6200 S�.W.73 STREET IREEfi SOUTH MIAMI, i=LOt' °9;10,0 313 143 Approved by: _ti Drawn Icy °,,..._ „�..,.._. J.13. 12/19/(38 SHANTJAKL C. F'�IATEL F2evised:� "`".. °". BURGLAR ALARM SIERVICEES 5650 SkiERIpAN STREET, HOLLY'1JYOOD, FLGRIDAA ::13021 ....'A DRhWiNG NUMESEF;- i.1A rJ E, IN Il.S,A Required Operating Time of Secondary Power source from N.F.P.A, 72 1.5.2.5 Standby Condition :24 flours Alarm Condition : 5 Minutes x 1 /60 1) All conduit to be 1/2" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3} All wires for the Initiating Circuit will be THWN wire, 14" gauge 4 All Ices for the Notification Circuit rt will THW;J 14" g,.t.ga 5) All work to he done in accordance with the Nati ^rz' electrical Core and shall comply with ill the local rules and ordinances G) The Fire Alarm /Communicator Control Panel is i'b6d by a .;ol,duit n:fl, (3)11Z Ta'NN ..ondl ctors (one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch branch circuit breaker at 120vac with i breaker lock 7 The w- e rr Expander Control Panel i s feed by a 1/2 EMT conduit with (3) X12 cu THWN conductors i one phase conductor, one neutral T conductor ciao and one grounding conductor) supplied by a 20 amp single pole dedicated branch circuit breaker at 120vac with a breaker lock i) All equipment instilled are " U.L. Listed" for the Fire Alarm Services and shall be compatible between them 9} All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association 4 72 1 n} The Fire Alarm Control Panel is Power Limited 11) The Power Expander Control Panel is Power Limited 12) The Bzckup 15atttry Charger is inside the Fire Alarm Control Panel (batteries must be UL Listed Batteries not to exceed 17 AH ) 13} The Qackup Battery Charger is inside the Power Expander Control Panel (Batteries must be UL t.istr3d Batteries not to exceed 13 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall) activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 41111" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor 18) Pull Stations to be instilled at least one per floor and within 200' of any point in the premises 19) Smoke Detectors and Heat Detectors to be installed at 6" away from the wall or 6" below the ceiling 20) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 21) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 22) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 23) Smoke Detectorsind Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 7.4} The Wall Mount Horn /Strobes, Ceiling Mount Horn /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 25) The Wall Mount Horn/Strobes to be installed at 80" A.F.F. or 6" below the ceiling (which ever is Iowls:, ) 26) The Ceiling Mount Hom /Strobes to be installed at 95" A.F.F. or above 27 All Wall } Mount Horn /Strobes and Ceiling Mount Flom /Strobes will provide 15dbA above ambient or 5 bA above peak levels 211111) All Strobe Lights are adequate for the area that are covering 29) All Corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends olf the corridor 30) The ceiling heights inside the Data /Phone /Fire Alarm Area and Electrical Panel Area is between T Bold i' from the floor 31) The Acoustic ceiling heights inside the Gym Area are between T and 10' from the floor 32) The Acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room are between 6.G' and 7.1' from the floor 33) All ranks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 34) Na Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 35) All the devices will be instilled at normal conditions as per the N.F.P.A. 72 36) The Devices and Appliances that are in areas which the voltage, temperature and humidity variation;; exceed the normal conditions have a W.P. label next to it 37) The Fire Alarm Control Panel and the Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 3E) The Remote Annunciator will be located inside an occupied area and will be protected by a Smoke Detector 39) The Fire Alarm will be connected to z Proprietary Supervising Station 40) The method of communication of the F=irel Alarm Control Panel with the Proprietary Supervising Station is by the Fire Alarm Control Panel Alarm Dry Contacts and the Trouble Dry Contacts 40) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the Fire Alarm Control Panel 41) The Fire Alarm System a Fire Alarm System will be provided with i 24 hours Secondary Power 42) The Fire Alarm Control Panel has nine Initiating Circuits 43) The Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "81" or meet Style "A" or Style "D" (Class "A") 44) The maximum smoke Detectors in each Initaitiny Zones can not exceed a draw of 3mA per Initaitng !'_one 45) The Fire Alarm Control Panel his, is Manufacturer Specification, a Capacity of 2.5 amps for the one Notification Circuit 46) The Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2.5 amps 47) The Notification Appliance Circuits for the Fire Alarm Control Panel meet the NFPA Style "Y" (Class "13 ")and Style 7" ( Class "A") 50) The Power Expander Control Panel has four Notification Appliance Circuits 51) The Notification Appliance Circuits for the Power Expander Control Panel meet the NFPA Style "Y" (loose "B ")and Style "z" ( Class "A") 52) The Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the Notification Circuits 53} The Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Circuits and the DC Power Output