09-98-002BATTERY CALCULATIONS FOR
THE FIRE ALARM CONTROL PANEL
THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS
THE EXISTING FIRE ALARM CONTROL PANEL STANDBY CONDITION CURRENT VALUE IS 120mA AND THE ALARM CONDITION CURRENT VALUE IS 700MA
THE NEW POWER EXPANDER CONTROL PANEL STANDBY CURRENT VALUE IS Oma AND THE ALARM TRIIGGER CURRENT IS 15mA ( USING ONE INPUT)
THE EXISTING REMOTE ANNUNCIATOR STANDBY CONDITION CURRENT VALUE IS 6OmA AND THE ALARM CONDITION CURRENT VALUE IS 120 mA
THE EXISTING PULL STATION STANDBY CONDITION CURRENT VALUE IS OmA AND THE ALARM CONDITION CURRENT IS OMA
THE EXISTING SMOKE DETECTOR ( 4 -WIRE) STANDBY CONDITION CURRENT VALUE IS 0.000050 mA AND THE ALARM CONDITION CURRENT IS 35MA
THE NEW SMOKE DETECTOR ( 4 -WIRE) STANDBY CONDITION CURRENT VALUE IS 0.000050 mA AND THE ALARM CONDITION CURRENT IS 35mA
THE END -OF- THE -LINE RELAY STANDBY CONDITION CURRENT VALUE IS 20mA AND THE ALARM CONDITION CURRENT IS 20mA
- THE EXISTING HEAT DETECTOR STANDBY CONDITION CURRENT VALUE IS OmA AND THE ALARM CONDITION CU RRENT IS 0
mA
THE EXISTING HORNISTROBE "TYPE 1 " STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 35 mA
THE EXISTING HORN /STROBE "TYPE 2" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 47 mA
THE EXISTING HORN /STROBE "TYPE 3" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 35 mA
THE EXISTING HORN /STROBE "TYPE 4" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 160 ITA
- THE EXISTING HORNISTROBE "TYPE 5" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 209 mA
THE EXISTING HORN /STROBE "TYPE 6" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 212 mA
:. Standby Current III Total Standb
Description Of Device Quantity per unit Current per Its
A
Amps Amos
Existing Fire Alarm Control Pane[ x 0.200000 - 0.200000
Fxistinn Remnte Annunciator 1 x 0,060000 = 0.060000
Pull Stations
24
x
0.000000
Total System
0.000000
Smoke Detectors 4 -wire
3
x
0,000050
Alarm Current
0.000150
oke Detectors 4 -wire
1
x
0.000050
=
0.000050
End -of -the Line Relay
2
x
0.020000
-
0.040000
Heat Detectors
1
x
0,000000
0.000000
Horn /Strobes "Type 1"
1
x
0.000000
-
0.000000
Horn /Strobes ' a 2"
1
x
0.000000
0.000000
Horn /Strobes "Type 3"
3
x
0.000000
0.000000
Horn /Strobes "TvDe 4"
_
3
x
0.000000
-
0.000000
0.300200
( Amps )
Required Operating Time of Secondary Power Source from N.F.P.A. 72 1 -6.2.5
Standby Condition : 24 hours Alarm Condition : 6 Minutes x 1/60 = 0.0833
y AQuantity, Alarm Current Total Alarm
m per unit Current
Am s Am s 0.235000 0.2iF0 o
0.120000 - 0.120000
0.015000 0.015000
24 x 0.000000 - 0.000000
3 x 0,035000 - 0.105000
1 x 0.035000 - 0,035000
2 x 0.020000 - 0.040000
1 x 0.000000 = 0.000000
1 x 0.035000 - 0.035000
1 x 0.047000 - 0.047000
3 x 0.035000 - 0.105000
3 x 0.160000 0.480000
2 x 0.209000 - 0.418000
2 x .212000 = 0.424000
Total System Alarm Current 2.109000
( Amps )
.�.-- �..r..
Required
�.,', Total SycUm �
� Required
Required
Total System
.. Ras(uhed
Standby Time
Standby Current
Standby Capacity
Alarm Time
Alarm Current
Alarm Capacity
( Hours)
( Amps )
( Amps - Hours)
( Hours )
I Amps)
( Amps -Hours )
24�
x 0.300200
7.2p4G00
0.0233
x 2.109000 -
0.175680
- 0.34
.�.-- �..r..
Required
�.,', Total SycUm �
� Required
Required
Total System
.. Ras(uhed
Standby Time
Standby Current
Standby Capacity
Alarm Time
Alarm Current
Alarm Capacity
( Hours)
( Amps )
( Amps - Hours)
( Hours )
I Amps)
( Amps -Hours )
24�
x 0.300200
7.2p4G00
0.0233
x 2.109000 -
0.175680
_
Required
" ReMuired
Total Required Optional Factor
e:,,,< Required
„� y
tandMy Capacity
Alarm Capacity
Capacity Of Safety
Battery Capacit
( Amps - Hours)
1 ( Amps-Hours )
( Amps Hours)
-' i ( Amps -Hours
7.204 pp
+ 0.17-' 0
7 38048 1 x 1.2
i.i56576
NOTE
1) THE FIRE ALARM CONTROL PANEL NEEDS TWO 12 VOLTS WITH 12 AMPS /HOURS BACKUP BATTERIES
2) THE BACKUP BATTERIES CAN ME INSTALLED INSIDE THE FIRE ALARM CONTROL PANEL OR IN A SEPARATE BACKUP BATTERY HOUSING
BATTERY CALCULATIONS FOR
THE POWER EXPANDER CONTROL PANEL
THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS
THE DC OPERATING CURRENT VALUE HAS BEEN USED BECAUSE THE POWER EXPANDER CONTROL PANEL HAS A FILTERED AND REGULATED
24VDC POWER FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS
THE DIP SWITCHES FOR THE HORN /STROBES ( WALL MOUNT) WILL BE SELECTED ON "HIGH" AND "'TE'MPORAL'"
THE CANDELA SELECTABLE SWITCH FOR THE HORN /STROBES ( WALL MOUNT) WILL BE SET AT "110cd "'
THE DIP SWITCHES FOR THE HORN /STROBES ( CEILING MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL"
THE CANDELA SELECTABLE SWITCH FOR THE HORNISTROBES ( CEILING MOUNT) WILL BE SET AT' "110ce
THE DIP SWITCHES FOR THE HORN /STROBES ( WALL MONUT) WEATHR PROOF WILL BE SELECTED Ohl "HIGH" AND "TEMPORAL"
THE CANDELA SELECTABLE SWITCH FOR THE HORN /STROBES ( WALL MONUT) WEATHER PROOF WILL BE SET AT "110cd"
ET AT "75cd"
-
THE CANDELA SELECTABLE SWITCH FOR THE STROBE: LIGHTS (CEILING MOUNT) WILL BE S
THE CANDELA SELECTABLE SWITCH FOR THE STROBE: LIGHTS ( CEILING MOUNT) WEATHER PROOF WILL BE SET AT "75cd"
Alarm Current
Standby Current Total Standby
Description Of Device Quantity per unit Current par Item + Quantity per unit
(Amps) Am s
Horn /strobes wail mount 110ed �• 1 x 0.000 - 6.000 1 x 0.212
. I
Horn /Strobes (ceiling mount 110Cd 5 x 0.000 = 0.000 5 x 0.212
Horn /Strobes weather roof wall mount 110cd 6 x 0.000 0.000 6 x 0.212
Strobe Lights ( ceiling mount) 75cd 4 x 0.000 0.000 4 x 0.158
S robe Li hts weather roof ceilino 7ount) 75cd 6 x 0.000 - 0.000 G x 0.151
Total System Standby Current Total System Alarm Current
( Amps) 0.00 ( Amps )
Required Operating Time of Secondary Power Source from N.F.P.A. 72 1 -6.2.5
Standby Condition : 24 hours Alarm Condition : 6 Minutes x 1160 = 0,0233
Current
Am s'
0.212
1.0i0
1.272
4.12
Total System ReNuired
Kquired
System
ReNuired
RaMuireal
Alarm Capacity
Capacity Of Safety
dby
Standby Current
Standby Capacity
Alarm Time
Alarm Current
Alarm Capacity
E.nTotal
He., s
(Amps)
( Amps - Hours)
(Hours)
(Amps)
(Amps -Hours )
60 -ten'
0.00
0.0133
x 4.12
- 0.34
..r......r.
Required
Kquired
Total Resiuired Optional Factor
Required
tandby Capacity
Alarm Capacity
Capacity Of Safety
Battery Capacit
( Amps- Hleurs
( Amps-Hours )
( Amps -Heurs }
(( Amps
000 +
0.34
- 0.34 x 1.2
0.41
NOTE
1) THE POWER EXPANDER CONTROL PANEL NEEDS TWO 12 VOLTS WITH 7 AMPS /HOURS BACKUP BATTERIES
2) THE TWO BACKUP BATTERIES CAN BE STORED INSIDE THE POWER EXPANDER CONTROL PANEL
rECHIMICA4. IMAGE PPOMUCTS
CURRENT LOAD CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS FOR
Tul- SIPS= Al LPM %nNTRC)L PANEL
THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS
THE POWER EXPANDER CONTROL PANEL USES A TRIGGER CURRENT OF 2.0 mA D AND REGULATED 24VDC POWER
THE DC OPERATING CURRENT VALUE HAS BEEN USED BECAUSE THE FIRE ALARM CONTROL PANEL HAS A FILTERED
FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS
THE EXISTING HORNISTROBE "TYPE 1" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 35 mA
THE EXISTING HORN /STROBE "TYPE 2" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 47 mA
ALARM CONDITION CURRENT IS 35 mA
-THE EXISTING HORN /STROBE "TYPE 3" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE CURRENT IS 160 mA
THE EXISTING HORNISTROBE "TYPE 4" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION
THE EXISTING HORN /STROBE "TYPE 5" STANDBY CONDITION
2 0 mA
I 0 mA AND
THE ALARM
CONDITION
CURRENT IS 0
VALUE S
CURRENT
- O
THE EXISTING HORN /STROBE "TYPE G" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 212 mA
THE NON- RESETABLE POWER INCLUDES THE FOLLOWING:
THE ONE REMOTE ANNUNCIATOR THE ALARM CONDITION CURRENT IS 120mA
THE RESETABLE POWER INCLUDES THE FOLLOWING:
THE THREE EXISTING 4 -WIRE SMOKE DETECTOR THE ALARM CONDITION CURRENT IS 3imA
THE ONE NEW 4 -WIRE SMOKE DETECTOR THE ALARM CONDITION CURRENT IS 35mA
THE ONE EXISTING END -OF -THE -LINE RELAY THE ALARM CONDITION CURRENT IS 20mA
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 1
Alarm Current zl Total Alarm
Description Of Device Quantity per unit Current
( Amps) (Amps J
+
Power "Expander Control Panel 1 01002 f 0.002
lHorn/Strobe wall mount' 2cd TYPE "1" 1 0.035 Fr;,- 0.035
ti.,
Horn /Strobe (wall mount) TYPE '2" 1 (;a� 0 -047 0.047 r
Horn /Strobe wall mount) 2cd TYPE "3" 3 0.035 0.105
Horn /Strobe wail mount 75cd TYPE "4" 3x'_ 0.160 0.480
Horn/Strobe wall mount 11Ocd TYPE "5" 2 0.209 ';. 0.411
Horn /Strobe wall mount) 110cd TYPE "i "_ . 2 0.212) 0.424
Total System Alarm Current 1.511
(Amps)
CALCULATIONS FOR THE AUXILARY POWER OUTPUT
,t(yi Alarm Current Total Alarm
f
Description Of Device Quantity k p er unit Current t� „x
( Amps) (Amps)
Nonresettable AwdlaryPowcr 1 0.120 0.120
Resettable k xilary Power 1 0.600 0,600
Total System Alarm Current 0.72
( Amps )
TOTAL CURRENT PEK CII2CUiT
NOTIFICATION APPLIANCE CIRCUIT # (Amps)
NOTIFICATION APPLIANCE. CIRCUIT S 1 1.51
AUXILARY OUTPUT CIRCUITS 0.72
TOTAL ALARM CURRENT i 2.23
Am s
NOTES:
1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 2.5 AMPS,
2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 2.5 Amps
CURRENT LOAD CALCULATIONS
PER NO`i IriCATION APPLIANCE CIRCUITS IN
THE POWER EXPANDER CONTROL PANEL
THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS
- THE DC OPERATING CURRENT VALUE HAS KEEN USED BECAUSE THE POWER EXPANDER CONTROL PANEL HAS A FILTERED AND REGULATED
24VDC POWER FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS
- THE DIP SWITCHES FOR THE HORN /STROBES ( WALL MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL"
- THE CANDELA SELECTABLE SWITCH FOR THE HORNISTROBES ( WALL MOUNT) WILL BE SET AT "110cd"
- THE DIP SWITCHES FOR THE HORNISTROBES ( CEILING MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL"
THE CANDELA S ELECTABLE SWITCH FOR THE HORN /STROBES ( CEILING MOUNT) WILL BE SET AT "110ed"
- THE DIP SWITCHES FOR THE HOKNISTROMES ( WALL MONUT) WEATHR PROOF WILL ME SELECTED ON "HIGH" AND "TEMPORAL"
- THE CANDELA SELECTABLE SWITCH FOR THE HORN / STROBES ( WALL MONUT) WEATHER PROOF WILL BE SET AT "110cd"
- THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WILL ME SET AT "75cd"
- THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WEATHER PROOF WILL BE SET AT 75cd"
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT #i 1
Alarm Current m` Total Alarm
Description Of Device Quantity ") per unit �. Current
i ( Amps) tea (Amps)
HorniStrobes ( wall mount) 11000 1r , 0.212 tf 0.212
FlornlSirobes (ceifin� mount ) 11 0C 1 0.212 0 -212
Horn /Strobes weather Proof wail mount 11Ocd 0 0.212 Irv.' 0.000
Strobe Lights ceilin mount 75cd 0 � 0.158 0.000
Strobe Li hts weather Proof ceilin mount 75cd 6 0.15E 0.94E
:y
Total System Alarm Current 11-37
(AMPS)
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT ## 2
Alarm Current g? Total Alarm
Description Of Device Quantity per unit Current
( Amps) (Amps)
Horn /Strobes (wall mount) 110cd 0*r ^212 0.000
Horn /Strobes (ceiling mount 110Cd 4 0 -212 0.848
Horn /Strobes weather proof wall mount 110cd 0 0.212 0.000
Strobe lights ( ceiling mount 75cd _4 N 0.158 ~0.632
Strobe Li his weather proof ceilin mount 75cd 0 0.159 ) 0 -000
Total System Alarm Current 1.49
( Amps )
CALCULATIONS FOR THE NOTIFICATION APPLIANL:t L:IKt;UI I ?F,5
Alarm Current Total Alarm
Description Of Device Quantity '„ per unit '' Current
[ Amps) (Amps)
Horn /Strobes ( wall mount ) 110cd 0 0.212 r� 0.000
HorniStrobes ( ceiling mount 11 Ocd 0 0 212 0.000
Hom / Strobos weather proof ( wall mount) 110cd 6� 0.212 1.272
Strobe Lights ceilin mount 75cd 0 ? 0.153 0.000
Strobe Li hts weather roof (ceilin mount 75cd 0 u 0.153 0.000
- Total System Alarm Current 1.27
(Amps)
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 4
- 3 Alarm Current ( Total Alarm
Description Of Device Quantity ) per unit Current
( Amps) i 1 Amps )
Horn/Strobes ( wall mount) 110cd 0 0.212 0.000
Ilorn /Strobes ceilinQTount 110cd 0 0212 0.000
Horn /Strobes weather Proof wall mount 110cd 0 0212 0.000
Strobe Li hts c ifino mount 75cd 0 s' 0 -158 0.000
Strobe Lights weather proof ceiling mount 75cd 0 0.153 0.000
Total System Alarm Current 0.00
( Amps )
CALCULATIONS FOR THE AUXILARY ROWER OUTPUT
r; Alarm Current Total Alarm
z }f' w .
Description OF Device Quantity per unit Current
( Amps) ( Amps )
Nonresettable AuxllaryPower 0 0.000 0.000
Resettable Auxilary Power
0 prep! 0.000 r 0.000
Total System Ala nn Current 0.00
( Amps 1
TOTAL CURRENT PER CIRCUIT
NOTIFICATION APPLIANCE CIRCUIT R (Amps)
NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37
NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS
NOTIFICATION APPLIANCE CIRCUIT 8 3 127
NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp
AUXILARY POWFR OUTPUT 0.00
TOTAL ALARM CURRENT 4.12
(Amps
NOTES:
1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS.
2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps
VOLTAGE DROP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
THE FIDE ALARM CONTROL PANEL NOTES
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE
NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT
FOR THE FIRE ALARM CONTROL PANEL CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1
,r`.."■^.,.,.. - ...-.
Tootal tal Voltage
i Wire Total I Total g
wiring run gauge line current drop
for the resistance resistance load for the
Notification forthe forthe forthe Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) ( Ohmslfeet) (Ohm) (amps) ( volts )
2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269
Beginning ! Voltage:( Total
voltage �. +i drop 1 voltage
for the t, forthe %?' forthe
Indicating Indicating ng IPM
icatin
g
Appliance Appliance ,y;, Appliance
Circuit Circuit Circuit
( volts) (volts) �t "�� ( volts )
20.40 4 -27 - 16.13
NOTES:
1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
EXISTING NOTIFICATION APPLIANCES
mnnFl TYPF TABLE
DESCRIPTION MANUFACTURER MODEL DISCONTINUED
Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES
Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES
Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES
Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES
Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES
Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO
VOLTAGE DF:OP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
TWP Pt')WFR II=XPANDER CONTROL PANEL
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF
NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS
FOR THE POWER EXPANDER CONTROL PANEL" CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FUR. i nr
Total
- ..,.wTotal
i Wire I Total Total ��h Voltage
wiring run gauge line current drop
forthe resistance resistance .� load ,i"t forthe
rN
Notification for the forthe for the ',�i, Indicating
Appliance 14 gauge Notification Notiticatl•n Appliance
Circuit wire Circuit Circuit,. Circuit
( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts )
12001.1 130 x 0 -00307 0.3991 x 1.37 0.547
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z
Total Wire Total- Total Voltage
wiring run gauge line current --fit drop
forthe resistance resistance ;i load - forthe
Notification forthe for the for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts )
=60 x 0.00307 = 0.7982 x 1.48 = 1.191
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
TOTAL CURRENT PEK CII2CUiT
NOTIFICATION APPLIANCE CIRCUIT # (Amps)
NOTIFICATION APPLIANCE. CIRCUIT S 1 1.51
AUXILARY OUTPUT CIRCUITS 0.72
TOTAL ALARM CURRENT i 2.23
Am s
NOTES:
1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 2.5 AMPS,
2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 2.5 Amps
CURRENT LOAD CALCULATIONS
PER NO`i IriCATION APPLIANCE CIRCUITS IN
THE POWER EXPANDER CONTROL PANEL
THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS
- THE DC OPERATING CURRENT VALUE HAS KEEN USED BECAUSE THE POWER EXPANDER CONTROL PANEL HAS A FILTERED AND REGULATED
24VDC POWER FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS
- THE DIP SWITCHES FOR THE HORN /STROBES ( WALL MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL"
- THE CANDELA SELECTABLE SWITCH FOR THE HORNISTROBES ( WALL MOUNT) WILL BE SET AT "110cd"
- THE DIP SWITCHES FOR THE HORNISTROBES ( CEILING MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL"
THE CANDELA S ELECTABLE SWITCH FOR THE HORN /STROBES ( CEILING MOUNT) WILL BE SET AT "110ed"
- THE DIP SWITCHES FOR THE HOKNISTROMES ( WALL MONUT) WEATHR PROOF WILL ME SELECTED ON "HIGH" AND "TEMPORAL"
- THE CANDELA SELECTABLE SWITCH FOR THE HORN / STROBES ( WALL MONUT) WEATHER PROOF WILL BE SET AT "110cd"
- THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WILL ME SET AT "75cd"
- THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WEATHER PROOF WILL BE SET AT 75cd"
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT #i 1
Alarm Current m` Total Alarm
Description Of Device Quantity ") per unit �. Current
i ( Amps) tea (Amps)
HorniStrobes ( wall mount) 11000 1r , 0.212 tf 0.212
FlornlSirobes (ceifin� mount ) 11 0C 1 0.212 0 -212
Horn /Strobes weather Proof wail mount 11Ocd 0 0.212 Irv.' 0.000
Strobe Lights ceilin mount 75cd 0 � 0.158 0.000
Strobe Li hts weather Proof ceilin mount 75cd 6 0.15E 0.94E
:y
Total System Alarm Current 11-37
(AMPS)
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT ## 2
Alarm Current g? Total Alarm
Description Of Device Quantity per unit Current
( Amps) (Amps)
Horn /Strobes (wall mount) 110cd 0*r ^212 0.000
Horn /Strobes (ceiling mount 110Cd 4 0 -212 0.848
Horn /Strobes weather proof wall mount 110cd 0 0.212 0.000
Strobe lights ( ceiling mount 75cd _4 N 0.158 ~0.632
Strobe Li his weather proof ceilin mount 75cd 0 0.159 ) 0 -000
Total System Alarm Current 1.49
( Amps )
CALCULATIONS FOR THE NOTIFICATION APPLIANL:t L:IKt;UI I ?F,5
Alarm Current Total Alarm
Description Of Device Quantity '„ per unit '' Current
[ Amps) (Amps)
Horn /Strobes ( wall mount ) 110cd 0 0.212 r� 0.000
HorniStrobes ( ceiling mount 11 Ocd 0 0 212 0.000
Hom / Strobos weather proof ( wall mount) 110cd 6� 0.212 1.272
Strobe Lights ceilin mount 75cd 0 ? 0.153 0.000
Strobe Li hts weather roof (ceilin mount 75cd 0 u 0.153 0.000
- Total System Alarm Current 1.27
(Amps)
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 4
- 3 Alarm Current ( Total Alarm
Description Of Device Quantity ) per unit Current
( Amps) i 1 Amps )
Horn/Strobes ( wall mount) 110cd 0 0.212 0.000
Ilorn /Strobes ceilinQTount 110cd 0 0212 0.000
Horn /Strobes weather Proof wall mount 110cd 0 0212 0.000
Strobe Li hts c ifino mount 75cd 0 s' 0 -158 0.000
Strobe Lights weather proof ceiling mount 75cd 0 0.153 0.000
Total System Alarm Current 0.00
( Amps )
CALCULATIONS FOR THE AUXILARY ROWER OUTPUT
r; Alarm Current Total Alarm
z }f' w .
Description OF Device Quantity per unit Current
( Amps) ( Amps )
Nonresettable AuxllaryPower 0 0.000 0.000
Resettable Auxilary Power
0 prep! 0.000 r 0.000
Total System Ala nn Current 0.00
( Amps 1
TOTAL CURRENT PER CIRCUIT
NOTIFICATION APPLIANCE CIRCUIT R (Amps)
NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37
NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS
NOTIFICATION APPLIANCE CIRCUIT 8 3 127
NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp
AUXILARY POWFR OUTPUT 0.00
TOTAL ALARM CURRENT 4.12
(Amps
NOTES:
1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS.
2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps
VOLTAGE DROP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
THE FIDE ALARM CONTROL PANEL NOTES
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE
NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT
FOR THE FIRE ALARM CONTROL PANEL CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1
,r`.."■^.,.,.. - ...-.
Tootal tal Voltage
i Wire Total I Total g
wiring run gauge line current drop
for the resistance resistance load for the
Notification forthe forthe forthe Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) ( Ohmslfeet) (Ohm) (amps) ( volts )
2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269
Beginning ! Voltage:( Total
voltage �. +i drop 1 voltage
for the t, forthe %?' forthe
Indicating Indicating ng IPM
icatin
g
Appliance Appliance ,y;, Appliance
Circuit Circuit Circuit
( volts) (volts) �t "�� ( volts )
20.40 4 -27 - 16.13
NOTES:
1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
EXISTING NOTIFICATION APPLIANCES
mnnFl TYPF TABLE
DESCRIPTION MANUFACTURER MODEL DISCONTINUED
Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES
Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES
Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES
Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES
Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES
Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO
VOLTAGE DF:OP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
TWP Pt')WFR II=XPANDER CONTROL PANEL
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF
NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS
FOR THE POWER EXPANDER CONTROL PANEL" CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FUR. i nr
Total
- ..,.wTotal
i Wire I Total Total ��h Voltage
wiring run gauge line current drop
forthe resistance resistance .� load ,i"t forthe
rN
Notification for the forthe for the ',�i, Indicating
Appliance 14 gauge Notification Notiticatl•n Appliance
Circuit wire Circuit Circuit,. Circuit
( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts )
12001.1 130 x 0 -00307 0.3991 x 1.37 0.547
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z
Total Wire Total- Total Voltage
wiring run gauge line current --fit drop
forthe resistance resistance ;i load - forthe
Notification forthe for the for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts )
=60 x 0.00307 = 0.7982 x 1.48 = 1.191
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
NOTES:
1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 2.5 AMPS,
2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 2.5 Amps
CURRENT LOAD CALCULATIONS
PER NO`i IriCATION APPLIANCE CIRCUITS IN
THE POWER EXPANDER CONTROL PANEL
THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS
- THE DC OPERATING CURRENT VALUE HAS KEEN USED BECAUSE THE POWER EXPANDER CONTROL PANEL HAS A FILTERED AND REGULATED
24VDC POWER FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS
- THE DIP SWITCHES FOR THE HORN /STROBES ( WALL MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL"
- THE CANDELA SELECTABLE SWITCH FOR THE HORNISTROBES ( WALL MOUNT) WILL BE SET AT "110cd"
- THE DIP SWITCHES FOR THE HORNISTROBES ( CEILING MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL"
THE CANDELA S ELECTABLE SWITCH FOR THE HORN /STROBES ( CEILING MOUNT) WILL BE SET AT "110ed"
- THE DIP SWITCHES FOR THE HOKNISTROMES ( WALL MONUT) WEATHR PROOF WILL ME SELECTED ON "HIGH" AND "TEMPORAL"
- THE CANDELA SELECTABLE SWITCH FOR THE HORN / STROBES ( WALL MONUT) WEATHER PROOF WILL BE SET AT "110cd"
- THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WILL ME SET AT "75cd"
- THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WEATHER PROOF WILL BE SET AT 75cd"
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT #i 1
Alarm Current m` Total Alarm
Description Of Device Quantity ") per unit �. Current
i ( Amps) tea (Amps)
HorniStrobes ( wall mount) 11000 1r , 0.212 tf 0.212
FlornlSirobes (ceifin� mount ) 11 0C 1 0.212 0 -212
Horn /Strobes weather Proof wail mount 11Ocd 0 0.212 Irv.' 0.000
Strobe Lights ceilin mount 75cd 0 � 0.158 0.000
Strobe Li hts weather Proof ceilin mount 75cd 6 0.15E 0.94E
:y
Total System Alarm Current 11-37
(AMPS)
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT ## 2
Alarm Current g? Total Alarm
Description Of Device Quantity per unit Current
( Amps) (Amps)
Horn /Strobes (wall mount) 110cd 0*r ^212 0.000
Horn /Strobes (ceiling mount 110Cd 4 0 -212 0.848
Horn /Strobes weather proof wall mount 110cd 0 0.212 0.000
Strobe lights ( ceiling mount 75cd _4 N 0.158 ~0.632
Strobe Li his weather proof ceilin mount 75cd 0 0.159 ) 0 -000
Total System Alarm Current 1.49
( Amps )
CALCULATIONS FOR THE NOTIFICATION APPLIANL:t L:IKt;UI I ?F,5
Alarm Current Total Alarm
Description Of Device Quantity '„ per unit '' Current
[ Amps) (Amps)
Horn /Strobes ( wall mount ) 110cd 0 0.212 r� 0.000
HorniStrobes ( ceiling mount 11 Ocd 0 0 212 0.000
Hom / Strobos weather proof ( wall mount) 110cd 6� 0.212 1.272
Strobe Lights ceilin mount 75cd 0 ? 0.153 0.000
Strobe Li hts weather roof (ceilin mount 75cd 0 u 0.153 0.000
- Total System Alarm Current 1.27
(Amps)
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 4
- 3 Alarm Current ( Total Alarm
Description Of Device Quantity ) per unit Current
( Amps) i 1 Amps )
Horn/Strobes ( wall mount) 110cd 0 0.212 0.000
Ilorn /Strobes ceilinQTount 110cd 0 0212 0.000
Horn /Strobes weather Proof wall mount 110cd 0 0212 0.000
Strobe Li hts c ifino mount 75cd 0 s' 0 -158 0.000
Strobe Lights weather proof ceiling mount 75cd 0 0.153 0.000
Total System Alarm Current 0.00
( Amps )
CALCULATIONS FOR THE AUXILARY ROWER OUTPUT
r; Alarm Current Total Alarm
z }f' w .
Description OF Device Quantity per unit Current
( Amps) ( Amps )
Nonresettable AuxllaryPower 0 0.000 0.000
Resettable Auxilary Power
0 prep! 0.000 r 0.000
Total System Ala nn Current 0.00
( Amps 1
TOTAL CURRENT PER CIRCUIT
NOTIFICATION APPLIANCE CIRCUIT R (Amps)
NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37
NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS
NOTIFICATION APPLIANCE CIRCUIT 8 3 127
NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp
AUXILARY POWFR OUTPUT 0.00
TOTAL ALARM CURRENT 4.12
(Amps
NOTES:
1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS.
2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps
VOLTAGE DROP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
THE FIDE ALARM CONTROL PANEL NOTES
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE
NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT
FOR THE FIRE ALARM CONTROL PANEL CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1
,r`.."■^.,.,.. - ...-.
Tootal tal Voltage
i Wire Total I Total g
wiring run gauge line current drop
for the resistance resistance load for the
Notification forthe forthe forthe Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) ( Ohmslfeet) (Ohm) (amps) ( volts )
2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269
Beginning ! Voltage:( Total
voltage �. +i drop 1 voltage
for the t, forthe %?' forthe
Indicating Indicating ng IPM
icatin
g
Appliance Appliance ,y;, Appliance
Circuit Circuit Circuit
( volts) (volts) �t "�� ( volts )
20.40 4 -27 - 16.13
NOTES:
1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
EXISTING NOTIFICATION APPLIANCES
mnnFl TYPF TABLE
DESCRIPTION MANUFACTURER MODEL DISCONTINUED
Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES
Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES
Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES
Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES
Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES
Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO
VOLTAGE DF:OP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
TWP Pt')WFR II=XPANDER CONTROL PANEL
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF
NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS
FOR THE POWER EXPANDER CONTROL PANEL" CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FUR. i nr
Total
- ..,.wTotal
i Wire I Total Total ��h Voltage
wiring run gauge line current drop
forthe resistance resistance .� load ,i"t forthe
rN
Notification for the forthe for the ',�i, Indicating
Appliance 14 gauge Notification Notiticatl•n Appliance
Circuit wire Circuit Circuit,. Circuit
( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts )
12001.1 130 x 0 -00307 0.3991 x 1.37 0.547
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z
Total Wire Total- Total Voltage
wiring run gauge line current --fit drop
forthe resistance resistance ;i load - forthe
Notification forthe for the for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts )
=60 x 0.00307 = 0.7982 x 1.48 = 1.191
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
CALCULATIONS FOR THE NOTIFICATION APPLIANL:t L:IKt;UI I ?F,5
Alarm Current Total Alarm
Description Of Device Quantity '„ per unit '' Current
[ Amps) (Amps)
Horn /Strobes ( wall mount ) 110cd 0 0.212 r� 0.000
HorniStrobes ( ceiling mount 11 Ocd 0 0 212 0.000
Hom / Strobos weather proof ( wall mount) 110cd 6� 0.212 1.272
Strobe Lights ceilin mount 75cd 0 ? 0.153 0.000
Strobe Li hts weather roof (ceilin mount 75cd 0 u 0.153 0.000
- Total System Alarm Current 1.27
(Amps)
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 4
- 3 Alarm Current ( Total Alarm
Description Of Device Quantity ) per unit Current
( Amps) i 1 Amps )
Horn/Strobes ( wall mount) 110cd 0 0.212 0.000
Ilorn /Strobes ceilinQTount 110cd 0 0212 0.000
Horn /Strobes weather Proof wall mount 110cd 0 0212 0.000
Strobe Li hts c ifino mount 75cd 0 s' 0 -158 0.000
Strobe Lights weather proof ceiling mount 75cd 0 0.153 0.000
Total System Alarm Current 0.00
( Amps )
CALCULATIONS FOR THE AUXILARY ROWER OUTPUT
r; Alarm Current Total Alarm
z }f' w .
Description OF Device Quantity per unit Current
( Amps) ( Amps )
Nonresettable AuxllaryPower 0 0.000 0.000
Resettable Auxilary Power
0 prep! 0.000 r 0.000
Total System Ala nn Current 0.00
( Amps 1
TOTAL CURRENT PER CIRCUIT
NOTIFICATION APPLIANCE CIRCUIT R (Amps)
NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37
NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS
NOTIFICATION APPLIANCE CIRCUIT 8 3 127
NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp
AUXILARY POWFR OUTPUT 0.00
TOTAL ALARM CURRENT 4.12
(Amps
NOTES:
1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS.
2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps
VOLTAGE DROP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
THE FIDE ALARM CONTROL PANEL NOTES
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE
NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT
FOR THE FIRE ALARM CONTROL PANEL CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1
,r`.."■^.,.,.. - ...-.
Tootal tal Voltage
i Wire Total I Total g
wiring run gauge line current drop
for the resistance resistance load for the
Notification forthe forthe forthe Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) ( Ohmslfeet) (Ohm) (amps) ( volts )
2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269
Beginning ! Voltage:( Total
voltage �. +i drop 1 voltage
for the t, forthe %?' forthe
Indicating Indicating ng IPM
icatin
g
Appliance Appliance ,y;, Appliance
Circuit Circuit Circuit
( volts) (volts) �t "�� ( volts )
20.40 4 -27 - 16.13
NOTES:
1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
EXISTING NOTIFICATION APPLIANCES
mnnFl TYPF TABLE
DESCRIPTION MANUFACTURER MODEL DISCONTINUED
Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES
Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES
Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES
Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES
Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES
Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO
VOLTAGE DF:OP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
TWP Pt')WFR II=XPANDER CONTROL PANEL
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF
NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS
FOR THE POWER EXPANDER CONTROL PANEL" CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FUR. i nr
Total
- ..,.wTotal
i Wire I Total Total ��h Voltage
wiring run gauge line current drop
forthe resistance resistance .� load ,i"t forthe
rN
Notification for the forthe for the ',�i, Indicating
Appliance 14 gauge Notification Notiticatl•n Appliance
Circuit wire Circuit Circuit,. Circuit
( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts )
12001.1 130 x 0 -00307 0.3991 x 1.37 0.547
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z
Total Wire Total- Total Voltage
wiring run gauge line current --fit drop
forthe resistance resistance ;i load - forthe
Notification forthe for the for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts )
=60 x 0.00307 = 0.7982 x 1.48 = 1.191
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 4
- 3 Alarm Current ( Total Alarm
Description Of Device Quantity ) per unit Current
( Amps) i 1 Amps )
Horn/Strobes ( wall mount) 110cd 0 0.212 0.000
Ilorn /Strobes ceilinQTount 110cd 0 0212 0.000
Horn /Strobes weather Proof wall mount 110cd 0 0212 0.000
Strobe Li hts c ifino mount 75cd 0 s' 0 -158 0.000
Strobe Lights weather proof ceiling mount 75cd 0 0.153 0.000
Total System Alarm Current 0.00
( Amps )
CALCULATIONS FOR THE AUXILARY ROWER OUTPUT
r; Alarm Current Total Alarm
z }f' w .
Description OF Device Quantity per unit Current
( Amps) ( Amps )
Nonresettable AuxllaryPower 0 0.000 0.000
Resettable Auxilary Power
0 prep! 0.000 r 0.000
Total System Ala nn Current 0.00
( Amps 1
TOTAL CURRENT PER CIRCUIT
NOTIFICATION APPLIANCE CIRCUIT R (Amps)
NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37
NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS
NOTIFICATION APPLIANCE CIRCUIT 8 3 127
NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp
AUXILARY POWFR OUTPUT 0.00
TOTAL ALARM CURRENT 4.12
(Amps
NOTES:
1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS.
2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps
VOLTAGE DROP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
THE FIDE ALARM CONTROL PANEL NOTES
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE
NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT
FOR THE FIRE ALARM CONTROL PANEL CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1
,r`.."■^.,.,.. - ...-.
Tootal tal Voltage
i Wire Total I Total g
wiring run gauge line current drop
for the resistance resistance load for the
Notification forthe forthe forthe Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) ( Ohmslfeet) (Ohm) (amps) ( volts )
2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269
Beginning ! Voltage:( Total
voltage �. +i drop 1 voltage
for the t, forthe %?' forthe
Indicating Indicating ng IPM
icatin
g
Appliance Appliance ,y;, Appliance
Circuit Circuit Circuit
( volts) (volts) �t "�� ( volts )
20.40 4 -27 - 16.13
NOTES:
1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
EXISTING NOTIFICATION APPLIANCES
mnnFl TYPF TABLE
DESCRIPTION MANUFACTURER MODEL DISCONTINUED
Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES
Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES
Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES
Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES
Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES
Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO
VOLTAGE DF:OP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
TWP Pt')WFR II=XPANDER CONTROL PANEL
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF
NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS
FOR THE POWER EXPANDER CONTROL PANEL" CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FUR. i nr
Total
- ..,.wTotal
i Wire I Total Total ��h Voltage
wiring run gauge line current drop
forthe resistance resistance .� load ,i"t forthe
rN
Notification for the forthe for the ',�i, Indicating
Appliance 14 gauge Notification Notiticatl•n Appliance
Circuit wire Circuit Circuit,. Circuit
( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts )
12001.1 130 x 0 -00307 0.3991 x 1.37 0.547
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z
Total Wire Total- Total Voltage
wiring run gauge line current --fit drop
forthe resistance resistance ;i load - forthe
Notification forthe for the for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts )
=60 x 0.00307 = 0.7982 x 1.48 = 1.191
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
TOTAL CURRENT PER CIRCUIT
NOTIFICATION APPLIANCE CIRCUIT R (Amps)
NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37
NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS
NOTIFICATION APPLIANCE CIRCUIT 8 3 127
NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp
AUXILARY POWFR OUTPUT 0.00
TOTAL ALARM CURRENT 4.12
(Amps
NOTES:
1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS.
2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps
VOLTAGE DROP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
THE FIDE ALARM CONTROL PANEL NOTES
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE
NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT
FOR THE FIRE ALARM CONTROL PANEL CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1
,r`.."■^.,.,.. - ...-.
Tootal tal Voltage
i Wire Total I Total g
wiring run gauge line current drop
for the resistance resistance load for the
Notification forthe forthe forthe Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) ( Ohmslfeet) (Ohm) (amps) ( volts )
2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269
Beginning ! Voltage:( Total
voltage �. +i drop 1 voltage
for the t, forthe %?' forthe
Indicating Indicating ng IPM
icatin
g
Appliance Appliance ,y;, Appliance
Circuit Circuit Circuit
( volts) (volts) �t "�� ( volts )
20.40 4 -27 - 16.13
NOTES:
1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
EXISTING NOTIFICATION APPLIANCES
mnnFl TYPF TABLE
DESCRIPTION MANUFACTURER MODEL DISCONTINUED
Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES
Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES
Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES
Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES
Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES
Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO
VOLTAGE DF:OP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
TWP Pt')WFR II=XPANDER CONTROL PANEL
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF
NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS
FOR THE POWER EXPANDER CONTROL PANEL" CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FUR. i nr
Total
- ..,.wTotal
i Wire I Total Total ��h Voltage
wiring run gauge line current drop
forthe resistance resistance .� load ,i"t forthe
rN
Notification for the forthe for the ',�i, Indicating
Appliance 14 gauge Notification Notiticatl•n Appliance
Circuit wire Circuit Circuit,. Circuit
( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts )
12001.1 130 x 0 -00307 0.3991 x 1.37 0.547
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z
Total Wire Total- Total Voltage
wiring run gauge line current --fit drop
forthe resistance resistance ;i load - forthe
Notification forthe for the for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts )
=60 x 0.00307 = 0.7982 x 1.48 = 1.191
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
NOTES:
1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS.
2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps
VOLTAGE DROP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
THE FIDE ALARM CONTROL PANEL NOTES
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE
NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT
FOR THE FIRE ALARM CONTROL PANEL CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1
,r`.."■^.,.,.. - ...-.
Tootal tal Voltage
i Wire Total I Total g
wiring run gauge line current drop
for the resistance resistance load for the
Notification forthe forthe forthe Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) ( Ohmslfeet) (Ohm) (amps) ( volts )
2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269
Beginning ! Voltage:( Total
voltage �. +i drop 1 voltage
for the t, forthe %?' forthe
Indicating Indicating ng IPM
icatin
g
Appliance Appliance ,y;, Appliance
Circuit Circuit Circuit
( volts) (volts) �t "�� ( volts )
20.40 4 -27 - 16.13
NOTES:
1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
EXISTING NOTIFICATION APPLIANCES
mnnFl TYPF TABLE
DESCRIPTION MANUFACTURER MODEL DISCONTINUED
Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES
Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES
Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES
Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES
Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES
Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO
VOLTAGE DF:OP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
TWP Pt')WFR II=XPANDER CONTROL PANEL
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF
NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS
FOR THE POWER EXPANDER CONTROL PANEL" CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FUR. i nr
Total
- ..,.wTotal
i Wire I Total Total ��h Voltage
wiring run gauge line current drop
forthe resistance resistance .� load ,i"t forthe
rN
Notification for the forthe for the ',�i, Indicating
Appliance 14 gauge Notification Notiticatl•n Appliance
Circuit wire Circuit Circuit,. Circuit
( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts )
12001.1 130 x 0 -00307 0.3991 x 1.37 0.547
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z
Total Wire Total- Total Voltage
wiring run gauge line current --fit drop
forthe resistance resistance ;i load - forthe
Notification forthe for the for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts )
=60 x 0.00307 = 0.7982 x 1.48 = 1.191
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
Beginning ! Voltage:( Total
voltage �. +i drop 1 voltage
for the t, forthe %?' forthe
Indicating Indicating ng IPM
icatin
g
Appliance Appliance ,y;, Appliance
Circuit Circuit Circuit
( volts) (volts) �t "�� ( volts )
20.40 4 -27 - 16.13
NOTES:
1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
EXISTING NOTIFICATION APPLIANCES
mnnFl TYPF TABLE
DESCRIPTION MANUFACTURER MODEL DISCONTINUED
Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES
Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES
Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES
Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES
Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES
Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO
VOLTAGE DF:OP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
TWP Pt')WFR II=XPANDER CONTROL PANEL
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF
NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS
FOR THE POWER EXPANDER CONTROL PANEL" CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FUR. i nr
Total
- ..,.wTotal
i Wire I Total Total ��h Voltage
wiring run gauge line current drop
forthe resistance resistance .� load ,i"t forthe
rN
Notification for the forthe for the ',�i, Indicating
Appliance 14 gauge Notification Notiticatl•n Appliance
Circuit wire Circuit Circuit,. Circuit
( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts )
12001.1 130 x 0 -00307 0.3991 x 1.37 0.547
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z
Total Wire Total- Total Voltage
wiring run gauge line current --fit drop
forthe resistance resistance ;i load - forthe
Notification forthe for the for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts )
=60 x 0.00307 = 0.7982 x 1.48 = 1.191
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
NOTES:
1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
EXISTING NOTIFICATION APPLIANCES
mnnFl TYPF TABLE
DESCRIPTION MANUFACTURER MODEL DISCONTINUED
Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES
Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES
Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES
Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES
Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES
Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO
VOLTAGE DF:OP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
TWP Pt')WFR II=XPANDER CONTROL PANEL
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF
NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS
FOR THE POWER EXPANDER CONTROL PANEL" CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FUR. i nr
Total
- ..,.wTotal
i Wire I Total Total ��h Voltage
wiring run gauge line current drop
forthe resistance resistance .� load ,i"t forthe
rN
Notification for the forthe for the ',�i, Indicating
Appliance 14 gauge Notification Notiticatl•n Appliance
Circuit wire Circuit Circuit,. Circuit
( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts )
12001.1 130 x 0 -00307 0.3991 x 1.37 0.547
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z
Total Wire Total- Total Voltage
wiring run gauge line current --fit drop
forthe resistance resistance ;i load - forthe
Notification forthe for the for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts )
=60 x 0.00307 = 0.7982 x 1.48 = 1.191
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
VOLTAGE DF:OP CALCULATIONS
PER NOTIFICATION APPLIANCE CIRCUITS IN
TWP Pt')WFR II=XPANDER CONTROL PANEL
- THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN
- THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT
- THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF
NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS
FOR THE POWER EXPANDER CONTROL PANEL" CHART
- THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS
CALCULATIONS FUR. i nr
Total
- ..,.wTotal
i Wire I Total Total ��h Voltage
wiring run gauge line current drop
forthe resistance resistance .� load ,i"t forthe
rN
Notification for the forthe for the ',�i, Indicating
Appliance 14 gauge Notification Notiticatl•n Appliance
Circuit wire Circuit Circuit,. Circuit
( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts )
12001.1 130 x 0 -00307 0.3991 x 1.37 0.547
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z
Total Wire Total- Total Voltage
wiring run gauge line current --fit drop
forthe resistance resistance ;i load - forthe
Notification forthe for the for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts )
=60 x 0.00307 = 0.7982 x 1.48 = 1.191
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z
Total Wire Total- Total Voltage
wiring run gauge line current --fit drop
forthe resistance resistance ;i load - forthe
Notification forthe for the for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts )
=60 x 0.00307 = 0.7982 x 1.48 = 1.191
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3
- vrrrew�.
Total -_ - - -- Wire Total Total Voltage
wiring run gauge line current drop
forthe resistance resistance � load j for the
Notification forthe for the forthe ! Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit Circuit
( feet I (OhmsReet) ( Ohm) ( amps) ( volts )
2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
Beginning r�I Voltage ;.i Total
voltage tya drop I voltage
forthe forthe ? forthe
Indicating Indicating Indicating
W
�I
Appliance r y Appliance ;; Appliance
CircuitCircuit ''u Circuit
( volts) .�- (volts) (volts )
20.40 0.55 T 19.95
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
Beginning :F1 Voltage Total
voltage drop voltage
forthe forthe forthe
Indicating i Indicating Indicating
r! _
Appliance Appli ance App liance
Circuit Circuit Circuit
( volts) ( volts) '0'i ( volts )
20.40 1.18
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
Beginning" -,t Voltage '' Total
voltage drop voltage
forthe '�;, forthe _. forthe
Indicating Indicating R. Indicating
Appliance Appliance y�te Appliance
Circuit Circuit Circuit
( volts),` ( vdts)I ( volts )
,.a
20.40 0.62
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S
Total Wire Total Total Voltage
wiring run gauge line j current drop
forthe resistance resistance lead forthe
Notification forthe forthe i for the Indicating
Appliance 14 gauge Notification Notification Appliance
Circuit wire Circuit Circuit circuit
( feet) (Ohmsffeet) ( Ohm) ( amps) (volts )
x 0 x 0.00307 - 0- 0.000
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
Beginning Voltage 3 Total
voltage tr` drop voltage
for the for the - for the
Indicating ,r. Indicating" Indicating
S..
Appliance Appliance Appliance
Circuit r Circuit Circuit
( volts ) ? Uli ( volts) (volts )
20.40 0.00
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v
NOTES:
1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS
2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT
3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS
ENGINEER'S INFORMATION:
1) All conduit to be 112" EMT or larger
2) All flexible conduit to be 1/2" EMT or larger
3) All wires for the Initiating Circuit will be THWN wire, 14" gauge
4) All wires for the Notification Circuit will be THWN wire, 14" gauge
5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and
ordinances
6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor,
one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker
at 120vac with a breaker lock
7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase
i conductor supplied b a 20 am single pole dedicated branch
conductor, one neutral conductor and one grounding ) pp Y P
circuit breaker at 120vac with a breaker lock
8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there
9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72
10) The existing Fire Alarm Control Panel is Power Limited
11) The new Power Expander Control Panel is Power Limited
12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to
exceed 17 AH )
13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not
to exceed 19 AH )
14) Pull Stations are installed as per the Manufacturers Specifications
15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition
16) Pull Stations are to be installed at 48" A.F.F.
17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor
it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises
1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition
20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling
21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents
22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications
23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas
24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas
25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the
Manufacturers Specifications
26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower)
27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above
29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels
29) All Strobe Lights are adequate for the area that are covering
30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor
31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor
32) The acoustic ceiling heights inside the Gym Area is 8' from the floor
33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor
34) The roiling file selves height are about 6 feet
35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any
Notification Appliances
36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System
37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72
39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal
conditions have a W.P. label next to it
39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied
room and will be protected by a Smoke Detector
40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather
proof housing )
41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station
42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the
main Fire Alarm System of the hospital
43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel
44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power
45) The existing Fire Alarm Control Panel has nine Initiating Circuits
46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or
style "D" ( Class "A" )
47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone
49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification
Circuit
49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit
and other DC Power Outputs cannot exceed 2 -5 amps
150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and
Style "Z" ( Class "A" )
51) The new Power Expander Control Panel has four Notification Appliance Circuits
52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and
Style "Z" ( Class "A" )
53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four
Notification Appliances Circuits
54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification
Appliances Circuits and the DC Power Output cannot exceed 6.0 amps
r Elevator Recall
r not Capable fo E
The existing elevators are 55 P
9
BURGLAR ALARM SERVICES
5650 SHERIDAN STREET
HOLLYWOOD, FLORIDA 33021 -3250
PHONE: (945) 963 -3366
FAX: (954) 981 -4302
STATE LICENSE: EF000022R
COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION:
NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS
ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET
COOPER CITY, FLORIDA 33330. '
KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021
LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228
I
t
SIG , -;TURE `SIGNATURE
SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R
6200 S.W. 73 STREET
SOUTH MIAMI, FLORIDA 33143
1 r ,•n Approved by: C(r2wn by:: J,Y2. .�
12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -��
BURGLAR ALARM SERVICES
-f HOLLYWOOD,
.�..... LRIDA ;'13021
5650 SHERIDAN STREET ()
RAWING NUMBER
2014
v