09-98-002BATTERY CALCULATIONS FOR THE FIRE ALARM CONTROL PANEL THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS THE EXISTING FIRE ALARM CONTROL PANEL STANDBY CONDITION CURRENT VALUE IS 120mA AND THE ALARM CONDITION CURRENT VALUE IS 700MA THE NEW POWER EXPANDER CONTROL PANEL STANDBY CURRENT VALUE IS Oma AND THE ALARM TRIIGGER CURRENT IS 15mA ( USING ONE INPUT) THE EXISTING REMOTE ANNUNCIATOR STANDBY CONDITION CURRENT VALUE IS 6OmA AND THE ALARM CONDITION CURRENT VALUE IS 120 mA THE EXISTING PULL STATION STANDBY CONDITION CURRENT VALUE IS OmA AND THE ALARM CONDITION CURRENT IS OMA THE EXISTING SMOKE DETECTOR ( 4 -WIRE) STANDBY CONDITION CURRENT VALUE IS 0.000050 mA AND THE ALARM CONDITION CURRENT IS 35MA THE NEW SMOKE DETECTOR ( 4 -WIRE) STANDBY CONDITION CURRENT VALUE IS 0.000050 mA AND THE ALARM CONDITION CURRENT IS 35mA THE END -OF- THE -LINE RELAY STANDBY CONDITION CURRENT VALUE IS 20mA AND THE ALARM CONDITION CURRENT IS 20mA - THE EXISTING HEAT DETECTOR STANDBY CONDITION CURRENT VALUE IS OmA AND THE ALARM CONDITION CU RRENT IS 0 mA THE EXISTING HORNISTROBE "TYPE 1 " STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 35 mA THE EXISTING HORN /STROBE "TYPE 2" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 47 mA THE EXISTING HORN /STROBE "TYPE 3" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 35 mA THE EXISTING HORN /STROBE "TYPE 4" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 160 ITA - THE EXISTING HORNISTROBE "TYPE 5" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 209 mA THE EXISTING HORN /STROBE "TYPE 6" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 212 mA :. Standby Current III Total Standb Description Of Device Quantity per unit Current per Its A Amps Amos Existing Fire Alarm Control Pane[ x 0.200000 - 0.200000 Fxistinn Remnte Annunciator 1 x 0,060000 = 0.060000 Pull Stations 24 x 0.000000 Total System 0.000000 Smoke Detectors 4 -wire 3 x 0,000050 Alarm Current 0.000150 oke Detectors 4 -wire 1 x 0.000050 = 0.000050 End -of -the Line Relay 2 x 0.020000 - 0.040000 Heat Detectors 1 x 0,000000 0.000000 Horn /Strobes "Type 1" 1 x 0.000000 - 0.000000 Horn /Strobes ' a 2" 1 x 0.000000 0.000000 Horn /Strobes "Type 3" 3 x 0.000000 0.000000 Horn /Strobes "TvDe 4" _ 3 x 0.000000 - 0.000000 0.300200 ( Amps ) Required Operating Time of Secondary Power Source from N.F.P.A. 72 1 -6.2.5 Standby Condition : 24 hours Alarm Condition : 6 Minutes x 1/60 = 0.0833 y AQuantity, Alarm Current Total Alarm m per unit Current Am s Am s 0.235000 0.2iF0 o 0.120000 - 0.120000 0.015000 0.015000 24 x 0.000000 - 0.000000 3 x 0,035000 - 0.105000 1 x 0.035000 - 0,035000 2 x 0.020000 - 0.040000 1 x 0.000000 = 0.000000 1 x 0.035000 - 0.035000 1 x 0.047000 - 0.047000 3 x 0.035000 - 0.105000 3 x 0.160000 0.480000 2 x 0.209000 - 0.418000 2 x .212000 = 0.424000 Total System Alarm Current 2.109000 ( Amps ) .�.-- �..r.. Required �.,', Total SycUm � � Required Required Total System .. Ras(uhed Standby Time Standby Current Standby Capacity Alarm Time Alarm Current Alarm Capacity ( Hours) ( Amps ) ( Amps - Hours) ( Hours ) I Amps) ( Amps -Hours ) 24� x 0.300200 7.2p4G00 0.0233 x 2.109000 - 0.175680 - 0.34 .�.-- �..r.. Required �.,', Total SycUm � � Required Required Total System .. Ras(uhed Standby Time Standby Current Standby Capacity Alarm Time Alarm Current Alarm Capacity ( Hours) ( Amps ) ( Amps - Hours) ( Hours ) I Amps) ( Amps -Hours ) 24� x 0.300200 7.2p4G00 0.0233 x 2.109000 - 0.175680 _ Required " ReMuired Total Required Optional Factor e:,,,< Required „� y tandMy Capacity Alarm Capacity Capacity Of Safety Battery Capacit ( Amps - Hours) 1 ( Amps-Hours ) ( Amps Hours) -' i ( Amps -Hours 7.204 pp + 0.17-' 0 7 38048 1 x 1.2 i.i56576 NOTE 1) THE FIRE ALARM CONTROL PANEL NEEDS TWO 12 VOLTS WITH 12 AMPS /HOURS BACKUP BATTERIES 2) THE BACKUP BATTERIES CAN ME INSTALLED INSIDE THE FIRE ALARM CONTROL PANEL OR IN A SEPARATE BACKUP BATTERY HOUSING BATTERY CALCULATIONS FOR THE POWER EXPANDER CONTROL PANEL THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS THE DC OPERATING CURRENT VALUE HAS BEEN USED BECAUSE THE POWER EXPANDER CONTROL PANEL HAS A FILTERED AND REGULATED 24VDC POWER FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS THE DIP SWITCHES FOR THE HORN /STROBES ( WALL MOUNT) WILL BE SELECTED ON "HIGH" AND "'TE'MPORAL'" THE CANDELA SELECTABLE SWITCH FOR THE HORN /STROBES ( WALL MOUNT) WILL BE SET AT "110cd "' THE DIP SWITCHES FOR THE HORN /STROBES ( CEILING MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL" THE CANDELA SELECTABLE SWITCH FOR THE HORNISTROBES ( CEILING MOUNT) WILL BE SET AT' "110ce THE DIP SWITCHES FOR THE HORN /STROBES ( WALL MONUT) WEATHR PROOF WILL BE SELECTED Ohl "HIGH" AND "TEMPORAL" THE CANDELA SELECTABLE SWITCH FOR THE HORN /STROBES ( WALL MONUT) WEATHER PROOF WILL BE SET AT "110cd" ET AT "75cd" - THE CANDELA SELECTABLE SWITCH FOR THE STROBE: LIGHTS (CEILING MOUNT) WILL BE S THE CANDELA SELECTABLE SWITCH FOR THE STROBE: LIGHTS ( CEILING MOUNT) WEATHER PROOF WILL BE SET AT "75cd" Alarm Current Standby Current Total Standby Description Of Device Quantity per unit Current par Item + Quantity per unit (Amps) Am s Horn /strobes wail mount 110ed �• 1 x 0.000 - 6.000 1 x 0.212 . I Horn /Strobes (ceiling mount 110Cd 5 x 0.000 = 0.000 5 x 0.212 Horn /Strobes weather roof wall mount 110cd 6 x 0.000 0.000 6 x 0.212 Strobe Lights ( ceiling mount) 75cd 4 x 0.000 0.000 4 x 0.158 S robe Li hts weather roof ceilino 7ount) 75cd 6 x 0.000 - 0.000 G x 0.151 Total System Standby Current Total System Alarm Current ( Amps) 0.00 ( Amps ) Required Operating Time of Secondary Power Source from N.F.P.A. 72 1 -6.2.5 Standby Condition : 24 hours Alarm Condition : 6 Minutes x 1160 = 0,0233 Current Am s' 0.212 1.0i0 1.272 4.12 Total System ReNuired Kquired System ReNuired RaMuireal Alarm Capacity Capacity Of Safety dby Standby Current Standby Capacity Alarm Time Alarm Current Alarm Capacity E.nTotal He., s (Amps) ( Amps - Hours) (Hours) (Amps) (Amps -Hours ) 60 -ten' 0.00 0.0133 x 4.12 - 0.34 ..r......r. Required Kquired Total Resiuired Optional Factor Required tandby Capacity Alarm Capacity Capacity Of Safety Battery Capacit ( Amps- Hleurs ( Amps-Hours ) ( Amps -Heurs } (( Amps 000 + 0.34 - 0.34 x 1.2 0.41 NOTE 1) THE POWER EXPANDER CONTROL PANEL NEEDS TWO 12 VOLTS WITH 7 AMPS /HOURS BACKUP BATTERIES 2) THE TWO BACKUP BATTERIES CAN BE STORED INSIDE THE POWER EXPANDER CONTROL PANEL rECHIMICA4. IMAGE PPOMUCTS CURRENT LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR Tul- SIPS= Al LPM %nNTRC)L PANEL THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS THE POWER EXPANDER CONTROL PANEL USES A TRIGGER CURRENT OF 2.0 mA D AND REGULATED 24VDC POWER THE DC OPERATING CURRENT VALUE HAS BEEN USED BECAUSE THE FIRE ALARM CONTROL PANEL HAS A FILTERED FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS THE EXISTING HORNISTROBE "TYPE 1" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 35 mA THE EXISTING HORN /STROBE "TYPE 2" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 47 mA ALARM CONDITION CURRENT IS 35 mA -THE EXISTING HORN /STROBE "TYPE 3" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE CURRENT IS 160 mA THE EXISTING HORNISTROBE "TYPE 4" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION THE EXISTING HORN /STROBE "TYPE 5" STANDBY CONDITION 2 0 mA I 0 mA AND THE ALARM CONDITION CURRENT IS 0 VALUE S CURRENT - O THE EXISTING HORN /STROBE "TYPE G" STANDBY CONDITION CURRENT VALUE IS 0 mA AND THE ALARM CONDITION CURRENT IS 212 mA THE NON- RESETABLE POWER INCLUDES THE FOLLOWING: THE ONE REMOTE ANNUNCIATOR THE ALARM CONDITION CURRENT IS 120mA THE RESETABLE POWER INCLUDES THE FOLLOWING: THE THREE EXISTING 4 -WIRE SMOKE DETECTOR THE ALARM CONDITION CURRENT IS 3imA THE ONE NEW 4 -WIRE SMOKE DETECTOR THE ALARM CONDITION CURRENT IS 35mA THE ONE EXISTING END -OF -THE -LINE RELAY THE ALARM CONDITION CURRENT IS 20mA CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 1 Alarm Current zl Total Alarm Description Of Device Quantity per unit Current ( Amps) (Amps J + Power "Expander Control Panel 1 01002 f 0.002 lHorn/Strobe wall mount' 2cd TYPE "1" 1 0.035 Fr;,- 0.035 ti., Horn /Strobe (wall mount) TYPE '2" 1 (;a� 0 -047 0.047 r Horn /Strobe wall mount) 2cd TYPE "3" 3 0.035 0.105 Horn /Strobe wail mount 75cd TYPE "4" 3x'_ 0.160 0.480 Horn/Strobe wall mount 11Ocd TYPE "5" 2 0.209 ';. 0.411 Horn /Strobe wall mount) 110cd TYPE "i "_ . 2 0.212) 0.424 Total System Alarm Current 1.511 (Amps) CALCULATIONS FOR THE AUXILARY POWER OUTPUT ,t(yi Alarm Current Total Alarm f Description Of Device Quantity k p er unit Current t� „x ( Amps) (Amps) Nonresettable AwdlaryPowcr 1 0.120 0.120 Resettable k xilary Power 1 0.600 0,600 Total System Alarm Current 0.72 ( Amps ) TOTAL CURRENT PEK CII2CUiT NOTIFICATION APPLIANCE CIRCUIT # (Amps) NOTIFICATION APPLIANCE. CIRCUIT S 1 1.51 AUXILARY OUTPUT CIRCUITS 0.72 TOTAL ALARM CURRENT i 2.23 Am s NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 2.5 AMPS, 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 2.5 Amps CURRENT LOAD CALCULATIONS PER NO`i IriCATION APPLIANCE CIRCUITS IN THE POWER EXPANDER CONTROL PANEL THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS - THE DC OPERATING CURRENT VALUE HAS KEEN USED BECAUSE THE POWER EXPANDER CONTROL PANEL HAS A FILTERED AND REGULATED 24VDC POWER FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS - THE DIP SWITCHES FOR THE HORN /STROBES ( WALL MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL" - THE CANDELA SELECTABLE SWITCH FOR THE HORNISTROBES ( WALL MOUNT) WILL BE SET AT "110cd" - THE DIP SWITCHES FOR THE HORNISTROBES ( CEILING MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL" THE CANDELA S ELECTABLE SWITCH FOR THE HORN /STROBES ( CEILING MOUNT) WILL BE SET AT "110ed" - THE DIP SWITCHES FOR THE HOKNISTROMES ( WALL MONUT) WEATHR PROOF WILL ME SELECTED ON "HIGH" AND "TEMPORAL" - THE CANDELA SELECTABLE SWITCH FOR THE HORN / STROBES ( WALL MONUT) WEATHER PROOF WILL BE SET AT "110cd" - THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WILL ME SET AT "75cd" - THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WEATHER PROOF WILL BE SET AT 75cd" CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT #i 1 Alarm Current m` Total Alarm Description Of Device Quantity ") per unit �. Current i ( Amps) tea (Amps) HorniStrobes ( wall mount) 11000 1r , 0.212 tf 0.212 FlornlSirobes (ceifin� mount ) 11 0C 1 0.212 0 -212 Horn /Strobes weather Proof wail mount 11Ocd 0 0.212 Irv.' 0.000 Strobe Lights ceilin mount 75cd 0 � 0.158 0.000 Strobe Li hts weather Proof ceilin mount 75cd 6 0.15E 0.94E :y Total System Alarm Current 11-37 (AMPS) CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT ## 2 Alarm Current g? Total Alarm Description Of Device Quantity per unit Current ( Amps) (Amps) Horn /Strobes (wall mount) 110cd 0*r ^212 0.000 Horn /Strobes (ceiling mount 110Cd 4 0 -212 0.848 Horn /Strobes weather proof wall mount 110cd 0 0.212 0.000 Strobe lights ( ceiling mount 75cd _4 N 0.158 ~0.632 Strobe Li his weather proof ceilin mount 75cd 0 0.159 ) 0 -000 Total System Alarm Current 1.49 ( Amps ) CALCULATIONS FOR THE NOTIFICATION APPLIANL:t L:IKt;UI I ?F,5 Alarm Current Total Alarm Description Of Device Quantity '„ per unit '' Current [ Amps) (Amps) Horn /Strobes ( wall mount ) 110cd 0 0.212 r� 0.000 HorniStrobes ( ceiling mount 11 Ocd 0 0 212 0.000 Hom / Strobos weather proof ( wall mount) 110cd 6� 0.212 1.272 Strobe Lights ceilin mount 75cd 0 ? 0.153 0.000 Strobe Li hts weather roof (ceilin mount 75cd 0 u 0.153 0.000 - Total System Alarm Current 1.27 (Amps) CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 4 - 3 Alarm Current ( Total Alarm Description Of Device Quantity ) per unit Current ( Amps) i 1 Amps ) Horn/Strobes ( wall mount) 110cd 0 0.212 0.000 Ilorn /Strobes ceilinQTount 110cd 0 0212 0.000 Horn /Strobes weather Proof wall mount 110cd 0 0212 0.000 Strobe Li hts c ifino mount 75cd 0 s' 0 -158 0.000 Strobe Lights weather proof ceiling mount 75cd 0 0.153 0.000 Total System Alarm Current 0.00 ( Amps ) CALCULATIONS FOR THE AUXILARY ROWER OUTPUT r; Alarm Current Total Alarm z }f' w . Description OF Device Quantity per unit Current ( Amps) ( Amps ) Nonresettable AuxllaryPower 0 0.000 0.000 Resettable Auxilary Power 0 prep! 0.000 r 0.000 Total System Ala nn Current 0.00 ( Amps 1 TOTAL CURRENT PER CIRCUIT NOTIFICATION APPLIANCE CIRCUIT R (Amps) NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37 NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS NOTIFICATION APPLIANCE CIRCUIT 8 3 127 NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp AUXILARY POWFR OUTPUT 0.00 TOTAL ALARM CURRENT 4.12 (Amps NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS. 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps VOLTAGE DROP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN THE FIDE ALARM CONTROL PANEL NOTES - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT FOR THE FIRE ALARM CONTROL PANEL CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1 ,r`.."■^.,.,.. - ...-. Tootal tal Voltage i Wire Total I Total g wiring run gauge line current drop for the resistance resistance load for the Notification forthe forthe forthe Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) ( Ohmslfeet) (Ohm) (amps) ( volts ) 2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269 Beginning ! Voltage:( Total voltage �. +i drop 1 voltage for the t, forthe %?' forthe Indicating Indicating ng IPM icatin g Appliance Appliance ,y;, Appliance Circuit Circuit Circuit ( volts) (volts) �t "�� ( volts ) 20.40 4 -27 - 16.13 NOTES: 1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS EXISTING NOTIFICATION APPLIANCES mnnFl TYPF TABLE DESCRIPTION MANUFACTURER MODEL DISCONTINUED Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO VOLTAGE DF:OP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN TWP Pt')WFR II=XPANDER CONTROL PANEL - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR THE POWER EXPANDER CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FUR. i nr Total - ..,.wTotal i Wire I Total Total ��h Voltage wiring run gauge line current drop forthe resistance resistance .� load ,i"t forthe rN Notification for the forthe for the ',�i, Indicating Appliance 14 gauge Notification Notiticatl•n Appliance Circuit wire Circuit Circuit,. Circuit ( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts ) 12001.1 130 x 0 -00307 0.3991 x 1.37 0.547 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z Total Wire Total- Total Voltage wiring run gauge line current --fit drop forthe resistance resistance ;i load - forthe Notification forthe for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts ) =60 x 0.00307 = 0.7982 x 1.48 = 1.191 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v TOTAL CURRENT PEK CII2CUiT NOTIFICATION APPLIANCE CIRCUIT # (Amps) NOTIFICATION APPLIANCE. CIRCUIT S 1 1.51 AUXILARY OUTPUT CIRCUITS 0.72 TOTAL ALARM CURRENT i 2.23 Am s NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 2.5 AMPS, 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 2.5 Amps CURRENT LOAD CALCULATIONS PER NO`i IriCATION APPLIANCE CIRCUITS IN THE POWER EXPANDER CONTROL PANEL THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS - THE DC OPERATING CURRENT VALUE HAS KEEN USED BECAUSE THE POWER EXPANDER CONTROL PANEL HAS A FILTERED AND REGULATED 24VDC POWER FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS - THE DIP SWITCHES FOR THE HORN /STROBES ( WALL MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL" - THE CANDELA SELECTABLE SWITCH FOR THE HORNISTROBES ( WALL MOUNT) WILL BE SET AT "110cd" - THE DIP SWITCHES FOR THE HORNISTROBES ( CEILING MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL" THE CANDELA S ELECTABLE SWITCH FOR THE HORN /STROBES ( CEILING MOUNT) WILL BE SET AT "110ed" - THE DIP SWITCHES FOR THE HOKNISTROMES ( WALL MONUT) WEATHR PROOF WILL ME SELECTED ON "HIGH" AND "TEMPORAL" - THE CANDELA SELECTABLE SWITCH FOR THE HORN / STROBES ( WALL MONUT) WEATHER PROOF WILL BE SET AT "110cd" - THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WILL ME SET AT "75cd" - THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WEATHER PROOF WILL BE SET AT 75cd" CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT #i 1 Alarm Current m` Total Alarm Description Of Device Quantity ") per unit �. Current i ( Amps) tea (Amps) HorniStrobes ( wall mount) 11000 1r , 0.212 tf 0.212 FlornlSirobes (ceifin� mount ) 11 0C 1 0.212 0 -212 Horn /Strobes weather Proof wail mount 11Ocd 0 0.212 Irv.' 0.000 Strobe Lights ceilin mount 75cd 0 � 0.158 0.000 Strobe Li hts weather Proof ceilin mount 75cd 6 0.15E 0.94E :y Total System Alarm Current 11-37 (AMPS) CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT ## 2 Alarm Current g? Total Alarm Description Of Device Quantity per unit Current ( Amps) (Amps) Horn /Strobes (wall mount) 110cd 0*r ^212 0.000 Horn /Strobes (ceiling mount 110Cd 4 0 -212 0.848 Horn /Strobes weather proof wall mount 110cd 0 0.212 0.000 Strobe lights ( ceiling mount 75cd _4 N 0.158 ~0.632 Strobe Li his weather proof ceilin mount 75cd 0 0.159 ) 0 -000 Total System Alarm Current 1.49 ( Amps ) CALCULATIONS FOR THE NOTIFICATION APPLIANL:t L:IKt;UI I ?F,5 Alarm Current Total Alarm Description Of Device Quantity '„ per unit '' Current [ Amps) (Amps) Horn /Strobes ( wall mount ) 110cd 0 0.212 r� 0.000 HorniStrobes ( ceiling mount 11 Ocd 0 0 212 0.000 Hom / Strobos weather proof ( wall mount) 110cd 6� 0.212 1.272 Strobe Lights ceilin mount 75cd 0 ? 0.153 0.000 Strobe Li hts weather roof (ceilin mount 75cd 0 u 0.153 0.000 - Total System Alarm Current 1.27 (Amps) CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 4 - 3 Alarm Current ( Total Alarm Description Of Device Quantity ) per unit Current ( Amps) i 1 Amps ) Horn/Strobes ( wall mount) 110cd 0 0.212 0.000 Ilorn /Strobes ceilinQTount 110cd 0 0212 0.000 Horn /Strobes weather Proof wall mount 110cd 0 0212 0.000 Strobe Li hts c ifino mount 75cd 0 s' 0 -158 0.000 Strobe Lights weather proof ceiling mount 75cd 0 0.153 0.000 Total System Alarm Current 0.00 ( Amps ) CALCULATIONS FOR THE AUXILARY ROWER OUTPUT r; Alarm Current Total Alarm z }f' w . Description OF Device Quantity per unit Current ( Amps) ( Amps ) Nonresettable AuxllaryPower 0 0.000 0.000 Resettable Auxilary Power 0 prep! 0.000 r 0.000 Total System Ala nn Current 0.00 ( Amps 1 TOTAL CURRENT PER CIRCUIT NOTIFICATION APPLIANCE CIRCUIT R (Amps) NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37 NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS NOTIFICATION APPLIANCE CIRCUIT 8 3 127 NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp AUXILARY POWFR OUTPUT 0.00 TOTAL ALARM CURRENT 4.12 (Amps NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS. 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps VOLTAGE DROP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN THE FIDE ALARM CONTROL PANEL NOTES - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT FOR THE FIRE ALARM CONTROL PANEL CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1 ,r`.."■^.,.,.. - ...-. Tootal tal Voltage i Wire Total I Total g wiring run gauge line current drop for the resistance resistance load for the Notification forthe forthe forthe Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) ( Ohmslfeet) (Ohm) (amps) ( volts ) 2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269 Beginning ! Voltage:( Total voltage �. +i drop 1 voltage for the t, forthe %?' forthe Indicating Indicating ng IPM icatin g Appliance Appliance ,y;, Appliance Circuit Circuit Circuit ( volts) (volts) �t "�� ( volts ) 20.40 4 -27 - 16.13 NOTES: 1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS EXISTING NOTIFICATION APPLIANCES mnnFl TYPF TABLE DESCRIPTION MANUFACTURER MODEL DISCONTINUED Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO VOLTAGE DF:OP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN TWP Pt')WFR II=XPANDER CONTROL PANEL - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR THE POWER EXPANDER CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FUR. i nr Total - ..,.wTotal i Wire I Total Total ��h Voltage wiring run gauge line current drop forthe resistance resistance .� load ,i"t forthe rN Notification for the forthe for the ',�i, Indicating Appliance 14 gauge Notification Notiticatl•n Appliance Circuit wire Circuit Circuit,. Circuit ( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts ) 12001.1 130 x 0 -00307 0.3991 x 1.37 0.547 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z Total Wire Total- Total Voltage wiring run gauge line current --fit drop forthe resistance resistance ;i load - forthe Notification forthe for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts ) =60 x 0.00307 = 0.7982 x 1.48 = 1.191 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 2.5 AMPS, 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 2.5 Amps CURRENT LOAD CALCULATIONS PER NO`i IriCATION APPLIANCE CIRCUITS IN THE POWER EXPANDER CONTROL PANEL THE INFORMATION IS OBTAIN FROM THE DATA SHEETS ATTACHED TO THE PLANS - THE DC OPERATING CURRENT VALUE HAS KEEN USED BECAUSE THE POWER EXPANDER CONTROL PANEL HAS A FILTERED AND REGULATED 24VDC POWER FOR THE FOUR NOTIFICATION APPLIANCE CIRCUITS - THE DIP SWITCHES FOR THE HORN /STROBES ( WALL MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL" - THE CANDELA SELECTABLE SWITCH FOR THE HORNISTROBES ( WALL MOUNT) WILL BE SET AT "110cd" - THE DIP SWITCHES FOR THE HORNISTROBES ( CEILING MOUNT) WILL BE SELECTED ON "HIGH" AND "TEMPORAL" THE CANDELA S ELECTABLE SWITCH FOR THE HORN /STROBES ( CEILING MOUNT) WILL BE SET AT "110ed" - THE DIP SWITCHES FOR THE HOKNISTROMES ( WALL MONUT) WEATHR PROOF WILL ME SELECTED ON "HIGH" AND "TEMPORAL" - THE CANDELA SELECTABLE SWITCH FOR THE HORN / STROBES ( WALL MONUT) WEATHER PROOF WILL BE SET AT "110cd" - THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WILL ME SET AT "75cd" - THE CANDELA SELECTABLE SWITCH FOR THE STROBE LIGHTS ( CEILING MOUNT) WEATHER PROOF WILL BE SET AT 75cd" CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT #i 1 Alarm Current m` Total Alarm Description Of Device Quantity ") per unit �. Current i ( Amps) tea (Amps) HorniStrobes ( wall mount) 11000 1r , 0.212 tf 0.212 FlornlSirobes (ceifin� mount ) 11 0C 1 0.212 0 -212 Horn /Strobes weather Proof wail mount 11Ocd 0 0.212 Irv.' 0.000 Strobe Lights ceilin mount 75cd 0 � 0.158 0.000 Strobe Li hts weather Proof ceilin mount 75cd 6 0.15E 0.94E :y Total System Alarm Current 11-37 (AMPS) CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT ## 2 Alarm Current g? Total Alarm Description Of Device Quantity per unit Current ( Amps) (Amps) Horn /Strobes (wall mount) 110cd 0*r ^212 0.000 Horn /Strobes (ceiling mount 110Cd 4 0 -212 0.848 Horn /Strobes weather proof wall mount 110cd 0 0.212 0.000 Strobe lights ( ceiling mount 75cd _4 N 0.158 ~0.632 Strobe Li his weather proof ceilin mount 75cd 0 0.159 ) 0 -000 Total System Alarm Current 1.49 ( Amps ) CALCULATIONS FOR THE NOTIFICATION APPLIANL:t L:IKt;UI I ?F,5 Alarm Current Total Alarm Description Of Device Quantity '„ per unit '' Current [ Amps) (Amps) Horn /Strobes ( wall mount ) 110cd 0 0.212 r� 0.000 HorniStrobes ( ceiling mount 11 Ocd 0 0 212 0.000 Hom / Strobos weather proof ( wall mount) 110cd 6� 0.212 1.272 Strobe Lights ceilin mount 75cd 0 ? 0.153 0.000 Strobe Li hts weather roof (ceilin mount 75cd 0 u 0.153 0.000 - Total System Alarm Current 1.27 (Amps) CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 4 - 3 Alarm Current ( Total Alarm Description Of Device Quantity ) per unit Current ( Amps) i 1 Amps ) Horn/Strobes ( wall mount) 110cd 0 0.212 0.000 Ilorn /Strobes ceilinQTount 110cd 0 0212 0.000 Horn /Strobes weather Proof wall mount 110cd 0 0212 0.000 Strobe Li hts c ifino mount 75cd 0 s' 0 -158 0.000 Strobe Lights weather proof ceiling mount 75cd 0 0.153 0.000 Total System Alarm Current 0.00 ( Amps ) CALCULATIONS FOR THE AUXILARY ROWER OUTPUT r; Alarm Current Total Alarm z }f' w . Description OF Device Quantity per unit Current ( Amps) ( Amps ) Nonresettable AuxllaryPower 0 0.000 0.000 Resettable Auxilary Power 0 prep! 0.000 r 0.000 Total System Ala nn Current 0.00 ( Amps 1 TOTAL CURRENT PER CIRCUIT NOTIFICATION APPLIANCE CIRCUIT R (Amps) NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37 NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS NOTIFICATION APPLIANCE CIRCUIT 8 3 127 NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp AUXILARY POWFR OUTPUT 0.00 TOTAL ALARM CURRENT 4.12 (Amps NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS. 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps VOLTAGE DROP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN THE FIDE ALARM CONTROL PANEL NOTES - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT FOR THE FIRE ALARM CONTROL PANEL CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1 ,r`.."■^.,.,.. - ...-. Tootal tal Voltage i Wire Total I Total g wiring run gauge line current drop for the resistance resistance load for the Notification forthe forthe forthe Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) ( Ohmslfeet) (Ohm) (amps) ( volts ) 2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269 Beginning ! Voltage:( Total voltage �. +i drop 1 voltage for the t, forthe %?' forthe Indicating Indicating ng IPM icatin g Appliance Appliance ,y;, Appliance Circuit Circuit Circuit ( volts) (volts) �t "�� ( volts ) 20.40 4 -27 - 16.13 NOTES: 1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS EXISTING NOTIFICATION APPLIANCES mnnFl TYPF TABLE DESCRIPTION MANUFACTURER MODEL DISCONTINUED Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO VOLTAGE DF:OP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN TWP Pt')WFR II=XPANDER CONTROL PANEL - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR THE POWER EXPANDER CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FUR. i nr Total - ..,.wTotal i Wire I Total Total ��h Voltage wiring run gauge line current drop forthe resistance resistance .� load ,i"t forthe rN Notification for the forthe for the ',�i, Indicating Appliance 14 gauge Notification Notiticatl•n Appliance Circuit wire Circuit Circuit,. Circuit ( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts ) 12001.1 130 x 0 -00307 0.3991 x 1.37 0.547 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z Total Wire Total- Total Voltage wiring run gauge line current --fit drop forthe resistance resistance ;i load - forthe Notification forthe for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts ) =60 x 0.00307 = 0.7982 x 1.48 = 1.191 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v CALCULATIONS FOR THE NOTIFICATION APPLIANL:t L:IKt;UI I ?F,5 Alarm Current Total Alarm Description Of Device Quantity '„ per unit '' Current [ Amps) (Amps) Horn /Strobes ( wall mount ) 110cd 0 0.212 r� 0.000 HorniStrobes ( ceiling mount 11 Ocd 0 0 212 0.000 Hom / Strobos weather proof ( wall mount) 110cd 6� 0.212 1.272 Strobe Lights ceilin mount 75cd 0 ? 0.153 0.000 Strobe Li hts weather roof (ceilin mount 75cd 0 u 0.153 0.000 - Total System Alarm Current 1.27 (Amps) CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 4 - 3 Alarm Current ( Total Alarm Description Of Device Quantity ) per unit Current ( Amps) i 1 Amps ) Horn/Strobes ( wall mount) 110cd 0 0.212 0.000 Ilorn /Strobes ceilinQTount 110cd 0 0212 0.000 Horn /Strobes weather Proof wall mount 110cd 0 0212 0.000 Strobe Li hts c ifino mount 75cd 0 s' 0 -158 0.000 Strobe Lights weather proof ceiling mount 75cd 0 0.153 0.000 Total System Alarm Current 0.00 ( Amps ) CALCULATIONS FOR THE AUXILARY ROWER OUTPUT r; Alarm Current Total Alarm z }f' w . Description OF Device Quantity per unit Current ( Amps) ( Amps ) Nonresettable AuxllaryPower 0 0.000 0.000 Resettable Auxilary Power 0 prep! 0.000 r 0.000 Total System Ala nn Current 0.00 ( Amps 1 TOTAL CURRENT PER CIRCUIT NOTIFICATION APPLIANCE CIRCUIT R (Amps) NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37 NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS NOTIFICATION APPLIANCE CIRCUIT 8 3 127 NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp AUXILARY POWFR OUTPUT 0.00 TOTAL ALARM CURRENT 4.12 (Amps NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS. 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps VOLTAGE DROP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN THE FIDE ALARM CONTROL PANEL NOTES - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT FOR THE FIRE ALARM CONTROL PANEL CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1 ,r`.."■^.,.,.. - ...-. Tootal tal Voltage i Wire Total I Total g wiring run gauge line current drop for the resistance resistance load for the Notification forthe forthe forthe Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) ( Ohmslfeet) (Ohm) (amps) ( volts ) 2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269 Beginning ! Voltage:( Total voltage �. +i drop 1 voltage for the t, forthe %?' forthe Indicating Indicating ng IPM icatin g Appliance Appliance ,y;, Appliance Circuit Circuit Circuit ( volts) (volts) �t "�� ( volts ) 20.40 4 -27 - 16.13 NOTES: 1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS EXISTING NOTIFICATION APPLIANCES mnnFl TYPF TABLE DESCRIPTION MANUFACTURER MODEL DISCONTINUED Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO VOLTAGE DF:OP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN TWP Pt')WFR II=XPANDER CONTROL PANEL - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR THE POWER EXPANDER CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FUR. i nr Total - ..,.wTotal i Wire I Total Total ��h Voltage wiring run gauge line current drop forthe resistance resistance .� load ,i"t forthe rN Notification for the forthe for the ',�i, Indicating Appliance 14 gauge Notification Notiticatl•n Appliance Circuit wire Circuit Circuit,. Circuit ( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts ) 12001.1 130 x 0 -00307 0.3991 x 1.37 0.547 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z Total Wire Total- Total Voltage wiring run gauge line current --fit drop forthe resistance resistance ;i load - forthe Notification forthe for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts ) =60 x 0.00307 = 0.7982 x 1.48 = 1.191 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT # 4 - 3 Alarm Current ( Total Alarm Description Of Device Quantity ) per unit Current ( Amps) i 1 Amps ) Horn/Strobes ( wall mount) 110cd 0 0.212 0.000 Ilorn /Strobes ceilinQTount 110cd 0 0212 0.000 Horn /Strobes weather Proof wall mount 110cd 0 0212 0.000 Strobe Li hts c ifino mount 75cd 0 s' 0 -158 0.000 Strobe Lights weather proof ceiling mount 75cd 0 0.153 0.000 Total System Alarm Current 0.00 ( Amps ) CALCULATIONS FOR THE AUXILARY ROWER OUTPUT r; Alarm Current Total Alarm z }f' w . Description OF Device Quantity per unit Current ( Amps) ( Amps ) Nonresettable AuxllaryPower 0 0.000 0.000 Resettable Auxilary Power 0 prep! 0.000 r 0.000 Total System Ala nn Current 0.00 ( Amps 1 TOTAL CURRENT PER CIRCUIT NOTIFICATION APPLIANCE CIRCUIT R (Amps) NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37 NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS NOTIFICATION APPLIANCE CIRCUIT 8 3 127 NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp AUXILARY POWFR OUTPUT 0.00 TOTAL ALARM CURRENT 4.12 (Amps NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS. 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps VOLTAGE DROP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN THE FIDE ALARM CONTROL PANEL NOTES - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT FOR THE FIRE ALARM CONTROL PANEL CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1 ,r`.."■^.,.,.. - ...-. Tootal tal Voltage i Wire Total I Total g wiring run gauge line current drop for the resistance resistance load for the Notification forthe forthe forthe Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) ( Ohmslfeet) (Ohm) (amps) ( volts ) 2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269 Beginning ! Voltage:( Total voltage �. +i drop 1 voltage for the t, forthe %?' forthe Indicating Indicating ng IPM icatin g Appliance Appliance ,y;, Appliance Circuit Circuit Circuit ( volts) (volts) �t "�� ( volts ) 20.40 4 -27 - 16.13 NOTES: 1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS EXISTING NOTIFICATION APPLIANCES mnnFl TYPF TABLE DESCRIPTION MANUFACTURER MODEL DISCONTINUED Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO VOLTAGE DF:OP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN TWP Pt')WFR II=XPANDER CONTROL PANEL - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR THE POWER EXPANDER CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FUR. i nr Total - ..,.wTotal i Wire I Total Total ��h Voltage wiring run gauge line current drop forthe resistance resistance .� load ,i"t forthe rN Notification for the forthe for the ',�i, Indicating Appliance 14 gauge Notification Notiticatl•n Appliance Circuit wire Circuit Circuit,. Circuit ( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts ) 12001.1 130 x 0 -00307 0.3991 x 1.37 0.547 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z Total Wire Total- Total Voltage wiring run gauge line current --fit drop forthe resistance resistance ;i load - forthe Notification forthe for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts ) =60 x 0.00307 = 0.7982 x 1.48 = 1.191 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v TOTAL CURRENT PER CIRCUIT NOTIFICATION APPLIANCE CIRCUIT R (Amps) NO I (FICA: [ION APPLIANCL: CIRCUIT S t 1.37 NOTIFICA I ION APPLIANCE CIRCUIT 2 1.4lS NOTIFICATION APPLIANCE CIRCUIT 8 3 127 NOTIFICATION APPI. IANCE CIRCUIT 84 p.pp AUXILARY POWFR OUTPUT 0.00 TOTAL ALARM CURRENT 4.12 (Amps NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS. 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps VOLTAGE DROP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN THE FIDE ALARM CONTROL PANEL NOTES - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT FOR THE FIRE ALARM CONTROL PANEL CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1 ,r`.."■^.,.,.. - ...-. Tootal tal Voltage i Wire Total I Total g wiring run gauge line current drop for the resistance resistance load for the Notification forthe forthe forthe Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) ( Ohmslfeet) (Ohm) (amps) ( volts ) 2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269 Beginning ! Voltage:( Total voltage �. +i drop 1 voltage for the t, forthe %?' forthe Indicating Indicating ng IPM icatin g Appliance Appliance ,y;, Appliance Circuit Circuit Circuit ( volts) (volts) �t "�� ( volts ) 20.40 4 -27 - 16.13 NOTES: 1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS EXISTING NOTIFICATION APPLIANCES mnnFl TYPF TABLE DESCRIPTION MANUFACTURER MODEL DISCONTINUED Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO VOLTAGE DF:OP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN TWP Pt')WFR II=XPANDER CONTROL PANEL - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR THE POWER EXPANDER CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FUR. i nr Total - ..,.wTotal i Wire I Total Total ��h Voltage wiring run gauge line current drop forthe resistance resistance .� load ,i"t forthe rN Notification for the forthe for the ',�i, Indicating Appliance 14 gauge Notification Notiticatl•n Appliance Circuit wire Circuit Circuit,. Circuit ( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts ) 12001.1 130 x 0 -00307 0.3991 x 1.37 0.547 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z Total Wire Total- Total Voltage wiring run gauge line current --fit drop forthe resistance resistance ;i load - forthe Notification forthe for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts ) =60 x 0.00307 = 0.7982 x 1.48 = 1.191 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v NOTES: 1) TOTAL CURRENT DRAWN BY ANY ONE NOTIFICATION APPLIANCE CIRCUIT CAN NOT EXCEED 3.0 AMPS. 2) TOTAL CURRENT DRAWN FROM THE FOUR NOTIFICATION APPLIANCE CIRCUITS AND OTHER DC POWER OUTPUTS CAN NOT EXCEED 6.00 Amps VOLTAGE DROP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN THE FIDE ALARM CONTROL PANEL NOTES - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS THWN 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT" FROM THE ONE NOTIFICATION APPLIANCE CIRCUIT FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUIT FOR THE FIRE ALARM CONTROL PANEL CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT 4 1 ,r`.."■^.,.,.. - ...-. Tootal tal Voltage i Wire Total I Total g wiring run gauge line current drop for the resistance resistance load for the Notification forthe forthe forthe Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) ( Ohmslfeet) (Ohm) (amps) ( volts ) 2.00 x 46CI x 0.00307 2.1244 x 1.511 4.269 Beginning ! Voltage:( Total voltage �. +i drop 1 voltage for the t, forthe %?' forthe Indicating Indicating ng IPM icatin g Appliance Appliance ,y;, Appliance Circuit Circuit Circuit ( volts) (volts) �t "�� ( volts ) 20.40 4 -27 - 16.13 NOTES: 1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS EXISTING NOTIFICATION APPLIANCES mnnFl TYPF TABLE DESCRIPTION MANUFACTURER MODEL DISCONTINUED Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO VOLTAGE DF:OP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN TWP Pt')WFR II=XPANDER CONTROL PANEL - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR THE POWER EXPANDER CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FUR. i nr Total - ..,.wTotal i Wire I Total Total ��h Voltage wiring run gauge line current drop forthe resistance resistance .� load ,i"t forthe rN Notification for the forthe for the ',�i, Indicating Appliance 14 gauge Notification Notiticatl•n Appliance Circuit wire Circuit Circuit,. Circuit ( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts ) 12001.1 130 x 0 -00307 0.3991 x 1.37 0.547 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z Total Wire Total- Total Voltage wiring run gauge line current --fit drop forthe resistance resistance ;i load - forthe Notification forthe for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts ) =60 x 0.00307 = 0.7982 x 1.48 = 1.191 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v Beginning ! Voltage:( Total voltage �. +i drop 1 voltage for the t, forthe %?' forthe Indicating Indicating ng IPM icatin g Appliance Appliance ,y;, Appliance Circuit Circuit Circuit ( volts) (volts) �t "�� ( volts ) 20.40 4 -27 - 16.13 NOTES: 1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS EXISTING NOTIFICATION APPLIANCES mnnFl TYPF TABLE DESCRIPTION MANUFACTURER MODEL DISCONTINUED Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO VOLTAGE DF:OP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN TWP Pt')WFR II=XPANDER CONTROL PANEL - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR THE POWER EXPANDER CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FUR. i nr Total - ..,.wTotal i Wire I Total Total ��h Voltage wiring run gauge line current drop forthe resistance resistance .� load ,i"t forthe rN Notification for the forthe for the ',�i, Indicating Appliance 14 gauge Notification Notiticatl•n Appliance Circuit wire Circuit Circuit,. Circuit ( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts ) 12001.1 130 x 0 -00307 0.3991 x 1.37 0.547 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z Total Wire Total- Total Voltage wiring run gauge line current --fit drop forthe resistance resistance ;i load - forthe Notification forthe for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts ) =60 x 0.00307 = 0.7982 x 1.48 = 1.191 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v NOTES: 1) THE LOWEST VOLTAGE ON THE NOTIFICATION APPLIANCE CIRCUIT CAN ME IS 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS EXISTING NOTIFICATION APPLIANCES mnnFl TYPF TABLE DESCRIPTION MANUFACTURER MODEL DISCONTINUED Horn/Strobe wall Mount TYPE "1" WHEELOCK 24T -34 YES Horn/Strobe wall Mount TYPE "2" SIMPLEX 4903 -9219 YES Horn/Strobe wall Mount TYPE "3" FARADAY 602015511 YES Horn /Strobe wall Mount TYPE "4" SENSOR SYSTEM P122475 YES Horn /Strobe wall Mount TYPE "5"_1 SENSOR SYSTEM P1224110 YES Horn/Strobe wall Mount TYPE "6" SENSOR SYSTEM P2R NO VOLTAGE DF:OP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN TWP Pt')WFR II=XPANDER CONTROL PANEL - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR THE POWER EXPANDER CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FUR. i nr Total - ..,.wTotal i Wire I Total Total ��h Voltage wiring run gauge line current drop forthe resistance resistance .� load ,i"t forthe rN Notification for the forthe for the ',�i, Indicating Appliance 14 gauge Notification Notiticatl•n Appliance Circuit wire Circuit Circuit,. Circuit ( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts ) 12001.1 130 x 0 -00307 0.3991 x 1.37 0.547 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z Total Wire Total- Total Voltage wiring run gauge line current --fit drop forthe resistance resistance ;i load - forthe Notification forthe for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts ) =60 x 0.00307 = 0.7982 x 1.48 = 1.191 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v VOLTAGE DF:OP CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS IN TWP Pt')WFR II=XPANDER CONTROL PANEL - THE TOTAL WIRE RUN VALUE IS OBTAIN BY MEASURING THE APPROXIMATE CONDUIT RUN IN THE FLOOR PLAN - THE WIRE USED IS FPL SOLID 14 GAUGE, WHICH HAS A RESISTANCE OF 0.00307 OHMS PER FOOT - THE CURRENT LOAD VALUE IS OBTAIN FROM THE CORRESPONDING "TOTAL ALARM CURRENT' FROM EACH OF NOTIFICATION APPLIANCE CIRCUITS FROM THE "LOAD CALCULATIONS PER NOTIFICATION APPLIANCE CIRCUITS FOR THE POWER EXPANDER CONTROL PANEL" CHART - THE CONSIDERED VALUE FOR THE BEGINNING VOLTAGE MEASUREMENT IS 20.40 VOLTS CALCULATIONS FUR. i nr Total - ..,.wTotal i Wire I Total Total ��h Voltage wiring run gauge line current drop forthe resistance resistance .� load ,i"t forthe rN Notification for the forthe for the ',�i, Indicating Appliance 14 gauge Notification Notiticatl•n Appliance Circuit wire Circuit Circuit,. Circuit ( feet) ( ohmsifeet) ( Ohm) ( amps) ( volts ) 12001.1 130 x 0 -00307 0.3991 x 1.37 0.547 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z Total Wire Total- Total Voltage wiring run gauge line current --fit drop forthe resistance resistance ;i load - forthe Notification forthe for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts ) =60 x 0.00307 = 0.7982 x 1.48 = 1.191 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIIrtCUI i a z Total Wire Total- Total Voltage wiring run gauge line current --fit drop forthe resistance resistance ;i load - forthe Notification forthe for the for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet) (Ohmslfeet) ( Ohm) j ( amps) ( volts ) =60 x 0.00307 = 0.7982 x 1.48 = 1.191 CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v CALCULATIONS FOR THE NOTIFICATION APPLIANCE CIRCUIT * 3 - vrrrew�. Total -_ - - -- Wire Total Total Voltage wiring run gauge line current drop forthe resistance resistance � load j for the Notification forthe for the forthe ! Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit Circuit ( feet I (OhmsReet) ( Ohm) ( amps) ( volts ) 2.00 x 160 x 0 -00307 0.4212 x 1.27 - 0.624 Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v Beginning r�I Voltage ;.i Total voltage tya drop I voltage forthe forthe ? forthe Indicating Indicating Indicating W �I Appliance r y Appliance ;; Appliance CircuitCircuit ''u Circuit ( volts) .�- (volts) (volts ) 20.40 0.55 T 19.95 Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v Beginning :F1 Voltage Total voltage drop voltage forthe forthe forthe Indicating i Indicating Indicating r! _ Appliance Appli ance App liance Circuit Circuit Circuit ( volts) ( volts) '0'i ( volts ) 20.40 1.18 Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v Beginning" -,t Voltage '' Total voltage drop voltage forthe '�;, forthe _. forthe Indicating Indicating R. Indicating Appliance Appliance y�te Appliance Circuit Circuit Circuit ( volts),` ( vdts)I ( volts ) ,.a 20.40 0.62 JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v JLATIONS FOR THE NOTIFTCA I IUN Air L1AM,r "Mi.ur i TM S Total Wire Total Total Voltage wiring run gauge line j current drop forthe resistance resistance lead forthe Notification forthe forthe i for the Indicating Appliance 14 gauge Notification Notification Appliance Circuit wire Circuit Circuit circuit ( feet) (Ohmsffeet) ( Ohm) ( amps) (volts ) x 0 x 0.00307 - 0- 0.000 Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v Beginning Voltage 3 Total voltage tr` drop voltage for the for the - for the Indicating ,r. Indicating" Indicating S.. Appliance Appliance Appliance Circuit r Circuit Circuit ( volts ) ? Uli ( volts) (volts ) 20.40 0.00 NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v NOTES: 1) THE LOWEST VOLTAGE ON EACH OF THE NOTIFICATION APPLIANCE CIRCUITS CAN BE 16 VOLTS 2) THE MAXIMUM VOLTAGE DROP CAN BE 4.40 VOLTS PER NOTIFICATION APPLIANCE CIRCUIT 3) THE OPERATING VOLTAGE RANGE FOR THE NOTIFICATION APPLIANCES IS BETWEEN 16 TO 33 VOLTS ENGINEER'S INFORMATION: 1) All conduit to be 112" EMT or larger 2) All flexible conduit to be 1/2" EMT or larger 3) All wires for the Initiating Circuit will be THWN wire, 14" gauge 4) All wires for the Notification Circuit will be THWN wire, 14" gauge 5) All work to be done in accordance with the Nation @, I- le(.trical Curie and shall comply with all The local rules and ordinances 6) The existing Fire Alarm Control Panel is feed by a '/2 EMT conduit with (3) x`12 Th'WN c: nductors ( one phase conductor, one neutral conductor and one grounding conductor) supplied by a 20 amp single pole dedicated branch r;ircuit breaker at 120vac with a breaker lock 7) The new Power Expander Control Panel is feed by a 1/2 EMT conduit with (3) *12 cu THWN conductors ( one phase i conductor supplied b a 20 am single pole dedicated branch conductor, one neutral conductor and one grounding ) pp Y P circuit breaker at 120vac with a breaker lock 8) All equipment installed are " U.L. Listed" for the Fire Alarm Services and shall be compatible between there 9) All Fire Alarm Devices, Appliances and Components to be installed as per the National Fire Protection Association * 72 10) The existing Fire Alarm Control Panel is Power Limited 11) The new Power Expander Control Panel is Power Limited 12) The Backup Battery Charger is inside the existing Fire Alarm Control Panel ( Batteries must be (1L Listed Batteries nol to exceed 17 AH ) 13) The Backup Battery Charger is inside the new Power Expander Control Panel ( Batteries must be UL Listed Batteries not to exceed 19 AH ) 14) Pull Stations are installed as per the Manufacturers Specifications 15) Pull Stations shall activate the Fire Alarm Control Panel into alarm condition 16) Pull Stations are to be installed at 48" A.F.F. 17) Pull Stations to be installed within 5 feet from the exit doorway opening at each exit on each floor it) Pull Stations to be installed at least one per floor and within 200' of any point in the Premises 1�) Smoke Detectors and Heat detectors shall activate the Fire Alarm Control Panel into alarm condition 20) Smoke Detectors and Heat Detectors to be installed at 6" away from the wail or 6" below the ceiling 21) Smoke Detectors and Heat Detectors to be installed at least 3' away from Air Conditioners supply vents 22) Smoke Detectors and Heat Detectors to be installed as per the Manufacturers Specifications 23) Smoke Detectors and Heat Detectors to be spaced accordingly in smooth ceiling areas 24) Smoke Detectors and Heat Detectors to be spaced accordingly in peaked or sloped ceilings areas 25) The Wall Mount Horn /Strobes, Ceiling Mount Hom /Strobes and Ceiling Mount Strobe Lights to be installed as per the Manufacturers Specifications 26) The Wall Mount Horn /Strobes to be installed at 80" A.F.F. or 6" below the ceiling ( which ever is lower) 27) The Ceiling Mount Horn/Strobes to be installed at 95" A.F.F. or above 29) All Wall Mount Horn /Strobes and Ceiling Mount Horn /Strobes will provide 15dbA above ambient or 5dbA above peak levels 29) All Strobe Lights are adequate for the area that are covering 30) All corridor spaced Strobe Lights are placed a maximum of 100' apart and within 15' from the ends of the corridor 31) The ceiling heights inside the Data /Phone /Fire Alarm Room and Electrical Panel Area is 8' from the floor 32) The acoustic ceiling heights inside the Gym Area is 8' from the floor 33) The acoustic ceiling heights inside the Men's Locker Room and the Women's Locker Room is 7' from the floor 34) The roiling file selves height are about 6 feet 35) All racks, shelves and equipment in any of the areas in the premises are not blocking any Initiating Device or any Notification Appliances 36) No Hood Extinguishing Systems or FM -200 Extinguishing System are connected to the Fire Alarm System 37) All the devices will be installed at normal Conditions as per the N.F.P.A. 72 39) The Devices and Appliances that are in areas which the voltage, temperature and humidity variations exceed the normal conditions have a W.P. label next to it 39) The existing Fire Alarm Control Panel and the new Power Expander Control Panels will be located inside an unoccupied room and will be protected by a Smoke Detector 40) The existing Remote Annunciator will be located outside of the building at the main entrance ( inside a NI =MA -4X weather proof housing ) 41) The existing Fire Alarm Control Panel will be connected to a Existing Remote Supervising Station 42) The existing Fire Alarm Control Panel will be connect ( through the alarm dry contact and the trouble dry contact ) to the main Fire Alarm System of the hospital 43) The Alarm Dry Contacts and the Trouble Dry Contacts will be inside the existing Fire Alarm Control Panel 44) The existing Fire Alarm System a Fire Alarm System will be provided with a 24 hours Secondary Power 45) The existing Fire Alarm Control Panel has nine Initiating Circuits 46) The existing Fire Alarm Control Panel has nine Initiating Circuits that meet the NFPA Style "8" or meet Style "A" or style "D" ( Class "A" ) 47) The maximum Smoke Detectors in each Initiating Zones can not exceed a draw of 3mA per Initiating Zone 49) The existing Fire Alarm Control Panel has, as Manufacturer Specification, a capacity of 2.5 amps for the one Notification Circuit 49) The existing Fire Alarm Control Panel's Total Current Draw, as per manufacturer specifications, from the Notification Circuit and other DC Power Outputs cannot exceed 2 -5 amps 150) The Notification Appliance Circuits for the existing Fire Alarm Control Panel meet the NFPA Style: "Y" (Class "B" ) and Style "Z" ( Class "A" ) 51) The new Power Expander Control Panel has four Notification Appliance Circuits 52) The Notification Appliance Circuits for the new Power Expander Control Panel meet the NFPA Style "Y" ( C(ass "t3" ) and Style "Z" ( Class "A" ) 53) The new Power Expander Control Panel has, as Manufacturer Specification, a capacity of 3.0 amps per each of the four Notification Appliances Circuits 54) The new Power Expander Control Panel's Total Current Draw, as per manufacturer specifications, from the four Notification Appliances Circuits and the DC Power Output cannot exceed 6.0 amps r Elevator Recall r not Capable fo E The existing elevators are 55 P 9 BURGLAR ALARM SERVICES 5650 SHERIDAN STREET HOLLYWOOD, FLORIDA 33021 -3250 PHONE: (945) 963 -3366 FAX: (954) 981 -4302 STATE LICENSE: EF000022R COMPANY GPM ENGINEERING, INC. QUALIFIER'S INFORMATION: NAME: SHANTJLAL C. PATEL NAME: BRUCE HOTCHKISS ADDRESS: 5502 S.W. 114 AVENUE ADDRESS: 5650 SERIDAN STREET COOPER CITY, FLORIDA 33330. ' KIND OF ENGINEER: MECHANICAL / ELECTRIC _AI - ENC.lr4J!l °R `� HOLLYWOOD, FLORIDA 33021 LICENSE NUMBER: P.E. #� 028551 LICENSE NUMBER: EF0000228 I t SIG , -;TURE `SIGNATURE SOUTH MIAMI HOSPITAL FITNESS CE,;NTE:R 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 1 r ,•n Approved by: C(r2wn by:: J,Y2. .� 12 /19 1Q08 SHANTJAKIIL C. PATEL f evs d: -�� BURGLAR ALARM SERVICES -f HOLLYWOOD, .�..... LRIDA ;'13021 5650 SHERIDAN STREET () RAWING NUMBER 2014 v