09-979-020ENLARGED ELECTRICAL RM. DEMO - NORTH TOWER
SCALE: 1/4" = 1' -0"
GENERAL DEMOLITION NOTES:
1. ALL DEVICES SHOWN ON THIS PLAN ARE EXISTING. REFER TO SYMBOL LEGEND FOR DEVICE
DESCRIPTION.
2, EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL DRAWINGS AND FIELD
INVESTIGATION. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO BID. FIELD CONDITIONS
SHALL GOVERN.
3. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN THE PROJECT AREA.
IT IS INTENDED TO PROVIDE THE CONTRACTOR WITH A GENERAL KNOWLEDGE OF THE EXISTING
CONDITIONS WITHIN THE PROJECT AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THIS
PLAN SHALL ME BROUGHT TO THE ATTENTION OF THE ENGINEER, THE CONTRACTOR IS
RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT.
4. ALL CONDUITS SERVING OTHER SPACES OR FLOORS, THAT RUN THROUGH THE PROJECT AREA SHALL
REMAIN ACTIVE DURING CONSTRUCTION, SO AS NOT TO CAUSE ANY DISRUPTION TO THESE OTHER
SPACES. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSURE THAT ALL CONDUITS, NEW OR
EXISTING, WITHIN THE PROJECT AREA ARE PROPERLY SUPPORTED AND PROVIDED WITH BONDING
BUSHINGS IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE.
5. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE DISPOSED OF OR TURNED OVER TO THE
OWNER AT THE OWNER'S DISCRETION,
6 THIS CONTRACTOR SHALL PROVIDE ELECTRICAL FOR PHASING WORK AS REQUIRED OR DIRECTED BY
THE ARCHITECT, REFER TO ARCHITECTURAL PHASING PLAN. TEMPORARY ELECTRICAL SERVICES
(POWER, LIGHTING, NURSE CALL, FIRE ALARM, ETC) SHALL BE PROVIDED WHEN NEW WORK AFFECTS
SERVICES NEEDING TO REMAIN ACTIVE. IF FIRE ALARM SYSTEM CANNOT BE MAINTAINED IN THE
CONSTRUCTION AREA, A FIRE WATCH SHALL BE PROVIDED.
7. UNLESS OTHERWISE NOTED, ALL EQUIPMENT, WIRING DEVICES, LIGHT FIXTURES, CONDUIT AND WIRE IN
THE PROJECT AREA SHALL BE REMOVED. THE CONTRACTOR SHALL INVESTIGATE THE PROJECT AREA
PRIOR TO BID TO DETERMINE ALL REQUIRED DEMOLITION.
8. CONTRACTOR SHALL PROVIDE MEANS OF AUTOMATIC SMOKE DETECTION VIA INSTALLED SMOKE
DETECTORS CONNECTED TO THE FACILITY FIRE ALARM SYSTEM FOR COVERAGE DURING NON —
OCCUPIED PERIODS WITHIN THE CONSTRUCTION AREA. IF DESIRED, A DOCUMENTED FIRE WATCH OF
THE ENTIRE AREA PERFORMED IN INCREMENTS NO GREATER THAN ONE HOUR MAY BE PERFORMED
PROVIDED THAT IT IS DOCUMENTED IN FULL ACCORDANCE WITH NFPA 72. COORDINATE ACTIVITY IN
FIELD WITH GENERAL CONTRACTOR.
9. "ETR" DENOTES EXISTING ELECTRICAL DEVICE TO REMAIN.
DEMOLITION PLAN NOTES:
REMOVE EXISTING ATS -3N. ALL CONDUITS SHALL REMAIN IN PLACE FOR RECONNECTION TO NEW
ATS -3N. REFER TO ONE —LINE DIAGRAM SHEET E002 FOR FUTHER INFORMATION,
DEMOLITION PLAN NOTES:
OPROVIDE ATS WITH PULL BOX AS SHOWN. THE CONTRACTOR SHALL COORDINATE THE EXACT
LOCATION OF THIS EQUIPMENT WITH EXISTING CONDITIONS. REFER TO SEQUENCE OF WORK
DESCRIPTION ON ONE -LINE DIAGRAM FOR FURTHER INFORMATION RELATED TO THE CONSTRUCTION
PHASING IN THIS AREA.
v w � • • u r • •
ENGINEERING
FOR ARCHITECTURE
255 S. Orange Avenue
Suite 1600
Orlando, Florida 32801
PH: 407.841.9050
www.tic- engineers.com
EB -0000015
O Copyright 2009 TLC Engineering for Architecture, Inc.
.0
0
CU
(n co
'a
'-a
Q M O
1`' LL
CD
O C\1 ca
nd
CL
co
00
iJ
'
FL
LAB. o l i
Revisions:
i
UPS- �'�❑
7^ ° ! No Date Description
P -S T AIR 3
COMPUTER
UPS -' & 5�
r
- -
I
FE,
T.
CORRIDOR
o NDP2- - SECTION 1 SECTION 2 NDP1 MDP -1 MDP -2 MDP -3 MDP -4
�t NH1S NL1S -- 4,— —i CLINICAL LABORATORY
CL1S - ,:
u _
o"
0
r °0
\ E 1S ATS -2 BLOOD BA��K SEROLOGY j
QL1S CH Seal
� � I, James Ferris, P.E.
A 3N CDP EQDP / ° Florida License #65156
TS-
C
-_h ' #� p
C7 � � �i1t! 111 /
Lj
EXISTING FIRE
v�
ALARM PANEL
ATS -1,��
XL1
;E XL,3 EL> 4
OUTPATIENT
°J
�,.
4 PHLEBOTOMY
LSL1 S M' LSDP - =_ , _ _ r. _.. i.,...;u -tea: - r : ` ` M n '' •,
' y
__ , .
L
La_ 1
.
LSH1S
•, rte+ ` 4`
EL. - 5
LOBBY
U
0
Q
Q.
s
F_
r'roject No.. 109355
Issue Date:
10/05/2009
Drawn By: LAR
Approved By: JDF
Scale: 1/41' = 1' -0"
Drawing Title:
s
ENLARGED
ENLARGED ELECTRICAL RM. RENOVATION - NORTH TOWER FIFTH FLOOR PARTIAL ELECTRICAL PLAN - NORTH TOWER ELECTRICAL ROOM
SCALE: 1/41t = 1' -0" SCALE: 1/4" = 1' -0° NORTH TOWER
Ln
n
m
0
Drawing No.:
E602
G
'
N
THIS DRAWING IS BEING RELEASED FOR THE PURPOSE OF 100% CONSTRUCTION DOCUMENTS
• •
.•••
. •
ENGINEERING
FOR ARCHITECTURE
255 S. Orange Avenue
Suite 1600
Orlando, Florida 32801
PH: 407.841.9050
www.tic- engineers.com
EB -0000015
O Copyright 2009 TLC Engineering for Architecture, Inc.
.0
0
CU
(n co
'a
'-a
Q M O
1`' LL
CD
O C\1 ca
nd
CL
co
00
iJ
'
FL
LAB. o l i
Revisions:
i
UPS- �'�❑
7^ ° ! No Date Description
P -S T AIR 3
COMPUTER
UPS -' & 5�
r
- -
I
FE,
T.
CORRIDOR
o NDP2- - SECTION 1 SECTION 2 NDP1 MDP -1 MDP -2 MDP -3 MDP -4
�t NH1S NL1S -- 4,— —i CLINICAL LABORATORY
CL1S - ,:
u _
o"
0
r °0
\ E 1S ATS -2 BLOOD BA��K SEROLOGY j
QL1S CH Seal
� � I, James Ferris, P.E.
A 3N CDP EQDP / ° Florida License #65156
TS-
C
-_h ' #� p
C7 � � �i1t! 111 /
Lj
EXISTING FIRE
v�
ALARM PANEL
ATS -1,��
XL1
;E XL,3 EL> 4
OUTPATIENT
°J
�,.
4 PHLEBOTOMY
LSL1 S M' LSDP - =_ , _ _ r. _.. i.,...;u -tea: - r : ` ` M n '' •,
' y
__ , .
L
La_ 1
.
LSH1S
•, rte+ ` 4`
EL. - 5
LOBBY
U
0
Q
Q.
s
F_
r'roject No.. 109355
Issue Date:
10/05/2009
Drawn By: LAR
Approved By: JDF
Scale: 1/41' = 1' -0"
Drawing Title:
s
ENLARGED
ENLARGED ELECTRICAL RM. RENOVATION - NORTH TOWER FIFTH FLOOR PARTIAL ELECTRICAL PLAN - NORTH TOWER ELECTRICAL ROOM
SCALE: 1/41t = 1' -0" SCALE: 1/4" = 1' -0° NORTH TOWER
Ln
n
m
0
Drawing No.:
E602
G
'
N
THIS DRAWING IS BEING RELEASED FOR THE PURPOSE OF 100% CONSTRUCTION DOCUMENTS