09-979-009ALL GYPSUM BOARD PANELS
4' -0" GYPSUM BOARD PANEL SHALL BE APPLIED VERTICALLY
� I
4' -0" GYPSUM BOARD PANEL
STAGGER VERTICAL JOINTS SO THAT THEY OCCUR OVER DIFFERENT I 16" O.C.
STUDS ON OPPOSITE SIDES OF PARTITION AND STAGGER JOINTS OF
SECOND LAYER FROM FIRST LAYER. COMPLY WITH REQUIREMENTS I MAXIMUM
IN "WALLS /PARTITIONS /BARRIERS LEGEND" ON SHEET X1.1 STUD
I SPACING ,I
F 4' -0" GYPSUM BOARD PANEL I JOINTS IN FINISH LAYER JI '
SHALL RECEIVE TAPE
AND JOINT COMPOUND I
FOR ALL WALLS /PARTITIONS /BARRIERS I 4' -0 GYPSUM BOARD PANEL
FOR NON -RATED PARTITIONS
FINISH CEILING DECKS (SEE "WALLS /PARTITIONS /BARRIERS
LEGEND" ON SHEET X1.1)
+ ALTHOUGH HORIZONTAL JOINTS MAY
+ ' ' NOT NORMALLY BE REQUIRED TO
BE STAGGERED IN NON -RATED
PARTITIONS, THEY MAY BE REQUIRED
I I TO BE STAGGERED TO COMPLY WITH
AN STC RATING. VERIFY.
ALL HORIZONTAL JOINTS SHALL
OCCUR ABOVE THE CEILING.
I
GYPSUM BOARD PANEL LENGTHS
I I I SHALL ALLOW FOR JOINTS TO
BE ABOVE THE CEILING (USE
1 8' -0" MINIMUM BOARD LENGTH
IN SPACES WITHOUT CEILINGS)
FLOOR SLAB FOR ALL PARTITIONS: CUT GYP BD TO WITHIN 112" OF DECK FLUTES
AND SEAL AS INDICATED ON "WALLS /PARTITIONS /BARRIERS LEGEND"
~ FOR RATED FIRE BARRIERS � SMOKE
FINISH CEILING DECK BARRIERS (SEE "WALLS /PARTITIONS/
BARRIERS LEGEND' ON SHEET X1:1)
HORIZONTAL JOINTS ARE
I I I
REQUIRED TO BE STAGGERED
- - - - - -- -
�- - - - - ' - -- -- - - -� -- -- -� - 2,- 0" (MINIMUM) O.C. AND ALL
JOINTS SHALL OCCUR ABOVE
THE CEILING BY USING VARYING
' LENGTHS OF GYPSUM BOARD
PANELS
GYPSUM BOARD PANEL LENGTHS
�1 SHALL ALLOW FOR HORIZONTAL
JOINTS TO BE ABOVE THE
' CEILING (USE 8'--0" MINIMUM
AT SPACES WITHOUT CEILINGS)
FLOOR SLAB 1/4" MINIMUM/ 1/2" MAXIMUM JOINT AT ALL FLOOR SLABS. SEAL AS
INDICATED ON WALLS /PARTITIONS /BARRIERS LEGEND" ON SHEET X1.1
DETAIL LOCATION OF JOINTS IN GYPSUM
NOT TO SCALE BOARD WALLS /PARTITIONS /BARRIERS
NOTES:
1. SEE "WALLS /PARTITIONS /BARRIERS LEGEND" ON PROJECT INFORMATION SHEET A8.1 FOR
ADDITIONAL REQUIREMENTS FOR THIS BARRIER, AND COMPLY WITH ALL REQUIREMENTS OF THE
DESIGNATED TESTED ASSEMBLY REFERENCED IN THE "WALLS /PARTITIONS /BARRIERS LEGEND"
ON PROJECT INFORMATION SHEET A8.1
2. COMPLY WITH ALL REQUIREMENTS OF THE FBC SECTION 713 - FIRE RESISTANT
JOINT SYSTEMS. ALL JOINTS INSTALLED IN OR BETWEEN FIRE - RESISTANCE -RATED WALLS/
BARRIERS OR FLOOR ASSEMBLIES AND ROOF ASSEMBLIES SHALL BE PROTECTED BY AN
APPROVED "FIRE- RESISTANT JOINT SYSTEM" DESIGNED TO RESIST THE PASSAGE OF FIRE
FOR A TIME PERIOD NOT LESS THAN THE REQUIRED FIRE - RESISTANCE RATING OF THE
WALL /BARRIER, FLOOR OR ROOF IN OR BETWEEN WHICH IT IS INSTALLED. FIRE- RESISTANT
JOINT SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF EITHER
ASTM E 1966 OR UL 2079. COMPLY WITH REQUIREMENTS OF SPECIFICATION SECTION 07 8446.
3. SEAL ALL PENETRATIONS THROUGH THESE BARRIERS TO COMPLY WITH REQUIREMENTS
INDICATED ON PROJECT INFORMATION SHEET A8.1
4. PROVIDE LEAD -LINED TYPE "RB -LBG" GYPSUM BOARD WHERE LEAD - LINING IS INDICATED ON
THE FLOOR PLANS, AND COMPLY WITH ALL REQUIREMENTS OF THE DESIGNATED TESTED
ASSEMBLY THAT SPECIFICALLY APPLIES TO A LEAD -LINED RATED BARRIER AS REFERENCED IN
THE "WALLS /PARTITIONS /BARRIERS LEGEND" ON PROJECT INFORMATION SHEET A8.1
BOTH LAYERS OF 5/8" TYPE "X" GYPSUM
BOARD SHALL BE CUT TO FIT WITHIN DECK
PROVIDE APPROVED "FIRE- FLUTES PER MAXIMUM GAP ALLOWED BY
RESISTANT JOINT SYSTEM" APPROVED "FIRE RESISTANT JOINT SYSTEM"
PER NOTE 2 ABOVE. ALSO, PER NOTE 2 ABOVE (COMPLY WITH NOTE 4
COMPLY WITH REQUIREMENTS FOR RATED LEAD -LINED BARRIERS)
INDICATED ON PROJECT
INFORMATION SHEET X1.1
NOTES:
1. SEE "WALLS /PARTITIONS /BARRIERS LEGEND" ON PROJECT INFORMATION SHEET A8.1 FOR
ADDITIONAL REQUIREMENTS FOR THIS BARRIER, AND COMPLY WITH ALL REQUIREMENTS OF THE
DESIGNATED TESTED ASSEMBLY REFERENCED IN THE "WALLS /PARTITIONS /BARRIERS LEGEND"
ON PROJECT INFORMATION SHEET A8.1.
2. COMPLY WITH ALL REQUIREMENTS OF THE FBC SECTION 713 -FIRE RESISTANT
JOINT SYSTEMS. ALL JOINTS INSTALLED IN OR BETWEEN FIRE - RESISTANCE -RATED WALLS/
BARRIERS OR FLOOR ASSEMBLIES AND ROOF ASSEMBLIES SHALL BE PROTECTED BY AN
APPROVED "FIRE- RESISTANT JOINT SYSTEM" DESIGNED TO RESIST THE PASSAGE OF FIRE
FOR A TIME PERIOD NOT LESS THAN THE REQUIRED FIRE - RESISTANCE RATING OF THE
WALL /BARRIER, FLOOR OR ROOF IN OR BETWEEN WHICH IT IS INSTALLED. FIRE - RESISTANT
JOINT SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF EITHER
ASTM E 1966 OR UL 2079. COMPLY WITH REQUIREMENTS OF SPECIFICATION SECTION 07 8446.
3, IN HEALTH CARE FACILITIES, EVEN IN NON -RATED CMU PARTITIONS, SEAL ALL PENETRATIONS
TO COMPLY WITH 2006 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE
FACILITIES SECTION 2.1- 8.2.3.5.
4. WHERE INDICATED AND /OR REQUIRED, PROVIDE CONCRETE MASONRY UNITS THAT WILL
PROVIDE THE REQUIRED STC RATING. USE "SOUNDBLOX" THAT IS TESTED FOR BOTH THE
REQUIRED FIRE RATING AND THE REQUIRED STC RATING. SEE SPECIFICATIONS.
I
,tql
FLOOR OR ROOF ASSEMBLY PER U.L. DESIGN
NUMBER (SEE THE PLAN REVIEW DATA ON SHEET
X1.1 FOR THE DESIGNATED U.L. DESIGN NUMBER
FOR THE FLOOR AND ROOF ASSEMBLIES)
PROVIDE APPROVED "FIRE- RESISTANT JOINT SYSTEM"
PER NOTE 2 ABOVE. ALSO, COMPLY WITH REQUIREMENTS
INDICATED ON PROJECT INFORMATION SHEET X1.1 UNDER
"WALLS /PARTITIONS /BARRIERS LEGEND ". SEAL ALL
"HEAD -OF- WALLS" BOTH AIR -TIGHT AND SOUND- TIGHT.
STRUCTURAL BRACE (SEE STRUCTURAL FOR TYPE,
SIZE AND LOCATIONS OF BRACES)
RATED CONCRETE MASONRY UNITS. SEE FLOOR PLANS
AND "WALLS /PARTITIONS /BARRIERS LEGEND" ON
SHEET X1.1 FOR SIZE AND RATING OF CONCRETE
MASONRY UNITS. SEE STRUCTURAL DRAWINGS FOR
REINFORCEMENT OF CMU. ALSO, SEE NOTE 4 ABOVE.
RAKE MORTAR JOINT AND ADD CONTINUOUS
ACOUSTICAL SEALANT BEAD
CONCRETE FLOOR SLAB
SEE STRUCTURAL FOR CONNECTION OF CMU AND
ITS REINFORCMENT INTO CONCRETE FLOOR SLAB
RATED FIRE BARRIER AND /OR
DETAIL RATED SMOKE BARRIER USING
NOT TO SCALE CONCRETE MASONRY UNITS [CMU]
TAPE 1. JOINT COMPOUND (TYPICAL)
LOWER PRIORITY PARTITION /BARRIER
LOWER
PRIORITY
PARTITION/
BARRIER -
11 ^ 91
TAPE & SEAL HIGHER PRIORITY WALL/
PARTITION /BARRIER EVEN WHEN HIDDEN
BEHIND INTERSECTING LOWER PRIORITY
PARTITION /BARRIER (TYPICAL)
TAPE Ec JOINT COMPOUND (TYPICAL)
HIGHER PRIORITY WALL /PARTITION /BARRIER
HIGHER PRIORITY WALL/
PARTITION /BARRIER
TAPE Et JOINT
COMPOUND
(TYPICAL)
LOWER PRIORITY
PARTITION /BARRIER
"D"
\ --TAPE & JOINT
"Ell COMPOUND (TYPICAL)
HIGHER PRIORITY WALL/
PARTITION /BARRIER
"B it
LOWER PRIORITY
PARTITION /BARRIER
TAPE AND SEAL BEHIND
INTERSECTING LOWER
PRIORITY PARTITION/
BARRIER (TYPICAL)
HIGHER PRIORITY WALL/
PARTITION /BARRIER
TAPE & SEAL HIGHER
PRIORITY WALL/
PARTITION /BARRIER
BEHIND INTERSECTING
LOWER PRIORITY
PARTITION /BARRIER
_ (TYPICAL)
LOWER PRIORITY
PARTITION /BARRIER
NOTES-
1. REFER TO FLOOR PLANS AND TO "WALLS /PARTITIONS /BARRIERS LEGEND" ON PROJECT
INFORMATION SHEET A8.1 FOR NUMBER OF LAYERS & TYPE OF GYPSUM BOARD AND FOR
REQUIRED TYPE AND THICKNESS OF SOUND ATTENUATION BLANKETS.
2. THE HIGHER PRIORITY WALL /BARRIER /PARTITION SHALL ALWAYS PASS CONTINUOUSLY
THROUGH THE LOWER PRIORITY BARRIER /PARTITION
3. TAPE AND SEAL ALL JOINTS IN GYPSUM BOARD IN HIGHER PRIORITY WALLS /PARTITIONS/
BARRIERS EVEN WHEN JOINT IS HIDDEN BEHIND INTERSECTING OR ABUTTING LOWER PRIORITY
BARRIERS /PARTITIONS
4. ALTERNATE LAYERS OF GYPSUM BOARD SHALL OVERLAP AT CORNER INTERSECTIONS OF
MULTI - LAYERED RATED GYPSUM BOARD WALLS /BARRIERS
5. SEE DETAIL 2/A8.3 "PRIORITY LEGEND FOR ABUTMENT OF DIFFERING WALLS /PARTITIONS/
BARRIERS"
6. CRITICAL: THESE DETAILS APPLY TO BOTH "FIRE RATING PRIORITY" AND TO "SOUND
TRANSMISSION CLASS [STC] PRIORITY"
DETAI L INTERSECTION OF DIFFERING PRIORITY
NOT TO SCALE WALLS /PARTITIONS /BARRIERS
wvwo wow • 0 00000 000
•
•
WALLS/PARTITIONS/BARRIERS LEGEND*...' •
GENERAL NOTES FOR WALLS /PARTITIONS /BARRIERS •y
1. EACH INDIVIDUAL WALL /PARTITION /BARRIER ASSEMBLY SHALL COMPLY WITH THE TESTED ASSEMBLY REFERENCED BELOW. • +• •'.
2. ALL ASSEMBLIES USING GYPSUM BOARD: COMPLY WITH THE MOST STRINGENT OF THE REQUIREMENTS OF THE MOST CURRENT EDITION
OF THE UNDERWRITERS LABORATORIES U.L. FIRE RESISTANCE DIRECTORY AND THE MOST CURRENT EDITION OF THE "GYPSUM ASSOC.ADON ..
GA -600 FIRE RESISTANCE DESIGN MANUAL ". SEE DETAIL 5/A8.1 "LOCATION OF JOINTS IN GYPSUM BOARD WALLS /PARTITIONS /BARRIER '
FOR DETAILS PERTAINING TO METAL STUD AND GYPSUM BOARD WALLS, SEE SPECIFICATIONS IN THE PROJECT MANUAL AND DETAILS IN
THESE DRAWINGS FOR REQUIRED GAGE OF METAL STUDS. 0.00 • •.
3. HEAD OF WALLS: WALLS /PARTITIONS /BARRIERS THAT ARE REQUIRED TO EXTEND TO THE DECK ABOVE SHALL HAVE ALL LAYERS OF
THE GYPSUM BOARD CUT TO FIT WITHIN 1/2 INCH OF THE SHAPE OF THE DECK ABOVE. ALL LAYERS OF THE GYPSUM BOARD SHALL
BE SEALED FOR THE FULL DEPTH OF THE GYPSUM BOARDS WITH FLEXIBLE SEALANT PER GA- 600 -03 FIRE RESISTANCE DESIGN
MANUAL (FIGURE 9). THIS GAP SHALL BE SEALED AIR -TIGHT AND SOUND- TIGHT. (A) AT ALL RATED WALLS /BARRIERS, PROVIDE AN
APPROVED U.L. TESTED FIRE - RESISTANT JOINT SYSTEM TO COMPLY WITH NOTE 6 BELOW.
4. PENETRATIONS: THE GYPSUM BOARD SHALL BE CUT SO THAT THE CLEARANCE BETWEEN METALLIC ELECTRICAL OUTLET BOXES AND
THE GYPSUM BOARD DOES NOT EXCEED 1/8 INCH. SEE DETAIL 3/A8.1 "METALLIC ELECTRICAL OUTLET BOXES RECESSED IN RATED
FIRE BARRIERS AND /OR RATED SMOKE BARRIERS . THE GYPSUM BOARD SHALL BE CUT TO FIT WITHIN A 1/4 INCH MAXIMUM TOLERANCE
AROUND ALL OTHER PENETRATIONS AND SHALL BE SEALED FOR THE FULL DEPTH OF THE GYPSUM BOARD WITH FLEXIBLE SEALANT. THE
GAPS AROUND ALL PENETRATIONS SHALL BE SEALED AIR -TIGHT AND SOUND- TIGHT. COMPLY WITH NOTE 6 BELOW.
(A) AT ALL RATED WALLS /BARRIERS, IF AT ANY POINT AROUND THE PENETRATION THE GAP IS GREATER THAN INDICATED HEREIN,
PROVIDE AN APPROVED U.L. TESTED "THROUGH - PENETRATION FIRESTOP SYSTEM" TO COMPLY WITH NOTE 6 BELOW, AND COMPLY
WITH SPECIFICATION SECTION 07 8413.
(B) IN HEALTH CARE FACILITIES, SEAL PENETRATIONS THROUGH BOTH RATED BARRIERS AND NON -RATED PARTITIONS TO COMPLY
WITH SOUND TRANSMISSION LIMITATIONS PER NOTE 7 BELOW AND WITH THE "2006 GUIDELINES FOR DESIGN AND CONSTRUCTION
OF HEALTH CARE FACILITIES" SECTION 8.2.3.5.
5, BOTTOM OF WALLS: THE GAP AT THE BOTTOM OF THE GYPSUM BOARD ON ALL WALLS SHALL BE 1/4 INCH MINIMUM AND 1/2
INCH MAXIMUM ABOVE THE CONCRETE FLOOR SLAB, AND IT SHALL BE SEALED FOR THE FULL DEPTH OF THE GYPSUM BOARD WITH
FLEXIBLE SEALANT. THIS GAP SHALL BE SEALED AIR -TIGHT AND SOUND- TIGHT.
(A) AT ALL RATED WALLS /BARRIERS WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IF THE GAP IS GREATER THAN,
1/2 INCH AT ANY POINT ALONG THE BOTTOM OF A RATED WALL /BARRIER, PROVIDE AN APPROVED U.L. TESTED "FIRE - RESISTANT '
JOINT SYSTEM" PER *IBC* *FBC * * --- * SECTION 713; AND COMPLY WITH SPECIFICATION SECTION 07 8446.
6, FOR ALL RATED WALLS /BARRIERS: PER THE REQUIREMENTS OF *IBC* *FBC * * --- * SECTIONS 712 AND 713, PROVIDE APPROVED
U.L. TESTED "FIRE- RESISTANT JOINT SYSTEM" OR "THROUGH- PENETRATION FIRESTOP SYSTEM" TO COMPLY WITH ALL REQUIREMENTS
OF EACH SPECIFIC CONDITION AS APPROPRIATE FOR ALL ADJACENT BUILDING COMPONENTS PER THE REQUIREMENTS OF THE
MOST CURRENT EDITION OF THE . FIRE RESISTANCE DIRECTORY - VOLUME 2A ", AND COMPLY WITH REQUIREMENTS OF
SPECIFICATION SECTION 07 8413 "PENETRATION FIRESTOPPING" AND SPECIFICATION SECTION 07 8446 "FIRE- RESISTIVE JOINT SYSTEMS ".
7. SOUND TRANSMISSION LIMITATIONS:
(A) SEE THE NEW CONSTRUCTION FLOOR PLANS FOR NOTES AND KEYNOTES THAT PROVIDE ADDITIONAL INFORMATION REGARDING
REQUIRED STC RATINGS.
(B) IN HOSPITALS, COMPLY WITH *TABLE 2.1- -1 "SOUND TRANSMISSION LIMITATIONS IN GENERAL HOSPITALS" IN THE "2006
GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES ".* *TABLE 2.2 -1 "SOUND TRANSMISSION LIMITATIONS
IN GENERAL HOSPITALS" IN THE "2001 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND HEALTH CARE
FACILITIES.* * ------- *
TWO -HOUR RATED FIRE BARRIER
3 5/8" (MINIMUM) METAL STUDS AT V -4" MAXIMUM O.C. (UNLESS CLOSER
SPACING IS INDICATED).COMPLY WITH
REQUIREMENTS OF "GENERAL NOTES FOR WALLS /PARTITIONS /BARRIERS" ABOVE.
THIS FIRE BARRIER SHALL ALSO COMPLY WITH THE REQUIREMENTS OF U.L.
DESIGN NUMBER U411, 2006 NFPA 101 LIFE SAFETY CODE SECTION
7.2.4.3 AND 2006 IBC SECTIONS 706, 708, 712 & 713. 2007
FLORIDA EDITION OF NFPA 101 LIFE SAFETY CODE SECTION 7.2.4.3 AND
2007 (W/ 2009) FBC SECTIONS 706, 708, 712 do 713.
5/8" TYPE "X" GYPSUM BOARD SHALL BE APPLIED VERTICALLY IN TWO LAYERS
ON EACH SIDE. ATTACH ALL GYPSUM BOARD TO METAL STUDS WITH TYPE "S"
STEEL SCREWS TO COMPLY WITH REFERENCED U.L. DESIGN NUMBER. STAGGER
ALL VERTICAL FACE LAYER AND BASE LAYER JOINTS V -4" MINIMUM O.C. AND
STAGGER ALL HORIZONTAL JOINTS 2' -0" MINIMUM O.C. ALL HORIZONTAL JOINTS
SHALL OCCUR ABOVE THE CEILING.
SEAL EACH LAYER OF GYPSUM BOARD TO FLOOR SLAB BELOW PER GENERAL
NOTES 5 do 6 ABOVE. EXTEND EACH LAYER OF GYPSUM BOARD TO DECK ABOVE
AND SEAL EACH LAYER OF GYPSUM BOARD TO DECK PER GENERAL NOTES 3 do
6 ABOVE. SEAL ALL PENETRATIONS PER GENERAL NOTES 4 & 6 ABOVE. USE
DETAIL 1/A8.1 "PATCHING AND SEALING PENETRATIONS IN RATED FIRE BARRIERS
AND /OR RATED SMOKE BARRIERS" ONLY IF PRE - APPROVED BY ALL AUTHORITIES
HAVING JURISDICTION.
INSTALL 3" MINIMUM SOUND ATTENUATION BLANKETS FROM FLOOR TO DECK.
SEE SPECIFICATION FOR SIZE AND TYPE. COMPLY WITH GENERAL NOTE 7
ABOVE REGARDING SOUND TRANSMISSION LIMITATIONS.
TWO -HOUR RATED (CMU) FIRE BARRIER
�,v�� �'%M
UNDER WALLS/PARTITIONS/ - i i
I - -
i 1 i - -
� ����tiC�
ONLY CLASSIFICATION D LAID OF MORTAR
BARRIERS LEGEND ". SEAL ALL
DETAIL 3M�E. COMPLY WITBHDT E
REQUIREMENTS OF "GENERAL NOTES FOR WALLS /PARTITIONS /BARRIERS" ABOVE.
0t�,p�tt�',
THIS FIRE BARRIER SHALL ALSO COMPLY WITH THE REQUIREMENTS OF U.L. DESIGN
AND
Co ,
"HEAD -OF- WALLS" BOTH
�T,h ,/p�3..Q�� --'
2006 IBC SECTIONS 706, 708, 712 & 713. 2007
C�
G
OF NFPA 101 LIFE SAFETY CODE SECTION 7.2.4.3 AND 2007 (W/ 2009) FBC
-2
AIR -TIGHT AND SOUND- TIGHT.
t�..
EXTEND CMU FIRE BARRIER TO DECK ABOVE AND SEAL WITH APPROVED U.L.
"HEAD -OF -WALL JOINT SYSTEM." SEAL ALL PENETRATIONS WITH APPROVED U.L.
r-�- FL
"THROUGH- PENETRATION FIRESTOP SYSTEM."
SEE FLOOR PLANS FOR LOCATIONS WHERE FURRING IS REQUIRED.
FLOOR OR ROOF ASSEMBLY PER U.L.
N
PROVIDE 3" MINIMUM FULL -
NUMBER (SEE THE "PLAN REVIEW
DATA" ON PROJECT INFORMATION
HEIGHT SOUND ATTENUATION
SHEET X1.1 FOR THE DESIGNATED
BLANKETS WHERE INDICATED
U.L. DESIGN NUMBER FOR THE
AND /OR WHERE AN STC
RATING IS REQUIRED
FLOOR AND ROOF ASSEMBLIES)
FINISH CEILING --
MINIMUM OF TWO LAYERS OF 5/8"
TYPE "X" GYPSUM BOARD ON EACH
METAL STUD RUNNERS
SIDE - ATTACHED TO COMPLY WITH
DESIGNATED TESTED ASSEMBLY
SHALL BE ATTACHED TO
(COMPLY WITH NOTE 4 FOR RATED
COMPLY WITH DESIGNATED
LEAD -LINED BARRIERS)
TESTED ASSEMBLY.
WHERE AN STC RATING IS
f-AT
3 5/8" (MINIMUM) METAL STUDS
REQUIRED, THE RUNNERS
16" O.C. (MAXIMUM)
SHALL BE SET IN TWO
CONTINUOUS BEADS OF
1/4" MINIMUM/ 112" MAXIMUM GAP -
ACOUSTICAL SEALANT.
SEAL EACH LAYER OF GYPSUM BOARD
(ON EACH SIDE OF BARRIER) TO
CONCRETE SLAB WITH FLEXIBLE SEALANT
CONCRETE FLOOR SLAB
TO PROVIDE AIR -TIGHT AND SOUND -TIGHT
CONDITION. IF THE GAP IS LARGER THAN
1/2 ", SEAL THE BOTTOM OF THE BARRIER
WITH AN APPROVED "FIRE- RESISTANT
JOINT SYSTEM" PER NOTE 2 ABOVE.
DETAIL TWO
-HOUR
RATED FIRE BARRIER OR
NOT TO SCALE TWO --HOUR
RATED SMOKE BARRIER
NOTES:
1. SEE "WALLS /PARTITIONS /BARRIERS LEGEND" ON PROJECT INFORMATION SHEET A8.1 FOR
ADDITIONAL REQUIREMENTS FOR THIS BARRIER, AND COMPLY WITH ALL REQUIREMENTS OF THE
DESIGNATED TESTED ASSEMBLY REFERENCED IN THE "WALLS /PARTITIONS /BARRIERS LEGEND"
ON PROJECT INFORMATION SHEET A8.1.
2. COMPLY WITH ALL REQUIREMENTS OF THE FBC SECTION 713 -FIRE RESISTANT
JOINT SYSTEMS. ALL JOINTS INSTALLED IN OR BETWEEN FIRE - RESISTANCE -RATED WALLS/
BARRIERS OR FLOOR ASSEMBLIES AND ROOF ASSEMBLIES SHALL BE PROTECTED BY AN
APPROVED "FIRE- RESISTANT JOINT SYSTEM" DESIGNED TO RESIST THE PASSAGE OF FIRE
FOR A TIME PERIOD NOT LESS THAN THE REQUIRED FIRE - RESISTANCE RATING OF THE
WALL /BARRIER, FLOOR OR ROOF IN OR BETWEEN WHICH IT IS INSTALLED. FIRE - RESISTANT
JOINT SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF EITHER
ASTM E 1966 OR UL 2079. COMPLY WITH REQUIREMENTS OF SPECIFICATION SECTION 07 8446.
3, IN HEALTH CARE FACILITIES, EVEN IN NON -RATED CMU PARTITIONS, SEAL ALL PENETRATIONS
TO COMPLY WITH 2006 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE
FACILITIES SECTION 2.1- 8.2.3.5.
4. WHERE INDICATED AND /OR REQUIRED, PROVIDE CONCRETE MASONRY UNITS THAT WILL
PROVIDE THE REQUIRED STC RATING. USE "SOUNDBLOX" THAT IS TESTED FOR BOTH THE
REQUIRED FIRE RATING AND THE REQUIRED STC RATING. SEE SPECIFICATIONS.
I
,tql
FLOOR OR ROOF ASSEMBLY PER U.L. DESIGN
NUMBER (SEE THE PLAN REVIEW DATA ON SHEET
X1.1 FOR THE DESIGNATED U.L. DESIGN NUMBER
FOR THE FLOOR AND ROOF ASSEMBLIES)
PROVIDE APPROVED "FIRE- RESISTANT JOINT SYSTEM"
PER NOTE 2 ABOVE. ALSO, COMPLY WITH REQUIREMENTS
INDICATED ON PROJECT INFORMATION SHEET X1.1 UNDER
"WALLS /PARTITIONS /BARRIERS LEGEND ". SEAL ALL
"HEAD -OF- WALLS" BOTH AIR -TIGHT AND SOUND- TIGHT.
STRUCTURAL BRACE (SEE STRUCTURAL FOR TYPE,
SIZE AND LOCATIONS OF BRACES)
RATED CONCRETE MASONRY UNITS. SEE FLOOR PLANS
AND "WALLS /PARTITIONS /BARRIERS LEGEND" ON
SHEET X1.1 FOR SIZE AND RATING OF CONCRETE
MASONRY UNITS. SEE STRUCTURAL DRAWINGS FOR
REINFORCEMENT OF CMU. ALSO, SEE NOTE 4 ABOVE.
RAKE MORTAR JOINT AND ADD CONTINUOUS
ACOUSTICAL SEALANT BEAD
CONCRETE FLOOR SLAB
SEE STRUCTURAL FOR CONNECTION OF CMU AND
ITS REINFORCMENT INTO CONCRETE FLOOR SLAB
RATED FIRE BARRIER AND /OR
DETAIL RATED SMOKE BARRIER USING
NOT TO SCALE CONCRETE MASONRY UNITS [CMU]
TAPE 1. JOINT COMPOUND (TYPICAL)
LOWER PRIORITY PARTITION /BARRIER
LOWER
PRIORITY
PARTITION/
BARRIER -
11 ^ 91
TAPE & SEAL HIGHER PRIORITY WALL/
PARTITION /BARRIER EVEN WHEN HIDDEN
BEHIND INTERSECTING LOWER PRIORITY
PARTITION /BARRIER (TYPICAL)
TAPE Ec JOINT COMPOUND (TYPICAL)
HIGHER PRIORITY WALL /PARTITION /BARRIER
HIGHER PRIORITY WALL/
PARTITION /BARRIER
TAPE Et JOINT
COMPOUND
(TYPICAL)
LOWER PRIORITY
PARTITION /BARRIER
"D"
\ --TAPE & JOINT
"Ell COMPOUND (TYPICAL)
HIGHER PRIORITY WALL/
PARTITION /BARRIER
"B it
LOWER PRIORITY
PARTITION /BARRIER
TAPE AND SEAL BEHIND
INTERSECTING LOWER
PRIORITY PARTITION/
BARRIER (TYPICAL)
HIGHER PRIORITY WALL/
PARTITION /BARRIER
TAPE & SEAL HIGHER
PRIORITY WALL/
PARTITION /BARRIER
BEHIND INTERSECTING
LOWER PRIORITY
PARTITION /BARRIER
_ (TYPICAL)
LOWER PRIORITY
PARTITION /BARRIER
NOTES-
1. REFER TO FLOOR PLANS AND TO "WALLS /PARTITIONS /BARRIERS LEGEND" ON PROJECT
INFORMATION SHEET A8.1 FOR NUMBER OF LAYERS & TYPE OF GYPSUM BOARD AND FOR
REQUIRED TYPE AND THICKNESS OF SOUND ATTENUATION BLANKETS.
2. THE HIGHER PRIORITY WALL /BARRIER /PARTITION SHALL ALWAYS PASS CONTINUOUSLY
THROUGH THE LOWER PRIORITY BARRIER /PARTITION
3. TAPE AND SEAL ALL JOINTS IN GYPSUM BOARD IN HIGHER PRIORITY WALLS /PARTITIONS/
BARRIERS EVEN WHEN JOINT IS HIDDEN BEHIND INTERSECTING OR ABUTTING LOWER PRIORITY
BARRIERS /PARTITIONS
4. ALTERNATE LAYERS OF GYPSUM BOARD SHALL OVERLAP AT CORNER INTERSECTIONS OF
MULTI - LAYERED RATED GYPSUM BOARD WALLS /BARRIERS
5. SEE DETAIL 2/A8.3 "PRIORITY LEGEND FOR ABUTMENT OF DIFFERING WALLS /PARTITIONS/
BARRIERS"
6. CRITICAL: THESE DETAILS APPLY TO BOTH "FIRE RATING PRIORITY" AND TO "SOUND
TRANSMISSION CLASS [STC] PRIORITY"
DETAI L INTERSECTION OF DIFFERING PRIORITY
NOT TO SCALE WALLS /PARTITIONS /BARRIERS
wvwo wow • 0 00000 000
•
•
WALLS/PARTITIONS/BARRIERS LEGEND*...' •
GENERAL NOTES FOR WALLS /PARTITIONS /BARRIERS •y
1. EACH INDIVIDUAL WALL /PARTITION /BARRIER ASSEMBLY SHALL COMPLY WITH THE TESTED ASSEMBLY REFERENCED BELOW. • +• •'.
2. ALL ASSEMBLIES USING GYPSUM BOARD: COMPLY WITH THE MOST STRINGENT OF THE REQUIREMENTS OF THE MOST CURRENT EDITION
OF THE UNDERWRITERS LABORATORIES U.L. FIRE RESISTANCE DIRECTORY AND THE MOST CURRENT EDITION OF THE "GYPSUM ASSOC.ADON ..
GA -600 FIRE RESISTANCE DESIGN MANUAL ". SEE DETAIL 5/A8.1 "LOCATION OF JOINTS IN GYPSUM BOARD WALLS /PARTITIONS /BARRIER '
FOR DETAILS PERTAINING TO METAL STUD AND GYPSUM BOARD WALLS, SEE SPECIFICATIONS IN THE PROJECT MANUAL AND DETAILS IN
THESE DRAWINGS FOR REQUIRED GAGE OF METAL STUDS. 0.00 • •.
3. HEAD OF WALLS: WALLS /PARTITIONS /BARRIERS THAT ARE REQUIRED TO EXTEND TO THE DECK ABOVE SHALL HAVE ALL LAYERS OF
THE GYPSUM BOARD CUT TO FIT WITHIN 1/2 INCH OF THE SHAPE OF THE DECK ABOVE. ALL LAYERS OF THE GYPSUM BOARD SHALL
BE SEALED FOR THE FULL DEPTH OF THE GYPSUM BOARDS WITH FLEXIBLE SEALANT PER GA- 600 -03 FIRE RESISTANCE DESIGN
MANUAL (FIGURE 9). THIS GAP SHALL BE SEALED AIR -TIGHT AND SOUND- TIGHT. (A) AT ALL RATED WALLS /BARRIERS, PROVIDE AN
APPROVED U.L. TESTED FIRE - RESISTANT JOINT SYSTEM TO COMPLY WITH NOTE 6 BELOW.
4. PENETRATIONS: THE GYPSUM BOARD SHALL BE CUT SO THAT THE CLEARANCE BETWEEN METALLIC ELECTRICAL OUTLET BOXES AND
THE GYPSUM BOARD DOES NOT EXCEED 1/8 INCH. SEE DETAIL 3/A8.1 "METALLIC ELECTRICAL OUTLET BOXES RECESSED IN RATED
FIRE BARRIERS AND /OR RATED SMOKE BARRIERS . THE GYPSUM BOARD SHALL BE CUT TO FIT WITHIN A 1/4 INCH MAXIMUM TOLERANCE
AROUND ALL OTHER PENETRATIONS AND SHALL BE SEALED FOR THE FULL DEPTH OF THE GYPSUM BOARD WITH FLEXIBLE SEALANT. THE
GAPS AROUND ALL PENETRATIONS SHALL BE SEALED AIR -TIGHT AND SOUND- TIGHT. COMPLY WITH NOTE 6 BELOW.
(A) AT ALL RATED WALLS /BARRIERS, IF AT ANY POINT AROUND THE PENETRATION THE GAP IS GREATER THAN INDICATED HEREIN,
PROVIDE AN APPROVED U.L. TESTED "THROUGH - PENETRATION FIRESTOP SYSTEM" TO COMPLY WITH NOTE 6 BELOW, AND COMPLY
WITH SPECIFICATION SECTION 07 8413.
(B) IN HEALTH CARE FACILITIES, SEAL PENETRATIONS THROUGH BOTH RATED BARRIERS AND NON -RATED PARTITIONS TO COMPLY
WITH SOUND TRANSMISSION LIMITATIONS PER NOTE 7 BELOW AND WITH THE "2006 GUIDELINES FOR DESIGN AND CONSTRUCTION
OF HEALTH CARE FACILITIES" SECTION 8.2.3.5.
5, BOTTOM OF WALLS: THE GAP AT THE BOTTOM OF THE GYPSUM BOARD ON ALL WALLS SHALL BE 1/4 INCH MINIMUM AND 1/2
INCH MAXIMUM ABOVE THE CONCRETE FLOOR SLAB, AND IT SHALL BE SEALED FOR THE FULL DEPTH OF THE GYPSUM BOARD WITH
FLEXIBLE SEALANT. THIS GAP SHALL BE SEALED AIR -TIGHT AND SOUND- TIGHT.
(A) AT ALL RATED WALLS /BARRIERS WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IF THE GAP IS GREATER THAN,
1/2 INCH AT ANY POINT ALONG THE BOTTOM OF A RATED WALL /BARRIER, PROVIDE AN APPROVED U.L. TESTED "FIRE - RESISTANT '
JOINT SYSTEM" PER *IBC* *FBC * * --- * SECTION 713; AND COMPLY WITH SPECIFICATION SECTION 07 8446.
6, FOR ALL RATED WALLS /BARRIERS: PER THE REQUIREMENTS OF *IBC* *FBC * * --- * SECTIONS 712 AND 713, PROVIDE APPROVED
U.L. TESTED "FIRE- RESISTANT JOINT SYSTEM" OR "THROUGH- PENETRATION FIRESTOP SYSTEM" TO COMPLY WITH ALL REQUIREMENTS
OF EACH SPECIFIC CONDITION AS APPROPRIATE FOR ALL ADJACENT BUILDING COMPONENTS PER THE REQUIREMENTS OF THE
MOST CURRENT EDITION OF THE . FIRE RESISTANCE DIRECTORY - VOLUME 2A ", AND COMPLY WITH REQUIREMENTS OF
SPECIFICATION SECTION 07 8413 "PENETRATION FIRESTOPPING" AND SPECIFICATION SECTION 07 8446 "FIRE- RESISTIVE JOINT SYSTEMS ".
7. SOUND TRANSMISSION LIMITATIONS:
(A) SEE THE NEW CONSTRUCTION FLOOR PLANS FOR NOTES AND KEYNOTES THAT PROVIDE ADDITIONAL INFORMATION REGARDING
REQUIRED STC RATINGS.
(B) IN HOSPITALS, COMPLY WITH *TABLE 2.1- -1 "SOUND TRANSMISSION LIMITATIONS IN GENERAL HOSPITALS" IN THE "2006
GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES ".* *TABLE 2.2 -1 "SOUND TRANSMISSION LIMITATIONS
IN GENERAL HOSPITALS" IN THE "2001 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND HEALTH CARE
FACILITIES.* * ------- *
TWO -HOUR RATED FIRE BARRIER
3 5/8" (MINIMUM) METAL STUDS AT V -4" MAXIMUM O.C. (UNLESS CLOSER
SPACING IS INDICATED).COMPLY WITH
REQUIREMENTS OF "GENERAL NOTES FOR WALLS /PARTITIONS /BARRIERS" ABOVE.
THIS FIRE BARRIER SHALL ALSO COMPLY WITH THE REQUIREMENTS OF U.L.
DESIGN NUMBER U411, 2006 NFPA 101 LIFE SAFETY CODE SECTION
7.2.4.3 AND 2006 IBC SECTIONS 706, 708, 712 & 713. 2007
FLORIDA EDITION OF NFPA 101 LIFE SAFETY CODE SECTION 7.2.4.3 AND
2007 (W/ 2009) FBC SECTIONS 706, 708, 712 do 713.
5/8" TYPE "X" GYPSUM BOARD SHALL BE APPLIED VERTICALLY IN TWO LAYERS
ON EACH SIDE. ATTACH ALL GYPSUM BOARD TO METAL STUDS WITH TYPE "S"
STEEL SCREWS TO COMPLY WITH REFERENCED U.L. DESIGN NUMBER. STAGGER
ALL VERTICAL FACE LAYER AND BASE LAYER JOINTS V -4" MINIMUM O.C. AND
STAGGER ALL HORIZONTAL JOINTS 2' -0" MINIMUM O.C. ALL HORIZONTAL JOINTS
SHALL OCCUR ABOVE THE CEILING.
SEAL EACH LAYER OF GYPSUM BOARD TO FLOOR SLAB BELOW PER GENERAL
NOTES 5 do 6 ABOVE. EXTEND EACH LAYER OF GYPSUM BOARD TO DECK ABOVE
AND SEAL EACH LAYER OF GYPSUM BOARD TO DECK PER GENERAL NOTES 3 do
6 ABOVE. SEAL ALL PENETRATIONS PER GENERAL NOTES 4 & 6 ABOVE. USE
DETAIL 1/A8.1 "PATCHING AND SEALING PENETRATIONS IN RATED FIRE BARRIERS
AND /OR RATED SMOKE BARRIERS" ONLY IF PRE - APPROVED BY ALL AUTHORITIES
HAVING JURISDICTION.
INSTALL 3" MINIMUM SOUND ATTENUATION BLANKETS FROM FLOOR TO DECK.
SEE SPECIFICATION FOR SIZE AND TYPE. COMPLY WITH GENERAL NOTE 7
ABOVE REGARDING SOUND TRANSMISSION LIMITATIONS.
TWO -HOUR RATED (CMU) FIRE BARRIER
�,v�� �'%M
0
8" MINIMUM WIDTH x 8" x 16" (NOMINAL) CMU. (SEE DRAWINGS FOR WIDTHS.)
WITH VERTICAL
� ����tiC�
ONLY CLASSIFICATION D LAID OF MORTAR
Ct�Ot�
DETAIL 3M�E. COMPLY WITBHDT E
REQUIREMENTS OF "GENERAL NOTES FOR WALLS /PARTITIONS /BARRIERS" ABOVE.
0t�,p�tt�',
THIS FIRE BARRIER SHALL ALSO COMPLY WITH THE REQUIREMENTS OF U.L. DESIGN
AND
Co ,
NUMBER U905, 2006 NFPA 101 LIFE SAFETY CODE SECTION 7.2.4.3
FLORIDA EDITION
�T,h ,/p�3..Q�� --'
2006 IBC SECTIONS 706, 708, 712 & 713. 2007
C�
G
OF NFPA 101 LIFE SAFETY CODE SECTION 7.2.4.3 AND 2007 (W/ 2009) FBC
-2
SECTIONS 706, 708, 712 do 713.
t�..
EXTEND CMU FIRE BARRIER TO DECK ABOVE AND SEAL WITH APPROVED U.L.
"HEAD -OF -WALL JOINT SYSTEM." SEAL ALL PENETRATIONS WITH APPROVED U.L.
r-�- FL
"THROUGH- PENETRATION FIRESTOP SYSTEM."
SEE FLOOR PLANS FOR LOCATIONS WHERE FURRING IS REQUIRED.
NON- -RATED PARTITION TO
4 INCHES MINIMUM ABOVE CEILING * **
3 5/8" (MINIMUM) METAL STUDS AT V -4" MAXIMUM O.C. (UNLESS CLOSER
SPACING IS INDICATED) FROM FLOOR SLAB TO DECK ABOVE. COMPLY WITH
REQUIREMENTS OF "GENERAL NOTES FOR WALLS /PARTITIONS /BARRIERS" ABOVE.
MINIMUM OF ONE LAYER 5/8" TYPE "X" GYPSUM BOARD EACH SIDE, APPLIED
VERTICALLY TO 4" MINIMUM ABOVE THE CEILING. HORIZONTAL JOINTS SHALL
OCCUR ABOVE THE CEILING. SEAL ALL JOINTS AND PENETRATIONS WITH FLEXIBLE
SEALANT TO BE AIR -TIGHT AND SOUND- TIGHT.
WHEN AN STC RATING IS REQUIRED AND /OR INDICATED TO BE USED, PROVIDE
3" MINIMUM SOUND ATTENUATION BLANKETS AND A MINIMUM OF ONE LAYER OF
GYPSUM BOARD ON EACH SIDE OF THE PARTITION (UP TO DECK ABOVE), STAGGER
ALL VERTICAL JOINTS 1 ` -6" MINIMUM O.C. AND STAGGER HORIZONTAL JOINTS 2' -0"
O.C. MINIMUM, AND COMPLY WITH GENERAL NOTE 7 ABOVE REGARDING SOUND
TRANSMISSION LIMITATIONS.
WHEN SOUND ATTENUATION BLANKETS ARE INDICATED TO BE USED, BUT AN STC
RATING IS NOT REQUIRED, PROVIDE A MINIMUM OF ONE LAYER OF GYPSUM BOARD
ON AT LEAST ONE SIDE OF THE PARTITION (UP TO DECK ABOVE).
CITY OF SOUTH MIAMI
BUILDING DEPT.
STRUCTURAL �:CTION
#"PROVED QY. _,
ENGINEERING
FOR ARCHITECTURE
255 S. Orange Avenue
Suite 1600
Orlando, Florida 32801
PH: 407.841.9050
www.tic- engineers.com
EB #0000015
O Copyright 2009 TLC Engineering for Architecture, Inc.
%0
Consultant:
G R E S H A M
SMITH AND
P A R T N E R S
6030 Hollywood Blvd.
Suite 210
Hollywood, Florida 33024
954.981.9100
FIRM'S FLORIDA
CERT. NO.
AAP000034 /EB0003806
IB26000797
Revisions:
No. Date Description
Seal LUIS CANO
AR- 0015894
f •... ,
Project No.: 109355
Issue Date:
10/09/2009
Drawn By:
Approved By.
Scale:
Drawing Title:
MISCELLANEOUS
DETAILS
j
Drawing No.:
II.
0
2
M
•rte
E
E
T
U
cn co
C�
G
(�
-2
t�..
co O
r-�- FL
O
E
N
CID
Consultant:
G R E S H A M
SMITH AND
P A R T N E R S
6030 Hollywood Blvd.
Suite 210
Hollywood, Florida 33024
954.981.9100
FIRM'S FLORIDA
CERT. NO.
AAP000034 /EB0003806
IB26000797
Revisions:
No. Date Description
Seal LUIS CANO
AR- 0015894
f •... ,
Project No.: 109355
Issue Date:
10/09/2009
Drawn By:
Approved By.
Scale:
Drawing Title:
MISCELLANEOUS
DETAILS
j
Drawing No.:
II.