09-963-006a 0 H O J a ELECTRICAL ABBREVIATIONS ': AFC ELECTRICAL SYMBOLS N NEW DEVICE AFF ABOVE FINISHED FLOOR NC (N.C.) NORMALLY CLOSED GENERAL NOTES: AUTOMATIC TRANSFER SWITCH ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS. SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE. TE LE P H 0 N E DATA A. KAIC RATINGS SHALL MATCH LOWEST RATED DEVICE FOR NEW CIRCUIT BREAKERS TO BE INSTALLED LIGHTING BOTTOM OF FIXTURE NIC NOTIN CONTRACT C CONDUIT NL IN THE EXISTING PANELBOARDS. CB,C/B OR CIRCUIT BREAKER NO (N.O.) SYMBOL DESCRIPTION DEVICE MTG. HT. SYMBOL DESCRIPTION DEVICE MTG. HT. B. NOT USED. W CKT. ELSEWHERE ON THE PLAN CKT CIRCUIT 4' SQUARE BOX WITH SINGLE GANG ADAPTER FOR TELEPHONE OUTLETS. STUB C. CONTRACTOR SHALL REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATION OF LIGHT 'c � PB PULL BOX SEE FIXTURE O O 2'x2' / 2'x4' FLUORESCENT LIGHT FIXTURE ON NORMAL CIRCUIT. SCHEDULE AXT 3/4" C. ABOVE ACCESSIBLE CEILING FROM OUTLET BOX. "X" DENOTES QUATITY OF TELEPHONE (T) OUTLETS. 18" AFF D. FIXTURES AND ALL CEILING MOUNTED DEVICES. CONTRACTOR SHALL PROVIDE AND INSTALL AN IDENTIFICATION NAMEPLATE FOR EACH ELECTRICAL 7711 2'x2' / 2'x4' FLUORESCENT LIGHT FIXTURE ON CRITICAL CIRCUIT. SEE FIXTURE PWR POWER SCHEDULE CABINET HEATER EQUIPMENT /APPURTENANCE DEPICTING THE DESIGNATION INDICATED ON THE DRAWINGS. R RELOCATED DEVICE DFA 0 2'x2' / 2'x4' FLUORESCENT LIGHT FIXTURE ON LIFE SAFETY CIRCUIT. SEE FIXTURE SCHEDULE 4" SQUARE BOX WITH SINGLE GANG ADAPTER FOR DATA OUTLET. STUB 3/4" C. RECEPTACLE(S) EC EMPTY CONDUIT 10D ABOVE ACCESSIBLE CEILING FROM OUTLET BOX. "X" DENOTES QUANTITY OF DATA t8' AFF E. ALL EMPTY CONDUIT SYSTEMS SHALL CONTAIN A PULL WIRE FOR FUTURE PULLING OF CONDUCTORS. ELECTRIC 2'x4' FLUORESCENT LIGHT FIXTURE W/INBOARD LAMPS ON CRITICAL SEE FIXTURE p CIRCUIT AND OUTBOARD LAMPS ON NORMAL CIRCUIT. SCHEDULE EMERGENCY — RED (D), PACS (P), OR PATIENT MONITOR (PM) OUTLETS. F. CONTRACTOR SHALL COORDINATE ALL REQUIRED ENERGY MANAGEMENT SYSTEM POINTS AND CONTACT CONNECTIONS TO ENSURE THE COMPLETE AND PROPER OPERATION OF ALL SYSTEMS. .=ir= WALL MOUNTED FIXTURE ON NORMAL CIRCUIT. SEE FIXTURE v ENERGY MANAGEMENT SYSTEM SCHEDULE 4" SQUARE BOX WITH SINGLE GANG ADAPTER FOR TELEPHONE OUTLETS AND DATA 18" AFF G. CONTRACTOR SHALL PROVIDE AND INSTALL A 1" CONDUIT W /PULL WIRE FROM EACH WALL MOUNTED SUPPLY AIR FAN EP SEE FIXTURE WALL MOUNTED FIXTURE ON CRITICAL CIRCUIT. SCHEDULE '4XD/XT OUTLET. STUB 3/4" C. ABOVE ACCESSIBLE CEILING FROM OUTLET BOX. "X" DENOTES QUANTITY OF DATA (D), TELEPHONE (T), OR PACS (P) OUTLETS. SPACE ONLY TELEPHONE AND /OR DATA OUTLET STUB UP fi" ABOVE FINISHED CEILING. ELECTRIC WATER COOLER SEE FIXTURE c3r� i WALL MOUNTED FIXTURE ON LIFE SAFETY CIRCUIT. SCHEDULE SPARE EX H. THE CONTRACTOR SHALL COORDINATE WITH OTHER TRADES ALL NECESSARY WIRING AND CONNECTIONS REQUIRED PRIOR TO PULLING CONDUCTORS INTO NEW CONDUITS. SEE FIXTURE Q RECESSED /SUSPENDED DOWNLIGHT FIXTURE ON NORMAL CIRCUIT. SCHEDULE FUSE 4" SQUARE BOX WITH SINGLE GANG ADAPTER FOR ONE WALL MOUNTED SW SWITCH ♦w TELEPHONE OUTLET. STUB 3/4- C. ABOVE ACCESSIBLE CEILING FROM OUTLET BOX. 48" '� I. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT AND MATERIAL NECESSARY FOR A COMPLETE AND SEE FIXTURE ® RECESSED /SUSPENDED DOWNLIGHT FIXTURE ON CRITICAL CIRCUIT. SCHEDULE 4" SQUARE BOX WITH SINGLE GANG ADAPTER FOR PATIENT MONITOR OUTLET FOR TELEMETRY SYSTEM - STUB 3/4 C. ABOVE ACCESSIBLE CEILING FROM OUTLET BOX. " 60 J. OPERATIONAL INSTALLATION. CONTRACTOR SHALL NOT DISRUPT SERVICE TO ELECTRICAL APPURTENANCES TO REMAIN. TEL RECESSED /SUSPENDED DOWNLIGHT FIXTURE ON LIFE SAFETY CIRCUIT. SEE FIXTURE FAN COIL UNIT EDUILE QV 4" SQUARE BOX WITH SINGLE GANG ADAPTER (UNO) FOR VENDOR SUPPLIED CABLE AND 18. K. CONTRACTOR SHALL CONNECT ALL NEW FIRE ALARM DEVICES, AS INDICATED ON DRAWINGS, TO FIXT FIXTURE SEE 0 RECESSED DOWNLIGHT FIXTURE WITH WALL WASH TRIM. SCHEDULE TP OUTLET - STUB 3/4 C. ABOVE ACCESSIBLE CEILING FROM OUTLET BOX. STACKED DATA OUTLET BOXES OR THE LIKE THAT SHARE 3/4" C. STUB UP. 18" AFF EXISTING SYSTEM. CONTRACTOR SHALL PROVIDE NEW EXPANDABLE MODULES, CARDS, ETC. AS REQUIRED TO EXISTING SYSTEM IN ORDER TO ACCOMODATE NEW DEVICES. ' e Fo x CEILING OR WALL MOUNTED EXIT SIGN. SHADING INDICATES DOUBLE OR SEE FIXTURE SINGAL FACE ARROWS INDICATE CHEVRON DIRECTIONS. SCHEDULE ® FLOOR MOUNTED BOX FOR TWO TELEPHONE OUTLETS. STUB 3/4" C. UNDER FLOOR TO ABOVE ACCESSIBLE CEILING. 30" AFF L, FLUSH M. ALL PANELBOARDS SERVING THE AREA OF WORK SHALL BE BONDED TOGETHER IN COMPLIANCE WITH THE NEC. CONTRACTOR SHALL PROVIDE EQUIPOTENTIAL TEST FOR ALL ELECTRICAL DEVICES AND EQUIPMENT U WALL MOUNTED 90- MINUTE BATTERY - POWERED EGRESS LIGHTING. SCHEDULE FIXTURE 4� EXTERIOR POLE MOUNTED AREA LUMINAIRE. ARROW INDICATES DIRECTION OF SEE FIXTURE PHOTOMETRIC OPTIC ROTATION. SCHEDULE ® FLOOR MOUNTED BOX FOR TWO TELEPHONE OUTLETS. STUB 3/4" C. UNDER FLOOR TO ABOVE ACCESSIBLE CEILING. FLUSH WITHIN THE AREA OF WORK. FAN TERMINAL UNIT SEE FIXTURE �� TRACK LIGHTING SCHEDULE UNIT HEATER FLOOR MOUNTED BOX FOR ONE DATA OUTLET. STUB 3/4" C. UNDER FLOOR TO FLUSH N. ALL RECEPTACLES AND SWITCH PLATES SHALL HAVE ENGRAVED COVER PLATES TO INDICATE THE UNLESS NOTED OR INDICATED OTHERWISE GEF GENERAL EXHAUST FAN SWITCHES V VOLTAGE GEN ® ABOVE ACCESSIBLE CEILING. PANEL BOARD AND CIRCUIT NUMBERS POWERING THE DEVICE. VP VAPOR PROOF GFCI, GFl GROUND FAULT CIRCUIT INTERRUPTER ® FLOOR MOUNTED BOX FOR TWO TELEPHONE OUTLETS AND ONE DATA OUTLET. STUB 3/4" C. UNDER FLOOR TO ABOVE ACCESSIBLE CEILING. FLUSH 0. ALL EMERGENCY RECEPTACLES, LIGHT SWITCHES, AND RESPECTIVE COVER PLATES SHALL BE RED. VARIABLE VOLUME UNIT HP HORSE POWER SYMBOL DESCRIPTION DEVICE MTG. HT. ® FLOOR MOUNTED BOX FOR TWO TELEPHONE OUTLETS AND TWO DATA OUTLETS. STUB 3/4 C. UNDER FLOOR TO ABOVE ACCESSIBLE CEILING. "X" FLUSH P. THE ELECTRICAL CONTRACTOR SHALL VERIFY THAT THE AIC RATING OF ALL EXISTING CIRCUIT BREAKERS IN PANELS AFFECTED BY THIS PROJECT ARE ABOVE THE FAULT CURRENT VALUES HIGH VOLTAGE WALL SWITCH SPST, 204, 120/277V 48" AFF W/ WITH HWAT ®X FLOOR MOUNTED BOX FOR DATA OUTLET(S). INDICATES THE NUMBER OF OUTLETS F CEILING FLUSH PROVIDED IN THE SHORT CIRCUIT CALCULATIONS. IF THE AIC RATINGS ARE BELOW THE FAULT WG WIRE GUARD $2 DOUBLE POLE TOGGLE SWITCH, 20A/120/277V 48 " AFF AND CABLES STUB C. UNDER FLOOR TO ABOVE ACCESSIBLE . . CURRENT VALUES, THE ELECTRICAL CONTRACTOR SHALL REPLACE ALL BREAKERS WITH NEW WEATHER PROOF ICAND INCANDESCENT �} CEILING MOUNTED BOX FOR TWO TELEPHONE OUTLETS. STUB 3/4" C. ABOVE FLUSH BREAKERS WITH AIC RATINGS ABOVE THE FAULT CURRENT VALUES. WT WATER TIGHT IG $3 3 -WAY WAIL SWITCH, 20A, 120/277V 48" AFF Y ' ACCESSIBLE CEILING. XFMR TRANSFORMER JB JUNCTION BOX CEILING MOUNTED BOX FOR ONE DATA OUTLET. STUB 3/4" C. ABOVE ACCESSIBLE CEILING. CEILING MOUNTED BOX FOR TWO TELEPHONE OUTLETS AND ONE DATA OUTLET. Q. FLUSH FLUSH R. CONTRACTOR SHALL UPDATE ALL ELECTRICAL PANEL SCHEDULES AFFECTED BY THIS PROJECT. HAND WRITTEN SCHEDULES ARE NOT ACCEPTED. SCHEDULES SHALL BE TYPED OR COMPUTER GENERATED. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO CONNECT ANY NEW FIRE /SMOKE $4 4 -WAY WALL SWITCH, 20A, 120/277V 48" AFF $n WALL BOX DIMMER SWITCH 48" AFF LIGHTING LTS STUB 3/4" C. ABOVE ACCESSIBLE CEILING. DAMPERS TO THE EXISTING FIRE ALARM SYSTEM. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT LV KEY OPERATED WALL SWITCH 48' AFF K MAN MASTER ANTENNA CEILING MOUNTED BOX FOR TWO TELEPHONE OUTLETS AND TWO DATA OUTLETS. STUB 3/4" C. ABOVE ACCESSIBLE CEILING. FLUSH AND MATERIAL NECESSARY FOR A COMPLETE AND OPERATIONAL INSTALLATION. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF FIRE SMOKE DAMPERS. �T WALL SWITCH WITH ADJUSTABLE COUNTDOWN TIMER 48" AFF MOTOR CONTROL CENTER MDP CEILING MOUNTED BOX FOR DATA OUTLET(S). "X" INDICATES THE NUMBER OF FLUSH S. CONTRACTOR SHALL PATCH /RESTORE ALL WALL /FLOOR PENETRATIONS AS REQUIRED TO MH MANHOLE $3D 3 -WAY WAIL DIMMER SWITCH, 20A, 120/277v 48" AFF YX OUTLETS AND CABLES. STUB 3/4" C. ABOVE ACCESSIBLE CEILING. CEILING MOUNTED BOX FOR PATIENT MONITORING OUTLET FOR TELEMETRY SYSTEM. STUB 3/4" C. ABOVE ACCESSIBLE CEILING. FLUSH T. MAINTAIN /RESTORE ORIGINAL FIRE RATING. IT IS THE RESPONSIBILITY OF MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION CONTRACTORS TO VISIT THE SITE AND EXAMINE IN DETAIL THE SCOPE OF WORK OF THIS PROJECT $3K 3 -WAY, KEY OPERATED WALL SWITCH, 20A, 120/277V 48" AFF me MOMENTARY WALL SWITCH, 204, 120/277V 48" AFF PRIOR TO BID AND SHALL NOTIFY THE ARCHITECT AND /OR ENGINEER IF A CONDITION EXISTS WHICH PREVENTS HIM /HER FROM ACCOMPLISHING THE WORK INDICATED AND INTENDED BY THESE DRAWINGS, $LV LOW VOLTAGE WALL SWITCH 48" AFF SO NO ADDITIONAL COST IS INCURRED BY THE OWNER. AFTER CONTRACT IS AWARDED IT WILL BE ASSUMED THAT THE SITE WAS VISITED AND EXAMINED AND ALL PARTIES ARE IN AGREEMENT WITH THE $as WALL MOUNTED OCCUPANCY SENSOR SWITCH 48" AFF SCOPE OF THE WORK. WIRING DEVICES & POWER SYMBOL DESCRIPTION DEVICE MTG. HT. G_ SINGLE RECEPTACLE - 20A/125V/2P/3W/G NEMA 5-20R 18" AFF U.N.O. & DUPLEX RECEPTACLE - 20A/125V/2P/3W/G NEMA 5 -20R 18" AFF U.N.O. @ DUPLEX RECEPTACLE GFl - 20A/125V/2P/3W/G NEMA 5 -20R COUNTERTOP 6" ABO U N.o DUPLEX RECEPTACLE GA - 20A/125V/2P/3W/G NEMA 5 -20R 18" AFF U.N.O. DUPLEX RECEPTACLE GFl - 20A/125V/2P/3W/G NEMA 5 -20R 6" ABOVE COUNTERTOP U.N.O. QUADRAPLEX RECEPTACLE TWO DUPLEX RCPTS. UNDER ONE 18" AFF U.N.O. COVERPLATE QUADRAPLEX RECEPTACLE TWO DUPLEX RCPTS. UNDER ONE 6" ABOVE COUNTERTOP COVERPLATE U.N.O. �iiGFI uWITH DUPLEX RECEPTACLE GA - 20A/125V/2P/3W/G NEMA 5 -20R 18" AFF U.N.O. WEATHERPROOF ENCLOSURE t,o,l;FI DUPLEX RECEPTACLE GFl - 20A/125V/2P/3W/G NEMA 5-20R 18" AFF U.N.O. �°yyyy�P WITH WEATHERPROOF ENCLOSURE - ROOF MOUNTED 0 DUPLEX RECEPTACLE - 20A/125V/2P/3W/G NEMA 5-20R FLOOR MOUNTED - FLUSH MOUNTED UNO DUPLEX RECEPTACLE - 20A/125V/2P/3W/G NEMA 5-20R _ CEILING MOUNTED - FLUSH MOUNTED UNO ® SPECIAL PURPOSE RECEPTACLE (NEMA NO. AS INDICATED) 18" AFF U.N.O. Q F-Q JUNCTION BOX - SIZE AND MOUNTING AS REQUIRED - 39==MCT MULTIOUTLET ASSEMBLY - LENGTH AND OUTLET SPACING AS INDICATED - _J PANELBOARD - SURFACE MOUNTED 72" TO TOP IPP'7 PANELBOARD - FLUSH MOUNTED 72" TO TOP r--I 30/3 CIRCUIT BREAKER DISCONNECT SWITCH - THERMAL MAGNETIC +54" U.N.O. CB IN NEMA 1 ENCLOSURE U.N.O.• AMPS /POLES AS INDICATED DISCONNECTNSWIITCHH - 30/3 N #/1. INDICATES 3 A H POLE, +54" U.N.O. 30/3/ * /1 TYPE, F ®2 MOTOR STARTER FVNR UNO; NUMBER INDICATES NEMA SIZE AS REQUIRED CB COMBINATION MOTOR CONTROLLER/DISCONNECT SWITCH AS REQUIRED MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD AND PILOT AS REQUIRED LIGHT MOTOR- NUMBER INSIDE SYMBOL INDICATES HORSEPOWER. REFER TO _ MOTOR FEEDER SCHEDULES FOR FEEDER INFORMATION TAG EMERGENCY POWER OFF BUTTON. WALL MOUNTED - STUB 3/4m C. AFF ABOVE ACCESSIBLE CEILING FROM OUTLET BOX X,X,X THREE SINGLE POLE DEVICE CIRCUIT NUMBERS - X /X /X MULTI -POLE DEVICE CIRCUIT NUMBERS - HOMERUN CONDUIT MINIMUM 4" U.N.O. (NUMBER OF ARROWHEADS INDICATE QUANTITY OF #12 PHASE CONDUCTORS). PROVIDE ONE #12 _ GROUND AND ONE X112 NEUTRAL IN EACH CONDUIT U.N.O. MAXIMUM OF THREE PHASE CONDUCTORS PER HOMERUN CONDUIT. a 0 H O J a ELECTRICAL ABBREVIATIONS ': AFC ABOVE FINISHED COUNTER N NEW DEVICE AFF ABOVE FINISHED FLOOR NC (N.C.) NORMALLY CLOSED ATS AUTOMATIC TRANSFER SWITCH NEC NATIONAL ELECTRIC CODE BFC BELOW FINISHED CEILING NF NONFUSED BOF BOTTOM OF FIXTURE NIC NOTIN CONTRACT C CONDUIT NL NIGHT LIGHT CB,C/B OR CIRCUIT BREAKER NO (N.O.) NORMALLY OPEN CKT BKR E Lo (ON) HOME RUN FOR CKT IS "ON" THE SAME c�Un�> � W CKT. ELSEWHERE ON THE PLAN CKT CIRCUIT ° °w x Q- W 'c � PB PULL BOX CCTV CLOSED CIRCUIT T.V. 0 0-- PNL PANEL CLG CEILING Q PWR POWER CUH CABINET HEATER R RELOCATED DEVICE DFA DOWN FROM ABOVE RCPT(S) OR RECEPTACLE(S) EC EMPTY CONDUIT RECEPT ELEC ELECTRIC RF RETURN AIR FAN E EMERGENCY — RED SEF SMOKE EXHAUST FAN EMS ENERGY MANAGEMENT SYSTEM SF SUPPLY AIR FAN EP EXPLOSION PROOF SO (S.O.) SPACE ONLY EWC ELECTRIC WATER COOLER SP SPARE EX EXISTING ST (S.T.) SHUNT TRIP F FUSE SW SWITCH FA FIRE ALARM TC TIME CLOCK FACP, FAP FIRE ALARM CONTROL PANEL TEL TELEPHONE FCU FAN COIL UNIT TF TRANSFER FAN FIXT FIXTURE TP TAMPER PROOF FLR FLOOR TV TELEVISION FLUOR FLUORESCENT OF UNDERFLOOR FTP, FTS FAN TERMINAL UNIT UG UNDERGROUND FTU FAN TERMINAL UNIT G, GND GROUND (EQUIPMENT) UH UNIT HEATER UNO (U.N.O.) UNLESS NOTED OR INDICATED OTHERWISE GEF GENERAL EXHAUST FAN V VOLTAGE GEN GENERATOR VP VAPOR PROOF GFCI, GFl GROUND FAULT CIRCUIT INTERRUPTER VV VARIABLE VOLUME UNIT HP HORSE POWER W WIRE HV HIGH VOLTAGE W/ WITH HWAT HEAT TRACE WG WIRE GUARD IC INTERRUPTING CAPACITY WP WEATHER PROOF ICAND INCANDESCENT WT WATER TIGHT IG ISOLATED GROUND XFMR TRANSFORMER JB JUNCTION BOX +xx MOUNTING HEIGHT IN INCHES. AFF UNO. KEF KITCHEN EXHAUST FAN LTG LIGHTING LTS LIGHTS LV LOW VOLTAGE MAN MASTER ANTENNA MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MDP MAIN DISTRIBUTION PANEL MH MANHOLE MLO MAIN LUGS ONLY MID MOUNT OR MOUNTED NOTES: 1. 48" AFF INDICATES TO TOP OF DEVICE; 18" AFF INDICATES TO BOTTOM OF DEVICE; 80" AFF INDICATES TO BOTTOM OF DEVICE; ALL OTHER MOUNTING HEIGHTS REFER TO CENTERLINE OF DEVICE. MISCELLANEOUS Q2 — NOTES: DENOTES "SEE NOTE NO. 2" �— MARK (ID) NUMBER FOR EQUIPMENT REF. 2/E2.02 — DENOTES: REFERENCE DETAIL 2 IN DRAWING (SHEET) E2.02 XX —XX PANEL AND CIRCUIT NOTE: THIS INFORMATION MAY NOT ALWAYS BE INDICATED IN THE FORMAT p a -. - SWITCHING DESIGNATION SHOWN, DUE TO SPACE RESTRICTIONS IN X -+--- FIXTURE TYPE THE FLOOR PLAN. ELECTRICAL SHEET LIST DWG No. DRAWING TITLE SCALE EO.00 GENERAL INFORMATION — ELECTRICAL NTS EO.OI PARTIAL REFERENCE LOCATION PLAN VARIES E1.00 PARTIAL FIFTH FLOOR PLANS — ELECTRICAL 1/4" = 1' —O" E2.00 PARTIAL ELECTRICAL DISTRIBUTION DIAGRAM NTS E3.00 ELECTRICAL SCHEDULES AND STUDIES NTS E4.00 ELECTRICAL SPECIFICATIONS NTS ° ° v C � ° (5 .. o v Z -0-0000 - E Lo N 0 0 X O o }o c�Un�> � W > U U � O= .�? ° ° °w x Q- W 'c � N U O U 0 0-- ;✓ 0 � cy) Fm v IL cl) J V) 0 a� U CO �o � O r2 .- Z V C" � L0�% I L6 � C oD ° ° ° v C � ° (5 .. o v Z -0-0000 - E Lo N 0 0 X O o }o c�Un�> � W > U U � O= .�? ° ° °w x Q- W 'c � N U O U 0 0-- ;✓ Q REVISIONS MARK: REMARKS: J a � Fm W N IL cl) J Z 0 2 z � � >= U Qa:Q a m W ix � W O= cl)U 69314 KEYPLAN Job No: 409325.000 Date: 08 -31 -2009 Sheet Title: GENERAL INFORMATION - ELECTRICAL 5-i ,' . .